Oldham iTrans User Manual

USER MANUAL
FIXED POINT SINGLE OR DUAL
GAS MONITOR WITH DUAL
ANALOG OUTPUTS
Part Number: 77023554-1 Version: 16.0 Release Date: April 20, 2016
The Fixed Gas Detection Experts
FIXED POINT SINGLE OR DUAL GAS MONITOR WITH DUAL
ANALOG OUTPUTS
Copyright © 2016 by Oldham S.A.S All rights reserved. No reproduction of all or part of this document, in any form, is
permitted without the written consent of Oldham S.A.S.
is a trademark of Oldham. ModBus® is a registered trademark of Schneider Automation Inc. ModBus® protocol™ is a trademark of Schneider Automation Inc. All other trademarks and registered trademarks are the property of their respective
owners. All of the information that is provided in this document is accurate to the best of
our knowledge. As a result of continuous research and development, the specifications of this
product may be changed without prior notice.
Oldham S.A.S Rue Orfila Z.I. Est – CS 20417 F–62027 ARRAS Cedex Tel.: +33 (0)3 21 60 80 80 Fax: +33 (0) 3 21 60 80 00
ii iTrans User Manual (P/N: 77023554-1)
Warnings and Cautionary Statements
CAUTION: Failure to perform certain procedures or note certain conditions may impair the performance of the monitor. For maximum safety and performance, please read and follow the procedures and conditions outlined below.
Oxygen deficient atmospheres may cause combustible gas readings that use
catalytic LEL sensors to be lower than actual concentrations.
Oxygen enriched atmospheres may cause combustible gas readings that use
catalytic LEL sensors to be higher than actual concentrations.
Calibrate the catalytic combustible gas sensor after each incident where the
combustible gas content causes the instrument to enter in the OVER-RANGE alarm condition.
Silicone compound vapors may affect the catalytic combustible gas sensor and
cause readings of combustible gas to be lower than actual gas concentrations. If the sensor has been used in an area where silicone vapors were present, always calibrate the instrument before continued use to ensure accurate measurements.
Sensor openings must be kept clean. Obstruction of the sensor openings may
cause readings to be lower than actual gas concentrations.
Sudden changes in atmospheric pressure may cause temporary fluctuations in
the oxygen readings.
Alarms relays are non-latching. When connecting 4-20 mA outputs to inductive loads, Oldham recommends
using an isolation barrier in line with the 4-20 mA signal.
Interior grounding terminal is to be used for grounding, the exterior terminal is
only to be used for bonding
iTrans Stand-Alone versions with on-board visible alarm are to be
installed in ordinary locations only; however, remote sensors can be installed in hazardous locations (Gas dependent. Read Agency Approvals paragraph).
(P/N: 77023554-1) iTrans User Manual iii
CALIBRATION ALERT: Gas detection instruments are potential life-saving devices. Recognizing this fact, calibration for the toxic and catalytic LEL sensors should be at least at quarterly intervals, while the infrared sensor should be calibrated on an annual basis with function test every 6 months.
Further, Oldham recommends prudent testing and/or includes calibration after a gas alarm. All calibration service to sensors should be recorded and accessible.
CAUTION: For safety reasons, this equipment must be operated and serviced by qualified personnel only.
