Omega Products CN8201-T1 User Manual

1
16 DIN Universal Temperature
and Process Controllers
with 8-Segment Ramp/Soak
CN8200 Series
Starts at
$
264
Standard Features Field-Configurable
Universal Inputs
Autotuning, Direct- or
Reverse-Acting for Both Outputs
User-Selectable
Ramp to Setpoint
8 Ramp and 8 Soak
Segments
Decimal Display in 0.1°
for Measured Temperatures Under 1000°F or °C
NEMA 4X (IP65)
Front Panel
Optional Features
RS232/485 Digital
Communications, Contact/Digital Remote Input, Transducer Excitation, and PV or SV Retransmission
24 Vac/Vdc
Power Supply
The CN8200 temperature/process controller is extremely versatile and user-friendly. During setup, the user needs to review only those parameters relevant to the particular application. A dual digital display offers optimal process information at a glance. Individual LEDs identify the status of outputs, alarms, digital communications, and special options. The CN8200 features a NEMA 4X front panel and a
universal power supply that accepts 100 to 250 Vac and 120 to 250 Vdc. A 24 Vac/24 Vdc power supply option is also available. Available control algorithms are P, PI, PD, PID, or on/off. The autotune feature automatically sets proportional band, derivative, and integral before the process reaches setpoint. These parameters provide quick stabilization of processes with minimum overshoot, hunting, or cycling. Eight-level ramp/soak control is standard and includes a decimal display on thermocouple ranges, digital display and signal filtering, and a percentage of power limit setting.
The dual control outputs can be configured for a variety of control and alarm applications, and 2 dedicated alarm outputs are also available.
The CN8200 offers a wide range of options, including RS232 and RS485 digital communications, 3 contact/digital input modes, 4 transducer excitation voltages, and 4 auxiliary output ranges.
CN8201-R1, $264.
Pa
n
e
l
punches
a
v
a
i
l
abl
o
m
e
ga.com
p
a
n
e
l
p
unches
e, v
i
s
i
/
t
P-45
1
8
A
CN8
S
P-
DIN
V
e
r
sio
va
ila
b
2
4
0
e
r
ie
s’
6
0
t
h
r
o
1
a
n
d
4
DI
e
S
e
CN8
Pa
P-
N
Al
so
e
t
h
e
2
6
0
g
e
s
6
2
!
n
s
Ar
le
!
a
n
d
o
n
u
g
h
Specifications
Performance
Accuracy: ±0.2% FS, ±1 digit Setpoint Resolution:1 count/0.1 count Repeatability: ±1 count Temperature Stability: 5 µV/°C max T/C Cold-Junction Tracking:
0.05°C/°C ambient
Common Mode Rejection: 100 dB Series Mode Rejection: >70 dB Process Sampling: 10 Hz (100 ms)
Inputs
Input Type: See Input Table Digital Input: For remote setpoint,
remote standby or ramp/soak run and hold
Thermocouple Lead Resistance:
100 Ω max for rated accuracy
Decimal Position: Selectable
Outputs
Output #1: Reverse- or direct-acting,
configured from menu Output #2: Reverse- or direct-acting, configured from menu Mechanical Relay: Rated 5 A @120 Vac, 3 A @ 240 Vac, normally open (NO), normally closed (NC) (output 1); rated 5 A @120 Vac, 3 A @ 240 Vac, NO (output 2)
Current: 4 to 20 mA,
E
xtended Warranty
P
rogram
SM
500 max (suffix F1, F2); 4 to 20 mA, 1000 max
suffix FH1, FH2)
(
Voltage: 20 Vdc pulse Solid State Relay:
SSR, 120/240 Vac, zero voltage switched, rated 1 A continuous, 10 A surge @ 25°C (77°F) Alarms: Mechanical relay rated 5 A @ 120 Vac, 3 A @ 240 Vac, NO; optically isolated SSR rated 1 A, 120/240 Vac @ 25°C (77°C); DC alarms, 24 Vdc
