The old refrigerant and lubricant in the existing piping
contains a large amount of chlorine which may cause the
lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.)
inside the piping and joints, deterioration of the lubricant
will result.
Use ESTER , ETHER or HAB as the lubricant to
coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause
deterioration of refrigerant oil etc.
Use liquid refrigerant to charge the system.
If gas refrigerant is used to seal the system, the composition
of the refrigerant in the cylinder will change and performance
may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the
refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant
cycle and cause the lubricant deterioration.
Store the piping to be used during installation
indoors with keep both ends sealed until just
before brazing.
(Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle,
deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
Gravimeter
Unit
SAFETY PRECAUTION
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R407C
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
4
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.Tool nameSpecifications
1Gauge manifold·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2Charge hose·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3Electronic scale
4Gas leak detector·Use the detector for R134a or R407C.
5Adapter for reverse flow check.·Attach on vacuum pump.
6Refrigerant charge base.
7Refrigerant cylinder.·For R407C·Top of cylinder (Brown)
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
PU/PUH-P25, P35, P50, P60 : max 20m
PU/PUH-P71, P100, P125, P140 : max 30m
The refrigerant circuit with LEV(Linear Expansion Valve) and a large accumulator always control the optimal refrigerant
level regardless of the length (20/30m max. and 5m min.) of piping. The additional refrigerant charging work during
installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality
and reliability of the work done.It also helps to speed up the installation time.
PUH-P125YGAA.UK
PUH-P140YGAA.UK
PU-P125YGAA.UK
PU-P140YGAA.UK
6
4SPECIFICATIONS
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Mode
Power supply (phase, cycle, voltage)
Running current
Max current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
FanFan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
OUTDOOR UNIT
REFRIGERANT PIPING
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Service Ref.
PUH-P25VAA.UK
PUH-P35VGAA / YGAA.UK
Cooling
5.32
Single,50Hz,230V
7.23
RE189VHSMT
0.9
45(1,590)
46
48
50(110)
1.7(3.8)
6.35(1/4)
12.7(1/2)
Max. 30m
Max. 30m
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
30
Plate fin coil
Propeller (direct) o 1
0.07
Reverse cycle
900(35-7/16)
330+20(13+3/4)
650(25-5/8)
R407C
0.57(Ester)MEL56
Flared
Flared
Heating
4.89
Cooling
7.61 / 2.54
Single,50Hz,230V / 3-ph,50Hz,400V
10.67/5.4
RE277VHSMT/RE277YFKM
1.3
45(1,590)
47
49
54(119)
2.5(5.5)
9.52(3/8)
15.88(5/8)
Max. 40m
Max. 40m
Heating
7.85 / 2.62
Internal thermostat
HP switch
Discharge thermo
Thermal relay
HP switch
Discharge thermo
Internal thermostat
HP switch
Discharge thermo
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Mode
Power supply (phase, cycle, voltage)
Running current
Max current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
FanFan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
OUTDOOR UNIT
REFRIGERANT PIPING
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Service Ref.
PUH-P50VGAA / YGAA.UK
PUH-P60VGAA / YGAA.UK
Cooling
10.97 / 3.98
15.35 /7.0
NE36VMJMT / NE36YEKMT
1.6
55(1,940)
49
74(163)
2.6(5.7)
Max. 40m
Max. 40m
Single, 50Hz, 230V / 3-ph, 50Hz,400V(4wires)
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
38
Plate fin coil
Propeller (direct) o 1
0.07
Reverse cycle
48
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
R407C
1.2 (Ester)MEL56
9.52(3/8)
15.88(5/8)
Flared
Flared
Heating
11.30 / 3.95
Cooling
13.27 / 4.43
18.03 / 7.7
NE41VMJMT / NE41YEKMT
1.9
50(1,770)
50
79(174)
3.1(6.8)
Max. 50m
Max. 50m
Heating
12.84/ 4.29
Internal thermostat
HP switch
Discharge thermo
Thermal relay
HP switch
Discharge thermo
4-1. HEAT PUMP
7
Service Ref.
Mode
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
OUTDOOR UNIT
FanFan(drive) o No.
