Oldham BM25, BM25W User Manual

BM 25/25W
Area
Gas Monitor
User Manual
2
BM 25/25W
Instruction Manual
Copyright Mars 2016 by Oldham S.A.S. All rights reserved. The reproduction of all or any section of this document in
any form whatsoever without the written permission of Oldham S.A.S. is forbidden.
The information contained in this manual is accurate to our knowledge. As a result of continuous research and development, the specifications of
this product may be modified at any time without prior notice. Oldham S.A.S. Rue Orfila Z.I. Est – CS 20417 62027 ARRAS Cedex Tel.: +33 (0)3 21 60 80 80 Fax: +33 (0)3 21 60 80 00
Table of Contents
3
Contents
Chapter 1 | Introduction ........................................................... 9
General information .................................................................................... 9
Product Overview ..................................................................................... 10
Additional equipment ................................................................................ 12
Connections ............................................................................................. 13
Gas sensors ............................................................................................. 15
LCD Display ............................................................................................. 16
Visual alarm.............................................................................................. 17
Audible alarm ........................................................................................... 17
Sampling system ...................................................................................... 17
Chapter 2 | Installation and Connections .............................. 19
Power supply ............................................................................................ 19
Charging the batteries .............................................................................. 19
Alarm Transfer.......................................................................................... 21
Connection of a manual call point ............................................................ 22
Chapter 3 | Operation ............................................................. 23
Start-up ..................................................................................................... 23
Gas monitor positioning ........................................................................... 24
Diffusion mode ......................................................................................... 24
Aspirated mode (with pump option) ......................................................... 25
Measurements.......................................................................................... 27
Alarms ...................................................................................................... 29
Data transfer............................................................................................. 32
Switching off the instrument ..................................................................... 33
Chapter 4 | Wireless Version ................................................. 35
Overview .................................................................................................. 35
Start-up ..................................................................................................... 39
Self-healing .............................................................................................. 42
Mac list menu ........................................................................................... 45
Chapter 5 | Maintenance ........................................................ 47
Accessing maintenance menus ............................................................... 47
Program Menu.......................................................................................... 48
4
BM 25/25W
Instruction Manual
Sensor calibration menu .......................................................................... 50
Auto-adjustment menu ............................................................................. 50
Date and time management menu ........................................................... 50
Radio communication menu ..................................................................... 50
MAC List menu ......................................................................................... 50
Exit menu ................................................................................................. 50
Chapter 6 | COM2100 software .............................................. 51
Subject ..................................................................................................... 51
Gas monitor connection ........................................................................... 52
Maintenance menu ................................................................................... 52
Alarm relay configuration and logic inputs ............................................... 57
Screen menu ............................................................................................ 58
Chapter 7 | Technical Specifications ..................................... 59
Gas monitor .............................................................................................. 59
Sensors .................................................................................................... 61
Chapter 8 | Accessories and Spare Parts ............................. 67
Accessories .............................................................................................. 67
Spare Parts .............................................................................................. 68
Chapter 9 | Special Instructions for use in explosive
atmospheres or hazardous locations ...................................... 71
ATEX areas and general rules ................................................................. 72
Input/output parameters ........................................................................... 72
Trickle charging connection (external power source) .............................. 73
Connectors wiring diagram ...................................................................... 73
ATEX and IECEx Markings ...................................................................... 74
Radio Communication Marking ................................................................ 75
Chapter 10 | Declaration of EC Conformity .......................... 77
General Information
5
Thank you for choosing this OLDHAM instrument. All of the necessary actions have been taken in order to ensure your complete
satisfaction with this equipment. It is important that you read this entire manual carefully and thoroughly.
The extent of our responsibility
OLDHAM shall not be held responsible for any damage to the equipment or for any
physical injury or death resulting in whole or in part from the inappropriate use, installation, or storage of the equipment, which is the result of not complying with the instructions and warnings, and/or with the standards and regulations in force.
OLDHAM does not support or authorize any business, person, or legal entity in
assuming responsibility on behalf of OLDHAM, even though they may be involved in the sale of OLDHAM products.
OLDHAM shall not be responsible for any damage, direct or indirect, or for
damages and interest, direct or indirect, resulting from the sale and use of any of its products UNLESS SUCH PRODUCTS HAVE BEEN DEFINED AND CHOSEN BY
OLDHAM FOR THE USE THAT THEY ARE INTENDED.
Ownership clauses
Drawings, specifications, and information herein contain confidential information
that is the property of OLDHAM.
This information shall not, either in whole or in part, by physical, electronic, or any
other means whatsoever, be reproduced, copied, divulged, translated, or used as the basis for the manufacture or sale of OLDHAM equipment, or for any other reason without the prior consent of OLDHAM.
6
BM 25/25W
Instruction Manual
IMPORTANT: Read and understand this manual before operating.
WARNING: SERVICING THE UNIT OR CHANGING THE BATTERIES
MUST ONLY BE DONE IN AN AREA KNOWN TO BE NONHAZARDOUS.
Prior to each day’s use, a bump test should be performed. If the instrument does not pass the bump test, a full calibration is recommended.
Oxygen deficient atmospheres may cause combustible gas readings to be lower than actual concentrations.
Oxygen enriched atmospheres may cause combustible gas readings to be higher than actual concentrations.
Verify the calibration of the combustible gas sensor after any incident where the combustible gas content has caused the instrument to display an over­range condition.
Silicone compound vapors or other known contaminants may affect the combustible gas sensor and cause readings of combustible gas to be lower than actual gas concentrations. If the instrument has been used in an area where silicone vapors were present, always calibrate the instrument before next use to ensure accurate measurements.
Sensor openings and water barriers must be kept clean. Obstruction of the sensor openings and/or contamination of the water barriers may cause readings to be lower than actual gas concentrations.
When in the hazardous area, connections to the battery charging or communications ports must be done in accordance with this technical manual.
WARNING: Substitution of components may impair intrinsic safety and may cause an unsafe condition.
Warnings and cautionary statements
This is not a contractual document. In the best interest of its customers and with the aim of improving performance, OLDHAM reserves the right to alter the technical features of its equipment without prior notice.
IMPORTANT: Failure to perform certain procedures or note certain conditions may impair the performance of this product. For maximum safety and optimal performance, please read and follow the procedures and conditions listed below.
General Information
7
CAUTION: For safety reasons, this equipment must be operated and
serviced by qualified personnel only. Read and understand the instruction manual completely before operating or servicing.
CAUTION: High off-scale readings may indicate explosive concentration.
CAUTION: Any rapid up-scale reading followed by a declining or erratic
reading may indicate a gas concentration beyond the upper scale limit which may be hazardous.
CAUTION: Before each day’s usage, sensitivity must be tested on a known concentration of pentane or methane equivalent to 25%-50% of full scale concentration. Accuracy must be within -0% to +20% of actual concentration. Accuracy may be corrected by referring to the zero/calibration section of the instruction manual.
BM 25/25W (with radio communication module) complies with Part 15 of FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interferences, and (2) this device must accept any interference received, including interference that may cause undesired operation.
BM 25/25W complies with FCC Maximum Permissible Exposure (MPE) requirements when used with an approved antenna and the antenna is at least 20cm away from the user. Use of the product closer than 20cm may exceed the MPE limits. Use of any antenna other than approved antennas will invalidate the certification of the product.
European Union (and EEA) only. This symbol indicates that, in conformity with directive DEEE (2002/96/CE) and according to local regulations, this product may not be discarded together with household waste.
Warranty
Under normal conditions of use and on return to the factory, parts and workmanship
carry a two year warranty, excluding consumables such as sensors, filters, etc.
Destruction of the equipment
It must be disposed of in a collection area that is set aside for this purpose, for example at a site that is officially designated for the recycling of electrical and electronic equipment (EEE) or a point of exchange for authorized products in the event of the acquisition of a new product of the same type as before.
8
BM 25/25W
Instruction Manual
1 – Introduction
9
Chapter 1 | Introduction
General information
The BM 25/25W is a portable gas monitor that can be used in explosive gas atmospheres.
It provides simultaneous detection of up to five gases present in the air by means of sensors specific to each risk to be evaluated (under-oxygenation, presence of combustible or toxic gases).
Figure 1
10
BM 25/25W
Instruction Manual
Product Overview
Figure 2: Product Overview
1 – Introduction
11
Ref.
Description
See page
1.
Carrying handle
2.
LED alarm indicator (visual warning for gas alarms, transferred alarms and faults)
Low Alarm: slow flash (1 Hz)
High Alarm: rapid flash (2 Hz)
Alarm Transfer: very slow flash (0.5 Hz)
Fault: steady (0 Hz)
29
3.
Loud speakers (audible warning for gas alarms, transferred alarms and faults)
Low Alarm: two-tone, slow (1 Hz)
High Alarm: two-tone, rapid (2 Hz)
Alarm Transfer: two-tone, very slow (0.5 Hz)
Fault: mono-tone, continuous (0 Hz)
29
4.
Charging port connection (red ring)
19
5.
Trickle charge port connection (black ring)
20
6.
Alarm acknowledgement and Menu key (*)
-
7.
Backlight/Menu key (*)
-
8.
On/Off/Enter key (*)
23
9.
LCD display
16
10.
Gas sensors
15
11.
Infrared port connection
51
12.
Relay outputs (black ring)
14
13.
Dry logic inputs (yellow ring)
14
14.
Brief instructions for use and approval label
-
(*) Push buttons are "piezo" type
12
BM 25/25W
Instruction Manual
Ref.
Description
See page
1.
Sensors Cover for use with aspirated versions (*)
25
2.
Calibration cup for use with manual sampling system or for sensors calibration
26
3.