Transducer Power Supply:
5, 10, 12, 15 Vdc ±10%
Control Characteristics
Setpoint Limits: Limited to configured
range for thermocouple and RTD; limited to scaled range Alarms: Adjustable for high/low; selectable process or deviation
Rate (Derivative): 0 to 2400 seconds Reset (Integral): 0 to 9600 seconds Cycle Time: 0.2 to 120 seconds Proportional Band: 1 to span
of sensor Deadband: Negative span to positive span of sensor
Hysteresis: 1 to span of sensor Autotune Damping: Adjustable
(low, normal, or high)
Ramp to Setpoint:
1 to 9999 minutes Autotune: Operator-initiated from front panel Manual Control: Operator-initiated from front panel
General
Power: 100 to 250V, 50/60 Hz
(single-phase); 120 to 250 Vdc, 24 Vac/24 Vdc (optional) Display: Dual LED—4-digit, orange: process display; green: menu/ parameter display; 9.2 mm (0.36") Power Consumption: Less than 6 VA (instrument) @ 120 Vac
Weight: 226 g (8 oz) Panel Cutout: 45 mm (1.771") square Dimensions:
53.3 H x 53.3 W x 8.21 mm D (2.1 x 2.1 x 0.72") bezel
Depth Behind Panel:
100 mm (3.937")
Front-Panel Rating: NEMA 4X (IP65) Operating Ambient Range:
0 to 55°C (32 to 131°F) @ 90% RH max, non-condensing
Memory Protection:
Solid state non-volatile memory
Connections: Screw terminals Contacts: Twin bifurcated Ramp/Soak Programming Intervals: 8 Loops: 0 to 99 Ramp Time: 0 to 9999 minutes Soak Time: 0 to 9999 minutes
Events/Alarms: 1 to 8 Ramp Setpoint: 1 to 9999 minutes CN8-SW (Optional Software): Minimum Hardware and Software Requirements:
IBM PC or 100% compatible, Windows 95/98/NT; RS485 interface or RS232
o RS485 converter
t
Software Compatibility:
CN8200 Series controllers
Software Capability:
Supports up to 254 CN8200 Series controllers
OMEGACARESMextended warranty program is available for models shown on this page. Ask your sales representative for full details when placing an order. OMEGACARE covers parts, labor and equivalent loaners.
SM
CN8202-R1, $289 shown actual size.
Input and Range Table for Universal Input Controller
Input Type Range
Iron-Constantan -200 to 760°C (-328 to 1400°F)
CHROMEGA®-ALOMEGA
®
-270 to 1354°C (-454 to 2469°F)
Copper-Constantan -270 to 400°C (-454 to 752°F)
OMEGALLOY
®
-268 to 1300°C (-450 to 2372°F)
Pt/13%Rh-Pt -50 to 1768°C (-58 to 3214°F)
Pt/10%Rh-Pt -50 to 1768°C (-58 to 3214°F)
Pt/30%Rh-Pt/6%Rh 0 to 1820°C (32 to 3308°F)
W/5%Re-W/26%Re 0 to 2315°C (32 to 4199°F)
CHROMEGA®-Constantan -150 to 1000°C (-238 to 1832°F)
NNM 18% molybdenum vs 0 to 1410°C (32 to 2570°F) nickel -06% cobalt
Platinel II -100 to 1232°C (-148 to 2250°F)
(3-wire) 100 Pt -200 to 850°C (-328 to 1562°F)
(3-wire) 100 Pt -199.9 to 375.0°C (-199.9 to 707.0°F)
0 to 1V Scalable (-1999 to 9999) selectable
1 to 5V Scalable (-1999 to 9999) selectable
0 to 5V Scalable (-1999 to 9999) selectable
0 to 10V Scalable (-1999 to 9999) selectable
10 to 50 mV Scalable (-1999 to 9999) selectable
0 to 50 mV Scalable (-1999 to 9999) selectable
0 to 10 mV Scalable (-1999 to 9999) selectable
0 to 100 mV Scalable (-1999 to 9999) selectable
4 to 20 mA Scalable (-1999 to 9999) selectable
0 to 20 mA Scalable (-1999 to 9999) selectable
P-46