iv iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Table of Contents
Table of Contents
CHAPTER 1: INTRODUCTION
1.1. Overview of the Gas Monitor ............................................................................1-1
1.2. Specifications .........................................................................................................................1-1
1.3. Agency Approvals - CSA .......................................................................................................1-3
1.4. Special Instructions for Safe Use (EU) ..................................................................................1-5
CHAPTER 2: HARDWARE OVERVIEW
2.1. Main Electronics Unit (Housing) ...........................................................................................2-1
2.2. Sensor .....................................................................................................................................2-2
2.3. Display ....................................................................................................................................2-3
2.4. Inputs – Intrusive and Non-Intrusive ......................................................................................2-3
2.5. Electronics Modules ...............................................................................................................2-4
CHAPTER 3: INSTALLATION
3.1. Introduction ............................................................................................................................3-1
3.2. Installation Considerations .....................................................................................................3-1
3.3. Wall Mounting........................................................................................................................3-1
3.4. Column Mounting ..................................................................................................................3-1
CHAPTER 4: SYSTEM WIRING
4.1. Introduction ............................................................................................................................4-1
4.2. Wiring Preparation .................................................................................................................4-1
4.3. Alarm Relay Wiring (J1, J5, and J6) ......................................................................................4-2
4.4. Power and Output Wiring (J1) ...............................................................................................4-3
4.5. Sensor Wiring (J3) ..................................................................................................................4-4
4.6. Digital ModBus RTU Interface Wiring (J1) ..........................................................................4-9
4.6.1. ModBus Interface Wiring Overview..........................................................................4-9
4.6.2. Setting the ModBus Address on the ......................................................4-9
4.6.3. Setting the ModBus Address for Stand-Alone Sensors ...........................................4-10
4.7. Wiring Conclusion................................................................................................................4-12
CHAPTER 5: OPERATION
5.1. Initial Start-up .........................................................................................................................5-1
5.2. Warm-up Period .....................................................................................................................5-1
5.3. Normal Operating Mode.........................................................................................................5-2
5.4. Programming Mode Overview ...............................................................................................5-3
5.5. Programming Mode – Non-intrusive Operation .....................................................................5-4
5.5.1. Introduction ................................................................................................................5-4
5.5.2. Sensor Type ...............................................................................................................5-5
5.5.3. Zeroing .......................................................................................................................5-5
5.5.4. Calibration ..................................................................................................................5-6
5.5.5. Changing Span Gas Concentration ............................................................................5-7
5.5.6. Sensor Span Reserve ..................................................................................................5-8
5.6. Programming Mode – Push Button Operation .......................................................................5-8
5.6.1. Introduction ................................................................................................................5-8
5.6.2. Entering Programming Mode and Selecting a Channel .............................................5-9
5.6.3. Set Low Alarm .........................................................................................................5-10
(P/N: 77023554-1) iTrans User Manual v
Table of Contents iTrans Fixed Point Single/Dual Gas Monitor
5.6.4. Set High Alarm ........................................................................................................5-10
5.6.5. 4-20 mA Analog Output Range ...............................................................................5-10
5.6.6. Set System Time – Minute .......................................................................................5-11
5.6.7. Set System Time – Hour ..........................................................................................5-11
5.6.8. Set System Time – Date ...........................................................................................5-12
5.6.9. Set System Time – Month ........................................................................................5-12
5.6.10. Set System Time – Year ..........................................................................................5-13
5.6.11. Zeroing ....................................................................................................................5-13
5.6.12. Calibration ...............................................................................................................5-14
5.6.13. Changing Span Gas Concentration ..........................................................................5-15
5.6.14. Sensor Span Reserve ................................................................................................5-16
5.6. Special Notes on Using Broadband Infrared (BBIR) Sensors ..............................................5-17
CHAPTER 6: MODBUS INTERFACE
6.1. Introduction ............................................................................................................................6-1
6.2. Sample Gas Reading via ModBus Network ...........................................................................6-1
6.3. ModBus Register List ............................................................................................6-2
6.4. ModBus Resources .................................................................................................................6-6
6.5. Termination ............................................................................................................................6-6
CHAPTER 7: MAINTENANCE
7.1. Introduction ............................................................................................................................7-1
7.2. Sensor Replacement ...............................................................................................................7-2
7.3. Zero and Calibration ...............................................................................................................7-2
CHAPTER 8: TROUBLESHOOTING
8.1. Introduction ............................................................................................................................8-1
8.2. Diagnosing Common Problems ..............................................................................................8-1
8.3. Fault Codes .............................................................................................................................8-2
8.4. Function Codes .......................................................................................................................8-3
CHAPTER 9: WARRANTY
9.1. Warranty .................................................................................................................................9-1
9.2. Limitation of Liability ............................................................................................................9-1
APPENDIX A: ACRONYMS AND ABBREVIATIONS APPENDIX B: DECIMAL, BINARY, AND HEXADECIMAL EQUIVALENTS APPENDIX C: ORDERING MATRIX APPENDIX D: FACTORY DEFAULT SETTINGS APPENDIX E: EU DECLARATION OF CONFORMITY CERTIFICATE APPENDIX F: INDEX
vi iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Introduction
INTRODUCTION
Chapter
1
The fixed gas monitor is an independent monitor capable of displaying one or two gas concentrations as well as sensor or instrument comes standard with independent 4-20 mA outputs for each channel, making it ideal for interfacing to control units. A digital ModBus RTU interface is also available, allowing the to interface to digital control systems. The is available with an optional relay board, allowing the unit to directly control external devices such as fans, pumps, alarm horns, or warning lights. Two of the relays can be programmed for alarm activation, while the third relay is a fault protection relay.
