A
IR CONNECTIONS
A
UPPLY
S
-4109/1104 IP510, EP510, IP511, EP511 SERIES
M
Connect air supply to 1/4 NPT port marked "IN." If the above specifications are not met, possibility of internal clogging
exists. Also see MAINTENANCE section.
OUTPUT
Connect output to 1/4 NPT port marked "OUT."
AUGE
G
The plugged 1/8 NPT port in the base of the transducer is internally connected with the "OUT" port. A pressure gauge can be
attached to this port to monitor output pressure.
In order to get optimal service from this transducer and ensure warranty coverage the following MUST be followed:
•The supply air quality to this instrument must be instrument quality air as defined by ISA Standard 57.0.01-1996.
1. Dew point not higher than 35˚F.
2. No particulates larger than 3 microns in size.
3. Maximum oil content of 1 ppm.
No mechanical adjustments or calibrations are necessary or allowed. All calibration MUST be done with electrical poten-
•
tiometers on the enclosed circuit board only. See “CALIBRATION” section of instructions for more information.
TABLE 1: SUPPLY PRESSURE REQUIREMENTS
Standard Output
Calibration
Transducer
Supply Pressure
0-2
PSI
20-45
PSI
0-5
PSI
20-45
PSI
0-30
PSI
50-90
PSI
0-60
PSI
80-120
PSI
0-100
PSI
110-130
PSI
0-120
PSI
130-140
PSI
1-17
PSI
30-70
PSI
3-9
PSI
20-100
PSI
3-15
PSI
20-100
PSI
3-27
PSI
35-100
PSI
6-30
PSI
35-100
PSI
3
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES
M
OUNTING
GENERAL
NEMA 1 and NEMA 4X transducers can be mounted in any position.
DIRECT MOUNTING
PIPE
•Any NEMA 1 transducers may be supported by its own plumbing for air supply and output. NEMA 4X transducers may
also be supported using 1/2" explosion proof conduit in the electrical port.
PANEL
•NEMA 1 transducers may be mounted to a panel with two No. 10-32 screws using threaded holes in the back of a trans-
ducer or with two to four No. 8-32 screws using threaded holes in the bottom of a transducer.
•NEMA 4X transducers may be mounted to a panel with three No. 10-32 screws using threaded holes in the back of a
transducer or with four No. 8-32 screws using threaded holes in the bottom of a transducer. In the case of back-mounting, if the panel extends towards the screw-on cover, a 3/16-inch-thick spacer MUST be used between the back of the
transducer and the panel in order for the panel to clear the transducer's screw-on cover.
EP510 AND IP510
WEIV EDISWEIVTNORF
Drawings and dimensions are for reference only.
4
WEIVPOTWEIV MOTTOB
A
LECTRICAL CONNECTIONS
E
RECAUTIONS TO BE OBSERVED DURING INSTALLATION
P
-4109/1104 IP510, EP510, IP511, EP511 SERIES
M
These Transducers were tested at the EMC Test Centre, Dunfermline, Fife, KY11 5LB to the Electromagnetic
Compatibility Directive effective January 1, 1996. The relevant EMC specifications tested were the following:
EN 50081-1 (1992) and EN 50082-2 (1992). A Technical Construction File, Serial #107 was written and
Certificate of Conformity issued by a Competent Body.
N 50081-1 (1992): Test results confirmed that no precautions need to be observed during installation regarding electro-
E
magnetic emissions from the 510 or 511 Series Transducers.
EN 50082-2 (1992): The following precautions should be taken during installation to maintain the advertised accuracy specifications. The input wiring to the transducer should be isolated from other high voltage transient wiring. The momentary
switching on and off of nearby relays, motors, or other high capacitive or inductive loads can have a minor effect on the
accuracy specification (0.25% of Span). Any change in output pressure is minimal and momentarily, and is considered to be
within the performance capabilities. Use of a ferrite bead collar on the input wires entering the transducer is recommended
should installation next to high electromagnetic interference be necessary.
WARNING: In explosive atmospheres, electrical power must be removed from the transducer before attempting to
remove the cover and until the cover is fully reinstalled. Failure to do so may result in electrical spark or explosion.
CAUTION: Care must be used when inserting wires into the NPT port. Wires must not enter below the circuit board
due to sensitive mechanical components.
DIRECTIONS
1. Remove the cover (see WARNING above).
2. Bring wiring to the terminal block, located on the circuit board, through 1/2 NPT electrical conduit connection. 18
A.W.G. is recommended; 14 A.W.G. is the maximum wire size. Connect wires to the terminal block per TABLE 2. Care
must be exercised to prevent damage to delicate internal parts when inserting wiring through the 1/2” NPT conduit
opening.
3. An internal grounding screw is provided on all units to facilitate separate ground when required. An external grounding
lug is also provided on NEMA 4X enclosures.
Reinstall the cover tightly using all o-rings and locking devices to insure compliance with Agency Approvals.
