Table 2.4 TC Wire Color Chart ....................................................................10
Table 3.1 Button Function in Configuration Mode ........................................17
ii
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by the following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provide you with information that is important to successfully
setup and use the Programmable Digital System.
CAUTION or WARNING: Tells you about the risk of
electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or
practices that can affect the instrument’s functionality and must refer to
accompanying documents.
TIP: Provides you helpful hints.
PART 1
INTRODUCTION
1.1 Description
This Device is a compact, wall-mountable controller or monitor that can be used
for applications that need a fixed location, when a control panel is not required.
The controller supports a variety of temperature and process inputs. The flip-top
enclosure makes programming and wire access easy to use.
For more complete specifications of the controller/monitor refer to the main
operator manual.
1
1.2 Safety Considerations
This device is marked with the international caution symbol. It is
important to read this manual before installing or commissioning this
device as it contains important information relating to Safety and
EMC (Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with
EN 61010-1:2001, electrical safety requirements for electrical equipment
for measurement, control and laboratory. Installation of this instrument
should be done by qualified personnel. In order to ensure safe
operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuitbreaker shall be included in the building installation as a disconnecting
device. It shall be marked to indicate this function, and it shall be in
close proximity to the equipment within easy reach of the operator. The
switch or circuit-breaker shall meet the relevant requirements of IEC
947–1 and IEC 947-3 (International Electrotechnical Commission). The
switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being
drawn from the main supply in case of a fault in the equipment, an
overcurrent protection device shall be installed.
• Do not exceed voltage rating on the label located on the top of
the instrument housing.
• Always disconnect power before changing signal and power
connections.
• Do not use this instrument on a work bench without its case for
safety reasons.
• Do not operate this instrument in flammable or explosive
atmospheres.
• Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical
strain and power requirements. Install without exposing bare wire
outside the connector to minimize electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if
EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
2
1.3 Before you Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything
listed. Inspect the container and equipment for signs of damage as
soon as you receive the shipment. Note any evidence of rough handling
in transit. Immediately report any damage to the shipping agent. The
carrier will not honor damage claims unless all shipping material is
saved for inspection. After examining and removing the contents, save
the packing material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation and Communication Manual as well as free
configuration software are available from the website listed in this manual.
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications you can easily configure the
controller on your computer or on-line.
To Disable Outputs:
To ensure that menu changes are properly stored, Standby Mode
should be used during setup of the instrument. During Standby Mode,
the instrument remains in a ready condition, but all outputs are disabled.
Standby Mode is useful when maintenance of the system is necessary.
When the instrument is in “RUN” Mode, pushdtwice to disable all
outputs and alarms. It is now in “STANDBY” Mode. Pushdonce more
to resume “RUN” Mode.
PUSH d TWICE to disable the system during an EMERGENCY.
To Reset the Meter:
When the controller is in the “MENU” Mode, pushconce to direct
controller one step backward of the top menu item.
Pushc twice to reset controller, prior to resuming “Run” Mode except
after “Alarms”, that will go to the “Run” Mode without resetting the
controller.
3
PART 2
SETUP
2.1 Front Panel
Figure 2.1 Front Panel Display
Table 2.1 Front Annunciators
1Output 1/Setpoint 1/ Alarm 1 indicator
2Output 2/Setpoint 2/ Alarm 2 indicator
ºC°C unit indicator
ºF°F unit indicator
Changes display to Configuration Mode
a
and advances through menu items*
Used in Program Mode and Peak Recall*
b
Used in Program Mode and Valley Recall*
c
Accesses submenus in Configuration Mode
d
* See Part 3 Operation: Configuration Mode
and stores selected values*
4
2.2 Disassembly
Figure 2.2 Disassembly
Not all cable glands may be in use. Please use the provided
“Plug-Kit” to keep the NEMA 4 rating on the unused glands.
See Appendix A for detailed diagram.
5
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.