Intrinsically Safe Trickle Charge Kit (provided with cables)
20
4.
Calibration/Sample tubing
-
5.
Communication Adaptor
51
6.
Universal charger 110/230 VAC
19
7.
Cable for IS power supply (see 3)
-
8.
Cable for alarm transfer (25, 50 or 100 meters)
21
Additional equipment
Figure 3: accessories
(*) Optional
1 – Introduction
13
Connection to Oldham universal charger
(110/230 VAC) or charger for vehicle (12/30 VDC)
Pin 1: V- charge
Pin 4: V+ charge
Connection prohibited in hazardous area.
Unused connectors must be equipped with their protective cap.
See details on pages 19.
Figure 4: local charging port
Only for connection to the intrinsically safe
certified trickle charger
Pin 1: V+ trickle charge
Pin 2: V- trickle charge
Pin 3: V+ trickle charge
Pin 4: V- trickle charge
Pins 1-3 and 2-4 are connected in parallel.
Unused connectors must be equipped with their protective cap.
See details on page Erreur ! Signet non défini..
Figure 5: trickle charge port
Connections
Charging port connection (red ring)
Trickle charge port connection (black ring)
14
BM 25/25W
Instruction Manual
Pins 1-6: alarm relay (NO) output
Pins 3-4: fault relay (NC) output
Unused connectors must be equipped with their protective cap.
See details on pages 21 and 57.
Figure 6: relay outputs
Pin 2: logic input for alarm transfer
Pin 5: logic input for alarm acknowledgement
Pin 7: common ground
Unused connectors must be equipped with their protective cap.
See details on pages 22 and 57.
Intrinsic safety parameters
Alarm relay output: dry relay contact,
Ui = 30 V, Ii = 150 mA, no L or C condition
Power supply for trickle charging: Ui = 30 V,
Ii = 160 mA, no L or C condition
Dry logic input: Uo = 5 V, Io = 50 mA, Lo = 8
mH, Co = 7 µF
Figure 7: dry logic inputs
The person responsible for the gas monitor must create a Descriptive System Document (for intrinsically safe circuits).
Relay Outputs (black ring)
Dry logic inputs (yellow ring)
1 – Introduction
15
Ref.
Description
1.
Combustible gas sensor (0 to 100% LEL)
2.
Mini sensors for toxic gases or the 1 year O2 sensor
3.
Mini sensors for toxic gases or the 1 year O2 sensor
4.
Medium sensors for:
O
2
(>2 year lifetime)
CO/H
2
S (combo medium sensor) and other toxic gases
CO
2
IR
5.
Medium sensors for:
O
2
sensor (>2 year lifetime)
Toxic gases (medium sensors except CO/H
2
S sensor)
CO
2
IR
Infrared sensor for combustible gases
PID sensor for VOCs (Volatile Organic Compounds)
Gas sensors
The sensors are located on the front of the monitor (Figure 2, ref. 10). They are smart, pre-calibrated from factory and interchangeable. They are composed of a sensitive element and electrical components, including an EEPROM memory in which the sensor characteristics are stored (gas type, range, span value, instantaneous, STEL and TWA alarm values, date of manufacture, serial number, date of last calibration, span reserve, etc.). The span reserve is updated after each calibration and allows the user to gage the optimal time for changing the sensor. Sensors must be positioned as indicated in the table above.
Figure 8: sensors configuration
16
BM 25/25W
Instruction Manual
Sensor slots and protection filters must be kept clean. Otherwise, gas measurements could be jeopardized.
Note:
If a sensor is present in slot #5, then sensor in slot #2 is not monitored
The “combo” CO/H
The PID sensor can only be plugged in slot #5
S sensor can only be plugged in slot #4
2
LCD Display
The instrument features a graphic LCD display with backlit (Figure 2, ref. 9). It automatically illuminates when an alarm or a fault occurs. It can be rotated by 180° using COM2100.
Figure 9: LCD display
The following information is displayed:
Up to 5 gas measurements along with gas names and units
Maintenance call for calibration
Date and time
Minimum and maximum values (peak) measured
STEL (short-term exposure limit) and TWA (time-weighted average) values
Remaining battery runtime (bargraph)
User’s and/or location’s identification
Maintenance menus
Alarm events (gas alarm, alarm transfer, sensor fault, battery fault, etc.)
1 Introduction
17
Visual alarm
A red bright flashlight (Figure 2, ref. 2) visible from all direction is located on the top of the device and alerts the user in the event of an alarm.
Audible alarm
Two powerful speakers (103 dB at 1 meter) located on each side of the BM 25/25W (Figure 2, ref. 3) alert the user in the event of an alarm.
Sampling system
The gas monitor can be equipped with an internal electric pump or an external manual aspirator for confined space monitoring.
18
BM 25/25W
Instruction Manual
2 – Installation and Connections
19
The gas monitor is approved for use in explosive atmosphere only when it is equipped with the battery pack type recommended by the manufacturer. Before changing the battery pack, make sure the instrument is off.
Charging the BM 25/25W with the truck-charger or the universal charger shall be done in non-classified area only.
Chapter 2 | Installation and
Connections
Power supply
General Information
Power is supplied to the gas monitor through an interchangeable and rechargeable battery pack (NiMH 7.2 V / 9 Ah). Under normal usage conditions and no radio communication, the battery life ranges from 40 to 170 hours depending on the configuration (100 hours under typical configuration: diffusion mode with 1 catalytic or 1 infrared sensor and 2 electrochemical sensors). For the wireless version, the battery life ranges from 35 to 135 hours (65 hours under standard configuration).
Charging the batteries
Charger for vehicle (12 to 30 VDC) or 110/230 VAC universal charger
Insert the male connector (Figure 10, ref. 1) from the charger (ref. 3) into the corresponding charging port and identified with a red ring (ref. 2) on the BM 25/25W. Connect the other end of the power supply (ref. 4) to the power source. Charging time is 4.5 hours with the 110/230 VAC universal charger.
20
BM 25/25W
Instruction Manual
The trickle charge connector (Figure 11, ref. 1) must be located in a non­hazardous location. The BM 25/25W can be used in hazardous area while trickle charging.
Figure 10: charging in safe area
Trickle charge kit
An intrinsically safe power supply (Figure 11: trickle charger connection provides power to the monitor while it is located in hazardous area through a dedicated connector on the left side (Figure 2, ref. 5). In this configuration, the internal battery is charged very slowly. The current supplied by the trickle charger is mostly used to power the electrical circuits.
Intrinsically safe power supply (trickle charger) features:
Io ≤ 160 mA.
Pmax= 1.2 W.
Maximum cable resistance = 16 ohm, based on a maximum cable length of 500
meters (AWG 16 – 1,5mm²).
Trickle chargers are available with 25, 50 or 100 meters of cable. The dual charging kits are intended for use with BM 25/25W monitors equipped with two high current draw sensors (catalytic, infrared, PID) or when the pump is continuously running. Only intrinsically safe power supplies provided by OLDHAM can be used.
Insert the male connector (Figure 11, ref. 6) from the trickle charger (ref. 1 and 3) into the port with a black ring that is located on the left side of the BM 25/25W (ref. 4). Connect the other end of the power supply (ref. 2) to the mains and only in areas known to be safe.
2 – Installation and Connections
21
Figure 11: trickle charger connection
Alarm Transfer
By connecting the output of a BM 25 to the input of another BM 25, and so on, it is possible to transfer alarms from instruments to instruments. This configuration is particularly useful for perimeter monitoring. For example, it may be used to monitor a fence by connecting the BM 25s on a daisy chain or to monitor a tank by connecting the units in loop.
Refer to the Connections paragraph on page 14 for the wiring of the dry logic input or the alarm relay output. The input and output can be configured using the COM 2100 software; see page 57.
22
BM 25/25W
Instruction Manual
Connection of a manual call point
By connecting a manual call point to the input of a BM 25/25W, it allows the user to fire the local audible and visible alarm in order to alert of an immediate danger (fire, man down, evacuation, etc.). When the BM 25 is in wireless mode or wired to another BM 25/25W, the local alarm is reported to the other instruments (Alarm Transfer).
Figure 12: Push button connection (Example. Refer to COM 2100 software chapter on page 57 for more details)
3 – Operation
23
When starting up the BM 25/25W for the first time or after a period of inactivity longer than one month, it is recommended to proceed a charge­discharge cycle. Moreover, keep in mind that all portable gas monitors must be tested with gas before each day of use.
Press the Enter button (ref. 1).
Before displaying current measurements, the BM
25/25W performs visual and audible tests during a few seconds and then displays:
- The OLDHAM logo,
- The software revision and the serial number,
- The alarm thresholds set for each measurement channel.
Continue to paragraph Test Routine and
Calibration Overdue on page 24.
Note: During normal operation, the BM 25/25W flashes every 2 minutes to indicate that it operates correctly. This confidence flash can be canceled and the frequency can be changed using the COM 2100 software; see page 51.
Figure 13: start-up in standard mode by pressing the Enter button
Chapter 3 | Operation
Start-up
Switching on the instrument
Selection of the flammable gas on start-up
On start-up, it is possible to change the calibration gas. This option allows the user to measure a different flammable gas (acetone, methanol, etc.) from that which was originally used (methane or pentane) to calibrate the instrument. This action allows the instrument software to compensate and display more accurate readings. Note:
Accuracy for the re-selected gas type is +/- 15%.
24
BM 25/25W
Instruction Manual
Step 1: Switch the instrument on
Press and hold the Acquit button (ref. 1). Press the
Enter button (ref. 2) to switch the instrument on.
Release both buttons.
When warm-up is complete, the BM 25/25W displays
the list of different gases. The gas currently selected is highlighted.
