Novatek UBZ-302 User guide

NOVATEK-ELECTRO LTD Research -and-Manufacture Company

ELECRTIC MOTORS

UNIVERSAL PROTECTION DEVICE

UBZ-302

SERVICE MANUAL
www.novatek-electro.com
- 2 -
1. GENERAL DESCRIPTION AND OPERATION
1.1 APPLICATION
UBZ-302 is the microprocessor based digital device, reliable and of highest degree of measurement accuracy. It doesn’t require the operational external power supply since the controlled voltage at the same time is the power supply for UBZ-302. It has 3 built-in current measurement transformers through which the motor power supply wires are looped for continuous currents monitoring.
Universal electric motor protection device (hereinafter UBZ-302) is designed for the continuous control of the power supply voltage, monitoring of acting values of phase/line currents in 3 phase electrical circuits and additiona­lly performs the resistance test to check the level of motor coils insulation.
UBZ-302 performs protection of asynchronous electric motors with rated power from 2,5 to 30 kW using built in current transformers. With the use of externally connected current transformers (not supplied together with UBZ-302) is possible to protect motors with rated power up to 315 kW. Moreover UBZ-302 is capable to work in electric circuits with isolated neutral (allows operation in both in 3 and 4 wire electric circuits).
UBZ-302 protects the electric motors in the following alarm situations:
Low quality power supply voltage:
o not allowable voltage surges and fluctuations, phase loss, wrong phase sequence, phase imbalance of
phase/line voltage, phase coincidences;
Mechanical overloads (symmetrical overload in phase/line currents);
Exceeding the threshold for reverse current sequence;
Non-symmetry of the phase currents in the absence of overload which may happen either due to fault of
insulation of the motor coils or the power supply cable. UBZ-302 performs comparison of non-symmetry coefficient for reverse sequence current with the non-symmetry coefficient of the voltage on the reverse sequence.
Disappearing of the drive torque of the motor shaft (dry stroke for the pumps) – protection on the minimal starting current and/or operation current;
Long lasting motor start or blocked rotor;
Checking the level of insulation between the stator and motor case before the motor start;
Earth leakage protection of stator coils during the motor operation;
Thermal overload protection for the motor;
Overheating protection for the motor coils. UBZ-302 performs temperature monitoring using built in to the
motor temperature sensors or the temperature of the motor case could be measured with the use of external temperature sensors.
For every type of protection mentioned above it’s possible to set individually the autoreclosing parameters (allowed or not allowed to start the motor automatically after certain type of fault or alarm situation).
UBZ-302 performs protection of a motor or equipment by operating with the magnetic coil of contactor which in its turn commutates the required power load.
UBZ-302 has 2 output relays: power load relay and functional relay. Presence of 2 output relays gives the possibility to arrange DELTA/STAR switching, turn ON with the delayed start (cascade turn ON of motors) and remote signalization. UBZ-302 detects the presence of the currents when the power load relay contacts are open and when the functional relay is in the DELTA/STAR mode. If these currents are detected then UBZ-302 indicates the fault of the external contactor that turns motor ON. UBZ-302 will keep on indicating this fault until it will not be deenergized (turned OFF).
DATA TRANSMISSION
- control operation and data transmission using RS-485 interface in accordance with MODBUS protocol,
- control operation and data transmission using RS-232 interface.
N o t i c e: Simultaneous use of RS-485 and RS-232 is impossible.
For work of the personal computer with UBZ-302 the program "Control panel UBZ-302", is placed on a company site can be used (http://www.novatek-electro.com/production_ubz.htm).
The program "Control panel UBZ-302" is intended for the control of a condition and data gathering from devices UBZ-302, to communication means (RS-232 or RS-485). The program allows to keep to (load) various options UBZ, to conduct data gathering and to keep them for the further researches.
