One Omega Drive, River Bend Technology Centre, Northbank
Irlam, Manchester M44 5BD England
Toll-Free: 0800-488-488TEL: +44 (0)161 777-6611
FAX: +44 (0)161 777-6622e-mail: sales@omega.co.uk
It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI
regulations that apply. OMEGA is constantly pursuing certification of its products to the European
New Approach Directives. OMEGA will add the CE mark to every appropriate device upon
certification.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, human applications.
A failure resulting in injury or damage may be caused by excessive
overpressure, excessive vibration or pressure pulsation, excessive instrument temperature, corrosion of the pressure containing parts, or
other misuse.
OVERPRESSURE:
Pressure spikes in excess of the rated overpressure capability of the transmitter may cause irreversible electrical and/or mechanical damage to the
pressure measuring and containing elements.
Fluid hammer and surges can destroy any pressure transmitter and must always be avoided. A pressure snubber should be installed to eliminate the
damaging hammer effects. Fluid hammer occurs when a liquid flow is suddenly stopped, as with quick closing solenoid valves. Surges occur when flow
is suddenly begun, as when a pump is turned on at full power or a valve is
quickly opened.
Liquid surges are particularly damaging to pressure transmitters if the pipe is
originally empty. To avoid damaging surges, fluid lines should remain full (if
possible), pumps should be brought up to power slowly, and valves opened
slowly. To avoid damage from both fluid hammer and surges, a surge chamber
should be installed.
Symptoms of fluid hammer and surge’s damaging effects:
• Pressure transmitter exhibits an output at zero pressure (large zero offset).
• Pressure transmitter output remains constant regardless of pressure
• In severe cases, there will be no output.
FREEZING:
Prohibit freezing of media in pressure port. Unit should be drained to prevent
possible overpressure damage from frozen media.
STATIC ELECTRICAL CHARGES:
Any electrical device may be susceptible to damage when exposed to static
electrical charges. To avoid damage to the transmitter observe the following:
• Ground the body of the transmitter BEFORE making any electrical
connections.
• When disconnecting, remove the ground LAST!
4
Note: The shield and drain wire in the cable (if supplied) is not connected to the
transmitter body, and is not a suitable ground.
1. PREFACE
Thank you for purchasing the PX5200 Rangeable Differential Pressure
Transmitter. Refer to the Omega PX5200 Data Sheet for product specifications and applicable operating conditions.
2. OVERVIEW
The PX5200 is a 4-20mA loop powered (two-wire) differential pressure
transmitter with integral display incorporating Ashcroft’s proven SiGlas silicon
based variable capacitance sensor with stainless steel media isolation diaphragms and silicone pressure transmission fluid. The device was designed
to offer the user small size and user adjustable ranging for applications such
as tank level measurements and gas / liquid flow measurements.
3. FEATURES
(1) Media Compatibility: Wetted materials consist of 316 stainless steel,
alumina ceramic and viton to handle a wide range of media with the
ability to offer ranges as low as 4˝ W.C. F.S. (URL).
(2) Linear Scaling Function:The linear (scaling) function allows the user
to adjust zero and span values providing a corresponding
4-20mA output signal.
flow rate and integrated volume can be displayed and analog signal
can be output.
(4) Digital Filter Function: User adjustable damping of the output signal
by means of internally calculated moving average to provide a stable
output signal in applications where the user wants to reduce the pulsating of the display and / or output signal.
(5) LED Back Light: To supplement the LCD display when conditions re-
quire (dark area, night etc.).
(
6) Loop Check Function: Allows the user to output an analog signal cor-
responding to differential pressure without applying pressure, simplifying system maintenance and troubleshooting.
5
(7) Zero and Span Adjustment: The adjustment of the Zero (4mA) and
Span (20mA) reading via internal push buttons.
(8) Key Lock Function: Prevents inadvertent overwriting of setting values.
Can not be reset by restoring power when activated.
(9) IP65 / NEMA 4X Environmental Rating: Enclosure environmental rat-
ing suitable for indoor and outdoor installation, depending upon operating temperature range.*
(10) CE Compliance: EN613261 1997, A1/1998, A2/2001 (Heavy Industrial).
*Display not to be mounted in direct sunlight.
4. SPECIFICATIONS
ITEMDESCRIPTION
1. Media/Wetted Parts
Gas or liquid compatible with 316SS, viton and alumina
ceramic (isolation fluid is silicone oil). Media temperature range: –10 to +70°C
2. Overpressure
(Proof)
Static (Line) Pressure: 300psi all ranges
Singe Side (Differential) Limits:
• Pressure Ranges <8˝W.C., ±4˝W.C.; 30psid
• Pressure Ranges >20˝W.C., ±8˝W.C.; 100psid
3. Supply Voltage
4. Output
12-32Vdc
4-20mAdc (two wires, Output range: 3.2 to 20.8mAdc)
Scaling function: Linear output, linear and momentary
flow rate display/output.
Filter function: User adjustable output damping select
from 0, 2, 4, 8 and 16 (None, 2, 4, 8, and 16 (s)).
Loop check function: User adjustable output for loop/
system check and troubleshooting, 4-20mA.
Material: Aluminum die cast
Environmental Rating: IP65 / NEMA 4X
1
⁄4 NPT female pressure ports w/equalizing valve
Cable Gland (Optional): Cable diameter 0.35 to 0.47˝
(9-12mm)
1
⁄2 NPT Female Conduit Adapter (Optional)
Terminal Block: 14-22 AWG (stranded or solid wire)
Permanently stored by EEPROM (nonvolatile memory)
CE Compliance: EN61326/1997, A1/1998, A2/2001
–10 to 60°C (14 to 140°F)
–20 to 70°C (–4 to 158°F)
5g’s, 150Hz
10g’s, 16ms
50Vdc, 100MΩ or more
Approx. 670g (1.5lbs)
7
5. MOUNTING
5.1 General
The GC52 was designed to be mounted using the bracket supplied.