Figure 1-1. Typical Gas
Monitor with Single Gas Sensor
(Stainless Steel Option)
1.1. Overview of the Gas Monitor
Calibration, changing span gas concentration, and checking the instrument’s configuration are easily accomplished using the non-intrusive magnetic wand.
The is powered with a 24 VDC (12-28 VDC) power supply and provides a 4-20 mA control signal for each sensor.
1.2. Specifications
Specifications for the gas monitor are listed in Table 1-1.
(P/N: 77023554-1) iTrans User Manual 1-1
Introduction iTrans Fixed Point Single/Dual Gas Monitor
Item
Description
Enclosure
Cast aluminum, poly-bonded coating or 316 stainless steel. Both are explosion-proof, NEMA 4X, IP66 rated.
Dimensions
5.0 6.0 5.0 inches (127 153 129 mm)
Sensors
Combustible Gases: Catalytic bead and/or Non-Dispersive Infrared (NDIR)
Oxygen/Toxic Gases: Electrochemical diffusion
Input Voltage
12-28 VDC operating range (24 VDC typical), 350 mA (nominal) Maximum current draw of 600 mA with 2 LEL sensors installed
Input Current (Max)
Toxic Gas/Oxygen
150 mA @ 24 VDC (single gas)
Combustible Gases (Catalytic)
175 mA @ 24 VDC, 0.6 A peak (single gas)
Combustible Gases (Infrared)
150 mA @ 24 VDC, 0.6 A peak (single gas)
Combined Catalytic/Infrared
280 mA @ 24 VDC (two gas)
Display
Dual-channel split-screen LED display (4-digit, 7-segment arrangement per channel) provides simultaneous display of one or two gases.
Signal Outputs
Digital
ModBus RTU: RS485 digital communication with ModBus RTU software protocol system at 9600 baud. Three- or four-wire system accommodates over 200 devices in bus configuration. Address selection through on-board 8-position DIP switch. NOTE: ModBus is not to be used for CSA C22.2 No. 152 compliance.
Analog
4-20 mA (linear analog)
Alarm Relays Quantity
3 alarm relays: Two user-programmable relays, SPST, N.O.; plus one fault relay, SPST, N.C.
