NOVUS N120, N125 User Manual

1
N120/N125 CONTROLLER
Holding
Registers
Parameter
Register Description
0000
Active SP
Read: Active control SP (main SP, from ramp and soak or from remote SP).
Write: to main SP
Range: from spll to spkl.
0001
PV
Read: Process Variable.
Write: Not allowed.
Range: Minimum value is the one configured in spll and the maximum value is the one configured in spkl. Decimal point position depends on dppo value.
In case of temperature reading, the value read is always multiplied by 10, independently of dppo value.
0002
MV
Read: Output Power in automatic or manual mode.
Write: Not allowed. See address 28.
Range: 0 to 1000 (0.0 to 100.0%).
0003
Remote SP
type
Read/Write: Selected input type for remote SP.
Range: 0 to 3
0004
Display
value
Read: Current value shown on display.
Write: Current value shown on display.
Range: -1999 to 9999. The range depends on the displayed parameter.
0005
Screen number
Read: Current screen number.
Write: not allowed. Range: 0000h to 060Ch
Prompt number format: XXYYh, where:
XXmenu cycle number (check item 4 - INSTALLATION/CONNECTIONS)
YYprompt number (index).
0006
Status Word
1
Read: Status bits. See table 2. Write: not allowed.
Read values: See table 2
0007
Software
Version
Read: The firmware version of controller.
Write: not allowed.
Read values: If V1.00, the read value will be 100.
0008
ID
Read: controller identification number. Write: not allowed.
Values: 32 – N120 Controller
37 – N125
Other values: special instruments.
0009
Status Word 2
Read: Status bits. Write: not allowed.
Read values: See table 2.
0010
Status Word 3
Read: Status bits. Write: not allowed.
Read values: See table 2.
0011
Ir
Integral Rate (in repetitions/min)
Range: 0 to 9999 (0.00 to 99.99)
0012
Dt
Derivative Time (in seconds).
Range: 0 to 3000 (0.0 to 300.0)
0013
Pb
Proportional Band (in percentage)
Range: 0 to 5000 (0.0 to 500.0)
0014
tbas
Read/Write: Time base for the ramp and soak programs.
Range: 0 – 1 (seconds/minutes)
0015
Ct
Cycle Time (PWM, in seconds)
Range: 5 to 1000 (0.5 to 100.0)
0016
Freq
Read/Write: Mains frequency.
Range: 0 – 1 (60/50Hz)
0017
kyst
On/Off Control Hysteresis (in selected type engineering unit).
Range: 0 to spkl - spll
0018
fltr
Read/Write: PV digital filter gain.
Range: 0 – 20
0019
ovll
Output Low Limit (minimum output power)
Range: 0 to 1000 (0.0 to 100.0%).
0020
ovkl
Output High Limit (minimum output power)
Range: 0 to 1000 (0.0 to 100.0%).
0021
Reserved
Internal use.
0022
Reserved
Internal use.
Communication Manual – V1.1x
1. SERIAL COMMUNICATION
1.1 COMMUNICATION INTERFACE
The optional serial interface RS485 allows to address up to 247 controllers in a network communicating remotely with a host computer or master controller.
RS485 Interface
Compatible line signals with RS485 standard 3 wire connection from master to up to 31 slaves indicators in a multidrop bus. It is
possible address 247 nodes with multiple outputs converters.
Maximum communication distance: 1000 meters The RS485 signals are:
D1 = D: Bidirectional data line. D0 = C = GND: Optional connection which left communication better.
General Characteristics
Optically isolated serial interface Programmable baud rate: 1200, 2400, 4800, 9600, 19200, 38400, 57600 or
115200 bps.
Data Bits: 8 Parity: None, Even or Odd. Stop Bits: 1
Communication Protocol
The MOSBUS RTU slave is implemented, available in most SCADA softwares in the market.
All configurable parameters can be accessed (for reading or writing) through the Registers Table. Broadcast commands are supported as well (address 0).
The available Modbus commands are:
03 - Read Holding Register
05 - Force Single Coil (Force Digital Output state)
06 - Preset Single Register
16 - Preset Multiple Registers (Block write to multiple holding registers)
The registers are arranged in a table in such a way that several registers can be read in the same request.
Bidirectional inverted data line.
D:
1.2 CONFIGURATION OF SERIAL COMMUNICATION PARAMETERS
Two parameters must be configured in the device for serial communication:
bavd: Baud rate. All devices with same baud rate. addr: Device communication address. Each device must have an exclusive address.
prty: Paraty.
1.3 REGISTERS TABLE
Equivalent to the registers referenced as 4XXXX.