1.1.2 CHARACTERISTICS OF THE BUILT-IN OUTPUT TERMINALS
Basic characteristics of the UBZ-302 output relays are shown in Tables 1.1 and 1.2 shown below
Cos ϕ = 0,4 Cos ϕ = 1,0
UBZ-302
Table 1.1 - Power load relay
Maximal current
at U~250V
2 A 5 A
Commutation lifetime х1000
100 100
Maximal power
for commutation
Maximal long lasting withstand AC voltage
1000 VA 460 V 3 A (50000)
Maximal current at
=30V (commut.)
U
const
NOVATEK-ELECTRO
- 3 -
Cos ϕ = 0,4 Cos ϕ = 1,0
Maximal current
at U~250V
5 A
16 A
Table 1.2 -Functional relay
Commutation lifetime х1000
100 100
Maximal power
for commutation
Maximal long lasting
withstand AC voltage
Maximal current at U
const
4000 VA 440/300 V 3 A
=30V(commut.)
1.1.3 Restrictions for the UBZ-302 application and the selection of the parameters
1.1.3.1 The use of built-in current transformers.
It’s prohibited to use the UBZ-302 for the protection of the motors with rated power more than 20 kW.
When measuring the currents in the range from 63 A to 300A the measurement error does not exceed 5% value but if the currents are more than 320 A, then the current transformer core saturation happens and this lead to significant decrease of measurement accuracy.
Disregarding the real value of the current the UBZ-302 will not be able to measure the currents more than 400A. The setting of several programmable parameters (maximal current protection, overcrank start and locked rotor or thermal overload) without taking into consideration the saturation of current transformers will lead to disabling of the effective protection.
For example when setting delay), i
=
S =9 (multiplication factor for tripping to maximal current faults) maximal current protection must trip
ind=50 (rated motor current), i = P =0 (current protection with independent time
when current is 450A. But due to the saturation of current transformer core measured value of current will never exceed 380-400A even there will be a short circuit in the coils of motor and currents more than 1000A – and thus
the UBZ-302 will not turn the motor OFF. In this case (
ind=50) the user must set the value for multiplication factor
for the maximal current protection and set the value not more than 6.
1.1.3.2 The use of external current transformers.
All the tested samples of standard current transformers the saturation of the core takes place when the measured current value exceed 4-5 fold of rated. Taking this fact into consideration it’s necessary to select the external current transformers with such a rated value that it will be at least 2-fold more than the rated motor current or to select the transformer taking into consideration possible saturation of the current transformer core.
1.1.3 LIST OF ABBREVIATIONS USED IN THIS PRESENT MANUAL
AR – automatic reclosing of the output contacts (autoreclosing)
MC – magnetic contactor
PC – personal computer
CT – current transformer
MMSP – mode with minimal number of setting parameters
Itt – rated current for the current transformers. It should be set up in case of using external current transformers ( For example CT Т-0.66 300/5, then Itt is 300А)
In – rated current of motor. As a rule it’s the value that is shown on the motor shield but depending on the usage
conditions it’s possible to set some other required value.
1.2 TECHNICAL PARAMETERS
1.2.1 Basic technical parameters are shown below in Table 1.3.
Table 1.3
Rated power supply voltage: three phase 415V 50 Hz Operational voltage frequency, Hz 48-62 Range of the rated currents when UBZ-302 use built in current transformers, А 5-63 Voltage hysteresis (phase/line), V 10/17 Thermal hysteresis, % of accumulated heat at turn OFF 33 Current tripping threshold detection accuracy, not more then, in % of rated 2 Voltage tripping threshold detection accuracy, not more then, V 3 Accuracy for the detection of phase imbalance basing voltage measurements, V, not more then 3 Operational input voltage:
-phase voltage, when power supply from one phase and neutral wire connected,
-line voltage, in case of 3 phase power supply, not more then, В Analog inputs:
not less then, V
180 450
- 2 analog inputs for the temperature sensors connection (type Pt100, Ni100, Ni120)