Contact Capacity
5A @ 30 VDC 5A @ 30 VAC
Temperature Range
-40º C ~ +75º C (-40º F ~ +167º F)
-20º C ~ +50º C (-4º F ~ +122º F) for BBIR only
Humidity Range
10% - 90% RH (non-condensing), typical Pressure
Atmospheric pressure 10%
Table 1-1. Specifications for the Monitor
1-2 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Introduction
Sensor
Gas
Range/Resolution
Combustible Gases
LEL
0 -100% LEL in 1% increments
Hydrogen
H2
0 - 999 ppm in 1 ppm increments
Oxygen
O2
0 - 30.0% by vol. in 0.1% increments
Ammonia
NH3
0 - 500 ppm in 1 ppm increments
Carbon Monoxide
CO
0 - 999 ppm in 1 ppm increments
Carbon Monoxide/H2 Null
CO
0 - 999 ppm in 1 ppm increments
Hydrogen Sulfide
H2S
0 - 500 ppm in 1 ppm increments
Sulfur Dioxide
SO2
0.2 - 99.9 ppm in 0.1 ppm increments
Hydrogen Cyanide
HCN
0.2 – 30.0 ppm in 0.1 ppm increments
Hydrogen Chloride
HCl
0.2 - 30.0 ppm in 0.1 ppm increments
Phosphine
PH3
0 - 1.00 ppm in 0.01 ppm increments
Nitrogen Dioxide
NO2
0.2 - 99.9 ppm in 0.1 ppm increments
Nitric Oxide
NO
0 - 999 ppm in 1 ppm increments
Chlorine
Cl2
0.2 - 99.9 ppm in 0.1 ppm increments
Chlorine Dioxide
ClO2
0.02 - 1.00 ppm in 0.01 ppm increments
Table 1-2. Sensor Ranges
1.3. Agency Approvals
The is certified by CSA, a NRTL laboratory, to the following US and Canadian Standards.
UL Std No. 916-Energy Management Equipment UL Std No. 1203-Explosion-Proof and Dust-Ignition-Proof
o Electrical Equipment for Use in Hazardous (Classified) Locations
UL Std No. 1604-Division 2 Hazardous Location Electrical Equipment ISA S12.13 Part I-2000-Performance Requirements, Combustible Gas
Detectors (catalytic sensors only)
CSA Std C22.2 No.30-M1986-Explosion-Proof Enclosures for Use in
Class I Hazardous Locations
CSA Std C22.2 No.142-M1987-Process Control Equipment
(P/N: 77023554-1) iTrans User Manual 1-3
Introduction iTrans Fixed Point Single/Dual Gas Monitor
CSA Std C22.2 No. 152-M1984-Combustible Gas Detection Instruments
(catalytic sensors only)
CSA Std C22.2 No. 213-M1987-Non-incendive Electrical Equipment for
Use in Class I, Division 2 Hazardous Locations
Marking: Transmitter Class I, Div 1, Groups B, C, D AEx d IIB + H2 T5
Sensor
Ambient for Model 7701-5857 Fixed IR sensor (BBIR) is -20C to +55C. Ambient for all other devices is
-40C to +75C.
(gas dependent)
(1)
Class I, Div 1, Groups B, C, D – AEx d IIB + H2 T5
(2)
Class I, Div 2, Groups A, B, C, D – AEx d IIB + H2 T5
The is certified under the IECEx scheme to:
IEC 60079-0:2007 - Electrical apparatus for potentially explosive atmospheres–General requirements.
IEC 60079-1:2003 - Electrical apparatus for potentially explosive
atmospheres–Flameproof enclosures ‘d’.
IEC 60079-15:2005 - Electrical apparatus for explosive gas atmospheres.
Type of protection "n".
Marking: Transmitter Ex d IIB+H2 T5; IP66; Ta (-40°C to +75°C)
Sensor
(gas dependent)
(1)
Ex d IIB+H2 T5 ; IP66 ; Ta (-40°C to +75°C)
(2)
Ex nA II T5; Ta (-40°C to +75°C)
The complies with relevant provisions, per listed standards, of European ATEX Directive 94/9/EC and EMC Directive 89/336/EEC, amended by Directives 92/31/EEC and 93/68/EEC, and is constructed with reference to published standards of Directive 72/23/EEC, to eliminate electrical risks and fulfill 1.2.7 of Annex II of Directive 94/9/EC.
EN 60079-0:2004 - Electrical apparatus for potentially explosive
atmospheres – General requirements.