Figure 14: press 1 and 2 to select the calibration gas
Step 2: Select the reference gas
Use the Acquit button (Figure 14: press 1 and 2 to select the calibration gasref. 1)
to scroll down the list of gas. Thirty-one (31) combustible gases are available in the library. Choose Other to select a gas for your specific needs.
Note: if a gas is not selected in the allotted time, the monitor will start in normal
mode without changing the reference gas.
Press the Enter button (ref. 2) to confirm your choice.
The BM 25/25W starts another test routine. Once the test is complete, the selected
gas is now the reference gas.
Test Routine and Calibration Overdue
During warm-up the BM 25/25W performs a self test and then starts gas measurement. If the test is not completed successfully, the BM 25/25W goes into fault mode (continuous audible and visual signal).
When the calibration date for a sensor is overdue, the BM 25/25W triggers a calibration alert for the appropriate channel. This warning message may be dismissed and the instrument will operate using its previous calibration settings; however, as the sensors response may have diminished, the instrument should be recalibrated and tested.
Gas monitor positioning
Position the monitor vertically at the relevant location by taking into account the density of the gases and the airflow.
Diffusion mode
In this configuration, the gas monitor is used without additional sampling device; the sensors monitor the ambient atmosphere.
3 – Operation
25
Sampling probes (rigid, semi-rigid or telescopic) and sampling tubing are not antistatic. The user must take the necessary precautions to avoid electrostatic discharges. In all cases, the user must prevent dangerous electrostatic discharges using a metallic probe.
Warning (Hand Aspirator): The BM 25 series is designed to be used with a built-in pump for remote sampling. A hand aspirator can be used for indicative sampling, but it must be noted that when using a hand aspirator, a reading error in the region of + 20% is possible. In addition, whereas the pump can sample quickly and accurately with up to 30 meters of sample line, the hand aspirator must only be used with up to 10 meters of sample line and the sample time is extended. The sample line must be intact and the proper flow established.
Aspirated mode (with pump option)
Remote sensing is possible with the internal electric pump option, or by using a hand aspirator.
Using an electric pump
The internal pump is powered by the gas monitor's battery and starts automatically
when the sensors cover is applied (Figure 15: positioning the sensors cover (BM 25/25W equipped with an electric pump)ref. 1); this cover can be identified by its hump (ref. 4).
Connect the sample line (ref. 2) to the gas inlet (ref. 3).
Wait a few seconds before reading the measurements. Any anomaly in the pump
system is indicated by an audible alarm and on the LCD display.
Figure 15: positioning the sensors cover (BM 25/25W equipped with an electric pump)
26
BM 25/25W
Instruction Manual
Before each use of the electrical pump, check the seal by obstructing the end of the sampling line until the Flow Fault alarm is triggered. Do not forget to remove the sensors cover to return to diffusion mode.
Once the sampling is complete, remember to remove the sensors cover to return to diffusion mode.
Using a manual pump
Figure 16: positioning the sensors cover (BM 25/25W non-equipped with an electric
Place and screw the cover over the sensors (Figure 16: positioning the sensors
Connect the sample line (ref. 2) to the gas inlet (ref. 3).
Wait for the measurements to stabilize before recording them; if measurements are
pump)
cover (BM 25/25W non-equipped with an electric pump)ref. 1); this cover has no hump as previously mentioned (ref. 4).
recorded too soon, they may be over-estimated (combustible gases), or under­estimated (oxygen).
3 – Operation
27
Combustible gas concentration measurements can be affected by high or low oxygen concentrations. Any reading rapidly changing from too high (exceeding 100% LEL) to too low can in fact indicate a hazardous gas level higher than the measurement scale.
Measurements
Reading measurements
The gas measurements are displayed at once on the LCD display in four separate fields. In each field, the measurement is displayed as follows:
Gas concentration
Unit (ppm, % vol. or % LEL)
Gas type
In "5 gas" configuration, channel #5 is displayed alternately with channel #3 at
bottom left
At the bottom of the screen, time, alarm status and wireless communication status (when applied) are displayed (see page 35).
Figure 17: on the left side, 4-gas monitor with no radio communication. On the right side, 3-gas monitor with radio ON.
Display management
Backlit
Press the button to read measurements in dark areas. Backlit turns off automatically after 4 minutes. Display automatically illuminates on fault event or alarm
event.
28
BM 25/25W
Instruction Manual
Displaying additional information
When the gas monitor is in normal operation, the user can access additional information. Press the button repeatedly to scroll through the following screens:
Date (backlit is ON)
Area identification or user name (only if Roundsman option is activated; see
paragraph Roundsman function, below)
Remaining battery life (bargraph)
min/max values for each sensor
STEL value for each toxic sensor
TWA value for each toxic sensor
Maintenance menu which is password protected. To enter the maintenance menu
enter the 4-digit code using the and buttons.
Press the button to return to normal operation.
Roundsman function
If the Roundsman function has been activated, a list of names can be programmed using COM 2100 software. This list can be viewed at any time by using the front keys on the device.
To select a location or a user, follow these steps:
Press the button repeatedly until Current location/name appears.
Press Enter.
Scroll through the list using the and buttons.
Press Enter to confirm your selection.
Press to return to normal mode.
Reset the Min/Max
Press simultaneously the and buttons to reset the min/max values. The BM 25/25W sounds a beep to confirm the action.
3 – Operation
29
Alarm information has priority over fault information.
Alarms
The BM 25/25W features visual and audible indicators:
Visual indicators: clear text messages on the display, one 360° red flashlight that is
visible from all directions
Audible indicators: two loud speakers (103 dB @ 1m)
Gas alarms
The gas monitor features:
Two instantaneous thresholds per channel for combustible, toxic or oxygen gases.
One falling and one ascending alarm for Oxygen (two falling alarms in option).
One STEL (Exposure Limit, country dependent) threshold per channel equipped
with a toxic gas sensor. The STEL value corresponds to the average of gas measurements made over the last 15 minutes.
One TWA (Time Weighted Average, country dependent) threshold per channel
equipped with a toxic gas sensor. The TWA value corresponds to the average of gas measurements made over the last 8 hours.
When an alarm is triggered, the monitor will fire its audible and visual indicators at different frequencies depending on the alarm type:
Low Gas Alarm (Alarm 1): two-tone, slow (1 Hz).
High Gas Alarm (Alarm 2): two-tone, fast (2 Hz).
Alarm Transfer (repeated alarm): two-tone, very slow (0.5 Hz).
Fault: mono-tone, continuous (0 Hz).
The display will also indicate the alarm message(s) (ALARM 1, ALARM 2, AL. TRANSFER, STEL, TWA, mini, etc.) as well as the gas measurement. In alarm mode, the monitor will display the peak values (min or max depending on the gas type)
until acknowledgement button is pressed.
Gas Alarms Acknowledgement
Latching Alarms
The audible alarm will be silenced when the button is pressed. The visual alarm will continue to blink while the gas measurement is outside the set limits. The visual alarm will turn off automatically when the measurement is within the set limits.
If after two minutes the gas measurement is still outside the set limits, the audible alarm will be automatically reactivated; this function can be deactivated by factory.
30
BM 25/25W
Instruction Manual
Unlatching Alarms
In this configuration, audible and visual alarms will be acknowledged automatically, without any action, as long as the gas measurement is within the set limits.
Fault alarms
Faults can be classified into two categories:
Sensor faults: out of range, low sensitivity, zero drift, etc.
Monitor faults (low battery, wireless communication fault, electronics fault, etc.).
In the event of a fault, the monitor sounds a continuous audible alarm and the flash is steady. The corresponding fault message appears at the bottom of the display.
Examples of information which may be brought to the user's attention
Battery fault
Low battery: remaining battery life is less than 20 minutes. The BM 25/25W is still
operating, the audible signal can be silenced.
Battery fault: detection is no longer guaranteed. The audible signal cannot be
silenced.
> 100% LEL: Over-Range Flammable Gas Alarm Function
Applies to the combustible channel only. In this case:
Value on display is frozen.
Continuous audible signal cannot be silenced.
Visual flashlight is steady and cannot be turned off.
Combustible sensor (LEL) is powered down to prevent damages from
overexposure to gas.
Normal operating conditions can be restored by power cycling the BM 25/25W. This operation must be performed outside the hazardous area.
Out of range
Negative Zero Drift (reading below -20% of full scale). This fault is automatically
resettable.
Over-Range (reading above 120% of full scale). This fault must be acknowledged
manually.
Alarm transfer
The gas monitor features:
one alarm relay output monitored by any channel and dedicated to alarm transfer
one dry logic input to trigger the local alarm
3 Operation
31
By connecting the alarm transfer cable (ref. 2), from the output of a BM 25 (ref. 1) to the input (ref. 3) of another BM 25, and so on, it is possible to transfer alarms from instruments to instruments. This configuration is particularly useful for perimeter monitoring. For example, it may be used to monitor a fence by connecting the BM 25s on a daisy chain or to monitor a tank by connecting the units in loop.
The input and output can be configured using the COM 2100 software; see page 57.
Figure 18: connection between two monitors
32
BM 25/25W
Instruction Manual
Mandatory parameters for inputs/outputs:
Voltages and alternating currents: I = 150 mA max. - U = 30 V max.
Voltages and direct currents: I = 150 mA max. - U = 30 V max.
If the gas monitor is used in an explosive atmosphere, it is imperative to consider output relay parameters, since contact must not impair the intrinsic safety of the gas monitor. These parameters are mentioned in the paragraph Special Instructions for use in explosive atmospheres on page
71. OLDHAM shall not, in any event, be liable for failure to follow regulations.
Data transfer
The BM 25/25W stores gas measurements, alarm and fault events. Those data can later be downloaded to a Personal Computer thanks to COM 2100 software.
