®
GEM-P801
Control Panel/Communicator
Installation Instructions
© NAPCO 2000 |
|
WI1089 09/01 |
|
|
|
WI1089 GEM-P801 Installation Instructions
Table of Contents |
|
General Information .......................................... |
2 |
GEM-P801 Features ......................................... |
2 |
Specifications.................................................... |
3 |
UL Compatible Smoke Detectors...................... |
4 |
Listings and Approvals...................................... |
4 |
Ordering Information ......................................... |
4 |
Optional Accessories ........................................ |
4 |
Programming the Panel .................................... |
5 |
Installation......................................................... |
6 |
Wiring................................................................ |
6 |
Keypad Operation ............................................. |
7 |
Panel Operation ................................................ |
8 |
Bypassing ........................................................ |
9 |
User Program Mode.......................................... |
10 |
GEM-P801 Commands..................................... |
10 |
Dealer Commands ........................................... |
11 |
Wireless Operation (Signal Strength) ............. |
11 |
Zone Features................................................... |
12 |
System Times ................................................... |
13 |
System Features............................................... |
14 |
Telephone Number 1 Programming.................. |
16 |
Backup Telephone Programming ..................... |
17 |
Pager Programming.......................................... |
17 |
Telephone Number 3 Programming.................. |
18 |
Report Codes.................................................... |
19 |
Enhanced Communicator Features .................. |
19 |
Wireless ............................................................ |
19 |
Downloading ..................................................... |
21 |
Dealer Programming......................................... |
22 |
System Troubles ............................................... |
23 |
Troubleshooting ................................................ |
25 |
GEM-P801 Wiring Diagram .............................. |
27 |
Limited Warranty............................................... |
28 |
General Information
The GEMINI GEM-P801 control panel provides up to 6 hardwired/wireless zones, a 2-wire fire zone and 2 wireless only zones. Up to eight 4-digit user codes can be programmed. Ambush, when selected, uses User 8 code as an Ambush code.
The GEM-P801 is wireless ready. When used with a GEM-RECV-XP8 receiver, the control panel can support up to 8 wireless zones, 4 wireless smoke detectors and 4 Keyfobs.
The GEM-RP8 keypad provides complete control of the GEM-P801 control panel. Information on system status, bypassed zones, system troubles etc. can be viewed at the keypad.
The control panel can be easily and quickly programmed from the keypad. The panel can also be locally or remotely downloaded using PCD-Windows Version 4.1 software and a PCI2000/3000 interface or PCL2000B local Download cable. See Downloading Section (pg. 5) for more information.
GEM-P801 Features
Control Panel
•8 Zones (6 Hardwired/Wireless + 2 wireless)
•2-wire Fire Zone
•3 Keypad Panics
•Wireless Ready
•Bell Supervision
•Line Cut Detection
•Answering Machine Override (Second Call)
•50 Event Log
Communicator
•2 Telephone Numbers
•Backup Reporting
•Pager Format
•Point ID Format
•Individually Report 8 Users
•Opening after Alarm Report (Cancel Code)
•Conditional Closing Report
NAPCO Security Systems, Inc.
333 Bayview Avenue Amityville, New York 11701 For Sales and Repairs, call Toll Free: (800) 645-9445
For Technical Assistance, Contact the NAPCO Toll Free Helpline
(800) 645-9440
2
Specifications
Current & Voltage Ratings
Alarm Output --------------------------------- |
Burg: |
12 |
VDC, 2A (max.) |
|
Fire: |
12 |
VDC, 65 mA |
Output Current Limiting -------------------- |
Burg/Fire: |