EN 60079-1:2004 - Electrical apparatus for potentially explosive
atmospheres – Flameproof enclosures ‘d’.
EN 60079-15:2003 - Electrical apparatus for explosive gas atmospheres.
Type of protection “n”.
1-4 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Introduction
EN 50270: Electromagnetic compatibility - Electrical apparatus for the
detection and measurement of combustible gases, toxic gases or oxygen (for Type 2 [Industrial] Apparatus).
The EC type examination certificate is KEMA 04 ATEX 2216X, with Marking code: Transmitter Ex d IIB+H2 T5; Ta (-40°C to +75°C)
Sensor
(gas dependent)
(1)
Ex d IIB+H2 T5 ; Ta (-40°C to +75°C)
(2)
Ex nA II T5; Ta (-40°C to +75°C)
(1)
LEL, H2, O2, CO, H2S, SO2, HCN, PH3, NO2, NO, CO2
(2)
Cl2, HCl, NH3, ClO2
(P/N: 77023554-1) iTrans User Manual 1-5
Introduction iTrans Fixed Point Single/Dual Gas Monitor
1.4. Special Instructions for Safe Use (EU)
Cable connection: The cable entry device shall be of a certified flameproof
type, suitable for the conditions of use and correctly installed.
Conduit Connection: An Ex d certified sealing device, such as, a conduit
seal with setting compound, suitable for the conditions of use, and correctly installed, shall be provided immediately to the entrance of the housing.
Unused openings: Unused openings shall be closed with suitable Ex d
certified closing elements.
Dual Onboard: The “Y” adapter parts used to assemble dual onboard
configurations do not have Atex approval. Consult factory for dual onboard Atex options.
  
1-6 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Introduction
(P/N: 77023554-1) iTrans User Manual 1-7
iTrans Fixed Point Single/Dual Gas Monitor Hardware Overview
HARDWARE OVERVIEW
Chapter
2
2.1. Main Electronics Unit (Housing)
The body is a cast aluminum housing that contains the electronics of the gas monitor. Details of a single-gas housing are shown in Figure 2-1.
Figure 2-1. Details of a Single-Gas Gas Monitor
(P/N: 77023554-1) iTrans User Manual 2-1
NOTE: Dimensions are in inches.
Hardware Overview iTrans Fixed Point Single/Dual Gas Monitor
Item
Descriptions
Catalytic and Toxics
Infrared (BBIR)
Sensor Housing Material
Aluminum, Anodized Explosion-proof: Class I, Divisions 1
and 2, Groups B, C, D and Ex d IIB +H2 T5 (ATEX and IECEx), Ex d
IICT6 Gb (China)
Stainless Steel Explosion-proof: Class I,
Divisions 1 and 2 Groups B, C, D, and Ex d IIB +H2 T4 (Europe), Ex d IIC T4 or IIC
T6 (China)
Aluminum, Anodized w/Gore-Tex Membrane: Class I, Division 2, Groups A, B, C, D and Ex nA IIC T5 (IECEx) and Ex nA II T5 (ATEX).
Dimensions
3.0 3.0 inches (76 76 mm)
3.5 3.0 inches (89 76 mm)
Accuracy
<  3% Toxic and Oxygen
<  5% Combustibles
Protection Class
IP 66 or NEMA4X
2.2. Sensor Table 2-3. Sensor Specifications
2-2 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Hardware Overview
2.3. Display
The gas monitor has a 4-digit, 7-segment LED display for each of 2 channels. A dual-gas sensor and sample display are shown in Figure 2-2.
Figure 2-2. The Display (Dual-Gas Monitor Shown)
2.4. Inputs – Intrusive and Non-Intrusive
The gas monitor can be configured using intrusive and non-intrusive means. Both methods of configuration are accomplished through physical inputs that are visible behind the glass panel of the gas monitor.
A set of four keys are used when intrusive programming is appropriate (i.e., when the enclosure can be removed and when the keys can be manually pressed). These keys are the mode, increment (+), decrement (-), and enter keys. Refer to Figure 2-3.