The holding registers are basically a list of the internal indicator parameters. All registers above address 12 can be read or written. The registers up to this address in more are read only. Please verify each case. Each table parameter is a 16 bits two complement signed word.
2
0023
Serial
number H
Serial Number High (Upper display).
Range: 0 to 9999. Read only.
0024
Serial
number L
Serial Number Low (Lower display).
Range: 0 to 9999. Read only.
0025
SV
Control Setpoint (Prompt Setpoint).
Range: from spll to spkl.
0026
spll
Setpoint Low limit.
Range: minimum value depends on the input type selected in type (see Table 1) to spkl.
0027
spkl
Setpoint High limit.
Range: minimum value is spll and maximum depends on the input type selected in type (see Table 1).
0028
Reserved
Internal use.
0029
offs
Offset value of PV(Process value).
Range: from spll to spkl.
0030
dppo
PV decimal point position
Range: 0 to 3
00.000; 100.00; 2000.0; 30000
0031
Sp.a1
Alarm 1 Setpoint.
Range: From spll to spkl for non differential; and spkl - spll for differential alarm.
0032
Sp.a2
Alarm 2 Setpoint. Range: same as in spa1.
0033
Sp.a3
Alarm 3 Setpoint. Range: same as in spa1.
0034
Sp.a4
Alarm 4 Setpoint. Range: same as in spa1.
0035
Fva1
Alarm 1 Function. Range: 0 to 8
0 off 1ierr 2 T.END 3 rs 4 lo 5 ki 6 dif 7 difl;
8 difk;
0036
Fva2
0037
Fva3
0038
Fva4
0039
Kya1
Alarm 1 Hysteresis. Range: 0 to 9999 (0.00 to 99.99%)
0040
Kya2
Alarm 2 Hysteresis. Range: same as in kya1.
0041
Kya3
Alarm 3 Hysteresis. Range: same as in kya1.
0042
Kya4
Alarm 4 Hysteresis. Range: same as in kya1.
0043
type
PV input type:
0 = J 1 = K 2 = T 3 = N 4 = R 5 = S 6 = B 7 = E 8 = Pt100 9 = 0-20 mA 10 = 4-20 mA 11 = 0-50 mV 12 = 0-5 V 13 = 0-10 V
0044
addr
Communication slave address. Range: 1 to 247
0045
bavd
Communication Baud-Rate:
01200;12400;24800;39600; 419200;
538400; 657600; 7115200;
0046
avto
Control Mode. Range: 0manual; 1automatic.
0047
rvn
Enable control. Range: 0no; 1yes.
0048
act
Control action. Range: 0direct; 1reverse.
0049
atvn
Auto tune enable:
0= off;1= Fast; 2= Full; 3= Self; 4= rSLF; 5= tGHt;
0050
Bla1
Alarm power-up inhibit. Range: 0no; 1yes.
0051
Bla2
0052
Bla3
0053
Bla4
0054
Key
Key press remote action. Range: 0 to 9
1: tecla P 2: tecla
4: tecla 8: tecla B
9: teclas P e B
0062
A1t1
Alarm 1 Time 1. Range: 0 to 6500s.
Refer to operation manual for more details.
0063
A1t2
Alarm 1 Time 2 (in seconds).
Range: same as in a1t1.
0064
A2t1
Alarm 2 Time 1 (in seconds).
Range: same as in a1t1.
0065
A2t2
Alarm 2 Time 2 (in seconds).
Range: same as in a1t1.
0066
sfst
Soft-Start time (in seconds).
Range: 0 to 9999
0067
vnit
Temperature unit. Range: 0 to 1.
0C; 1F.
0068
bias
Bias. Range: -100 to +100%.
0070
R&S
Segment
Ramp and Soak segment being executed (read only). Range: 0 to 9.
0071
Pr n
Ramp and Soak segment to be viewed or edited.
Range: 1 to 20.
0072
E pr
Ramp and Soak segment to be executed.
Range: 0 to 20.
0073
Remaining time
R&S
Indicates the remaining time of the Ramp and Soak segment.
0074
Sqrt
Square root of a linear input.
Range: 0->Disable;1->Enable.
0075
Calibration PV
Low
Enter the low input value currently applied in the PV input for calibration purposes.
0076
Calibration PV
High
Enter the high input value currently applied in the PV input for calibration purposes.
0077
Calib. remote
SP Low
Enter the low input value currently applied in the remote setpoint input for calibration purposes.
0078
Calib. remote
SP High
Enter the high input value currently applied in the remote setpoint input for calibration purposes.
0081
FLSH
Enables the top display blinking as a function of the selected alarm:
0-> Disable 1-> Enable to alarm 1 2-> Enable to alarm 2 3-> Enable to alarm 1 and 2
0086
Rstr
Restores original default calibration.