Stored data
Once turned on, the BM 25/25W records data in time-stamped frames. The monitor creates a new frame every time it starts up and every 24 hours. A frame contains:
Channels Information
Readings for each sensor at a defined recording interval (configurable).
Event logs for each channel:
- Alarm
- Fault
- Alarm Reset
- Maintenance operations (programming, calibration, sensor replacement, zeroing).
Memory capacity
The gas monitor can store approximately 200,000 measurement points. When the memory is full, oldest data are overwritten (FIFO).
Data storage
Data are stored as long as internal battery is charged. If the BM 25/25W is not used for a long period of time and/or main battery is discharged, a lithium battery will take over for a period of two years max.
3 – Operation
33
To switch the instrument off, press the Enter
button (ref. 1) located on the front plate, for 3 seconds.
The instrument display starts a countdown from 3
to 1 before it asks to confirm. Release the Enter button (ref. 1) and press again to switch the BM 25/25W off.
Figure 19: switch off by pressing Enter button
Switching off the instrument
34
BM 25/25W
Instruction Manual
4 – Wireless Version
35
This product complies with FCC Maximum Permissible Exposure (MPE) requirements when used with an approved antenna and the antenna is at least 20 cm away from the user. Use of the product closer than 20 cm may exceed the MPE limits. Use of any antenna other than approved antennas will invalidate the certification of the product.
Available as an option, the radio communication allows several BM 25Ws to communicate on the same network (BM 25 mode) or to send information wirelessly to a MX40 or X40 controller (CONTROLLER mode).
Wireless communication is made via a 2.4 GHz radio and emitted power is less than 100 mW. Maximum distance between two communicating devices is 3,300 feet line of sight. Up to 30 BM 25Ws can be meshed on the same network and up to 16 networks can coexist with no interference.
The network topology used by the BM 25W is a MESH network. In a mesh network all hosts are connected peer to peer without central hierarchy, thereby forming a net-like structure. Consequently, each node can receive, send and relay data. This avoids having sensitive points, which in case of failure, cut the connection of the network. If a node is down, its neighbors go through another route.
Mesh topology allows fast and simple deployment, high coverage versatility and high fault tolerance. It significantly reduces installation and operating costs of networks. These solutions reproduce the architecture of the Internet while optimizing for wireless.
Figure 20 : Wireless version, recognizable by the presence of an antenna
Chapter 4 | Wireless Version
Overview
BM 25 Mode
When in BM 25 mode, BM 25Ws send information regarding gas alarm and fault status. Once a BM 25W is in gas alarm, the alarm is repeated on all other BM 25Ws on the same network.
36
BM 25/25W
Instruction Manual
Main BM 25W
Secondary BM 25W
Case
Cause
Flash
Siren
Flash
Siren
1.
Fault (no communication at all, sensor fault, low battery, etc.)
Steady
Yes
Steady
Yes
2.
At least one BM 25W does not communicate
Steady
No
Steady
No
3.
Alarm 1
1 Hz
1 Hz
0.5 Hz
0.5 Hz
4.
Alarm 2
2 Hz
2 Hz
0.5 Hz
0.5 Hz
Two-way communication
Figure 21 : In the example above, BM 25W tag G communicates with E and F. In the event of a loss of communication between G and F, E still ensures the communication to the rest of the network. If G goes into gas alarm or fault condition, all BM 25Ws on the network will report a corresponding alarm
Alarm sequence differs depending on whether a BM 25W sends information (gas alarm or fault) or receives information (alarm transfer). This allows for quick identification of the BM 25W in alarm condition so that the appropriate action can be taken. Although there is no hierarchy in a mesh network, the unit in alarm and the unit reporting the alarm are referred to later in the manual as 'main and secondary BM 25W, respectively.
Table 1 : ‘Alarm’ mode – Table of events
4 – Wireless Version
37
Gas alarm Transfer
In the event one BM 25W goes into a gas alarm, all secondary BM 25Ws will display «
Al. Transfert » as shown below. Press the “acquit” button to silence the audible alarm.
The BM 25W strobe will continue to flash until the alarm event has ended. The audible alarm will reactivate after 5 minutes if the alarm event is still active.
Note that if a second BM 25W had to fire a gas alarm, then this BM 25W would pass
from ‘secondary’ to ‘main’ status and would sound at 1 or 2 Hz depending on the alarm
level being reached. The secondary BM 25Ws would not immediately reactivate the local siren.
Figure 22 : Secondary BM 25W reporting an ‘Alarm Transfer’ condition
Fault Transfert
In the event one BM 25W goes into fault condition, secondary BM 25Ws will display on their LCD screen the message « Def. Transfert » as shown below. This fault condition is not acknowledgeable and is automatically cleared as soon as the main BM 25W goes back into a normal operating condition.
Figure 23 : Secondary BM 25W reporting a ‘Fault Transfer’ condition
38
BM 25/25W
Instruction Manual
Two-way communication
Controller Mode
In Controller mode, BM 25Ws send fault status, alarm status and gas measurements to the controller. As soon as one BM 25W fires an alarm, the controller relays the gas alarm information to all BM 25Ws on the same network that then turn in Alarm Transfer mode.
Figure 24 : In the example above, BM 25Ws E and F are the last links between the controller and the rest of the network. If communication between BM 25W F and MX 40 fails, then BM 25W E continues to provide communication between the BM 25W network and the controller. If BM 25W A goes into gas alarm or fault condition, then MX 40 receives information and passes the gas alarm on all others BM 25Ws
The alarm sequence differs depending on whether a BM 25W sends information (gas alarm or fault) or receives information (alarm transfer). This allows for quick identification of the BM 25W that is in alarm so that appropriate action can be taken.
4 – Wireless Version
39
Main BM 25W
Secondary BM 25W
Controller
Case
Cause
Flash
Siren
Flash
Siren
Channel status
1.
Fault (no communication at all, sensor fault, low battery, etc.)
Steady
Yes
No
No
Fault
2.
Alarm 1
1 Hz
1 Hz
0.5 Hz
0.5 Hz
Alarm 1
3.
Alarm 2
2 Hz
2 Hz
0.5 Hz
0.5 Hz
Alarm 2
Tableau 2 : Controller Mode – Table of events
Start-up
From the Maintenance menu (see Chapter 5), choose Wireless. Leave it to 'OFF' if you do not want to activate the radio function. Select 'BM 25' or 'Controller' according to the chosen operation mode (see above).
Figure 25 : Wireless mode screenshots
In BM 25 mode: only the network ID (Channel) must be set between 0 and 15.
Address number (Slv Number) is not editable and is set to 'XXX'. In this mode, it is not necessary to assign an address as the network is automatically built in by using the MAC
In Controller mode: set the BM 25W address Slv Nb between 1 and 30 max. and
the network ID Channel between 0 and 15.
(*) MAC (Media Access Control): unique identifier assigned to network interfaces. Each BM 25W has its own unique MAC address.
WARNING
(*)
addresses of each device.
40
BM 25/25W
Instruction Manual
It is important that all BM 25Ws intended to be on the same network have the same
network ID.
In Controller mode, two BM 25Ws cannot share the same address otherwise you
will get a fault.
Once wireless mode is activated (‘BM 25’ or ‘Controller’ mode), you have 5 minutes to
declare another BM 25W on the same network. When the time is gone and no communication is established, BM 25W shows 'COMM ERR' and goes into fault (see case #1 from table of events).
Figure 26 : COMM ERR, no communication is established
Thereafter, in normal operation, each BM 25W sends its information over the network every ten seconds. If a BM 25W goes into gas alarm or fault condition, then the information is immediately sent without waiting ten seconds. In BM 25 mode, the number of BM 25Ws that are communicating on the network is shown at the bottom of the display screen (example 4 shown below).
Figure 27a – BM 25 mode : Four BM 25Ws communicate with each other on the same network
When in BM 25 mode, BM 25W displays the radio signal strength as indicated below in figure 27c. It corresponds to the average of signals received from all BM 25Ws that the BM 25W you are looking at is communicating with.
Figure 27b – Controller mode : BM 25W is communicating with the controller
4 – Wireless Version
41
Figure 27c – BM 25 mode : Radio Signal Strengh
When is displayed, the BM 25W has 100% of the signal and the radio communication is very good.
When is displayed, the signal strengh is less than 20% although BM 25Ws are still communicating.
When is displayed, no communication is established, BM 25W shows 'COMM ERR' and goes into fault (see case #1 from table of events).
Adding a BM 25W on an existing network
In BM 25 mode, the network is automatically built. Each BM 25W with the same network ID is automatically included as long as it communicates with at least one BM 25W belonging to the same network.
To add a new BM 25W to an existing network, simply turn the unit on, activate the radio communication and, if applicable, set the network ID.
In MODBUS mode, you must set the address number (Slv Nb), set the network ID (Channel) and configure, if applicable, a new input on the controller.
Removing a BM 25W from an existing network
In BM 25 mode
turn the unit off
or deactivate the radio module from the maintenance menu.
In both cases, before communication stops, the BM 25W broadcasts a last message to inform the other BM 25Ws on the same network that it will be removed.
In Controller mode
To remove a BM 25W from an existing network, just switch the controller channel off, then turn the BM 25W off or deactivate the radio module if you still need to use the BM 25W in local.
42
BM 25/25W
Instruction Manual
Self-healing
NOTE : This section covers the ‘BM 25’ mode only.