- analog input for the connection of the sensor with the output 0 – 10V
- analog input for the connection of the sensor with the output 4mA (0mA) – 20mA
- 3 analog inputs for the connection of current transformers with the output of 5 A (type Т-0.66 or similar)
NOVATEK-ELECTRO
UBZ-302
- 4 -
- input for the connection of the differential current transformer Basic outputs: Power load relay – 2 groups of changeover contacts to operate with the motor starting contac­tor - 5A 250V at cosφ=1; Functional relay – one group of changeover contacts 16A 250V at cosφ=1 (the application of this relay contact is user defined); Temperature sensors measurement accuracy, °С.
1 Consumed power (under the load), not more then, VA 5,0 Protection degree: - case enclosure
- contact terminals Operational temperature range, °С Storage temperature, °С
IP40
IP20 from-35 to +55 from-45 to +70
Weight, not more then, kg 0,5 Outer dimensions ( kindly see Fig.1.1) Nine standard S-modules width Mounting on standard DIN rail 35 mm Mounting position - arbitrary
1.2.2. The measured and calculated parameters, which values are deduced on the display device*, limits of
their measurement and an error are resulted in the Table 1.4.
Table 1.4 - Measured and Indicated parameters
Measurements Range Accuracy Indication on
display (mnemonics)
Currents
Acting value of phase currents, A 0,5-630 2%
iF1, iF2, iF3
Acting value of zero-sequence
0,3-5,0 2%
iF0
Address Measurement
units at data transmission
Tenths of
100, 101,
ampere
102 103
current, A Average current value on each of the phase within the time preset by the
iS1, iS2, iS3
104, 105,
106 parameter tSi Maximal value of average current on
each phase, obtained from the moment of the last load. To reset all average values press button RES/MEM/SEL – then UBZ-302 will
<3 Itt > 3 Itt
2% 10%
in1, in2, in3
107, 108,
109
display maximal average current value on corresponding phase and start further measurements (it doesn’t reset the initial value to zero after pressing RES/MEM/SEL). Starting current of motor (averaged by phases) Overload current (averaged by phases) Starting time, seconds Starting time – is a period of time from the moment when 3 phase currents exceed 1,2×In and up to the moment when all those 3 currents will decrease lower then 1,2×In. Maximal phase current that was achieved
<3 Itt > 3 Itt
0,1-600
2% 10%
iPU
iPE tPU
110
112
111
Tenths of ampere
during the startup is considered to be maximal starting current.
Reverse sequence current
0,2-200 5%
ioP
113
(imbalance), A
__________
* The display device correspond:
- Two three-digit seven-segment indicators on the UBZ face panel;
UBZ-302
NOVATEK-ELECTRO
- 5 -
- PC connected to one of UBZ interfaces (MODBUS, RS-232)
Measurements Range Accuracy Indication on
display (mnemonics)
Voltage
Acting value of phase voltage (measured when the neutral wire is connected to the UBZ-302), V
Acting value of line voltage, V 100-475 5 V
100-300 3 V
UF1, UF2,
UF3
UL1, UL2,
Address Measurement
units at data transmission
Volts 114,115 116
117,118 119
UL3
Positive sequence voltage, V 100-300 3 V Reverse sequence voltage, V 3 -300 3 V
Zero sequence voltage (vector sum of
3-100 3 V
UPP UÓP UnP
120 121 122
3 phase voltages divided by 3), (calcu­lated when neutral wire connected to the UBZ-302), V
Others Temperature of the Sensor 1 (type of the sensor is defined according the table 1.6.),
0
C * Temperature of the Sensor 2 (type of the sensor is defined according the table 1.6.),
0
C *
from -40 to +220
from -40 to +220
o
C
o
C
o
C
o
C
0
1
C
td1
123
5000 – sensor is disabled
0
C
1
td2
124
1000±10 –short circuit of the sensor 2000±10 –sensor is not connected or cut
Value of current input (4-20) mA, mA 0-25 2%
Voltage value on analog input 0-10 V 0-10 V 2%
Running time counter for the
0-999
ini
inU Str
125 Hundreds of µA 126 Tenths of Volt
127 machinery, days Power supply frequency, Hz 45-65 1%
Remaining time before tripping to
0-600 1 sec
FFF
tOP
128 Tenths of Hz
129 Seconds overload (shows the remaining time that is left before Turning OFF basing the thermal overload para-meter), sec
Remaining time to the end of
0-900 1 sec
tAP
130 Seconds
autoreclosing interval, sec**
Latency time after overload caused
0-900 1 sec
ttP