Range: 0 to 1; 0-> do not restore; 1-> restore calibration
3
0087
PASS
Write: 0
0089
PRTY
Serial communication parity.
0-> no parity; 1 - > even parity; 2 - >odd parity;
0090
Ctyp
Customized input type.
0091
Time
Timer set value.
0092
rate
Maximum rate of PV.
0093
Reserved
Internal use
0094
Fv.di
Digital input function:
0 – Off 1 – mAN 2 – RUN 3 – kprg
4 - Pr 1
0100
Pe1
Segment 1 Event of R&S Program 1.
Range: 0 to 15. Check table 6 of the instruction manual.
0101
Pe2
Segment 2 Event of R&S Program 1.
Range: same as in pe1
0102
Pe3
Segment 3 Event of R&S Program 1.
Range: same as in pe1.
0103
Pe4
Segment 4 Event of R&S Program 1.
Range: same as in pe1.
0104
Pe5
Segment 5 Event of R&S Program 1.
Range: same as in pe1.
0105
Pe6
Segment 6 Event of R&S Program 1.
Range: same as in pe1.
0106
Pe7
Segment 7 Event of R&S Program 1.
Range: same as in pe1.
0107
Pe8
Segment 8 Event of R&S Program 1.
Range: same as in pe1.
0108
Pe9
Segment 9 Event of R&S Program 1.
Range: same as in pe1.
0109
Pe1
Segment 1 Event of R&S Program 2.
Range: same as in pe1 of Program 1.
0110
Pe2
Segment 2 Event of R&S Program 2.
Range: same as in pe1.
0111
Pe3
Segment 3 Event of R&S Program 2.
Range: same as in pe1.
0112
Pe4
Segment 4 Event of R&S Program 2.
Range: same as in pe1.
0113
Pe5
Segment 5 Event of R&S Program 2.
Range: same as in pe1.
0114
Pe6
Segment 6 Event of R&S Program 2.
Range: same as in pe1.
0115
Pe7
Segment 7 Event of R&S Program 2.
Range: same as in pe1.
0116
Pe8
Segment 8 Event of R&S Program 2.
Range: same as in pe1.
0117
Pe9
Segment 9 Event of R&S Program 2.
Range: same as in pe1.
0119
Pe1
Segment 1 Event of R&S Program 3.
Range: same as in pe1 of Program 1.
0120
Pe2
Segment 2 Event of R&S Program 3.
Range: same as in pe1.
0118
Pe3
Segment 3 Event of R&S Program 3.
Range: same as in pe1.
0121
Pe4
Segment 4 Event of R&S Program 3.
Range: same as in pe1.
0122
Pe5
Segment 5 Event of R&S Program 3.
Range: same as in pe1.
0123
Pe6
Segment 6 Event of R&S Program 3.
Range: same as in pe1.
0124
Pe7
Segment 7 Event of R&S Program 3.
Range: same as in pe1.
0125
Pe8
Segment 8 Event of R&S Program 3.
Range: same as in pe1.
0126
Pe9
Segment 9 Event of R&S Program 3.
Range: same as in pe1.
0127
Pei
Segment 1 Event of R&S Program 4.
Range: same as in pe1 of Program 1.
0128
Pe2
Segment 2 Event of R&S Program 4.
Range: same as in pe1.
0129
Pe3
Segment 3 Event of R&S Program 4.
Range: same as in pe1.
0130
Pe4
Segment 4 Event of R&S Program 4.
Range: same as in pe1.
0131
Pe5
Segment 5 Event of R&S Program 4.
Range: same as in pe1.
0132
Pe6
Segment 6 Event of R&S Program 4.
Range: same as in pe1.
0133
Pe7
Segment 7 Event of R&S Program 4.
Range: same as in pe1.
0134
Pe8
Segment 8 Event of R&S Program 4.
Range: same as in pe1.
0135
Pe9
Segment 9 Event of R&S Program 4.
Range: same as in pe1.
0136
Pe1
Segment 1 Event of R&S Program 5.
Range: same as in pe1 of Program 1.
0137
Pe2
Segment 2 Event of R&S Program 5.
Range: same as in pe1.
0138
Pe3
Segment 3 Event of R&S Program 5.
Range: same as in pe1.
0139
Pe4
Segment 4 Event of R&S Program 5.
Range: same as in pe1.
0140
Pe5
Segment 5 Event of R&S Program 5.
Range: same as in pe1.
0141
Pe6
Segment 6 Event of R&S Program 5.
Range: same as in pe1.
0142
Pe7
Segment 7 Event of R&S Program 5.
Range: same as in pe1.
4
0143
Pe8
Segment 8 Event of R&S Program 5.
Range: same as in pe1.