Each BM 25W broadcasts a message every 10 seconds. Using the example shown below, if BM 25W tag A receives no message from BM 25W tag B for more than 2 minutes, then B is considered as missing by A which turns into fault mode (case No. 2 – Table of alarms) and transfers the information to all other BM 25Ws on the network. Note that BM 25W tag B can act the same if it receives no information from A. Number of BM 25Ws that do not communicate anymore is displayed on each BM 25W referring a communication fault. This number may differ depending on the BM 25W you are looking. Here below, one BM 25W out of four is no longer communicating.
Figure 28 : One BM 25W out of four does not communicate
In case of communication failure, the network tries to reestablish communication every ten seconds.
In BM 25 mode, if a BM 25W does not respond or if the network is split, then it is possible to ignore this fault and to continue to work by the time of the restoration of the network.
4 – Wireless Version
43
In the example above, BM 25W (unit D) is the only communication link between A, B, C and E, F, G. If BM 25W (unit D) had a fault (low battery for instance) or if an obstacle were to disrupt communication between D and E or D and B, then all BM 25Ws would report a fault failure (steady flashlight according to case No. 2 – see table of alarms).
IMPORTANT :
Note that the gas detection remains effective and that BM 25W (unit D) would still
locally alarm in the presence of gas. It is the same for each BM 25W on the network. Only the alarm would not be transferred to the whole network.
To ensure maximum network reliability, a BM 25W should always communicate
with at least two neighbors.
Figure 29 : group concept (read details below)
A long press on the « acquit » button forces the system to a new identification of the nodes present on the network. BM 25Ws that do no communicate are ignored without triggering a fault condition. In the example above, the communication between D and E is down. A long press on the « acquit » button of BM 25W (unit D) resets the network. All BM 25Ws communicating with D automatically launch a new identification in turn. On one side, BM 25Ws A, B, C and D discover each other and form a first group. On the other side, BM 25Ws E, F and G still report a communication failure since they do not receive data from the BM 25Ws of the newly formed group. A long press on the « acquit » button of one BM 25W (unit E, F or G) clears the list of BM
44
BM 25/25W
Instruction Manual
25Ws on the network and forces to a new identification. Similarly as above, BM 25Ws (units E, F and G) form a second group.
IMPORTANT :
The two groups run independently and alarm or failure events from one group
cannot be transferred to the other group.
When the obstacle (the truck in our example) is gone, the communication between
E and D resumes automatically without the need to restart identification. The two groups merge together to form only one group.
To start a new identification, keep pressing the « acquit » button for 3 seconds. The display successively shows 3, 2, 1 then « confirm ». Release the « acquit » button and press again.
Figure 30 : reset sequence of a group of BM 25Ws
NOTE :
When a new identification has started, communication errors are inhibited for one
minute.
Once the network healing is completed, it is possible that one or several BM 25Ws
remain isolated and stay in fault mode (case No. 1 – Table of alarms). To acknowledge this failure, turn the unit off or disable the radio communication from the maintenance menu.
Adding a new BM 25W to the network at a smart location overcomes the obstacle and restores the communication between the two groups which then merge together. This healing is automatic as long as BM 25W (unit H) belongs to the same network (same 'Channel' ID).
4 – Wireless Version
45
Figure 31 : bypassing an obstacle by adding a new BM 25W (H)
Mac list menu
NOTE : This section covers the BM 25 mode only.
Available from the Maintenance menu (see Chapter 5), the « MAC List » menu allows the user from any BM 25W belonging to the network to get the MAC BM 25W on the network and its particular status.
(*) MAC (Media Access Control): unique identifier assigned to network interfaces. Each BM 25W has its own unique MAC address.
(*)
address of each
Figure 32 : MAC List menu
46
BM 25/25W
Instruction Manual
When in the « MAC List » menu, the first address displayed and aligned to the right is the address of the BM 25W you are currently looking at (here 0487D2). Up to 6 MAC addresses can be displayed per page.
Figure 33 : List of the MAC addresses present on the network
A BM 25W in gas alarm mode is shown with the status ‘A’ (here, BM 25W with address No. 04C392 is in alarm). A BM 25W in fault mode (low battery for instance) is shown with the status ‘D’ (here, BM 25W with address No. 0487D1 is in fault).
When a BM 25W is no longer communicating on the network, its address appears in reverse video. See “SELF-HEALING” parapragh for trouble shooting.
Figure 34 : Status of each BM 25W on the network
Figure 35 : BM 25W with MAC address No. 0487D1 does not communicate
5 – Maintenance
47
The gas monitor is factory-programmed to display a maintenance alert if a calibration has not been performed in the last twelve months (the message Calibration due will appear on the screen).
The operations explained in this chapter must be performed by authorized, qualified personnel only, as they could adversely affect detection safety.
Chapter 5 | Maintenance
Gas monitors are safety instruments. Recognizing this fact, OLDHAM recommends that a functional test be performed on every portable gas monitor prior to each use. A functional test involves injecting a gas of sufficient concentration at the sensor level to trigger pre-set alarms. This test does not, in any event, replace a full calibration of the sensors.
If a gas monitor does not respond correctly to a gas test, a full calibration with a calibration gas is mandatory.
These recommendations are consistent with applicable industry safety protocols and with the standards and directives relative to the safety of industrial sites. OLDHAM is also not responsible for procedures performed onsite.
Accessing maintenance menus
When in normal operation mode,
Scroll to parameters using the / button until a request for an access code
and 0000 is displayed.
0018 is the default code. Scroll to each digit with the button. Use button to
select the right number and confirm access code with the ENTER button.
48
BM 25/25W
Instruction Manual
The list of available menus will then be displayed:
Program
Calibration
Auto-zero
date / hour
Wireless (see Chapter 4)
MAC List (see Chapter 4)
Exit
Program Menu
This is used to:
Activate/Deactivate a channel
Display sensor information (gas type and measurement range)
When using a catalytic sensor, to select the reference gas from the library (see
table below) or enter a correlation factor and to program alarm set points
When using an oxygen sensor, to set the low (descending) and high (rising) alarm
thresholds or 2 low alarm levels if this option was selected
When using a toxic gas sensor, to set alarm thresholds
The coefficients are given for information in relation to CH4 with an LEL of 5.0% volume, and are automatically used by the monitor during calibration or when changing the reference gas. If the combustible gas to be detected is not in this list, you can use the Other window by selecting a coefficient provided by OLDHAM (contact us).
5 – Maintenance
49
Gas
Molecular formula
LEL 1
LSE 2
Vapor density
Coef. / CH4.
Recom­mended calgas
Abbreviation (French)
Ethyl acetate
C4H8O2
2.1 %
11.5 %
3.0
1.35
But/Prop
AET
Acetone
C3H6O
2.15 %
13 %
2.1
1.55
But/Prop
ACO
Acetylene
C2H2
1.5 %
100 %
0.9
1.1
But/Prop
ACY
Butadiene
C4H6
1.4 %
16.3 %
1.85
1.25
But/Prop
BUD
Butane
C4H10
1.5 %
8.5 %
2.0
1.6
But/Prop
BUT
Butanone
C4H8O
1.8 %
11.5 %
2.5
1.75
But/Prop
BUN
Dimethylether
C2H6O
3.0 %
27.0 %
1.6
1.55
But/Prop
DIM
Unleaded petrol
Mixture
1.1 %
6 %
3 to 4
3.0
But/Prop
ESS
Ethanol
C2H6O
3.3 %
19.0 %
1.6
1.15
But/Prop
ETA
Ethylene
C2H4
2.7 %
34.0 %
0.98
1.0
But/Prop
ETY
G.P.L.
Prop+But
1.65 %
9.0 %
1.85
2.05
But/Prop
GPL
Diesel
Mixture
0.6 %
6.0 %
> 4
5.00
But/Prop
GSL
Natural gas
CH4
5.0 %
15.0 %
0.55
1.05
CH4
GNT
Hexane
C6H14
1.2 %
7.4 %
3.0
2.36
But/Prop
HEX
Hydrogen
H2
4.0 %
75.6 %
0.069
0.80
But/Prop
H2
Isobutane
C4H10
1.5 %
15 %
2.0
1.6
But/Prop
ISB
Isopropanol
C3H8O
2.15 %
13.5 %
2.1
1.6
But/Prop
ISP
Methane3
CH4
5.0 %
15.0%
0.55
1.00
CH4
CH4
4.4 %
1.14
Methanol
CH3OH
5.5 %
44.0 %
1.1
1.0
But/Prop
MTL
Methylamine
CH3NH2
4.9 %
20.7 %
1.1
2.0
CH4
MAM
Propylene oxide
C3H6O
2.3 %
37.0 %
2.0
2.0
But/Prop
OPR
Ethylene oxide
C2H4O
2.6 %
100 %
1.5
2.1
But/Prop
ETO
Pentane
C5H12
1.4 %
8.0 %
2.5
1.70
But/Prop
PNT
Propane
C3H8
2.0 %
9.5 %
1.6
1.3
But/Prop
PRO
Propylene
C3H6
2.0 %
11.7 %
1.5
1.2
But/Prop
PRY
Toluene
C7H8
1.2 %
7.0 %
3.1
2.05
But/Prop
TOL
White spirit
Mixture
1.1 %
6.5 %
> 2
5.0
But/Prop
WSP
Xylene
C8H10
1.0 %
7.6 %
3.7
2.5
But/Prop
XYL
(1) Lower flammable limit.
(2) Upper flammable limit.
(3) The LEL adopted value for methane varies by country. The monitor integrates two different LEL values for CH4 (4.4% vol. and 5.0% vol.)
List of pre-programmed combustible gases with coefficients
50
BM 25/25W
Instruction Manual
When battery is low, the user is notified with a Battery fault message before losing all stored data. The battery must then be replaced. This operation should only be performed by OLDHAM or OLDHAM approved personnel.