131 Seconds turn OFF (shows the latency time which remains to turn ON the motor after the thermal overload fault), sec*** Resistance of the motor insulation, MOhms ****
Termal balans of the motor Parame­ters only for reading the information using MODBUS or RS-232 protocols
0-19,9 10%
rid
Number 1100 thousand corresponds 100 % of saved up heat at which occurs the engine is “off” position at the included
132 Hundreds of
kOhms
133, 134
protection on a thermal overload (1.2.5.7)
Full Capacity, kVA***** 0-5000 5% Active power capacity, kW***** 0-5000 5% Reactive power capacity, kVAR***** 0-5000 5% Cos of the angle between voltage
0-1000 5% 141, 142
Pot
PoA PoJ
135, 136 Tens of W
137, 138
139, 140 Tens of W
and current on Phase A*1000 This parameter is read-only for the interface RS-232, RS-485 Cos of the angle between voltage
0-1000 5% 143,144 and current on Phase B*1000 This parameter is read-only for the interface RS-232, RS-485
NOVATEK-ELECTRO
UBZ-302
- 6 -
p
Cos of the angle between voltage
0-1000 5% 145,146 and current on Phase C*1000 This parameter is read-only for the interface RS-232, RS-485
* NOTICE. If the temperature value exceed the mentioned limits – then on the indicator will be displayed the alarm code according to the Table 2.6;
** NOTICE. If the autoreclosing is prohibited by the user – then on display will be glowing sing “not”; *** NOTICE. If the time interval before switching to thermal overload fault or the autoreclosing time interval
(ttP) is not defined (more then 900 sec), then on the indicator will be displayed code “---“. If the protection function is cancelled then the indicator should show sign “not”. **** NOTICE. If the value of the motor insulation is more then 20 MOhms – then indicator shows code “1.
(one with the decimal point in the lower order).
When the motor is turned ON (power supply is applied to the motor) the insulation resistance is not defined and
on the indicator is being displayed the code “---“ (if the insulation test measurement circuit is connected). ***** If the power capacity consumed by the load is more than 990 kW (kVA, kVAR) then MW (MVA) will be
displayed with dots looking like “n” in the middle decade. For example if the indicator shows “3n4”, then it means that 3,4 МW (МVА). ****** NOTES. In the program version 15 when working with external transformers with rated current more than 100A, measured currents and calculated values except the zero-sequence current (earthing current) on the RS-232/RS485 interface are being transmitted the values in Amperes.
1.2.3. Programmed parameters and their respective values are shown in the Table 1.5 below:
Default and readable parameters
Codes of parameters
Table 1.5 - Programmable parameters
Min value
Max Value
Default factory setting
Action Address
Current transformers
Use of current
transformer Rated current for the current transformer, А
tPt
tnt
0 1 0 0 - Use of built-in transformers
1-Use of external transformers
20 800 100 For the external current
transformer
150 151
Others
Rated current of
motor, А
ind
0 630 0 0 - current value is not set: UBZ-302
will not allow to close the output
152
power relay (see section 2.3.7.) Time frame for the measurement of ave­rage current value, sec
tSi
10 600 60 Time frame during which the avera-
ge current value is measured (para-
meters iS1, iS2, iS3 from Table1.4)
153
Protection from maximal currents Type of maximal current protection
i = P
0 5 0 0- protection with the independent
time delay;
154
Type of protections with time depen-
dent delays: 1-SIT; 2-VIT (LTI);
3-EIT; 4-UIT; 5-RI Tripping threshold to cut the load basing the
i = S
0,8 9,0 4,0 Multiplication factor value is set up
basing the rated current of motor.
155
detected maximal, cur­rent values. User de­fined multiplication factor Tripping time delay for
i = t
0,1 600 10,0 156
current faults, sec
ON/OFF mode for this type of protection
i = r
0 2 2 0- protection disabled
1- protection enabled, but auto-
reclosing after the fault is prohibited
157
2- protection enabled and auto-
reclosing is allowed afterwards
Tripping sequence of
rotection depen-
the
i = n
0 1 1 0- protection trips the current inde-
pendently from thermal protection
158
UBZ-302
NOVATEK-ELECTRO
- 7 -
p
Default and readable parameters
ding on thermal over­load protection

