Omega Products CNi8C-EN Installation Manual

User’s Guide
Shop on line at
www.omega.com
e-mail: info@omega.com
iSeries info:
www.omega.com/specs/iseries
Temperature & Process
Controller/Monitor Manual
TABLE OF CONTENTS
Part 1: Introduction .....................................................................................1
1.1 Description ...................................................................................1
1.2 Safety Considerations ....................................................................2
1.3 Before You Begin ...........................................................................3
Part 2: Setup ................................................................................................4
2.1 Front Panel ...................................................................................4
2.2 Disassembly ...................................................................................5
2.3 Electrical Installation ......................................................................6
2.3.1 Power Connections ............................................................6
2.3.2 Rear Panel Connections ....................................................8
2.3.3 Thermocouple - Input Connection ....................................10
2.3.4 Two / Three / Four Wire RTD-Hookups ...........................11
2.3.5 Process Current - Wiring Hookup ....................................12
2.3.6 Process Voltage - Wiring Hookup ....................................12
2.3.7 Wiring Outputs - Wiring Hookup .......................................13
Part 3: Operation: Configuration Mode ...................................................16
3.1 Introduction .................................................................................16
Turning your Instrument On for the First Time .................16
Buttons Functions in Configuration Mode ........................17
Appendix A: ...............................................................................................18
i
LIST OF FIGURES:
Figure 2.1 Front Panel Display ........................................................................4
Figure 2.2 Disassembly ...................................................................................5
Figure 2.3 Main Power Connections ...............................................................6
Figure 2.4 Rear View - For Models with Outputs: 22, 23, 33 ..........................7
Figure 2.5 Rear View - For Models with Outputs: 52, 53 ................................7
Figure 2.6 Rear View - For Models with Outputs: 00 ......................................8
Figure 2.7 Rear Panel Power and Output Connector Labels ..........................8
Figure 2.8 Rear Panel Input Connector Labels ...............................................9
Figure 2.9 Thermocouple Wiring Hookup .....................................................10
Figure 2.10 Two/Three/Four-wire RTD
a) RTD-1000 ohm and 500 ohm Wiring Hookup ..............................11
b) RTD-100 ohm Wiring Hookup ......................................................11
Figure 2.11 Process Current Wiring Hookup
(Internal and External Excitation) .................................................12
Figure 2.12 Process Voltage Wiring Hookup
a) Without Sensor Excitation ............................................................12
b) With Sensor Excitation .................................................................12
Figure 2.13 Output Connections:
a) Mechanical Relay and SSR Outputs – Wiring Hook up ...............13
b) Pulse and Analog Outputs – Wiring Hook up ...............................13
Figure 2.14 Typical Application .......................................................................14
Figure 2.15 Communication Output:
a) RS-232 Output – Wiring Hook up ................................................14
b) RS-485 Output – Wiring Hook up ................................................14
Figure 2.16 Excitation Output ..........................................................................15
Figure 2.17 Snubber Circuits Wiring Hookup ..................................................15
Figure A-1 Plug-Kit ........................................................................................18
LIST OF TABLES:
Table 2.1 Front Panel Annunciators ..............................................................4
Table 2.2 Fuse Requirement .........................................................................6
Table 2.3 Rear Panel Connector ...................................................................9
Table 2.4 TC Wire Color Chart ....................................................................10
Table 3.1 Button Function in Configuration Mode ........................................17
ii
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by the following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provide you with information that is important to successfully
setup and use the Programmable Digital System.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or practices that can affect the instrument’s functionality and must refer to accompanying documents.
TIP: Provides you helpful hints.
PART 1 INTRODUCTION
1.1 Description
This Device is a compact, wall-mountable controller or monitor that can be used for applications that need a fixed location, when a control panel is not required. The controller supports a variety of temperature and process inputs. The flip-top enclosure makes programming and wire access easy to use.
For more complete specifications of the controller/monitor refer to the main operator manual.
1
1.2 Safety Considerations
This device is marked with the international caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with EN 61010-1:2001, electrical safety requirements for electrical equipment for measurement, control and laboratory. Installation of this instrument should be done by qualified personnel. In order to ensure safe operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit­breaker shall be included in the building installation as a disconnecting device. It shall be marked to indicate this function, and it shall be in close proximity to the equipment within easy reach of the operator. The switch or circuit-breaker shall meet the relevant requirements of IEC 947–1 and IEC 947-3 (International Electrotechnical Commission). The switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment, an overcurrent protection device shall be installed.
• Do not exceed voltage rating on the label located on the top of the instrument housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Unit mounting should allow for adequate ventilation to ensure instrument does not exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain and power requirements. Install without exposing bare wire outside the connector to minimize electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
2
1.3 Before you Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything listed. Inspect the container and equipment for signs of damage as soon as you receive the shipment. Note any evidence of rough handling in transit. Immediately report any damage to the shipping agent. The carrier will not honor damage claims unless all shipping material is saved for inspection. After examining and removing the contents, save the packing material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service Department, listed in this manual.
Manuals, Software:
The latest Operation and Communication Manual as well as free configuration software are available from the website listed in this manual.
For first-time users: Refer to the QuickStart Manual for basic operation and set-up instructions.
If you have the Serial Communications you can easily configure the controller on your computer or on-line.
To Disable Outputs:
To ensure that menu changes are properly stored, Standby Mode should be used during setup of the instrument. During Standby Mode, the instrument remains in a ready condition, but all outputs are disabled. Standby Mode is useful when maintenance of the system is necessary.
When the instrument is in “RUN” Mode, push d twice to disable all outputs and alarms. It is now in “STANDBY” Mode. Push d once more to resume “RUN” Mode.
PUSH d TWICE to disable the system during an EMERGENCY.
To Reset the Meter:
When the controller is in the “MENU” Mode, push c once to direct controller one step backward of the top menu item.
Push c twice to reset controller, prior to resuming “Run” Mode except after “Alarms”, that will go to the “Run” Mode without resetting the controller.
3
PART 2 SETUP
2.1 Front Panel
Figure 2.1 Front Panel Display
Table 2.1 Front Annunciators
1 Output 1/Setpoint 1/ Alarm 1 indicator
2 Output 2/Setpoint 2/ Alarm 2 indicator
ºC °C unit indicator
ºF °F unit indicator
Changes display to Configuration Mode
a
and advances through menu items*
Used in Program Mode and Peak Recall*
b
Used in Program Mode and Valley Recall*
c
Accesses submenus in Configuration Mode
d
* See Part 3 Operation: Configuration Mode
and stores selected values*
4
2.2 Disassembly
Figure 2.2 Disassembly
Not all cable glands may be in use. Please use the provided “Plug-Kit” to keep the NEMA 4 rating on the unused glands. See Appendix A for detailed diagram.
5
Loading...
+ 19 hidden pages