2.25 A |
|
|
AUX Power: 750 mA |
||
Residential Burglary (4 Hour Standby) |
|
|
|
Combined Standby Current: -------------- |
500 mA |
|
|
Bell Output: ----------------------------------- |
2 A |
|
|
(Using Rechargeable 12 VDC 4 AH BATTERY, minimal requirement)
Residential Fire (4 Hour Standby) |
|
Combined Standby Current: -------------- |
500 mA |
Bell Output: ----------------------------------- |
65 mA |
(Using Rechargeable 12 VDC 4 AH BATTERY, minimal requirement)
Residential Fire (24 Hour Standby) |
|
Combined Standby Current: -------------- |
120 mA |
Bell Output: ----------------------------------- |
95 mA |
(Using Rechargeable 12 VDC 7 AH BATTERY, minimal requirement)
Transformer and Battery
Required Transformer: -------------------- |
NAPCO TRF12 OR |
BASLER 16.5 VAC 20VA |
|
Required Battery: --------------------------- |
12V 4 AH or 7 AH Rechargeable |
Change Battery every 5 years or as required |
|
Maximum Charging Current: ------------- |
165 mA |
Maximum Input Current: ------------------- |
2.58 A |
Loop Characteristics
Loop Voltage: -------------------------------- |
5 Volts |
Loop Current : -------------------------------- |
1.1mA |
Loop Resistance: ---------------------------- |
300Ω per zone (max.) |
Device Specifications
Max # keypads: ------------------------------ |
4, GEM-RP8 current = 65 mA |
Max # of receivers: -------------------------- |
2, GEM-RECV-XP8 |
|
current = 65 mA each |
Max # of compatible |
|
2-wire smoke detectors : ------------------ |
10 |
Max Keypad wire length : ---------------- |
1000’ total wire length |
Miscellaneous |
|
Housing Dimensions : -------------------- |
11" x 121/8" x 3" |
|
(28 x 30.8 x 7.6) HxWxD |
Shipping Weight: --------------------------- |
GEM-P801 5.5 lbs. |
Operating Temperature: ------------------- |
0-49ºC (32-120°F) |
3
WI1089 GEM-P801 Installation Instructions
UL Compatible Smoke Detectors
GEM-P801 Compatible Smoke Detectors (Approved by UL)
Mfg |
4-Wire |
|
2-Wire |
Smoke Detector |
|
|
Smoke Detector |
Smoke Detector |
Base |
||
|
|
|
|
|
|
Sentrol |
449AT |
449CSST |
712U |
721UT |
701U |
|
449C |
449CLT |
722U |
731U |
702U |
|
449CRT |
449CSLT |
732U |
|
702RE |
|
449CST |
449CTE |
711U |
|
702RU |
|
449CSRT |
741U |
721U |
|
|
|
449CSRH |
742U |
|
|
|
|
|
|
|
|
|
System |
1112 |
2112T |
2100 |
1100 |
|
Sensor |
2112 |
2112TSRB |
2100T |
|
|
|
|
|
|
|
|
NAPCO |
FW-4 |
|
FW-2 |
|
|
|
|
|
|
|
|
Listings and Approvals
UL HOUSEHOLD FIRE AND BURGLARY WARNING SYSTEM CONTROL UNIT STANDARDS # 1023, 985
California State Fire Marshal (CSFM) - Control Unit (Household) # 7187-0992:126
VERIFIED TO COMPLY WITH F.C.C. PART 15 AS CLASS B : DIGITAL DEVICE
European E.M.C. Regulations CE
Certification
HARMONIZED STANDARDS: EN50081-1 and EN50082-1
EC DIRECTIVES: 89/336/EEC, Electromagnetic Compatibility Directive
Ordering Information
GEM-P801 8 zone Control Panel with 2-wire Fire
|
(6 Hardwire/Wireless+2 wireless) |
GEM-RP8 |
Keypad |
OI219 |
Operating Instructions GEM-P800 Series |
WI1090 |
Programming Instructions GEM-P801 |
Optional Accessories
GEM-RECV-XP8: |
*Wireless Receiver |
GEM-TRANS2 |
Window/Door Transmitter |
GEM-KEYF: |
Keyfob Transmitter |
GEM-WP: |
Wireless Waterproof Panic Button |
GEM-SMK: |
Wireless Smoke Detector |
GEM-HEAT: |
Wireless 135°F / Rate of Rise Heat Detector |
GEM-PIR: |
Wireless PIR |
GEM-PIRPET: |
Wireless Pet-Immune PIR |
GEM-DT: |
Wireless Dual-Technology Sensor |
GEM-GB: |
Wireless Glass-Break Detector |
RB1000 |
Single Form C Relay Board |
Veriphone: |
Audio Verification Module |
PCD-Windows: |
Downloading Software for IBM Compatible PC |
|
Must be PCD-Windows Version 4.1 |
PCI2000/3000: |
Downloading Interface for IBM Compatible PC |
|
(includes PCL2000B Local Download cable) |
PCL2000B: |
Local Download cable |
*Supports up to 8 zones, 4 Key Fobs, 4 Smoke Detectors
Note: Wireless and Access Features have not been evaluated by UL
4
Programming the Panel
Refer to GEM-P801 Programming Instructions (WI1090)
Defaulting the Panel
1.Remove power from the panel.
2.Remove all wiring from terminal 19 (PGM) and terminal 3.