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current
Max current
Model
Motor output
Starter type
Protection devices
Crankcase heater
Fan motor output
Airflow
Charge
Oil (Model)
Indoor side
Outdoor side
Height difference
Piping length
Cooling
Heating
W
D
H
Liquid
Gas
kW
kW
K
/min(CFM
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
PUH-P71VGAA / YGAA.UK
A
A
W
)
L
Cooling
15.66 / 5.23
NE52VNJMT / NE52YDKMT
Single, 50Hz, 230V / 3-ph, 50Hz, 400V(4wires)
22.66 / 10.8
Propeller (direct) o 1
0.07
50(1,770)
855(33-5/8)
79(174)
3.3(7.3)
15.88(5/8)
Heating
16.67 / 5.56
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
2.5
Line start
Internal thermostat
HP switch
Discharge thermo
Plate fin coil
Reverse cycle
49
51
900(35-7/16)
330+20(13+3/4)
R407C
1.3 (Ester)MEL56
9.52(3/8)
Flared
Flared
Max. 50m
Max. 50m
PUH-P100VGAA / YGAA.UK
Cooling
16.43/ 5.48
23.57 / 10.8
NE56VNJMT / NE56YDKMT
Thermal relay
HP switch
Discharge thermo
38
Propeller (direct) o 2
0.07+0.07
85(3,000)
1,260(49-5/8)
97(214)
4.0(8.8)
19.05(3/4)
Heating
17.34 / 5.79
2.7
51
53
Service Ref.
Mode
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Heat exchanger
OUTDOOR UNIT
FanFan(drive) o No.
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current
Max current
Model
Motor output
Starter type
Protection devices
Crankcase heater
Fan motor output
Airflow
Charge
Oil (Model)
Indoor side
Outdoor side
Height difference
Piping length
Cooling
Heating
W
D
H
Liquid
Gas
kW
kW
/min(CFM
K
dB(A)
dB(A)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
PUH-P125YGAA.UK
Cooling
A
A
W
)
L
7.52
18.0
BE82YADMT
95(3,360)
4.6(10.1)
Heating
3-ph, 50Hz, 400V(4wires)
8.06
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
3.5
Line start
Thermal relay, HP switch, Discharge thermo
38
Plate fin coil
Propeller (direct) o 2
0.07 +0.07
Reverse cycle
55
56
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
125(276)
R407C
1.7 (Ester) MEL56
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
PUH-P140YGAA.UK
Cooling
8.92
20.4
BE96YADMT
4.2
100(3,530)
57
58
4.9(10.8)
Heating
9.45
8
4-2. COOLING ONLY TYPE
A
A
kW
W
kW
K
/min(CFM
)
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
FanFan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
OUTDOOR UNIT
REFRIGERANT PIPING
Cooling
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Service Ref.PU-P71VGAA / YGAA.UKPU-P100VGAA / YGAA.UK
Cooling
15.66 / 5.23
22.66 / 10.8
NE52VNJMT / NE52YDKMT
2.5
Propeller (direct) o 1
0.07
50(1,770)
49
855(33-5/8)
79(174)
3.3(7.3)
15.88(5/8)
Single, 50Hz, 230V / 3-ph, 50Hz, 400V(4wires)
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
38
Plate fin coil
—
900(35-7/16)
330+20(13+3/4)
R407C
1.3 (Ester)MEL56
9.52(3/8)
Flared
Flared
Max. 50m
Max. 50m
Cooling
16.43/ 5.48
23.57 / 10.8
NE56VNJMT / NE56YDKMT
2.7
Propeller (direct) o 2
0.07+0.07
85(3,000)
51
1,260(49-5/8)
97(214)
4.0(8.8)
19.05(3/4)
Internal thermostat
HP switch
Discharge thermo
Thermal relay
HP switch
Discharge thermo
Service Ref.
Mode
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
OUTDOOR UNIT
Heat exchanger
FanFan(drive) o No.
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
REFRIGERANT PIPING
outdoor unit
Running current
Max. current
Model
Motor output
Starter type
Protection devices
Crankcase heater
Fan motor output
Airflow
Charge
Oil (Model)
/min(CFM
K
Cooling
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
These holes are provided for cases where the unit must
2
be secured by the base AND by the top surface together.
3
w1
Air
Intake
1246
1260
Handle
Use Self Tapping screws 5 x L15 or less.
