Omega Products PX541-003GI Installation Manual

PX541 SERIES
Pressure Transducers
INSTRUCTION
SHEET
M1145/0402
GENERAL DESCRIPTION
The OMEGA
®
Characteristics of the PX541 include:
• 4-20 mA Current Output, which is Ideal for Long Distance Signal Transmitting and Industrial Environments
• High Accuracy and Repeatability
• Corrosion Resistant
• Rugged NEMA-12 Dust-tight/Drip-tight Enclosure
AVAILABLE MODELS DIMENSIONS
WARNING!
READ BEFORE INSTALLATION
Fluid hammer and surges can destroy any pressure transducer and must always be avoided. Apressure snubber should be installed to eliminate the damaging hammer effects.
Fluid hammer occurs when a liquid flow is suddenly stopped, as with quick closing solenoid valves. Surges occur when flow is suddenly begun, as when a pump is turned on at full power or a valve is quickly opened.
Liquid surges are particularly damaging to pressure transducers if the pipe is originally empty. To avoid damaging surges, fluid lines should remain full (if possible), pumps should be brought up to power slowly, and valves opened slowly. To avoid damage from both fluid hammer and surges, a surge chamber should be installed, and a pressure snubber should be installed on every transducer.
Symptoms of fluid hammer and surge’s damaging effects: a) Pressure transducer exhibits an output at zero pressure (large zero offset). If zero offset is less than 10% FS,
user can usually re-zero meter, install proper snubber and continue monitoring pressures. b) Pressure transducer output remains constant regardless of pressure. c) In severe cases, there will be no output.
RANGE (PSI) MODEL
-15- to 15 PX541-15V15GI 15 to 30 PX541-15V30GI
-15 to 0 PX541-030VACI 0 to 1.5 PX541-1.5GI 0 to 3 PX541-003GI 0 to 7.5 PX541-7.5GI 0 to 15 PX541-015GI 0 to 30 PX541-030GI 0 to 75 PX541-075GI 0 to 150 PX541-150GI 0 to 300 PX541-300GI 0 to 750 PX541-750GI 0 to 1500 PX541-1.5KGI 0 to 3000 PX541-3KGI
SW 24
mm (inch)
1/2 NPT
20
.79
o
40
(1.57)
17.02 (.67)
30.5
(1.20)
109.98 (4.33) 150 PSI
85.85 (3.38) 300 PSI
WIRING
To access the screw terminals and wire the transducer, refer to Figure 1, and the following procedure:
1. Locate the screw at the top of the transducer and unscrew.
2. Separate connector from the rest of the transducer body. Remove the screw and rubber gasket from the connector and set aside.
3. Using a small blade screwdriver, insert it in the corner slot and pry off square cover (and terminals).
4. Insert cable into hole (not screw hole) past grommet and feed through into square part of assembly. Wire terminals in terminal block using wiring diagram (refer to Figure 2).
5. Replace terminal block and snap in place.
6. Put rubber gasket on unit.
7. Connect larger part of transducer to wired unit, observing positions of blades.
8. Insert screw in screw hole and tighten two parts to each other.
Figure 1. Pressure Transducer
Figure 2. Wiring Diagram Figure 3. Operating Range of Transducer
USER-PROVIDED WIRE
RUBBER GASKET
CONNECTOR
TRANSDUCER
SCREW THREADS
+ SUPPLY
+
+
CASE GROUND
SUPPLY
POWER
SUPPLY
1 2
3
0
0
700
1000
LOOP RESISTANCE
(OHMS)
prohibiting zone
10 24 30
VDC EXCITATION
Loading...
+ 2 hidden pages