3.Connect terminal 19 (PGM) to terminal 3.
4.Apply power to the GEM-P801 control panel.
5.After a few seconds the ARMED, READY and HSYSTEM TROUBLE LEDs will flash.
6.The keypad will beep 3 times indicating the panel default values have been loaded.
7.Remove wiring between terminal 19 (PGM) and terminal 3.
8.Re-install original wiring for terminal 19 (PGM) and terminal 3.
NOTE:
Any programming in Dealer Options 1 [96] and Dealer Options 2 [97] will not be defaulted. If Dealer Code Lockout has been programmed the panel will not default the Dealer Code.
Keypad Programming
Refer to WI1090 for information on keypad programming.
Downloading
The GEM-P801 panel can be download/uploaded with PCD-Windows Version 4.1 software using the Ring Method, Answering Machine Override (Second Call) or A6 method of
downloading. The panel can also be automatically downloaded/uploaded using the
PCPreset utilty. For Site Initiated Downloaded, see Auto Download ID Number [93].
Local Downloading
Wire as shown in Figure 1. Use the power up or A6 method of establishing a connection.
The power up method is recommended if the panel is attempting to report.
TELCO |
|
|
|
|
|
JACK |
|
|
|
16 |
17 |
18 |
19 |
20 |
+PWR |
GND |
|
|
|
RED |
|
|
|
|
BLACK |
|
|
|
|
*RED |
|
|
|
|
*GREEN |
|
|
|
|
*Insulate if not used |
PCL2000B |
|
MODEM
FIGURE 1 LOCAL DOWNLOAD
Remote Downloading
Wire as shown in Figure 2. The panel can be remotely download/uploaded using any one of the following methods:
1.The A6 method
2.Call-in method
3.Answering Machine Override (Second
Call)
4.Site-Initiated (PCPreset & A6)
5.Automatic Downloading (Using PCPreset)
TELCO JACK
RJ31X
GEM-P801 Panel at the site |
|
|||
|
|
|
TELCO |
|
|
|
|
PCI2000 |
|
J1 |
J2 |
J3 |
J4 |
J5 LINE |
LOCAL |
TELCO |
OUT TO |
||
TO COMPUTER |
TO EXTERNAL |
TO |
|
|
|
MODEM |
|
|
|
|
|
|
|
MODEM |
FIGURE 2 REMOTE DOWNLOAD
5
WI1089 GEM-P801 Installation Instructions
Installation
Mounting the Panel
Mount the Panel close to an unswitched AC source, a cold-water pipe ground, and a telephone line connection.
Mounting the Keypad
A keypad should be located near an exit/entry door. To remove the keypad from the backplate, insert a small screwdriver into the slots at the bottom of the keypad. Pull up on the screwdriver to pop off the cover.
Up to 4 keypads can be connected on individual wire runs with #22 AWG wire with a maximum total cable length of 1000 feet. Each keypad draws approximately 65 mA.
Keypad Wire Color |
Control Panel Terminal |
|
RED |
12 |
(+PWR) |
BLACK |
13 |
(GND) |
GREEN |
14 |
(GREEN) |
TABLE 1 KEYPAD WIRING
Typical Fire Installation
(Where permitted by local codes)
Install smoke detectors outside each sleeping area and on each floor, including the basement. Install the living room and basement smoke detectors near the stairway of the next upper level. For increased protection, additional detectors should be installed in areas other than
those required, such as the dining room, bedrooms and utility room. Heat detectors, rather than smoke detectors, are recommended in kitchens, attics, and garages due to conditions that may result in false alarms and improper operation.
Refer to NFPA Standard 74 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269) for additional information, including proper mounting methods.
FIGURE 3 Typical Fire Installation
Wiring
Grounding the Panel
Connect the control-panel EARTH GROUND screw through a No. 16 AWG or larger wire to a metal cold-water pipe. Do not use a gas pipe, plastic pipe or AC ground connections. Use at least #16 AWG wire. Connect a wire with a ground lug crimped or soldered onto one end and connect it to the EARTH GROUND screw in the cabinet.
AC Power and Battery Wiring
Complete all wiring before connecting the battery or AC Power. Do not plug the transformer into a switched outlet.
Telephone Wiring
Wire as shown in the wiring diagram in the back of this manual.
WARNING
The FCC restricts the use of this equipment on certain telephone lines. Read the FCC statement on the back of this manual to ensure compliance.