(Obtained Locally)
55
Rear Trunking Hole
(Knock-Out)
92
92
[
< Rear Side >
40
Power Supply Wiring Hole
(2-[27Knock-Out)
< Right Side >
100
Power Supply Wiring Hole
(2-[27Knock-Out)
40
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
5522
6368
4055
1002733
6368
5522
[92
33
50
33
92
Piping Knock-Out Hole Details
Front Trunking Hole
(Knock-Out)
Rear Piping Hole
(Knock-Out)
65
Right Piping Hole
(Knock-Out)
50
65
Front Piping Hole
(Knock-Out)
21
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
SV
PE
MF
MF
a
b
51C
63L
63H
WHT
BLK
WHT
BLK
BRN
BRN
WHT
WHT
BLU
BLU
BLK
BLK
ORN
ORN
WHT
WHT
TB2
S1
Y
L
W
(*1BLK)
(*1BLK)
O
R
N
S2
MF4
(WHT)
MF3
(WHT)
52C
(PNK)
(BLU)
21S4
(GRN)
(BLK)
51CM
(ORN)
(RED)
B
R
N
S3
CH
SV
FUSE2
63L
4/S
O.BOUTDOOR CONTROLLER BOARD
FUSE1 (O.B)FUSE (6.3A)
FUSE2 (O.B)FUSE (6.3A)
FUSE3 (O.B)FUSE (6.3A)
FUSE4 (O.B)FUSE (6.3A)
X51 (O.B)MC/CH RELAY
X52 (O.B)21S4 RELAY
X53 (O.B)SV RELAY
F.C (O.B)FAN CONTROLLER
SW1 (O.B)GROUP NUMBER ADDRESS
SW4 (O.B)TEST RUN
SW5 (O.B)FUNCTION SELECTION
J1~J6 (O.B)MODEL SELECTION
T (O.B)TRANSFORMER
CT (O.B)CURRENT TRANS
LED1 (O.B)OPERATION CHECK DISPLAY LED
LED2 (O.B)OPERATION CHECK DISPLAY LED
CN31 (O.B)EMERGENCY OPERATION CONNECTER
O.B
X51
X52
X53
F.C
RST
CT
TB4
CNM
ON
OFF
FUSE1
S3
S2
S1
CNVMNT
SW5
CN31
FUSE4
FUSE3
INDOOR
UNIT
CNMNT
(WHT)
LED1 (GRN)
LED2 (RED)
SW1SW4
J1J2J3J4J5
S1
S2
S3
(WHT)
J6
CNLEV
(WHT)
TH4
(WHT)
TH3/TH6
(RED)
T
*1 PUH-P125/140YGAA MODEL ONLY
*2 PU(H)-P100/125/140YGAA MODEL ONLY
*3 PU(H)-P125/140YGAA MODEL ONLY
*4 PUH-P35~ P140YGAA MODEL ONLY
BRN
RED
BLU
ORN
YLW
WHT
BLK
BLK
GRY
LEV
TH4
TH6
TH3
23
8WIRING SPECIFICATIONS
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L
B
N
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
B
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
L
N
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
B
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
1
2
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L
N
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity*1
Main switch (Breaker)
Outdoor unit power supply
)
2
Outdoor unit power supply earth
Indoor unit-Outdoor unit*2
Wiring
Indoor unit-Outdoor unit earth*2
Wire No. o
size (mm
Remote controller-Indoor unit*3
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2*4
Indoor unit-Outdoor unit S2-S3*4
Circuit rating
Remote controller-Indoor unit*4
*1. A breaker with at least 3 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Refer to 8-2.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
2 o Min. 1.52 o Min. 2.52 o Min. 44 o Min. 1.54 o Min. 2.5
1 o Min. 1.51 o Min. 2.51 o Min. 41 o Min. 1.51 o Min. 1.5
3 o 1.5 (Polar)3 o 1.5 (Polar)3 o 1.5 (Polar)3 o 1.5 (Polar)3 o 1.5 (Polar)
1 o Min. 1.51 o Min. 1.51 o Min. 1.51 o Min. 1.51 o Min. 1.5
2 o 0.3 (Non-polar)2 o 0.3 (Non-polar)2 o 0.3 (Non-polar)2 o 0.3 (Non-polar)2 o 0.3 (Non-polar)
*4
AC 230 VAC 230 VAC 230 VAC 230 VAC 230 V
AC 230 VAC 230 VAC 230 VAC 230 VAC 230 V
DC 24 VDC 24 VDC 24 VDC 24 VDC 24 V
DC 12 VDC 12 VDC 12 VDC 12 VDC 12 V
A-Control
Outdoor Unit
Isolator
S1
S2
S3
3 poles isolator
S1
S2
S3
A-Control
Indoor Unit
Warning:
In case of A-control wiring, there is high v oltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line
and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is
energized. If isolator should be used between indoor unit and outdoor unit, please use 3-poles type.