For applications that require non-intrusive manipulation, two magnetically­activated reed switches are used to accomplish programming without removing the cover. A magnetic wand is positioned over the appropriate reed switch (above the glass face plate) without the wand physically touching the reed switches. The locations of the reed switches are shown in Figure 2-3.
(P/N: 77023554-1) iTrans User Manual 2-3
Hardware Overview iTrans Fixed Point Single/Dual Gas Monitor
Figure 2-3. Locations of Input Keys and Reed Switches
Programming the gas monitor in both intrusive and non-intrusive modes is explained in detail in Chapter 5: Operation.
2.5. Electronics Modules
The electronics module of the gas monitor contains connectors and jumpers for wiring and configuring the device. The electronics module for a main
unit is shown in Figure 2-4. The electronics module for a remote unit is shown in Figure 2-5. Wiring details are explained in Chapter 4: System Wiring.
2-4 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Hardware Overview
Figure 2-4. Electronics Module for (Main Unit)
Figure 2-5. Electronics Board for Remote Sensor
(P/N: 77023554-1) iTrans User Manual 2-5
Hardware Overview iTrans Fixed Point Single/Dual Gas Monitor
2-6 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor Installation
INSTALLATION
Chapter
3
3.1. Introduction
The can be mounted in one of two ways. The unit can be wall-mounted using the wall mounting holes in the enclosure, or it can be mounted onto a column using U-bolts. Each of these options is discussed in this chapter. Be sure to review the installation considerations before mounting the gas monitor.
3.2. Installation Considerations
Regardless of the installation type (wall mounting or column mounting), the
should be installed at or near the location of a possible leak or the source of emissions. Installation height depends on the density of the gas being monitored. Moreover, speed and direction of air flow, and relative position to potential leaking points should also be considered.
IMPORTANT: The gas monitor must not be installed on vibrating or heat generating sources.
3.3. Wall Mounting
If your application is best addressed using a wall-mounted gas monitor, then use the four 8 mm mounting holes in the enclosure to secure the to an appropriate location on the wall. Refer to Figure 3-1.
3.4. Column Mounting
If your application is best addressed using a column-mounted gas monitor, then use the four 8 mm mounting holes and two U-bolts to secure the to an appropriately located segment of a target pipe or conduit. Refer to Figure 3-2.
(P/N: 77023554-1) iTrans User Manual 3-1
Installation iTrans Fixed Point Single/Dual Gas Monitor
Figure 3-1. Mounting the Gas Monitor on a Wall
Figure 3-2. Mounting the Gas Monitor on a Column Using U-Bolts
3-2 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor System Wiring
SYSTEM WIRING
Chapter
4
4.1. Introduction
This chapter outlines the steps required for wiring the gas monitor. These steps include the following:
Wiring Preparation Sensor Wiring Alarm Relay Wiring Power and Output Wiring ModBus Interface Wiring.
Each of these steps is outlined in the sections that follow.
IMPORTANT: Perform all wiring in accordance with local electrical codes and local authorities having jurisdiction.
IMPORTANT: DC signal and AC power should not be run in the same conduit.
NOTE: All field wiring colors are arbitrary (unless provided by Oldham).
4.2. Wiring Preparation
1. Collect the appropriate types and lengths of wire.
For control wire, use #18 AWG insulated, shielded cable. For signal and power wire, use three-conductor (or four-conductor for dual
channel) #18 AWG insulated and shielded cable.
For digital ModBus signal and power, use a minimum of five-conductor
#18 AWG insulated and shielded cable.
2. Power down the unit.
3. Unthread the windowed top from the housing.
4. Gently pull out the electronics module and place it safely to the side of the unit.
5. Thread control, signal, and power wires into the transmitter housing.
(P/N: 77023554-1) iTrans User Manual 4-1
System Wiring iTrans Fixed Point Single/Dual Gas Monitor
6. Shielding from either the controller or remote sensors should be bonded to the
enclosure screw located inside the .