6
Burglary Zone Wiring
The GEM-P801 provides 6 true hard-wired, End- Of-Line Resistor terminated burglary zones. Wire zones as shown in the wiring diagram (pg. 27). All resistors must be installed, even if the zone is not used. If required, the feature No End Of Line Resistor may be programmed, in which case a direct short across the zone will cause the zone to set up. (NOTE: Not for UL applications) Program the zone as a No EOL Resistor Zone [06].
If necessary, use the voltage chart below to verify proper voltages. These values represent the DC voltage of the zone while in the indicated state with reference to the the zone’s respective ground terminal.
Zone Normal (EOL across zone) |
2.5 V |
|
|
Zone shorted |
0 V |
|
|
Zone Open |
5 V |
|
|
TABLE 3 VOLTAGE AT TERMINALS 3&5, 6&8, 9&11
Fire Zone Wiring
Wire the Fire Zone as shown in the Wiring Diagram in the back of this manual. An EOL resistor must be installed, even if the Fire Zone is not used.
Fire Zone Normal |
13.0V |
|
|
Fire Trouble |
13.8V |
|
|
Fire |
0.0 V |
|
|
TABLE 4 VOLTAGE AT FIRE ZONE (Terminals 12&13)
PGM Wiring
The PGM (Terminal 19) is a switched negative output that is activated through programming option(s) that have been selected in programming blocks [08], [23] - [25], [26-2]. Connect the device controlled by the PGM between +PWR and the PGM terminal. (maximum load of 50 mA).
Keypad Operation
Keypad zone LEDs indicate zone status. ARMED, STATUS and HSYSTEM LEDs
provide system status. The keypad sounder provides feedback beeps for correct and incorrect entries.
Keypad Sounder
3 QUICK BEEPS
Panel Armed (System ON)
Chime ON
Fault Find Mode ON
Keypad Sounder ON
Zone Bypassed
6 QUICK BEEPS
Panel Disarmed (System OFF)
Chime OFF
Fault Find Mode OFF
Keypad Sounder OFF
Zone Un-Bypassed
1 SECOND - STEADY TONE
Incorrect Code Entered Invalid key entry
4 LONG BEEPS (PRIORITY CONDITION)
1.Entering an Arm Code with a faulted zone (Not an Auto-Bypass Reentry Zone).
2.Entering an Arm Code when the Bell or PGM is ON (Bell and PGM will turn OFF).
3.Arming with the Fire LED ON - reset required. Press the C key.
7
WI1089 GEM-P801 Installation Instructions
Keypad LEDs
ARMED LED DEFINITION |
|
Armed |
ON |
Instant Mode |
Rapid Flash |
Zone in Alarm |
Flashing |
STATUS LED DEFINITION |
|
Ready to be Armed |
ON |
Zone faulted |
OFF |
H TROUBLE LED DEFINITION |
|
AC Failure |
Flashing |
System Trouble(s) |
ON |
I FIRE LED DEFINITION |
|
Fire Alarm |
Flashing |
Fire Memory/*Fire Trbl |
ON |
*See Note 1 |
|
AC LED DEFINITION |
|
AC Present |
ON |
AC Failure |
OFF |
ZONE LED DEFINITION |
|
Faulted Zone |
ON |
Bypassed Zone |
Slow Flash |
Zone in Alarm |
Flashing |
NOTE:
* If Fire Trouble on Fire LED [96-4] has been enabled, a steady Fire LED will indicate Fire Trouble.
Panel Operation
Arming (System ON)
Before arming the system close all protected zones (unless programmed as Auto-Bypass Reentry Zones). Enter a 4-digit Arm/Disarm code, followed by the Dkey, the keypad will
provide a feedback beep for each key pressed. If a valid Arm/Disarm code is entered, the keypad will beep 3 times. If an incorrect Arm/ Disarm code is entered, the keypad will sound a 1-second tone indicating an incorrect entry.
Arming without Entry Delay (Instant Mode)
Enter the Fkey to eliminate the entry delay.
The ARMED LED will flash rapidly to indicate the panel is in Instant Mode. If an Exit/Entry Zone is tripped while the panel is in Instant Mode the panel will go into alarm immediately.
Arming/Disarming with a Keyfob
The system can be armed by pressing the K key, and disarmed by pressing the L key on
the Keyfob. Zones programmed as Exit/Entry Follower Zones can be bypassed when the M
or N keys on the Keyfob have been
programmed for Interior [81-84]. Zones programmed as Home/Away with Delay Zones can be armed regardless of the state of the
Exit/Entry Zones when the M or N keys on
the Keyfob have been programmed for Full Set [81-84]. To arm the system with all zones
protected press the K key. Press and hold the M or N key for 1.5s to fully set the system
(The LED on the Keyfob indicate the Keyfob has transmitted the signal). Program Keyfob/ Keyswitch Chirp [23-4] for an audible indication of system arming and disarming.
