BASIC OPERATING INSTRUCTIONS FOR THE MA3000 FIRE CONTROL PANEL

WITH THE CF3000LCD KEYPAD.

Note: Text in quotes indicates a displayed message; messages preceded and followed by asterisks indicate additional related message(s) to follow. Buttons markings are shown in brackets ( [ ] ).

Note: This system uses a “smart”menu-driven keypad; that is,

FIRE ALARM/TROUBLE CONDITIONS

when scrolled, the keypad will display only those options that

The keypad will constantly display the alarm/trouble condi-

are relevant to the existing condtion.

tions still present on the system. “ FIRE STATUS ” will dis-

STANDBY

play followed by the condition(s). To determine the particular

 

This is the normal mode. The keypad will read “NORMAL’; nozone(s) respansible for the condition(s), enter code and press

 

[INFO]. The keypad will display options one at a time. Press

reminders (“DISABLE”; “FIRE/TEL”; “SYS TEL”) will display; the

green AC-POWER light will be on.

[NO] to continue to scroll options or [YES] to select option.

 

FIRE ALARM

DISABLE/ENABLE ZONE BUTTON

Signal deviceswill sound. The keypad will display “ FIRE ”,

For installer’s use only.

followed by the number and description of the zone in alarm,

 

then “ FIRE STATUS ”, then “FIRE ALARM”. The “FIRE/TBL”

reminder and the ALARM light will come on.

ALARM TEST

Operate an initiating device. Signal devices will sound and the

SILENCING A FIRE ALARM

keypad will display an alarm. Silence the alarm and reset the

Enter code and press [SILENCE] to silence the signal devices

device.

and keypad sounder. The keypad will display “FIRESI-

 

LENCED, followed by “ FIRE STATUS ”, “FIRE ALARM”,FIRE DRILL TEST

then “FIRE SILENCED”. Another alarm will sound the signals Enter code and press [INFO]. Press [NO] until “FIRE DRILL?

again.

(YES/NO)” appears, Press [YES]. The fire signal devices

FIRE ALARM RESET

should sound. To terminate the test, enter code, then press

Enter code and press [INFO]. Press [NO] to continue to scroll

[SILENCE]. The keypad will display “NOT NORMAL”, indicating

options or [YES] to select option.

that the fire bell is active.

FIRE TROUBLE

The keypad will display “FIRE TROUBLE” followed by theSYSTEM TEST

 

To test the keypad, hold down the[*] and [3] keys simul-

number and description of the zone in trouble, then “ FIRE

taneously. The three reminders (“DISABLE”; “FIRE/TEL”; “SYS

 

STATUS ”, then “FIRE TROUBLE”. The “FIRE/TBL” reminder

will flash.

TBL”) will display and all screen characters will appear black.

FIRE TROUBLE RESET

Holding the [ ] key depressed, press [3] to view different

characters on the display. Press [RESET] to terminate the test.

Enter code and press [INFO]. The keypad will display options

 

one at a time. Press [NO] to continue to scroll options or [YES]

To test fire alarm signal devices, enter code and press

to select option.

[INFO]. Press [NO] until “TEST ALARMS? (YES/NO)” appears.

SUPERVISORY ALARM

Press [YES]. Fire signal devices should sound for 2 seconds.

The keypad will sound and display “ SUPV ALARM ” fol-

SYSTEM TROUBLE

lowed by the number and description of the fire supervisory

zone in alarm, then “ FIRE STATUS ”, then “SPRINK SUPV When a system trouble is detected, the “SYS TBL” reminder

ALARM”. This indicates that a device designed to monitor the

will flash, the screen will display the system trouble, and the

fire alarm system is in alarm.

keypad sounder will pulse. To acknowledge the system trouble,

enter code, then press [RESETI. The keypad will silence and

SUPERVISORY TROUBLE

the system trouble descrIption will clear. However If the system

The keypad will sound and display “ SUPV TROUBLE ”

trouble still exists, the “SYS TEL” reminder will remain on and

followed by the number and description of the supervisory zone

the screen will display “NOT NORMAL”.

in trouble, then “ FIRE STATUS ”, then “SPRINK SUPV

TRBL”.

To determine the particular condition responsible for the

SUPERVISORY ALARM/TROUBLE RESET

system trouble, enter code, then press [INFO]. Press [No] until

“DISP SYS TRBL? (YES/NO)” appears, then press [YES].

Enter code and press [INFO].The keypad will display options

one at a time. Press [NO] to continue to scroll options or [YES] to select option.

Local Service Representative: ________________________________________________________

Address: _________________________________________________________________________

Telephone Number: ________________________________________________________________

Note: (1) Test system weekly! (2) If panel sounder is on, call for service. (3) A complete functional checkout of the control unit is required following any programming or reprogramming. (4) This page is to be framed and mounted adjacent to the control unit.