Earth leakage protection Current tripping setting, А

Tripping time delay for the protection, sec ON/OFF mode for this type of protection
Reverse current sequence protection Tripping threshold, %
Tripping time delay,sec
ON/OFF mode for this type of protection
Analysis of the tripping basing the reverse current sequence Multiplication factor for the exceeding of 2 coefficients dependen­cy: when the reverse sequence current coef­ficient is devided by reverse sequence voltage coefficient
Permission of the
analysis
Thermal overload (thermal model of AC motor)
ON/OFF mode for
this type of protection
Tripping time in case of 2-times current over­load, sec Coefficient of the coo­ling time augmentation when the motor was switched of due to thermal overload

Minimal phase current

Tripping threshold
setting, %
Tripping time delay
for the protection, sec
ON/OFF mode for
this type of protection
Codes of parameters
i_S
i_t ñ
i_r
ioS
iot Ior ñ
iOS
iOr
dtr
dtt
dtP
i
S
=
i
t
=
i
r
=
Min value
0,3 5,0 0,5 If this parameter is not included into
0,1 2,0 1,0 160 0 2 2 0- protection is disabled
5 20 10 Is being set in the % of rated motor 0,2 10,0 5,0 163
0 2 2 0- protection is disabled
2 4 2 165
0 1 1 0- OFF
0 2 2 0- protection is disabled
10 120 60 168
1,0 4,0 1,0 Compensation of the time required
11 90 20 Tripping threshold for the protection
1 100 5 171 0 2 2 0- protection is disabled
Max Value
Default factory setting
Action Address
1- if there is no thermal overload then it’s indicated on the display but the power relay doesn’t turn the motor OFF
the list of MMSP then the default values are the following:
0,5 at In<=50A; 1,0 at In>50A
1- protection enabled but auto­reclosing after the fault is prohibited 2- protection enabled and auto­reclosing is allowed
current value
1- protection enabled but auto­reclosing after the fault is prohibited 2- protection enabled and autoreclosing is allowed
1- ON
1- protection enabled but auto­reclosing after the fault is prohibited 2- protection enabled and autoreclosing is allowed
for motor cooling after motor turn OFF due to the thermal overload
to minimal operating current in % of adjusted rated current
rotection enabled but autoreclo-
1-
159
161
162
164
166
167
169
170
172
NOVATEK-ELECTRO
UBZ-302
- 8 -
Default and readable
parameters
Codes of parameters
Min value
Max Value
Default factory setting
Action Address
sing after the fault is prohibited 2- protection enabled and autoreclosing is allowed

Long lasting (Overcrank) motor start, blocked rotor fault Tripping threshold to current, multiplicity

PPS
1,5 7,0 5,0 User defined multiplicity coefficient
to rated current value
173
coefficient Tripping time delay for
PPt
1 600 10 Time for starting up the motor 174 the protection from long lasting start of the motor, sec Tripping time delay in
Pbt
0,1 300 1.0 175 case the blocked rotor detected, sec
ON/OFF mode for this type of protection
PPr
0 2 1 0- protection is disabled
1- protection enabled but auto-
176
reclosing after the fault is prohibited 2- protection enabled and autoreclosing is allowed
Voltage monitoring and protection
Minimal line voltage, V
Tripping time delay to
U
U
=
=
S
t
270 415 320 177
5 30 10 178 minimal voltage fault, s
ON/OFF mode for minimal line voltage level protection
U
r
=
0 2 2 0- protection is disabled
1- protection enabled but auto-
179
reclosing after the fault is prohibited 2- protection enabled and autoreclosing is allowed
Maximal line voltage, V
Tripping time delay to
U = S
=
t
U
330 475 415 180
1 10 2 181
maximal voltage fault, sec
ON/OFF mode for maximal line voltage level protection
U = r
0 1 2 0- protection is disabled
1- protection enabled but auto­reclosing after the fault is prohibited
182
2- protection enabled and autoreclosing is allowed
Line voltage
U
n
S
15 120 35 Reverse voltage sequence 183
imbalance, V
Tripping time delay to
U n t ñ
1 30 5 184
line voltage imbalance fault, sec
ON/OFF mode for the protection from line voltage imbalance control
U n r
0 2 2 0- protection is disabled
1- protection enabled but auto­reclosing after the fault is prohibited 2- protection enabled and
185
autoreclosing is allowed ON/OFF mode for the correct phase sequence control
U Y r
0 2 1 0- protection is disabled
1- protection enabled but autoreclo-
sing after the fault is prohibited
186
2- protection enabled and
autoreclosing is allowed
AC motor operation and autoreclosing parameters
Autoreclosing time
Atn
0 900 600 187 after the tripping for minimal current fault, sec Autoreclosing time
Att
0 900 5 188 setting, sec
UBZ-302
NOVATEK-ELECTRO
Default and readable parameters
ON/OFF mode for all
Codes of parameters
Arr
Min
value
0 1 1 0-autoreclosing disabled type of faults
Permission of motor
APd
0 2 1 0 – motor is started manually
start after the power supply is given to the input terminals of UBZ-302
Motor operation
ACd
0 3 0 0-disabled using the UBZ-302