0144
Pe9
Segment 9 Event of R&S Program 5.
Range: same as in pe1.
0145
Pe1
Segment 1 Event of R&S Program 6.
Range: same as in pe1.
0146
Pe2
Segment 2 Event of R&S Program 6.
Range: same as in pe1.
0147
Pe3
Segment 3 Event of R&S Program 6.
Range: same as in pe1.
0148
Pe4
Segment 4 Event of R&S Program 6.
Range: same as in pe1.
0149
Pe5
Segment 5 Event of R&S Program 6.
Range: same as in pe1.
0150
Pe6
Segment 6 Event of R&S Program 6.
Range: same as in pe1.
0151
Pe7
Segment 7 Event of R&S Program 6.
Range: same as in pe1.
0152
Pe8
Segment 8 Event of R&S Program 6.
Range: same as in pe1.
0153
Pe9
Segment 9 Event of R&S Program 6.
Range: same as in pe1.
0154
Pe1
Segment 1 Event of R&S Program 7.
Range: same as in pe1 for Program 1.
0155
Pe2
Segment 2 Event of R&S Program 7.
Range: same as in pe1.
0156
Pe3
Segment 3 Event of R&S Program 7.
Range: same as in pe1.
0157
Pe4
Segment 4 Event of R&S Program 7.
Range: same as in pe1.
0158
Pe5
Segment 5 Event of R&S Program 7.
Range: same as in pe1.
0159
Pe6
Segment 6 Event of R&S Program 7.
Range: same as in pe1.
0160
Pe7
Segment 7 Event of R&S Program 7.
Range: same as in pe1.
0161
Pe8
Segment 8 Event of R&S Program 7.
Range: same as in pe1.
0162
Pe9
Segment 9 Event of R&S Program 7.
Range: same as in pe1.
0163
Pe1
Segment 1 Event of R&S Program 8.
Range: same as in pe1 of Program 1.
0164
Pe2
Segment 2 Event of R&S Program 8.
Range: same as in pe1.
0165
Pe3
Segment 3 Event of R&S Program 8.
Range: same as in pe1.
0166
Pe4
Segment 4 Event of R&S Program 8.
Range: same as in pe1.
0167
Pe5
Segment 5 Event of R&S Program 8.
Range: same as in pe1.
0168
Pe6
Segment 6 Event of R&S Program 8.
Range: same as in pe1.
0169
Pe7
Segment 7 Event of R&S Program 8.
Range: same as in pe1.
0170
Pe8
Segment 8 Event of R&S Program 8.
Range: same as in pe1.
0171
Pe9
Segment 9 Event of R&S Program 8.
Range: same as in pe1.
0172
Pe1
Segment 1 Event of R&S Program 9.
Range: same as in pe1 of Program 1.
0173
Pe2
Segment 2 Event of R&S Program 9.
Range: same as in pe1.
0174
Pe3
Segment 3 Event of R&S Program 9.
Range: same as in pe1.
0175
Pe4
Segment 4 Event of R&S Program 9.
Range: same as in pe1.
0176
Pe5
Segment 5 Event of R&S Program 9.
Range: same as in pe1.
0177
Pe6
Segment 6 Event of R&S Program 9.
Range: same as in pe1.
0178
Pe7
Segment 7 Event of R&S Program 9.
Range: same as in pe1.
0179
Pe8
Segment 8 Event of R&S Program 9.
Range: same as in pe1.
0180
Pe9
Segment 9 Event of R&S Program 9.
Range: same as in pe1.
0181
Pe1
Segment 1 Event of R&S Program 10.
Range: same as in pe1 of Program 1.
0182
Pe2
Segment 2 Event of R&S Program 10.
Range: same as in pe1.
0183
Pe3
Segment 3 Event of R&S Program 10.
Range: same as in pe1.
0184
Pe4
Segment 4 Event of R&S Program 10.
Range: same as in pe1.
0185
Pe5
Segment 5 Event of R&S Program 10.
Range: same as in pe1.
0186
Pe6
Segment 6 Event of R&S Program 10.
Range: same as in pe1.
0187
Pe7
Segment 7 Event of R&S Program 10.
Range: same as in pe1.
0188
Pe8
Segment 8 Event of R&S Program 10.
Range: same as in pe1.
0189
Pe9
Segment 9 Event of R&S Program 10.
Range: same as in pe1.
0190
Pe1
Segment 1 Event of R&S Program 11.
Range: same as in pe1 of Program 1.
0191
Pe2
Segment 2 Event of R&S Program 11.
Range: same as in pe1.
0192
Pe3
Segment 3 Event of R&S Program 11.
Range: same as in pe1.
Loading...
+ 9 hidden pages