NOVUS N1500FT User Manual

N15
FLOW RATE INDICATOR
InLL
InKL
k.1nst
k.tot
Un1t 1
k.1nst
k.tot
Un1t1
k.1nSt
k.tot
k.1nst
k.tot
Un1t1
1N.TYPE
InLL
InKL
k.tot
Un1t1
InLL
InKL
InLL
InKL
k.tot
00FT Indicator
– INSTRUCTIONS MANUAL – V1.2x
The symbols below are used on th e equipment and throughout this document to draw the user’s att ention to important operational and safety information.
CAUTION:
Read this manual carefully prior to
installation and operation of the
unit.
All safety related instructions that appear in the manual must be observed to ensure pe rsonal safety and to prevent damag e to either the instrument or the sys tem. If the device is used in a manner not specified in this manual, its safety features may be impaired.
CAUTION OR DAN GER:
Electric shock hazard

INTRODUCTION

This flow rate indicator provides indication, totalization, retransmission, alarm and RS4 85 communication features (optional RTU Modbus slave). It reads most flow signals available in the market, such as pulse, magneti c pickup and 4-20 mA. The pulse input allows connecting sensors with outputs such as reed-switch, NPN, PNP and tension. Both for pul se input and 4-20 mA in put, unit is selectable and a scal e factor is s et to turn the input signal i nto the unit of choice. It provi des an isolated pulse output for totalized flow retransmission and a 4-20 mA output for immediate flow retransmission. Alarms are set off through 2 to 4 relays, depending on the equipment model.
AC models provide a 24 Vdc / 50 mA output.

INPUTS

The flow rate indicator allows for two basic input types:
Instantaneous flo w input through a 4-20 mA signal. In t his case, flow totalization is obtained by integrating instantaneous flow rate.
Totalized flow input through a pulse signal. In this case, instantaneous flow rate is obtained by deriving totalized flow rate.
Pulse signals may c o me fr om sensors/transmit te rs wi t h NPN , P NP, dry contact (reed switch) and tension signal output, or even magnetic pickup outputs.
When the input is set to 4-20 mA, you should establish on screens
and
which flow values are equivalent to 4-20 mA.
When the 4-20 mA input is not used as flow input, it may be used alternatively as auxiliary input. This way it i s possibl e to measure the pressure of a pipeline, for instance.
The pulse flow input may be scaled, both for instantaneous and totalized flow rates (independentl y), through ‘ K’ multipl ication factors:
and
.
Both flow time base and uni t must be defined on scr een To do so, there are six char acters, the first fi ve of which are us ed to set the unit and the las t one (to the right) is used to set the ti me b as e on which the flow rate is measured. Available time bases are ‘s’ (seconds), ‘m’ (minutes), ‘h’ (hours) and ‘d’ (days).
.
With pulse flow input, totalizati on wi ll cont inue ev en if the input rate is below the minimum rate required. Instantaneous flow rate i ndication will be zero whenever there is a time lapse of 10 secon ds without input variation. In this cas e, whenever the re is a total ization i ncrease (more input pulses), the ins tantaneous flow value will be s hown for the nest 10 seconds.

“K” FACTORS

The instantaneous K factor ( allow the user to view the instantaneous and totalized flow in different units.
The instantaneous K factor will be available only i n case the s elected flow input type is different from 4-20 mA. When the input type is 4-20 mA, the configured ra nge limits already provide the parameters for the indication.
Instantaneous flow is directly related to the time base set in parameter
In case user erroneously configures parameters with value “0” (zero), this will be assigned value “0.00001”.
Example 1: Chosen meter gives us an information of (pulses per volume) 50
pulses per liter. User wants to v iew the i nstantan eous flo w in li ters (l) and the totalized flow in cubic meters (m³).
In order to do that, parameter so indicating the instantaneous flow in liters. Parameter be set a value of “50000”, so indicating the totalized flow in m³.
Instantaneous flow will be vi ewed ba sed on the selected time base in which means 1 liter/second, and the selected time base is m
(minute), the instantaneous flow indication will be 60 (liters/minute). Example 2:
Chosen sensor gives us an inf ormation in 4-20 mA that corresponds to a flow between 0 and 100 liters per minute. Us er wants to v iew the totalized flow in cubic meters (m³).
On this case, parameter and parameters “100”. This way, we pass to the equipment the infor mation that 4 mA relates to 0 liters per minute and 20 mA relates to 100 liters per minute. In case sensor output is 12 mA, flow will be displayed as 50 liters/minute.
Parameter This way, the totalized flow will be converted and displayed in m³ (cubic meters).
When the instantaneous flow type is selected as 4-20 mA, the time base selected in having just unit display purposes. The indication conversion from “liters per minute” to “liters per hour” should be adj usted directly on input limits
In case user wanted instantaneous flow indicated in cubic meters per hour (m³/h) with the same meter, the values “0” and “6” should h ave been selected in input limits value means 100 l/min conve rted to m³/h. be changed to “1” because input is already in m³.
.
. In case the example meter output is 50 pulses per second,
should have a value of 0.001 (1 liter = 0.001 m³).
and
) and the total K factor (
should be set a value of “50”,
and
have no influence over the indicated val ues,
sholud be selected as 4-20 mA
should b e configured as “0” and
.
and
, where the second
parameter should
and
should
)
NOVUS AUTOMATION 1/9
N1500FT Flow Indicator
InLL
InKL
1n LL
1n xl
RTLL
RTKL
off
I.error
FEEDER
ADVANCED
Alarm Event
Alarm
Output
Alarm Event
Alarm
Output
T2
Alarm Event
Alarm
Output
T1
Alarm Event
Alarm
Output
T1
T2
T1

