BASIC OPERATING INSTRUCTIONS FOR THE MA3000 FIRE CONTROL PANEL
WITH THE CF3000LCD KEYPAD.
Note: Text in quotes indicates a displayed message; messages preceded and followed by asterisks indicate additional related message(s) to follow. Buttons markings are shown in brackets ( [ ] ).
Note: This system uses a “smart”menu-driven keypad; that is, |
FIRE ALARM/TROUBLE CONDITIONS |
|
when scrolled, the keypad will display only those options that |
The keypad will constantly display the alarm/trouble condi- |
|
are relevant to the existing condtion. |
tions still present on the system. “ FIRE STATUS ” will dis- |
|
STANDBY |
play followed by the condition(s). To determine the particular |
|
|
||
This is the normal mode. The keypad will read “NORMAL’; nozone(s) respansible for the condition(s), enter code and press |
||
|
[INFO]. The keypad will display options one at a time. Press |
|
reminders (“DISABLE”; “FIRE/TEL”; “SYS TEL”) will display; the |
||
green AC-POWER light will be on. |
[NO] to continue to scroll options or [YES] to select option. |
|
|
||
FIRE ALARM |
DISABLE/ENABLE ZONE BUTTON |
|
Signal deviceswill sound. The keypad will display “ FIRE ”, |
||
For installer’s use only. |
||
followed by the number and description of the zone in alarm, |
||
|
||
then “ FIRE STATUS ”, then “FIRE ALARM”. The “FIRE/TBL” |
||
reminder and the ALARM light will come on. |
ALARM TEST |
|
Operate an initiating device. Signal devices will sound and the |
||
SILENCING A FIRE ALARM |
||
keypad will display an alarm. Silence the alarm and reset the |
||
Enter code and press [SILENCE] to silence the signal devices |
device. |
|
and keypad sounder. The keypad will display “FIRESI- |
|
LENCED, followed by “ FIRE STATUS ”, “FIRE ALARM”,FIRE DRILL TEST |
||
then “FIRE SILENCED”. Another alarm will sound the signals Enter code and press [INFO]. Press [NO] until “FIRE DRILL? |
||
again. |
(YES/NO)” appears, Press [YES]. The fire signal devices |
|
FIRE ALARM RESET |
||
should sound. To terminate the test, enter code, then press |
||
Enter code and press [INFO]. Press [NO] to continue to scroll |
[SILENCE]. The keypad will display “NOT NORMAL”, indicating |
|
options or [YES] to select option. |
that the fire bell is active. |
FIRE TROUBLE
The keypad will display “FIRE TROUBLE” followed by theSYSTEM TEST
|
To test the keypad, hold down the[*] and [3] keys simul- |
|
number and description of the zone in trouble, then “ FIRE |
taneously. The three reminders (“DISABLE”; “FIRE/TEL”; “SYS |
|
|
||
STATUS ”, then “FIRE TROUBLE”. The “FIRE/TBL” reminder |
||
will flash. |
TBL”) will display and all screen characters will appear black. |
|
FIRE TROUBLE RESET |
Holding the [ ] key depressed, press [3] to view different |
|
characters on the display. Press [RESET] to terminate the test. |
||
Enter code and press [INFO]. The keypad will display options |
||
|
||
one at a time. Press [NO] to continue to scroll options or [YES] |
To test fire alarm signal devices, enter code and press |
|
to select option. |
[INFO]. Press [NO] until “TEST ALARMS? (YES/NO)” appears. |
|
SUPERVISORY ALARM |
Press [YES]. Fire signal devices should sound for 2 seconds. |
|
The keypad will sound and display “ SUPV ALARM ” fol- |
SYSTEM TROUBLE |
|
lowed by the number and description of the fire supervisory |
||
zone in alarm, then “ FIRE STATUS ”, then “SPRINK SUPV When a system trouble is detected, the “SYS TBL” reminder |
||
ALARM”. This indicates that a device designed to monitor the |
will flash, the screen will display the system trouble, and the |
|
fire alarm system is in alarm. |
keypad sounder will pulse. To acknowledge the system trouble, |
|
enter code, then press [RESETI. The keypad will silence and |
||
SUPERVISORY TROUBLE |
||
the system trouble descrIption will clear. However If the system |
||
The keypad will sound and display “ SUPV TROUBLE ” |
trouble still exists, the “SYS TEL” reminder will remain on and |
|
followed by the number and description of the supervisory zone |
the screen will display “NOT NORMAL”. |
|
in trouble, then “ FIRE STATUS ”, then “SPRINK SUPV |
||
TRBL”. |
To determine the particular condition responsible for the |
|
SUPERVISORY ALARM/TROUBLE RESET |
system trouble, enter code, then press [INFO]. Press [No] until |
|
“DISP SYS TRBL? (YES/NO)” appears, then press [YES]. |
||
Enter code and press [INFO].The keypad will display options |
one at a time. Press [NO] to continue to scroll options or [YES] to select option.
Local Service Representative: ________________________________________________________
Address: _________________________________________________________________________
Telephone Number: ________________________________________________________________
Note: (1) Test system weekly! (2) If panel sounder is on, call for service. (3) A complete functional checkout of the control unit is required following any programming or reprogramming. (4) This page is to be framed and mounted adjacent to the control unit.
WI658C 08/99