IMPORTANT: Use of this product in areas where it may be subject to large amounts of electromagnetic interference may affect the reliable operation of this device and should be avoided.
WARNING: Supply wire with a minimum rating of 90oC must be used for interconnection to the .
NOTE: For classified locations, a “poured” wire seal must be installed within 18 inches of the main unit for both power entry and remote sensors.
NOTE: Remove power from the before making any wiring connections.
4.3. Alarm Relay Wiring (J1, J5, and J6)
To connect the control wires to the three relay terminals on the relay board, wire the unit to the connectors shown in Figure 2-4. The low alarm relay is activated when the low alarm threshold is met. This is a non-latching, Normally Open (NO) contact. The high alarm relay is activated when the high alarm threshold is met. This is a non-latching, Normally Open (NO) contact. The fault alarm relay is activated upon power-up of the . When the fault condition is met, the circuit opens. This is an Electronically closed (NO) contact. See Figure 4-1 for relay wiring.
NOTE: It is recommended that on-board relays should not be used to drive loads directly. On-board relays should be used to drive a secondary, higher-power relay which is connected to the control device (e.g., strobe, siren, exhaust fan, etc.).
4-2 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor System Wiring
Figure 4-1. Alarm Relay Connectors J6, J5 and J1
4.4. Power and Output Wiring (J1)
Connect the power and signal wires to the appropriate wiring terminals as follows.
24 V: Connect 24 VDC (12-28 VDC) supply power CH 1: Channel 1, 4-20 mA output signal CH 2: Channel 2, 4-20 mA output signal GND: DC return
Figure 4-2. Power and Signal Connector J1 on the
NOTE: Use supplied green conductor for enclosure ground. Public 485 GND is
to be used for ModBus digital ground.
NOTE: The is a 3- or 4-wire 4-20 mA device. For dual sensor configuration you must have a second 4-20 mA signal wire pulled to the unit.
(P/N: 77023554-1) iTrans User Manual 4-3
System Wiring iTrans Fixed Point Single/Dual Gas Monitor
NOTE: When not using 4-20 mA outputs, use the supplied resistors to connect CH-1 and CH-2 to GND. If these resistors are not connected and the 4-20 mA outputs are not used, a “P” will appear on the display, indicating an open loop condition.
4.5. Sensor Wiring (J3)
Connect the sensor wires (for on-board, remote or stand-alone) to the appropriate wiring terminals as follows.
24 V: Red wire from sensor head (Red wire on BBIR) 485A: Yellow wire from sensor head (White wire on BBIR) 485B: Black wire from sensor head (Green wire on BBIR) GND: Green wire from sensor head (Black wire on BBIR)
NOTE: Shielding from either the controller or remote sensors should be bonded
to the enclosure screw located inside the .
NOTE: The 24 V terminal supplies 24 VDC to the sensor for power. This terminal should not be connected to the output of a 24 VDC power supply.
Figure 4-3. Sensor Connector J3 on the
NOTE: For dual-sensor configurations, place both of the same colored wires in
the appropriate terminal block and firmly tighten.
4-4 iTrans User Manual (P/N: 77023554-1)
iTrans Fixed Point Single/Dual Gas Monitor System Wiring
NOTE: Use #18 AWG shielded cable for remote sensors. Maximum distance is 200 meters (BBIR maximum distance is 300 feet with #18 AWG wire).
NOTE: When wiring remote sensors to the , “485 B” on J3 should be connected to “B-” in the remote sensor enclosure, and “485 A” on J3 should be connected to “A+” in the remote sensor enclosure.
NOTE: For remote or standalone sensors, there are four terminal blocks located in the remote sensor housing. These terminal blocks are all tied together and follow the same wiring scheme mentioned above.
(P/N: 77023554-1) iTrans User Manual 4-5
Loading...
+ 61 hidden pages