4.
TABLE 2: ELECTRICAL CONNECTIONS
TERMINAL BLOCKI / P TRANSDUCER MODELSE / P TRANSDUCER MODELS
POSITION # 1( -- ) NEGATIVE SIGNAL( + ) POSITIVE SIGNAL
WARNING: In explosive atmospheres, electrical power must be removed from the transducer before attempting to
remove the cover and until the cover is fully reinstalled. Failure to do so may result in electrical spark or explosion.
CAUTION: Only attempt electrical adjustments as described below. Any mechanical adjustments made will void the
warranty.
1. Remove the cover to gain access to the "SPAN",(marked S), "FINE ZERO",(marked Z) and the "DAMPING", (3/4 turn low
profile) potentiometers. The unmarked pot “COURSE ZERO”, is used only for major calibration range changes. This
adjustment should only be attempted by factory trained personnel. For NEMA 1 enclosure, just slide open the access
door on the top of the cover.
2. Set electrical input signal to 0% (e.g. 4 mA or 0 VDC).
FORWARD ACTING UNITS: Using "FINE ZERO" potentiometer, adjust output pressure to 0% output (e.g. 3 psi).
3.
4. Set electrical input signal to 100% (e.g. 20 mA or 10 VDC).
5. FORWARD ACTING UNITS: Using "SPAN" potentiometer, adjust output pressure to 100% output (e.g. 15 psi).
6.Repeat steps 2 through 5 until output pressures are properly set.
NOTE: Under certain circumstances, output pressure may exhibit cycling action. To eliminate this condition, use the
"DAMPING" potentiometer.
7.Reinstall cover using original screws and gaskets, if equipped.
MAINTENANCE
When used properly, these transducers should provide more than one million cycles without failure. If a situation should
occur in which the transducer's behavior is abnormal, the cause is usually related to a pneumatic problem.
ELECTRICAL MAINTENANCE
An electrical problem must be isolated by a skilled technician. The power source and all wiring should be checked first.
Circuit board failures are very rare, and can be confirmed by the following method. Loosen the screws, or posts that hold
the circuit board in place. Unplug the blue connector from the circuit board, and insert two small pieces of wire into the connector.
IMPORTANT: Connect a current source with the polarity as follows. Positive to the (RED) coil wire and Negative to the
(BROWN) coil wire of 10 mA to the connector, which powers the yellow coil. With supply pressure on, the unit should pro-
duce an output pressure equivalent to 80% or more of the maximum output pressure. If there is little or no output, then the
unit is clogged. Should it produce an adequate output pressure, then the circuit board is the primary suspect. The unit must
be returned to the factory for repair.
PNEUMATIC MAINTENANCE
All 510 and 511 Series transducers also have an internal orifice filter, but if contaminates do invade the transducer, they can
clog the internal orifice and block the flow, or jam open the internal supply valve. The problem can be corrected through
replacement of the orifice (see TABLE 5: KITS) or by cleaning the internal supply valve, or both.
6
-4109/1104 IP510, EP510, IP511, EP511 SERIES
M
EPLACING ORIFICE:
R
his can be accomplished without removing the unit from its mounting or plumbing.
T
1. Turn off supply pressure and unscrew the brass orifice assembly located on the side of the housing with the gauge
port.
NOTE: Small sealing o-ring may remain inside of the housing. If it does, remove it with a paper clip or some other small
probe. The replacement assembly will contain this o-ring.
. Install the new orifice assembly making sure the o-ring is seated on the end of the screw.
2
CLEANING INTERNAL SUPPLY VALVE:
1. Turn off the supply pressure.
2. Use a 9/16" socket or wrench to unscrew the brass plug in the bottom of the transducer.
NOTE: Take care not to lose the supply valve spring which is retained by the bottom plug.
3. Clean out any dirt or debris and reassemble, making sure the stem of the supply valve is nested in the supply valve
spring.
AGENCY APPROVALS, SPECIAL NOTES, AND CAUTIONS
A
INTRINSIC SAFETY
All 510 and 511 Series transducers are rated intrinsically safe by both FM and CSA for:
CLASS I, DIVISION 1, GROUPS A,B,C,D HAZARDOUS LOCATIONS.
Proper FM-approved intrinsically-safe wiring requires external FACTORY MUTUAL RESEARCH CORPORATION ENTITYAPPROVED SINGLE-CHANNEL barriers to be selected, based upon MAXIMUM ENTITY PARAMETERS of 510 and 511 Series
transducers:
ENTITY PARAMETERS:
Vmax = 28 V, Imax = 150 mA, Ci = 0.22uF, Li = 0 mH.
Voc and Isc of a barrier shall not exceed Vmax and Imax of the transducer.
(Li + Lwiring) and (Ci + Cwiring) shall not exceed La and Ca of a barrier.
NOTICE: For proper FM and CSA approved intrinsically-safe wiring, request Drawing Number 990-439-000 from the
Factory.
