Oldham OLC 10, Olct 10 User Manual

0 (0)

User Manual

OLC 10 OLCT 10

Analog

Gas Detector

Part Number : NPO10GB

Revision : H.0

The Fixed Gas Detection Experts

2

GAS DETECTION

We are delighted that you have chosen an OLDHAM instrument and would like to thank you for your choice.

We have taken all the necessary measures to ensure that your instrument provides total satisfaction. Now it is important to read this document carefully.

E X T E N T O F R E S P O N S I B I L I T Y

*OLDHAM declines its responsibility towards any person for material damage, physical injury or death resulting wholly or partly from inappropriate use, installation or storage of its equipment resulting from failure to observe instructions and warnings and/or standards and regulations in force.

*OLDHAM neither supports nor authorises any company, physical or moral person to assume responsibility on behalf of OLDHAM, even if it is involved in the sale of OLDHAM products.

*OLDHAM cannot be held responsible for direct or indirect damage or be required to pay direct or indirect compensation resulting from the sale or use of any of its products IF THESE PRODUCTS HAVE NOT BEEN

DEFINED AND CHOSEN BY OLDHAM FOR THEIR SPECIFIC USE.

C L A U S E S C O N C E R N I N G P R O P E R T Y

*Drawings, plans, specifications and information included in this document contain confidential information that is the property of OLDHAM.

*None of this information may be reproduced, copied, divulged or translated, by physical, electronic or any other means, nor used as the basis for the manufacture or sale of OLDHAM equipment or for any other reasons without prior consent from OLDHAM.

W A R N I N G S

*This document is not contractually binding. In the interests of its customers, OLDHAM reserves to modify the technical specifications of its equipment without notice, in order to improve its performance.

*READ THIS MANUAL CAREFULLY BEFORE FIRST USE OF THE EQUIPMENT: this manual must be read by any person who is or will be responsible for using, maintaining or repairing this equipment.

*This equipment will only provide the announced performance levels if it is used, maintained and repaired according to OLDHAM directives, by OLDHAM personnel or by personnel approved by OLDHAM.

G U A R A N T E E

2 years guarantee in normal conditions of use on parts and technical labour, return in our workshops, excluding consumables (sensors, filters, etc.).

4

TA BL E OF CO NT EN T S

I. PRESENTATION OF DIFFERENT VERSIONS.................................................................

7

Different versions available ..........................................................................................................

7

II.MECHANICAL INSTALLATION OF DIFFERENT VERSIONS, DIMENSIONS AND

MOUNTING .............................................................................................................................

7

III. ELECTRICAL INSTALLATION OF DIFFERENT VERSIONS ......................................

9

1.Connection of OLC 10, OLCT 10 EXPLO or OLCT 10 SC (Semi-Conductor) to a

controller for combustible gas detection:...............................................................................

9

2. Connection of two OLC 10 TWIN to a controller ...............................................................

10

3.Connection of two OLCT 10 TOX (maximum 5) to a controller for detection of the same

toxic gas ...............................................................................................................................

11

4.Connection of two OLCT 10 TOX networks (5 detectors max. per network) for detection of two different toxic gases or monitoring of two conjoined areas to a two-channel

 

 

controller ..............................................................................................................................

12

IV.

MAINTENANCE....................................................................................................................

13

 

1.

Periodic maintenance with an OLC 10 detector (comb. gas) ..............................................

13

 

2.

Periodic maintenance with an OLC 10 TWIN transmitter (comb. gas) ..............................

13

 

3.

Periodic maintenance with an OLCT 10 transmitter (comb. or toxic gas) ..........................

13

 

4.

Periodic maintenance with several OLCT 10 transmitters for toxic gas .............................

15

 

5.

Sensor replacement ..............................................................................................................

15

 

6.

Scrapping .............................................................................................................................

15

V.

TECHNICAL SPECIFICATIONS .......................................................................................

17

 

1.

TECHNICAL SPECIFICATIONS - OLC 10 / OLC 10 Twin ............................................

17

 

2.

TECHNICAL SPECIFICATIONS - OLCT 10 Explo Transmitter .....................................

18

 

3.

TECHNICAL SPECIFICATIONS - OLCT 10 CO Transmitter .........................................

19

 

4.

TECHNICAL SPECIFICATIONS - OLCT 10 SC Transmitter..........................................

20

 

5.

TECHNICAL SPECIFICATIONS - OLCT 10 NO Transmitter.........................................

21

 

6.

TECHNICAL SPECIFICATIONS - OLCT 10 NO2 Transmitter.......................................

22

VI. DETAIL SPECIFICATIONS FOR USE IN EXPLOSIVE ATMOSPHERES IN

 

 

ACCORDANCE WITH THE ATEX 94/9/CE EUROPEAN DIRECTIVE......................

23

 

1.

Specifications for installation in ATEX Zone 2G ...............................................................

23

 

2.

Metrological specifications for OLC 10 combustible gas detector .....................................

23

 

 

2.1. Special precautions ........................................................................................................

23

 

 

2.2. Reactions to other combustible gases ............................................................................

23

 

3.

MARKING ..........................................................................................................................

24

 

 

3.1. Version OLC 10 / OLC 10 Twin.....................................................................................

24

 

 

3.2. Version OLCT 10 ...........................................................................................................

24

VII. DECLARATIONS OF CONFORMITY ..............................................................................

25

6

I . P R E S E N T A T I O N O F D I F F E R E N T V E R S I O N S

The OLC 10, OLC 10 TWIN and OLCT 10 EXPLO combustible gas detectors are detectors fitted with catalytic sensors and intended for use in boiler rooms and parking lots.

The OLCT 10 TOX gas detectors are 4-20mA transmitters equipped with electrochemical sensors and especially designed to detect toxic gases in commercial and light industrial applications (parking lots, boiler room, etc).

Different versions available

-OLC 10: combustible gas

-OLC 10 TWIN: combustible gas

-OLCT 10 EXPLO: combustible gas (transmitter version, 4-20 mA output)

-OLCT 10 TOX: toxic gas (transmitter version, 4-20 mA output)

I I . M E C H AN I C A L

I N S T AL L A T I O N

O F

D I F F E R E N T

V E R S I O N S , D I M E N S I O N S AN D M O U N T I N G

 

 

 

 

 

104 mm

The OLC/OLCT 10 gas detectors-transmitters are mounted vertically with the cable entries positioned downwards. Drill two holes 104 mm apart on the base to mount the units.

8

Oldham OLC 10, Olct 10 User Manual

I I I . E L E C T R I C A L I N S T AL L A T I O N O F D I F F E R E N T V E R S I O N S

1. Connection of OLC 10, OLCT 10 EXPLO or OLCT 10 SC (SemiConductor) to a controller for combustible gas detection:

Notes:

-

The controller configuration will be different based upon the use of an OLC 10 or OLCT 10

 

-

Cable to be used: 3 conductors, 3x1 mm² LiYCY type

e.g., CONTROLLER MX 15

OLC 10

1 2 3

Connect the 3 wires based on the corresponding numbering on the sensor.

1 2 3

Connect the 3 wires based on the corresponding numbering on the controller.

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

1= signal*

2

 

 

 

 

 

 

 

2= -

3

 

 

 

 

 

 

 

3= +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OLCT 10

EXPLO

*analog signal 4-20 mA (I out) on OLCT 10.