1:1 systemSynchronized twin and triple system Electrical wiring
• Synchronized twin
• Synchronized triple
24
Cross section
of cable
Round
2.5
2.5
1.5
2.5
3
3
4
4
(50)
✽2
(45)
✽3
60
✽4
Not
applicable
✽5
Flat
✽1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.
✽2 : In case that cable with stripe of yellow and green is available.
✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
2
.
✽4 : In case of regular polarity connection (S1-S2-S3).
✽5 : In the flat cables are connected as this picture, they can be used up to 80m.
✽6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
Flat
Round
Wire size
(mm
2
)
Number
of wires
Clockwise : S1-S2-S3
w Pay attention to stripe of yellow and green
Clockwise : S1-S2-S3-Open
w Connect S1 and S3 to the opposite angle
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Polarity
L(m)
✽6
(3C Flat cable ✕ 2)
S1 S2 S3
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate
connections).
Intermediate connections can lead to communication errors if water enters the cables and causes
insufficient insulation to ground or a poor electrical contact at the intermediate connection point.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering
the cables.)
8-2. INDOOR-OUTDOOR CONNECTING CABLE
25
8-3. M-NET WIRING METHOD
Group
remote
controller
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
A-control
remote
controller
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 00
M-NET
address 03
Power
supply
unit for
transmission
wire
Central
remote
controller
M-NET transmission wire
✕ Bad example (Multi spot grounding of shield wire)
Good example 1 (Single spot grounding of shield wire)
Power
supply
appliance
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Good example 2 (Single spot grounding of shield wire)
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET p.c. board may be burn out.
(3) Use 2-core x 1.25mm2shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
If there are more than two grounding spots on the shield wire, noise may enter into the shield wire because the ground wire
and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among grounding spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and shield
wire do not form one circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
26
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
12
~
50
M-NET Address No.
<Setting example>
Switng
setting
SW11
ones
digit
SW12
tens
digit
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
0
Refrigerant
address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
System
controller
A-control
remote
controller
Group AGroup BGroup C
A-control
remote
controller
TB5
A-control
remote
controller
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 00
M-NET
address 04
Power
supply
unit for
transmission
wire
A-control
remote
controller
A-control
remote
controller
TB5
Group AGroup B
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 01
M-NET
address 02
Refrigerant
address 00
M-NET
address 04
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
System
controller
Power
supply
unit for
transmission
wire
● M-NET wiring
(1) Use 2-core x 1.25mm
2
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block.Connect one core of the
transmission wire (non-polar) to Aterminal and the other to B. Peel the
shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
M-NET
terminal
block
ABS
Transmission
wire
Ground
wire
Shield
part
outdoor unit’s terminal, i.e. Ato A, B to B and S to S.In this case, choose one of those outdoor units and drive a screw
to fix an ground wire on the plate as shown on the right figure.
8-3-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to Free Combo
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in Free Combo system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET board of outdoor unit.
(Factory setting: all addresses are set to “0”.)
8-3-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Factory setting:
all switches are OFF. (All refrigerant addresses are “00”.)]
8-3-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
w Refrigerant addresses can be overlapped if they are in the different group.
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in
the group for the outdoor unit whose refrigerant address is “00”.
27
9
Service
port
Accumulator
Compressor
Refrigerant GAS pipe
19.05A({3/4")
Refrigerant LIQUID pipe
9.52A({3/8")
Stop valve
(with service port)
4-way valve
Service
port
High pressure
protect switch
Thermistor
(TH3)
Capillary tube
(O.D.4.0✕I.D.3.0-L350)✕2pcs
Refrigerant flow in cooling
Refrigerant flow in heating
Liner expansion valve
Thermistor
(TH4)
Muffler
Thermistor
(TH6)
Distributor
with
strainer
Ball valve
(#50)
Strainer
(#100)
Strainer
(#100)
Strainer
Service
port
Accumulator
Ball valve
Compressor
Refrigerant GAS pipe
P25···12.7A({1/2")
P35~P71···15.88A({5/8")
Judge what is wrong and take a corrective action according
to “10-4. Self-diagnosis action table”.
Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “10-5. Troubleshooting
by inferior phenomena”.
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, matters related to wiring
and etc.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
1Re-check the abnormal symptom.
2Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “10-5. Troubleshooting
by inferior phenomena”.
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
10-2. CHECK POINT UNDER TEST RUN
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Merger and
check that it is 1.0M" or over.
wDon’t use 500V Merger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Turn on power supply twelve hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
30
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.