NONINCENDIVE
All 510 and 511 Series transducers are approved as NONINCENDIVE by FM and approved as suitable by CSA for:
CLASS I, DIVISION 2, GROUP A, B, C, D HAZARDOUS LOCATIONS.
A barrier is not necessary when these transducers are in these locations.
ENCLOSURES
Compliance with NEMA 4X and CSA ENC4 enclosure ratings require that the screw-on cover has the O-ring installed. In case
of a need for replacement parts, see TABLE 3.
7
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES
EXPLOSION & DUST-IGNITION PROOF CERTIFICATIONS
ACTORY MUTUAL and CANADIAN STANDARDS ASSOCIATION
F
WARNING:
The following ratings are valid ONLY WHEN the cover is installed for FM and CSA. BOTH the cover and
the locking device, using tamper resistant screws must be installed. Screws are to be removed and installed with a
special driver bit (supplied). In case of a need for replacement parts, follow TABLE 4.
EXPLOSION PROOF FOR CLASS I, DIV 1, GROUP B, C, D.
DUST-IGNITION PROOF FOR CLASS II, DIV 1, GROUP E, F, G.
SUITABLE FOR CLASS III LOCATIONS.
TABLE 3: NEMA 4X, REPLACEMENT COVER O-RINGS
PART NAMEPART NUMBER
O-RING SEAL, VITON214-649-000-242
O-RING SEAL, BUNA-N214-649-000-240
TABLE 4: NEMA 4X, REPLACEMENT PARTS FOR COVER LOCKING DEVICE
PART NAMEPART NUMBER
LOCKING CLAMP224-669-000-016
TAMPER-PROOF SCREW214-648-000-401
DRIVER BIT010132-000
8
M-4109/1104 IP510, EP510, IP511, EP511 SERIES
TABLE 5: KITS
KIT NAMEPART NUMBER
1. Panel Mounting Kit010135-000
2. Valve Mounting Kit010134-000
3. 2" Pipe Mounting Kit (Valve Mounting Kit is required)010143-000
4. DIN Rail Adapter010115-000
5. Cover Locking Device Kit (for NEMA 4X enclosure only)010136-000
6. Zero based outlet range orifice with Buna-N O-rings010137-000
7. Zero based outlet range orifice with Viton O-rings010137-002
8. Standard outlet range orifice with Buna-N O-rings010137-001
9. Standard outlet range orifice with Viton O-rings010137-003
510 and 511 Series I/P AND E/P TRANSDUCER SPECIFICATIONS
Accuracy:
Hysteresis:
± 0.10% of output span, typical
± 0.25% of output span, maximum
0.01% of output span, typical
0.10% of output span, maximum
Dead Band:Not measurable
Repeatability:
Ambient Temperature Effect
Zero:
Span:
0.01% of output span, typical
0.10% of output span, maximum
± 0.004% of nominal span per ˚F, typical
± 0.022% of nominal span per ˚F, maximum
± 0.013% of calibrated span per ˚F, typical
± 0.022% of calibrated span per ˚F, maximum
Compensated Temperature Range:+32˚F to +122˚F
Operating Temperature Range
Buna-N elastomers:
Viton elastomers:
Storage Temperature Range
Buna-N elastomers:
Viton elastomers:
Vibration Effect:
-20˚F to 160˚F
0˚F to 160˚F
-40˚F to 200˚F
-15˚F to 200˚F
Less than 0.5% of SPAN per 1G,
5-2000 Hz, 3G maximum, 3 axes
Mounting Position Effect:Not measurable
Loop Load, I/P transducer:
Supply Voltage, E/P Transducer
Intrinsically Safe/Nonincendive:
General Purpose:
Less than 10 VDC drop at 20 mA
Less than 12 VDC drop at 50 mA
9 VDC to 28 VDC, less than 20 mA
9 VDC to 40 VDC, less than 20 mA
Supply Voltage Effect:Not measurable
Signal Impedance, E/P Transducer:6000 Ohm minimum
RFI/EMI Effect (NEMA 4X):Less than 0.25% of SPAN, 10V/meter, 20-1000 MHz.
Supply Pressure Requirements:See TABLE 1
Supply Pressure Effect:Not measurable
Air Consumption:6.0 SCFH maximum
Forward Flow Capacity (Supply):
Port Sizes:
Standard Range 7 SCFM
Extended Range (over 30 PSI) 12 SCFM
Pneumatic: 1/4" NPT
Electrical: 1/2" NPT
10
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month
grace period to the normal one (1) year product warranty to cover handling and shipping time. This
ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use of its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN
(AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return
package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR WARRANTY
RETURNS, please have the
following information available BEFORE
contacting OMEGA:
1. Purchase Order number under which the product
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems
relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA
for current repair charges. Have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST
of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the
prior written consent of OMEGA ENGINEERING, INC.