Sensor calibration menu
Calibration consists of a zero adjustment in clean air (free from any gases that could be detected by the gas monitor), as well as a sensitivity adjustment using calibration gas of concentration between 15% and 100% of the full sensor range. Test gas shall be applied at a 60 liters per hour flow rate.
Auto-adjustment menu
Allows to zero each sensor.
Date and time management menu
To set the instrument’s built-in-clock since saved data and event logs are time stamped.
Loss of date and time
An on-board lithium battery keeps date and time saved in memory (see paragraph Data storage on page 32) when the main battery is drained or when the monitor is turned off. Expected lithium battery’s runtime is 2 years.
Radio communication menu
This menu allows the user to:
Switch the radio on and off
Select the operation mode (BM25 or controller mode)
Set the BM 25W Modbus address (when in controller mode)
Set the network ID
MAC List menu
When in wireless mode, this menu displays:
The monitor's MAC address
MAC addresses of all BM 25Ws belonging to the same network
Status of each BM 25W on the same network
Exit menu
Return to normal mode.
6 – COM2100 software
51
Chapter 6 | COM2100 software
Subject
This software is for settings and service purpose. It features:
Channels settings
Diagnostics in case of failure
Instrument settings
Sensors calibration
Calibration and Control certificates
Datalogging management
Through its infrared port (ref. 1), the BM 25/25W can be connected to a computer by using a connection cable (ref. 2 and 3).
Figure 36: interconnection cable and welcome screen
52
BM 25/25W
Instruction Manual
Once COM 2100 is running, the BM 25/25W connects automatically and a window pops up as indicated in figure Figure 37: the parameter programming menu.
Follow the steps below:
Set communication parameters as necessary
(port, speed, language)
Click the Connect button.
Figure 37: the parameter programming menu
Follow the steps below:
From the main list of menus, access the
Maintenance menu.
Options are:
Program: see page 53
Calibration: see page 54
Time Setting: see page 55
Monitoring report: see page 55
Status report: see page 55
Figure 38: Maintenance menu
Gas monitor connection
Maintenance menu
6 – COM2100 software
53
Programming Menu
Proceed as follows:
From the Maintenance menu (Figure 38), select Programming
The screen here below pops up
Figure 39 - Program menu screen
Channel settings
Access is password protected. The default code is 1000 (to change this code, see
paragraph Screen menu on page 58).
The first column, Activated (top left) allows the user to switch on/off a channel. The
second column Present allows the user to display (or not to display) a channel that has been switched off, e.g. O2 OFF (or blank screen).
- Click Confirm to save the modification.
Alarm settings
Select the channel from the dropdown list (Channel selection - Figure 39):
Edit alarm threshold values
Click Alarm validation to save your settings.
54
BM 25/25W
Instruction Manual
Access is password protected. Select the
channel fitted with the catalytic sensor (Channel selection, see Figure 39).
Select the Reference Gas as necessary:
- Choose another gas from the list and click on Programming combustible gas (Figure 40: programming combustible gas.
- Click Exit.
Figure 40: programming combustible gas
From the Maintenance menu
(Figure 38), select Calibration.
Choose the sensor to calibrate.
Set the maintenance interval.
Enter the calibration gas
concentration value (shall be between 15 and 100% of the sensor range).
Click Zero to start the procedure.
Follow the software instructions. You will be asked first to inject Zero Air and then Calibration Gas.
Figure 41: Calibration menu
Once the calibration is complete, click OK to validate. If you miss something during the calibration, click Cancel and start the calibration again.
Once you have confirmed the calibration is complete, the BM 25/25W will notify whether the sensor passed or failed the calibration. In the event of a failure, repeat the calibration process or proceed with the sensor replacement.
Figure 42: confirming Calibration
Reference Gas settings
Calibration menu
6 – COM2100 software
55
Oldham recommends using pure gases: using mixed gases can alter the accuracy of gas measurements due to cross interferences between the sensors.
The calibration gas concentration value shall be between 15% and 100% of the measurement range.
From the Maintenance menu
(Figure 38), select the option
Update the BM 25/25W date and time from a PC.
Click OK to validate and exit.
Figure 43: the Time Settings menu
Follow the steps below:
From the Maintenance menu
(Figure 38), select ’Checking card’.
Fill in the fields (user's
information for instance)
Create the monitoring report
(.ctr file)
From the PC (COM 2100 files)
open the files to edit or print.
Figure 44: the Monitoring Report menu
Date and Time Settings
Monitoring Report menu
56
BM 25/25W
Instruction Manual
Step 1
Step 2 and 3
Step 4
Example:
Status Report menu
From the Maintenance menu (Figure 38), select ’State card’ and follow the same steps as described in the Monitoring Report menu (.etx files).
6 – COM2100 software
57
Set relay output and the logic input by
checking the different boxes (Figure 45).
Reference 1 Alarm relay output settings. In this example
all CO, O2 and LEL alarms will trigger the relay output.
Reference 3 To set the BM 25/25W modes when logic
input is activated (set to 1).
- Alarm relay: internal relay output is activated
- Alarm 1: BM 25/25W will turn in Alarm 1 mode
- Alarm 2: BM 25/25W will turn in Alarm 2 mode
- Remote alarm: BM 25/25W will turn in Alarm Transfer mode
Reference 4 Alarm acknowledgment
- Local acknowledgment: alarms must be acknowledged from the gas monitor keyboard.
- Remote acknowledgment: when on a network (wired or wireless), local alarms can be acknowledged from another BM 25/25W.
Click OK to confirm.
Figure 45: alarm output relay and logic input settings
Alarm relay configuration and logic inputs
58
BM 25/25W
Instruction Manual
To create a new entry, fill in the field Enter
new Location/User name.
Click on Save new Location/User name.
The new entry appears in the window on the left (Locations/Users available).
To add an (all) user/location to the BM
25/25W, select an input from the left and click on the ‘>’ (>>) icon.
To remove an user/location from the BM
25/25W, select an input from the right and
click on the ‘<’ (>>) icon.
Click OK to confirm.
Figure 46: list of users/locations
Screen menu
This menu displays the log events, gas measurements and device’s configuration. The password to access the maintenance menu is 0018 and software access code is
1000. Those passwords are user configurable. Lists of users and/or locations can be created from this menu. This function allows to
assign log events by user or location.
List of Users/Locations management
7 - Technical Specifications
59
Function
Manufacturer :
OLDHAM
Function:
Area Gas Monitor
Type:
BM 25 and BM 25W (wireless)
Gas
Configuration:
One to four sensors (catalytic, electrochemical, infrared or PID sensors)
Gases detected:
Combustible, toxic and oxygen
Measurement:
Continuous on all sensors in operation
Sensors:
Plug & Play
Display
Graphic LCD with backlit
Clear messages
Flip-Flap function
Various alarms
Operations check:
Self-test at start-up
Unit flashes every 2 minutes (Confidence test)
Alarm thresholds:
Combustible: 2 adjustable instantaneous thresholds
in 0-60 % LEL range
Oxygen: two adjustable instantaneous thresholds
over the sensor's entire measuring scale (over­oxygenation and under-oxygenation) or two optional under-oxygenation thresholds
Toxic (per sensor): two adjustable instantaneous
thresholds over the sensor's entire measuring scale
Toxic (per sensor): two adjustable averaged
thresholds over the sensor's entire measuring scale for STEL and TWA monitoring
Gas Alarm:
Visual and Audible alarm (1Hz and 2Hz)
Clear message on the display
Chapter 7 | Technical Specifications
Gas monitor
60
BM 25/25W
Instruction Manual
Sensor fault:
Visual and Audible alarm (continuous)
Clear message on the display
Battery fault:
Visual and Audible alarm (continuous)
Clear message on the display
Inputs and outputs
Inputs/Outputs
RS232 infrared link
Alarm relay output
Fault relay output
Dry Logic input
Optional Wireless Communication (2.4GHz - 100 mW)
Additional software
Additional software:
Maintenance software COM 2100
Power supply
Power Supply:
NiMH rechargeable battery pack
Battery life in hours (excluding alarms and as a function of the number of sensors):
Configuration
Without radio module (hours)
With radio module (hours)
1 catalytic and 2 infrared
40
35
1 catalytic and 1 infrared
70
50
1 catalytic and several Tox
100
65
Only Tox sensors
170
135
Charging Time:
4.5 hours
Weight and dimensions
Weight:
6.85 kg
Dimensions:
470 x 180 x 190 mm (H x W x D)
Certification
Ingress Protection:
IP 66
Certifications:
CE, ATEX, IECEx, FCC
7 - Technical Specifications
61
Methane (CH4)
Methane (CH4)
Methane (CH4)
Sensor reference
6314064
6313888
6313889
Standard range (1)
0 - 100% LEL CH4
0 - 100% LEL CH4
0 - 100% vol
Measurement principle
Infrared
Catalytic
Catharometric
Display resolution(1)
1 % LEL
1 % LEL
1% v/v
Accuracy (2)
2 2 2
Repeatability (3)
± 2 % LEL
± 1 % LEL
± 1% vol
Zero/Span drift (4)
1 / 2
0.5 / 5
0.2 / 2
Response time (5)
< 30s
< 20s
< 20s
Temperature (6)
-20°C to +55°C
-20°C to +50°C
-20°C to +50°C
Relative humidity and pressure range (7)
0 – 99 % RH
1 bar ± 10 %
0 – 99 % RH
1 bar ± 20 %
0 – 99 % RH
1 bar ± 20 %
Service life (8)
> 60 months
48 months
60 months
Storage conditions and maximum storage time (9)
4°C to +20 °C
10-60 % RH
1 bar ± 10 %
6 months
maximum
-40°C to +40 °C
10-60 % RH
1 bar ± 10 %
6 months
maximum
■ -40°C to +40 °C
10-60 % RH
1 bar ± 10 %
6 months
maximum
Warming-up delay (10)
300s
30s
30s
Notes
Hydrogen cannot be detected with IR sensor.