Temperature control and monitoring

ON/OFF mode for the
—1r
0 2 0
temperature control function and setting the type of the Sensor 1
Threshold temperature to turn OFF the motor (sensor 1),
o
C
Correction coefficient
C1S
C1c
0 100 80 193
-9 9 0 194 for the Sensor 1 ON/OFF mode for the
C2r
0 3 0 0 – disabled temperature control function and setting the type of the Sensor 2 Threshold tempera­ture to turn OFF the motor (sensor 2),
o
Alarm indication
C2S
C
C2A
0 220 180 196
0 220 170 197
temperature value
Correction coefficient
C2c
-9 9 0 198 for the Sensor 2 Autoreclosing after the
CPA
1 2 1 1- autoreclosing after the fault thermal overload fault detected and motor is OFF
Action in case the
——r
0 1 0 0- alarm indication and continuous
temperature sensor fault detected
Control of the motor coil insulation level
Max Value
- 9 -
Default factory setting
Action Address
1-autoreclosing enabled The action of the
Arr parameter is
valid for all faults and alarms except the voltage faults. To disable auto­reclosing on the detect of voltage faults it’s necessary to use the
=
parameters U
r , U = r, U n
1– motor starts with the user preset autoreclosing time 2 – Motor starts with 2 seconds de­lay after power supply is given to UBZ-302
1-motor start allowed 2-alarm motor stop allowed 3-motor start and stop allowed For details kindly see section 2.4.7.
– disabled
1- built-in sensor (protection trips the
motor if the sensor resistance exceed 1.7 kOhm) – external PTC sensor (1kOhm at
0
С)
25
1 –type Pt100 2- type Ni100 3- type Ni120
prohibited 2- autoreclosing after the fault allowed
operation of the motor running; 1- alarm indication and motor stop
189
190
191
192
195
199
200
NOVATEK-ELECTRO
UBZ-302
Default and readable parameters
Control of the
Codes of parameters
rid
Min
value
0 10 5 0-disabled
minimal insulation level of the AC motor

Other parameters and controls

Mode with minimal set
Sin
0 1 1 0-disabled
of user defined para­meters
Indication on the
SiP
0 2 1 0- line voltage in between lines AB
UBZ-302 front panel before the permission to start the motor
Parameter indication
SiC
0 1 1 0 – parameter value is being
mode
Operation mode for
rrS
0 2 0 0 – relay is used as a signalization
the functional relay output
Timer setting for the
rrt
0 300 30 Kindly see line above and functional relay, sec
Total running time for UBZ-302, days
Total motor running time, days
Users access code Advanced user
tbU
tCO
LOC
PAS
0
0
0 9 0 0 – keys are unblocked
000 999 123 000 – access to the advanced user
access code
Reset default factory
PPP
0 1 0 After the entry “1” and exit from the
settings Serial interface parameters (RS-485/ RS-232)
Communication
rSA
1 247 1 212 address of UBZ-302
Data transmission
rSS
0 1 0 0: 9600 symbols per second;
speed
Max Value
999
999
- 10 -
Default factory setting
0
0
Action Address
5-if the insulation resistance is less then 500 kOhms then motor start is not allowed.
Autoreclosing allowed
10- motor is not allowed to start if the resistance of the coils is less then 1000 kOhms.
Autoreclosing allowed
15- motor is not allowed to start if the resistance of the coils is less then 500 kOhms. A
utoreclosing prohibited
20- motor is not allowed to start if the resistance of the coils is less then 1000 kOhms.
Autoreclosing prohibited
1-enabled
(Uab) 1-Resistance of the insulation rid 2- Countdown of the remaining autoreclosing time
shown continuously 1 – parameter value is shown on display within 15 seconds
output 1- relay is used like a time delay relay (closes its contacts with the
user defined parameter
rrt. After
the power supply is given to the input of UBZ-302 2- relay is used for the delta-star switching
parameters of rrS * when information is transmitted using MODBUS/RS-232 interface – then the total running time is transmitted in hours * when information is transmitted using MODBUS/RS-232 interface – then the total running time is transmitted in hours
1-9 – user defined password settings allowed
000-999 – password of the advanced user
settings mode – UBZ-302 returns
to factory default settings
1: 19200 symbols per second;
201
202
203
204
205
206 207
208
209 210
211
213
UBZ-302
NOVATEK-ELECTRO
Loading...
+ 21 hidden pages