Pressure connections via the (2)
1
⁄4 NPT female pressure ports. Al-
though the display can be rotated in 90 degree increments by removing the display cover it is preferable to orientate the electrical
termination downward, particularly in applications where protection
from the environment is required.
5.2 Mounting Orientation
It is preferable to orientate the unit with the pressure ports either
downward or upward. If mounting with pressure ports to the side an
“orientation effect” will be seen at zero pressure as the pressure generated by the silicone oil fill will appear as a zero offset. If mounting in
this manner this effect may be taken out by re-setting zero in final
mounting orientation.
5.3 Installing Pressure Port Manifold
(1) Mounting 25.4mm Manifold (
1
⁄4˝ NPT female ports)
Manifold is secured using the (4) socket head bolts (M4x40) and
appropriate allen wrench which is supplied. Check for dust and
dirt on the O-ring and seal area, clean if necessary, before installing to ensure proper connection. The direction of the manifold
is not important, determine best position by ability to operate the
equalizing valve.The equalizing valve is used to open both ports
to the line pressure at time of installation. Once installed and the
system has been pressurized the valve needs to be closed to isolate the low and high pressure sides of the device.
Tighten the equalizing valve with a torque of 0.75 ft-lbs±15%.
When loosening the valve do not back off by more than three
turns from the closed position.
(2) Panel Mounting
Similar to (1) above except that the PX5200 is put between the
manifold and the bracket and then the (4) socket head bolts
(M4x40) are installed.
8
(2) 1/4˝ NPTF
1.4 (35)
.55 (14)
.83 (21)
1.8 (45.4)
1.0 (25.4)
Hex .83 (21)
.33 (8.5)
Equalizing
valve
Low pressure
inlet (L)
Panel mounting
bracket
High pressure
inlet (H)
Equalizing
valve
M4 x 40
O-rings
Lower connection diagram
Connection: Lower side.
• 1.0 in. (25.4mm) mounting manifold
6. PIPING
Note: High (H) and Low (L) pressure
sides of the device are marked on the
yellow label affixed to the housing of
the unit.
Install the high pressure side of the applied differential pressure in the pressure inlet of the high pressure side (H)
and the low pressure side in the pressure inlet of the low pressure side (L).
(Refer to the outline drawing of section 14.)
After the piping is completed check for leaks.
(1) Piping of 1.0 in (25.4mm) Manifold (
Use caution when installing to keep metal chips and other debris from
entering pressure transmitter. In addition, when sealing tape is used,
do not apply to last two threads at the end of the fitting
1
⁄4˝ npt female ports)
9
Note:
• When transporting and / or mounting do not apply excessive shock
or use device as a step.
• The piping should be of proper length so as not to apply load to the
connection point on the transmitter.
• At the time of mounting or when bleeding air from the device be sure
to open the equalizing valve with a flathead screwdriver so that excessive pressure (more than the allowable maximum differential pressure) is not applied to the differential pressure sensor. Maximum torque
to apply to equalizer valve is 0.75 ft-lbs ±5%.
7. WIRING
7.1 Cable/Wire Specifications
Use appropriate cable described below which is suitable for power
supply requirements and ground to housing.
Terminal Strip
Cable
Requirements
SMKDSP1.5/2-5.08 Phoenix Contact
• Two core shielded cable
• Cable outer diameter: 0.35˝ to 0.47˝ 9-12mm
(Required for correct installation with Cable
Gland option)
• Wire Gauge: 14-22 AWG (multi-strand or solid)
7.2. Wiring Instructions
• To reduce potential for noise do not run pressure transmitter cable /
wires alongside (same conduit as) high voltage (line power) lines.
For optimum results use dedicated conduit for PX5200 cable / wires.
• If using the Cable Gland termination option must use cable within
previously noted diameters to maintain environmental ratings.
• When connecting shield / drain wire, only connect one end which
should be at the receiver ground.
• Wiring stripping instructions, remove cable jacket 2-3˝ and strip wires
±0.25˝. Shield / drain wire should not be exposed at the pressure
transmitter termination.
• Remove cover and carefully remove the display to access the terminal strip, take care not to mishandle the display and associated electronics.
10
+
−
Terminal box
Display (board)
Shield
Power source
+−
Receiver
Transmission cable
CASE
DISPLAY
CAP
Inside sensor Line
LCD holder
Notch
Transmission cable
(Twist)
Sheath
Display
Wire terminals
Wire
Turn with a screwdriver
LCD clips (4)
Display board
Power supply
terminal block
P
X
5
2
0
0
• Turn display over to
expose terminal strip,
make positive and
negative connections,
insert wire depth is
equal to recommended
strip length (0.25˝).
11
• After completing connections locate retaining clips in the appropri-
1000
750
500
250
0
0322010
1020
30
Load Limitations 4-20mA Output Only
1224
545
OPERATING
REGION
Loop Resistance (V)
ate notches and carefully place into the housing. Be sure that internal sensor transmission wire does not cross the power supply lines
just installed.
• If using the Cable Gland be sure to properly tighten sealing grommet
before applying any tension on the cable, the cable gland provides
strain relief and environmental sealing.
• Tighten GC52 cover to maintain environmental rating.
• Connect to power source and receiver and power on to confirm correct wiring (see Section 10 for more detail).
• Power Supply Requirements: Although the 4-20mA signal can travel
over long distances one of the most common problems is inadequate
power at the pressure transmitter due to the voltage drop across the
loop. Be sure to review table below to determine that 12-32V is getting to the pressure transmitter.
12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.