Measurement is
underestimated if oxygen level is < 10 %.
Exposure to high
levels of silicon or sulfur vapors may damage the sensor.
The monitor is
sensitive to the majority of explosive gases.
Sensors
Non-exhaustive list.
Table No. 1
62
BM 25/25W
Instruction Manual
Isobutylene
Oxygen (O2) 2 years
Oxygen (O2) 1 year
Sensor P/N
6313998
6313780
6313817
Standard range (1)
0 – 1500ppm isobutylene
2 - 30% volume
2 – 30% volume
Measurement principle
PID
Electrochemical
Electrochemical
Display resolution(1)
1ppm
0.1% v/v
0.1% v/v
Accuracy (2)
150
0.3% v/v
0.3% v/v
Repeatability (3)
0.1% v/v
0.1% v/v
Zero/Span drift (4)
0.2 / 2
0.2 / 2
Response time (5)
< 20s
< 10s
< 10s
Temperature (6)
0°C to +40°C
-20°C to +40°C
-20°C to +40°C
Relative humidity and pressure range (7)
0 – 90% RH
1 bar ± 20%
10 – 95% RH
1 bar ± 20%
10 – 95% RH
1 bar ± 20%
Lifetime (8)
> 12 months
28 months
16 months
Storage conditions and maximum storage time (9)
4°C - 20°C
10-60% RH
1 bar ± 10%
6 months
maximum
4°C – 20°C
10 60% RH
1 bar ± 10%
3 months
4°C – 20°C
10 60% RH
1 bar ± 10%
3 months
Warm-up Delay (10)
60s
Operational upon start up
Notes
10.6ev lamp
Presence of high levels of CO2 can lead to
an over estimation of O2 concentration.
Table No. 2
7 - Technical Specifications
63
Carbon dioxide (CO2)
Carbon Monoxide (CO)
Hydrogen sulfide (H2S)
Sensor P/N
6313818
6313787
6313788
Standard range (1)
0 - 5% v/v
1000
100
Measurement principle
Absorption Infrared
Electrochemical
Electrochemical Display resolution(1)
0.1% v/v
1
1
Accuracy (2)
0.2% v/v
15
3
Repeatability (3)
0.1% v/v
1
1
Zero/Span drifty (4)
0.2 / 2
0.5 / 1.5
0.5 / 2.5
Response time (5)
< 30s
< 30s
< 25s
Temperature (6)
-10°C to +40°C
-20°C to +40°C
-20°C to +40°C
Relative humidity and pressure range (7)
10 – 95% RH
bar ± 20%
10 – 95 % RH
1 bar ± 20 %
10 – 95% RH
1 bar ± 20%
Lifetime (8)
60 months
36 months
36 months
Storage conditions and maximum storage time (9)
0°C – 40°C
10 – 60% RH
1 bar ± 20%
6 months
4°C – 20°C
10 – 60% RH
1 bar ± 10%
2 months
4°C – 20°C
10 – 60% RH
1 bar ± 10%
2 months
Warm-up Delay
120s
Operational upon start up
Notes
Exposure to high levels of organic solvents
can damage the sensors.
Exposure to gases at levels higher than the
monitor’s range can damage the device.
Recalibrate sensors if they go out of range.
Table no. 3
64
BM 25/25W
Instruction Manual
Chlorine (Cl2)
Hydrochloric acid (HCl)
Hydrogen cyanide (HCN)
Sensor P/N
6313809
6313804
6313805
Standard range (1)
10
30
10
Measurement principle
Electrochemical
Electrochemical
Electrochemical
Display resolution(1)
0.1
0.1
0.1
Accuracy (2)
0.25 1 0.25
Repeatability (3)
2 2 2
Zero/Span ndrift (4)
0.5 / 5
0.5 / 5
0.5 / 5
Response time (5)
< 60s
< 80s
< 60s
Temperature (6)
-20°C to +40°C
-20°C to +40°C
-20°C to +40°C
Relative humidity and pressure range (7)
10 – 90% RH
bar ± 20%
15 – 95% RH
1 bar ± 20%
15 – 95% RH
1 bar ± 20%
Lifetime (8)
30 months
24 months
24 months
Storage conditions and maximum storage time (9)
4°C – 20°C
10 – 60% RH
1 bar ± 10%
2 months
4°C – 20°C
10 – 60% RH
1 bar ± 10%
2 months
4°C – 20°C
10 – 60% RH
1 bar ± 10%
2 months
Warm-up Delay (10)
Operational upon start up
Notes
Exposure to high levels of organic solvents can damage the sensors.
Exposure to gases at levels higher than the monitor’s range can
damage the device. Recalibrate sensors if they go out of range.
Table No. 4
7 - Technical Specifications
65
Ammonia (NH3)
Ammonia (NH3)
Nitrogen oxide (NO)
Sensor P/N
6313799
6313800
6313802
Standard range (1)
100
1000
300
Measurement principle
Electrochemical
Electrochemical
Electrochemical
Display resolution(1)
1 1 1
Accuracy (2)
5
30
10
Repeatability (3)
2 2 1
Zero/Span drift (4)
1 / 2
1 / 2
0.5 / 3
Response time (5)
< 90s
< 90s
< 30s
Temperature (6)
-20°C to +40°C
-20°C to +40°C
-15°C to +40°C
Relative humidity and pressure range (7)
10 90% RH
bar ± 20%
15 95% RH
1 bar ± 20%
15 95% RH
1 bar ± 20%
Lifetime (8)
30 months
24 months
30 months
Storage conditions and maximum storage time (9)
4°C – 20°C
10 60 % RH
1 bar ± 10%
2 months
4°C – 20°C
10 60% RH
1 bar ± 10%
2 months
4°C – 20°C
10 60% RH
1 bar ± 10%
2 months
Warm-up Delay (10)
Operational upon start up
Notes
Exposure to high levels of organic solvents can damage the sensors.
Exposure to gases at levels higher than the monitor’s range can
damage the device. Recalibrate sensors if they go out of range.
Table no. 5
66
BM 25/25W
Instruction Manual
Nitrogen dioxide (NO2)
Sulfur dioxide (SO2)
Sensor P/N
6313801
6313819
Standard range (1)
30
30
Measurement principle
Electrochemical
Electrochemical
Display resolution(1)
1
1
Accuracy (2)
1
1
Repeatability (3)
1
1
Zero/Span drift (4)
0.5 / 5
0.5 / 2
Response time (5)
< 30s
< 60s
Temperature (6)
-20°C to +40°C
-20°C to +50°C
Relative humidity and pressure range (7)
10 90% RH
bar ± 20%
15 95% RH
1 bar ± 20%
Lifetime (8)
30 months
24 months
Storage conditions and maximum storage time (9)
4°C – 20°C
10 60% RH
1 bar ± 10%
2 months
4°C – 20°C
10 60% RH
1 bar ± 10%
2 months
Warm-up Delay (10)
Operational upon start up
Notes
Exposure to high levels of organic solvents
can damage the sensors.
Exposure to gases at levels higher than the
monitor’s range can damage the device.
Recalibrate sensors if they go out of range.
Table No. 6
1. In ppm unless otherwise specified.
2. At 50% of scale (same unit as range).
3. As % of signal read unless otherwise specified.
4. Nominative values in normal use conditions per month as % of scale for zero and as % of
measurement for sensitivity.
5. In seconds at 90% of final value.
6. In °C.
7. Without condensation.
8. Averaged value. In normal conditions. 12 month warranty.
9. All sensors must be protected from air when stored.
10. Time to reach full performance of the sensor after warm-up.
Other gases, other ranges: consult us at info@oldhamgas.com
8 – Accessories and Spare Parts
67
Part Number
Description
6511157
Universal charger 110/230 VAC for BM 25/25W - Charging time
4.5hrs
6511164
Vehicle charger 12/30 VDC for BM 25/25W
WCHMUBM
Wall charger for BM 25/25W
6321390
Support for BM 25/25W wall charger
WLOGUSB
COM 2100 software kit with infrared/USB cable
6314588
Connection cable IR/USB
6331159
Sensors cover for calibration and manual sampling
6327920
Sampling kit with rigid probe for use with electrical pump
6327919
Sampling kit with semi-rigid pump probe (not for use in hazardous areas) for use with electrical pump
6327918
Sampling kit with telescopic probe for use with electrical pump
6327921
Manual sampling kit with crystal tube (4 meters)
6327922
Manual sampling kit with telescopic probe
6327923
Manual sampling kit with semi-rigid probe (not for use in hazardous areas)
6327924
Manual sampling kit with rigid probe
6321388
Tripod
Trickle charge kits
BM25KITCHS25
Intrinsically Safe Trickle charger with one IS power supply and 25 meters of IS cable
BM25KITCHS50
Intrinsically Safe Trickle charger with one IS power supply and 50 meters of IS cable
BM25KITCHS100
Intrinsically Safe Trickle charger with one IS power supply and 100 meters of IS cable
Chapter 8 | Accessories and Spare
Parts
Accessories
68
BM 25/25W
Instruction Manual
Part Number
Description
BM25KITCHD25
Intrinsically Safe Trickle charger with two IS power supplies and 25 meters of IS cable
BM25KITCHD50
Intrinsically Safe Trickle charger with two IS power supplies and 50 meters of IS cable
BM25KITCHD100
Intrinsically Safe Trickle charger with two IS power supplies and 100 meters of IS cable
Alarm transfer kits
6315862
Alarm transfer kit. Length 25 m
6315863
Alarm transfer kit. Length 50 m
6315864
Alarm transfer kit. Length 100 m
Part Number
Combustible sensors (fit slot #1 only)
6313888
EXPLO sensor, 0-100% LEL
6313889
EXPLO CATHARO sensor, range 0-100% LEL and 5-100% vol
CH4 for BM 25 only (H2 version also available).