Arming/Disarming with a Keyswitch
The system can be armed/disarmed by using a momentary Keyswitch wired to Zone 6. Program Keyfob/Keyswitch Chirp [23-4] for an audible indication of system arming and disarming. To convert keyswitch operation from Normally Closed style to Normally Open, program [27-1] Keyswitch Polarity.
NOTE:
Faulted Keyswitch or silent 24 hour zone normally do not display at the keypad. If a silent 24 hour zone or Keyswitch is faulted at the time of arming the faulted zone will display only while the priority sound is ON.
Arming Instant with a Keyfob
The panel can be ARMED INSTANT when the [A1] or [A2] keys on the Keyfob have been programmed for Instant [81-84]. To arm the system with Instant protection press the [ON] key, then press and hold the [A1] or [A2] key for 1.5s to arm the panel with INSTANT protection.
Disarming (System OFF)
After entering the premises through an Exit/Entry Zone, the keypad will sound the Entry Delay Tone. Enter a valid Arm/Disarm code, then press J. If a valid Arm/Disarm code is entered, the
8
keypad will beep 6 times, indicating the panel has been disarmed. The red Armed LED will go out. If an incorrect Arm/Disarm Code is entered, the keypad will sound a 1-second tone, indicating incorrect entry. Press the Ckey and re-enter
the code.
Disarming after an Alarm (Alarm Memory)
The armed LED and the zone(s) that caused the alarm will be be flashing. Disarm the panel. The system is currently not detecting zone faults or displaying system trouble. The zone(s) that caused the alarm will continue to flash. The STATUS and HSYSTEM TRBL LEDs are out
indicating:
The system is displaying Alarm Memory. Press the Ckey to clear Alarm Memory.
Bypassing
Automatic Bypassing
Note: Automatic Bypassing has not been evaluated by UL
Home/Away with Delay Zones
This zone type has the following operation depending on whether an Exit/Entry Zone has been violated during the Exit Delay time.
Home
Exit/Entry Zone is not violated
Zones selected as Home/Away with Delay Zones will be bypassed automatically.
Away with Delay
Exit/Entry Zone is violated
Zones selected as Home/Away with Delay Zones will have a fixed 20-second entry delay when violated before an Exit/Entry Zone.
Full Setting the System with Automatic Bypassing - Home/Away with Delay Zones
From the Keypad
Press BC to return protection to
Home/Away with Delay Zones that have been automatically bypassed. Three minutes are allowed to walk through Exit/ Entry and Exit/Entry Follower Zones.
Using A Keyfob (GEM-KF)
All zones in the system can be armed regardless of the state of the Exit/Entry Zone when arming with a Keyfob and using an AUX key programmed as Full Set. Press [ON] and press and hold the [A1] or [A2] keys for 1.5s when leaving the premises. All zones, including Home/Away Zones are armed.
Bypassing a zone
Press the Bkey, then the zone number to
be bypassed. While the panel is DISARMED, the bypassed zone LED will flash slowly; indicating the zone has been bypassed. While the panel is ARMED, the bypassed zones will only be displayed if the Display Bypassed [21-3] option has been selected.
Unbypassing a zone (Disarmed only)
Press the Bkey then the number of the zone to be unbypassed.
Group Bypass
Press the E key to Bypass all Exit/Entry
Follower Zones [02] or Home/Away Zones
[01] (only if the system is programmed exclusively for Home/Away with Delay zones).
Using A Keyfob (GEM-KF)
Hold the [A1] or [A2] key on the Keyfob to Bypass all Exit/Entry Follower Zones [02] or
Home/Away Zones [01] (only if the system is programmed exclusively for Home/Away with Delay zones).
User Program Mode
To prevent the loss of the User 1 Code, the panel default program includes User 1 Code Lockout [96-2].
To change the User 1 Code from its default value of 1234, program the 4-digit User 1 Code through Dealer Programming [95]. User 1 Arm/Disarm code is also used to program User Codes 2 - 8. By default, the User 1 code cannot be reprogrammed by the user.
If it is necessary to change the User 1 code, it can be changed through downloading or Dealer keypad programming. From Dealer Program Mode, change the User 1 Code Lockout ([96-2] LED=OFF) to disabled.
Entering User Program Mode
9