CUSTOMIZED LINEARIZATION

When the flow rate is read through a 4-20 mA input, it is possibl e to apply a customized linearizati on composed of 30 input points and 30 output points. Whenever the re adi ng fal ls between two i nput poi nts, it will be normalized to the range defined by the res pecti v e points i n the output range.
The input range considered as an input to the li nearization table is
and
the range defined by the user in the
parameters (it is not the current in mA). In case us er wants to enter the v alues directly in mA to convert to the desired viewing uni t, parameter be set as 4 (mA) and parameter
as 20 (mA), using as many
must
decimal places as needed to the desired precisi on. It will be possible then to enter values between 4-20 (mA) as input points for the customized linearization.
The search for framing the valu e read is done while the lis t of input points is incrementally decl ared. The search is terminated i f the next point in the list is l ower than the current one. If the input value is lower than the first val ue in the list of input points, li nearization will return the first output value. Similarly, if the input value is greater than the highest value in the list of input points, linearization will return the highest value in the output list.
IMPORTANT: At least t wo pairs of input-output points are required for adequate customized linearization.

RETRANSMISSION

Flow rate retransmission c an be done vi a 4-20 mA output a nd pulse output.

The 4-20 mA output may be used regardless of the type of flow i nput.
and
To use it, just set the retransmission range to associating the flow rates to 4-20 mA.

In the case of retransmission via pulse output, one must choose between volumetric pulse output and frequency pulse output. The former may be used regardless of th e type of i nput, while the l atter i s available only for pulse inputs.

In the volumetric mode, a pulse of configurable length is generated every time the totalizer accumulates a preset volume. For example, for a period of 1 second and volume of 10 liters, a 1-second pulse will be generated for every 10 liters totalized. The counting to the output pulse will be reset every time the user resets the totalizer or whenever a feeding process is finished.
Note: In case the feeding process is running and the totalizer is reset by the user, the process will remain running normally, but the output pulse will not be synchronized with this process anymore, which can lead to a missing pulse informed at the end of the feeding process. As it is always reset at the end of the process, output pulse counter will synchronize again for a new feeding process.

In the frequency mode, the pulse output will divide the input frequency by a programmable constant whose val ue is equal to or higher than 2.

IMPORTANT: Maximum output frequency has hardware limitation. See Specifications. Check the “Specifications”.

ALARMS

The indicator’s basic versi on has 2 alarm outputs , with the option of up to 4 alarms. Whenever an alarm is on, a corresponding light signal will be displayed on the front panel.
Minimum Value – Lo It sets off when the reading is below the value determined by the
alarm Setpoint.
Maximum Value – Ki It sets off when the reading is abov e the value determined by the
alarm Setpoint.
Feeder Function – It activates the output relay when it is s tarted by pressing or
via the auxiliary digital input (according to setup) and deactivates when the reading reaches the value determined by the alarm setpoint
or when the key or digital input is pressed/closed again, putting the process on hol d. In case of pressing the key or
digital input more than 3 seconds, process is reset and stays waiti ng to be started.
Further details in the “Feeder” section.

ALARM TIMER

The indicator allows setting up an Alarm Timer , where users can set the alarm to go off with a delay, to go off in only one pulse or to go off in sequential pulses.
Figures in Table 1 show these functions. There, times T1 and T2 may vary from 0 to 32000 seconds and are defined while programming the indicator. For regular (no timers) operation of alarms, simply set T1 and T2 to 0 (zero).
He alarm light signals will be displayed whenever there is alarm condition, regardless of the c urrent status of the outpu t relay, which
,
may be temporarily out of power because of the timer function.
FUNCTION
Regular
Operation
Delay 0 1 to 32000
Pulse 1 to 32000 0
Oscillator 1 to 32000 1 to 32000
T1 T2 ACTION
0 0
Table 1 - Alarm timer functions
ALARM HYSTERESIS Hysteresis defines the difference between the value measured when
the alarm is triggered and the value at which it is deactivated.