MEDIUM sensors (fit slots #4 and #5 unless mentioned)
6313780
O2 sensor (lifetime 28 months)
6313823
Combo CO/H2S sensor (fits slot #4 only)
6313818
CO2 sensor 0-5% vol
6313857
NO2 sensor 0-30 ppm
6313843
Cl2 sensor 0-10 ppm
6313821
ETO sensor 0-30 ppm
6313819
SO2 sensor 0-30 ppm
6313822
SO2 sensor 0-100 ppm
MINI sensors (fit slots #2 and #3)
6313817
O2 sensor (lifetime 14 months)
6313787
CO sensor 0-1000 ppm
6313826
CO sensor 0-2000 ppm
6313788
H2S sensor 0-100 ppm
6313816
H2S sensor 0-30 ppm (special for hydrocarbons)
6313799
NH3 sensor 0-100 ppm
Spare Parts
8 – Accessories and Spare Parts
69
6313800
NH3 sensor 0-1000 ppm
6313801
NO2 sensor 0-30 ppm
6313802
NO sensor 0-300 ppm
6313803
H2 sensor – 0-2000 ppm
6313804
HCl sensor 0-30.0 ppm
6313805
HCN sensor 0-30.0 ppm
6313806
HF sensor 0-10 ppm
6313807
O3 sensor (Ozone) 0-1 ppm
6313808
SIH4 sensor (Silane) 0-50 ppm
6313809
Cl2 sensor 0-10.0 ppm
6313810
PH3 sensor (Phosphine) 0-1 ppm
6313811
AsH3 sensor (Arsine) 0-1 ppm
6313812
COCl2 sensor (phosgene) 0-1 ppm
6313820
F2 sensor 0-1 ppm
6313879
N2H4 sensor 0-1ppm
6313841
ClO2 sensor 0-3 ppm
MEDIUM sensors (fit slot #5 only)
6313998
PID isobutylene sensor 1500ppm
6314065
CH4 sensor IR 0-100% LEL (4.4%vol)
6314064
CH4 sensor IR 0-100% LEL (5.0%vol)
6314087
C3H8 sensor IR (0-100% LEL)
6314088
C4H10 sensor IR (0-100% LEL)
6314089
Isobutane IR sensor (0-100% LEL)
6314090
LPG IR sensor, (0-100% LEL)
6314092
CH4 IR sensor (0-100% vol)
Part Number
Accessory
6313832
Fake sensors kit (1 LEL, 2 mini, 2 medium)
6111303
Spare Intrinsically Safe power supply
6153027
Spare terminals for trickle charge kit
Note: this list is not exhaustive and may be modified. Sensors must be stored in a cool place (5°C).
70
BM 25/25W
Instruction Manual
9 – Special Instructions
71
ATEX
IECEx
EN 60079-0:2012
IEC 60079-0 (ed. 6), 2011
EN 60079-1:2007
IEC 60079-1 (ed. 6), 2007
EN 60079-11:2012
IEC 60079-11 (ed. 6), 2011
EN 60079-26:2007
IEC 60079-26 (ed. 2), 2007
EN 50303:2000
Chapter 9 | Special Instructions for
use in explosive atmospheres or
hazardous locations
Information in following paragraphs must be taken into account and followed by the person responsible for the equipment installation site. Refer to the provisions of European ATEX Directive 1999/92/EC or to the applicable local legislation, relevant to improving safety protection and health of workers exposed to the risks of explosive atmospheres.
The installation and maintenance of the gas monitor should be performed according to standards EN/IEC 60079-14 and EN/IEC 60079-17.
For intrinsically safe installations and especially for connections to the gas monitor, the person responsible for the intrinsic safety installation, called the System designer, must establish a system document demonstrating that the entire gas monitor system - Cable ­Body is Intrinsically Safe (see standard IEC 60079-25 for the preparation of this document).
The BM 25/25W complies with the following standards:
72
BM 25/25W
Instruction Manual
ATEX areas and general rules
Silicon vapors or other contaminants may have an adverse effect on catalytic sensors (slot 1) for combustible gas detection, and may distort measurements (under-estimated measurements).
If the device is used in a contaminated atmosphere, the catalytic sensor must be calibrated it before its next use.
The gas monitor can be used in explosive atmospheres in Group II surface industries and Group I mines containing firedamp.
The ambient temperature range for use is from –20° C to + 55° C. Depending on the type of sensors used on the device, categories covered by the gas
monitor are: a) BM 25/25W without infrared sensors
Surface industries: Category 1G, use in zones 0, 1 or 2
Mines containing firedamp: Category M1, for use in all gas levels
b) BM 25/25W with infrared sensors
Surface industries: Category 2G, use in zones 1 or 2
Mines containing firedamp: Category M2, for use below a certain concentration of
gas
The following operations are prohibited in explosive atmospheres:
Opening of the instrument: sensors cover or rear cover.
Charge the batteries using a universal or vehicle charger.
Link-up with a computer.
All servicing, adjustment and maintenance operations must be performed by duly approved personnel.
The battery pack must be replaced by the original part specified by the manufacturer – OLDHAM P/N 6311082.
Input/output parameters
Gas monitor recharge connector
The charger provided by OLDHAM should only be used outside of the ATEX areas. When the recharging is done by a charger other than the one provided by OLDHAM, its characteristics must not exceed a voltage of 30VDC and a current of 30 A.
9 – Special Instructions
73
The two previous circuits are separate intrinsic circuits. The cables connected to the ends of these circuits must comply with the requirements for intrinsically safe circuit wiring: cable type, insulation voltage, insulation, linear capacity and inductance. Refer to national and international standards, for example EN/IEC 60079-14.
Alarm relay output and dry logic input connectors
Input characteristics for the alarm relay output:
U
= 30 V max.
i
I
= 150 mA max.
i
Output characteristics for the dry logic input:
U
= 5 V.
o
I
= 50 mA.
o
L
= 8 mH.
o
C
= 7 µF.
o
Only circuits disconnected from power should be connected to digital input, or:
U
= 0 V.
i
I
= 0 A.
i
A Descriptive Document System should be established by the person responsible for the installation as explained above.
Trickle charging connection (external power source)
The external power source for battery pack maintenance must be intrinsically safe and must be compatible with the following gas detector input characteristics:
U
= 30 VDC.
i
I
= 160 mA.
i
C
= 0 µF.
i
L
= 0 mH.
i
It is possible to connect two external power supplies on the connector in accordance with the rules specified in the previous paragraph.
Connectors wiring diagram
The paragraph Connections on page 13 describes the gas monitor's various connections. Unused connectors must be equipped with their protective cap.
74
BM 25/25W
Instruction Manual
ATEX and IECEx Markings
II 1G/ I M1 Ex ia IIC T4 Ga / Ex ia I Ma
II 2G / I M2 Ex ia d IIC T4 Gb / Ex ia d I Mb
II 1G/ I M1 Ex ia IIB T4 Ga / Ex ia I Ma
II 2G / I M2 Ex ia IIC T4 Gb / Ex ia I Mb
II 2G / I M2 Ex ia d IIC T4 Gb / Ex ia d I Mb
BM 25 (without radio communication module)
OLDHAM CE 0080 BM 25 IP 66 Ambient T: -20° C +55° C
With infrared sensor block IP 66 Ambient T: -20° C +55° C
INERIS 05ATEX0044 Do not open in explosive atmospheres serial number manufacture year Warning: Read the instructions carefully before starting-up. Substitution of components may compromise intrinsic safety.
BM 25W (with radio communication module)
OLDHAM CE 0080 BM 25W IP 66 Ambient T: -20° C +55° C
or
With infrared sensor block IP 66 Ambient T: -20° C +55° C
INERIS 05ATEX0044 Do not open in explosive atmospheres Serial number Manufacture year Warning: Read the instructions carefully before starting-up. Substitution of components may compromise intrinsic safety.
9 – Special Instructions
75
Radio Communication Marking
Contains RF200 FCC ID : U9O-RF200 Contains RF200 IC : 7084A –RF200
This device complies with Part 15 of FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interferences, and (2) this device must accept any interference received, including interference that may cause undesired operation.
76
BM 25/25W
Instruction Manual
10 – Declaration of EC Conformity
77
Chapter 10 | Declaration of EC
Conformity
The document hereafter (2 pages) reproduces the EC declaration of conformity.
78
BM 25/25W
Instruction Manual
10 – Declaration of EC Conformity
79
EUROPEAN PLANT AND OFFICES
Z.I. Est – rue Orfila - CS 20417 – 62027 ARRAS Cedex FRANCE
Tél.: +33 (0)3 21 60 80 80 – Fax: +33 (0)3 21 60 80 00
Web site: http://www.oldhamgas.com
AMERICAS
Tel. : +1-713-559-9280 Fax : +1-281-292-2860
americas@oldhamgas.com
ASIA PACIFIC
Tel. : +86-21-3127-6373 Fax : +86-21-3127-6365
sales@oldhamgas.com
EUROPE
Tel. : +33 321 60 80 80 Fax : +33 321 60 80 00
info@oldhamgas.com
The Fixed Gas Detection Experts
Loading...