INITIAL ALARM BLOCK

The initial block opti on pr ev e nts the al ar m fro m goin g off i n c ase the re is alarm condition at the time the indicator is being energized. The alarm may be trigger ed only after a non-alarm condit ion is follow ed by an alarm condition. This function is not valid for alarms programmed as Open Sensor.

SPECIAL FUNCTIONS

ALARM FUNCTIONS

The alarms can be programmed to operate with four different functions, described below. They may also be turned
.
Alarms use only the instantaneous flow rate reading. Totalization readings cannot be used as input for alarms. T he auxiliary 4-20 mA input (when it is not being used f or flow rate measurement) may b e

MAXIMUM AND MINIMUM

The flow indicator continuously rec ords the minimum and maximum values of instantaneous f low rate. These values can be viewed on the first screen of the main cycle by pushing and , respectively. The key can be set to zero maximum and minimum values.
used only as input for the open sensor alarm.
Open Sensor – The open sensor alarm operates whenever the input sensor is badly
connected or broken. Valid only for 4-20 mA inputs.
NOVUS AUTOMATION 2/9
N1500FT Flow Indicator
Bat.rst

AUXILIARY DIGITAL INPUT AND KEY

Similarly to a digital input, the key can be set to zero the totalizer, freeze the main screen, zero minimum and maximum readings or control the feeder function.

FEEDER

The feeder function is used t o control the volume of fluids based on its flow rate. It is typicall y used for storage applic ations, where the re is a start signal that triggers a relay and the flow rate begins to be measured. When reaching a gi ven setpoint, this relay is deactivated to stop flow.
Its use depends on correct configuration of the related alarm. During the feeder process, it is not possible to change the alarm
setpoint. Process should be reset first to allow it. Functions of key and/or digital input, when assigned to the
feeder function:
When the key or digital input is activated, the feeder
process is started, activating all relays related to the feeder alarm;
In case the key or digital input i s act ivated onc e agai n, the
process i s frozen and all relays related to the feeder alarm are deactivated;
To restart the feeder process, key or digital input must be
activated for 3 seconds, until the process is restarted, ze roing all existing feeder indication. This can be done with the process stopped or running;
At the end of the feeder process, when alarm setpont is reached,
process values are frozen and all rel ated relays are deactivated. To restart a new process , just activate the key or digital
input for all counters to be reset and process will start running;
In case of a power shorta ge, if the feeder batch reset parameter
( powers up again the proces s will restore from where it s topped. This means that, if it was in the middle of a f eeder process, all relays assigned to the feeder alarm will be activated. If the process was stopped, all counte rs will keep their values an d the process will remain stopped until it is activated either by the
) is configured as no, whenever the equipment
key or the digital input.

ELECTRICAL CONNECTIONS

All the inside can be removed without the need to undo the el ectrical connections. Disposition of si gnal s in the rear panel of t he indi cat or is shown in Fig. 1.
Fig. 1 – Rear panel connect ions

POWER SUPPLY CONNECTION

Fig. 2 – Power supply terninals

CONNECTIONS FOR INPUT AND OUTPUT SIGNALS

It is important that these connections are well made, with signal or sensor wires securely attached to rear panel terminals. Check the “Specifications” section for the range of the input signals.

The images below show connections for different input types:

MANUAL OPERATION MODE

In the hardware cycle, outputs can be set manually. This can be extremely useful for tests and simulations. After exiting the cycle, outputs go back to their regular status.

24 VDC AUXILIARY POWER SUPPLY

DC power supply models provide a 24 Vdc output for field transmitters.

INSTALLATION

The indicator must be installed on a panel. T o do so, remov e the two plastic clamps, introduce the devi ce in the panel cutout and put the clamps back from the rear side of the indicator.

INSTALLATION RECOMMENDATIONS

Input signal conducers should be disposed in the system
separately from output conducers and power conducers, preferably in grounded electrodes.
Instruments should be powered through a dedicated network.
For control and monitoring applicati ons it is vital to consider what
might happen if any part of the system fai ls. The alarm internal relay does not ensure total protection.
It is recommended to use RC FILTERS (47 and 100 nF, series)
in contactor coils, solenoid coils, etc.
Fig. 3 – Auxiliary digital input
connection
Fig. 5 - Flow pulse input –
NPN signals
Fig. 7 - Flow pulse input – Dry
contact signals
Fig. 4 - Flow pulse input –
Voltage signals
Fig. 6 - Flow pulse input –
PNP signals
Fig. 8 – Coil Signal connection
(magnetic pickup)
NOVUS AUTOMATION 3/9
Loading...
+ 6 hidden pages