Mitsubishi PUH-P200MYA, PUH-P250MYA Service Manual

Page 1
TECHNICAL & SERVICE MANUAL
HEAT PUMP
PUH-P200MYA,PUH-P250MYA
(Single and Twin/Triple/Four)
Models
AIR-COOLED SPLIT-TYPE PACKAGED AIR CONDITIONERS
2005
For use with the R407C
Page 2
Page
Contents
1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT ...................................... 1
[1] Storage of Piping Material ...................................................................................................2
[2] Piping Machining ................................................................................................................. 3
[3] Necessary Apparatus and Materials and Notes on Their Handling ..................................... 4
[4] Brazing................................................................................................................................. 5
[5] Airtightness Test .................................................................................................................. 6
[6] Vacuuming ........................................................................................................................... 6
[7] Charging of Refrigerant ....................................................................................................... 7
2 SPECIFICATIONS ...................................................................................................................... 8
3 EXTERNAL DIMENSIONS ....................................................................................................... 10
4 ELECTRICAL WIRING DIAGRAM ............................................................................................ 11
[1] Outdoor Unit ....................................................................................................................... 11
[2] Skelton of Indoor/Outdoor Connection .............................................................................. 12
5 Technical Data of PUH-P200MYA/P250MYA to Meet LVD .................................................... 13
[1] Standard Operation Data ................................................................................................... 13
[2] Cooling Capacity Curves ................................................................................................... 15
[3] Heating Capacity Curves ................................................................................................... 15
[4] Capacity Reduction Ratio due to Changes in Piping Length ............................................. 16
[5] Center of Gravity (Outdoor unit) ........................................................................................ 17
[6] NC Curve (Outdoor unit) ................................................................................................... 18
6 SERVICE DATA ........................................................................................................................ 19
[1] Appearance of Equipment ................................................................................................. 19
[2] Refrigerant Circuit .............................................................................................................. 21
[3] Limitation of Refrigerant Piping Length.............................................................................. 21
[4] Refrigerant Piping .............................................................................................................. 22
[5] Refrigerant Charge ............................................................................................................ 22
[6] Operation Rage ................................................................................................................. 22
7 CONTROL ................................................................................................................................ 23
[1] Composition of Control ...................................................................................................... 23
[2] Control specifications......................................................................................................... 24
[3] Function of switches and connectors (outdoor unit) .......................................................... 28
[4] Simple parts check method ............................................................................................... 36
[5] Reference Data.................................................................................................................. 37
[6] Troubleshooting of each part ............................................................................................. 38
[7] Emergency operation......................................................................................................... 41
[8] Self-diagnosis and troubleshooting.................................................................................... 43
8T
est run
.................................................................................................................................... 53
Page 3
–1–
¡ PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT
Caution
Do not use the existing refrigerant piping.
•A large amount of chlorine that may be contained in the residual refrigerant and refrigerating machine oil in the existing piping may cause the refrigerating machine oil in the new unit to deteriorate.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
• These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
Store the pipes to be installed indoors, and keep both ends of the pipes sealed until immediately before brazing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate or cause the unit to malfunction.
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
• Infiltration of a large amount of mineral oil may cause the refrigerating machine oil to deteriorate.
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
• If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may result in performance loss.
Only use refrigerant R407C.
• The use of other types of refrigerant that contain chlorine (i.e. R22) may cause the refrigerating machine oil to deteriorate.
Use a vacuum pump with a reverse-flow check valve.
If a vacuum pump that is not equipped with a reverse-flow check valve is used, the vacuum pump oil may flow into the refrigerant cycle and cause the refrigerating machine oil to deteriorate.
Prepare tools for exclusive use with R407C. Do not use the following tools if they have been used with the conventional refrigerant (gauge manifold, charging hose, gas leak detector, reverse-flow check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.).
• If the refrigerant or the refrigerating machine oil left on these tools are mixed in with R407C, it may cause the refrigerating machine oil to deteriorate.
• Infiltration of water may cause the refrigerating machine oil to deteriorate.
• Gas leak detectors for conventional refrigerants will not detect an R407C leak because R407C is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant will change, and the unit may experience power loss.
Exercise special care when handling the tools for use with R407C.
• Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate.
If the refrigerant leaks, recover the refrigerant in the refrigerant cycle, then recharge the cycle with the specified amount of the liquid refrigerant indicated on the air conditioner.
•Since R407C is a nonazeotropic refrigerant, if addi­tionally charged when the refrigerant leaked, the com­position of the refrigerant in the refrigerant cycle will change and result in a drop in performance or abnor­mal stopping.
Page 4
–2–
[1] Storage of Piping Material
(1) Storage location
Store the pipes to be used indoors. (Warehouse at site or owner’s warehouse) Storing them outdoors may cause dirt, waste, or water to infiltrate.
(2) Pipe sealing before storage
Both ends of the pipes should be sealed until immediately before brazing. Wrap elbows and T’s in plastic bags for storage.
* The new refrigerator oil is 10 times more hygroscopic than the conventional refrigerator oil (such as Suniso). Water
infiltration in the refrigerant circuit may deteriorate the oil or cause a compressor failure. Piping materials must be stored
with more care than with the conventional refrigerant pipes.
OK
OK
NO
NO
Page 5
–3–
[2] Piping Machining
Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
Do not use oils other than ester oil, ether oil or alkylbenzene.
Use only the necessary minimum quantity of oil.
Reason:
1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside.
Notes:
Introducing a great quantity of mineral oil into the refrigerant circuit may also cause a compressor failure.
Page 6
–4–
[3] Necessary Apparatus and Materials and Notes on Their Handling
The following tools should be marked as dedicated tools for R407C.
<<Comparison of apparatus and materials used for R407C and for R22>>
Apparatus Used Use R22 R407C
Gauge manifold Evacuating, refrigerant filling Current product Charging hose Operation check Current product Charging cylinder Refrigerant charging Current product Do not use Gas leakage detector Gas leakage check Current product Shared with R134a Refrigerant collector Refrigerant collection R22 For R407C use only Refrigerant cylinder Refrigerant filling R22 Identification of dedi-
cated use for R407C: Record refrigerant name and put brown belt on upper part of cylinder.
Vacuum pump Vacuum drying Current product Can be used by attach-
ing an adapter with a
check valve. Vacuum pump with a check valve Current product Flare tool Flaring of pipes Current product Bender Bending of pipes Current product Application oil Applied to flared parts Current product Ester oil or Ether oil or
Alkybenzene (Small
amount) Torque wrench Tightening of flare nuts Current product Pipe cutter Cutting of pipes Current product Welder and nitrogen cylinder Welding of pipes Current product Refrigerant charging meter Refrigerant charging Current product Vacuum gauge Checking the vacuum degree Current product
Symbols: To be used for R407C only. Can also be used for conventional refrigerants.
Tools for R407C must be handled with more care than those for conventional refrigerants. They must not come into contact
with any water or dirt.
Page 7
–5–
[4] Brazing
No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt, etc.) does not enter the refrigerant circuit.
Example: Inner state of brazed section
When non-oxide brazing was not used When non-oxide brazing was used
Items to be strictly observed:
1. Do not conduct refrigerant piping work outdoors on a rainy day.
2. Apply non-oxide brazing.
3. Use a brazing material (BCuP-3) which requires no flux when brazing between copper pipes or between a copper pipe and copper coupling.
4. If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends of them.
Reasons:
1. The new refrigerant oil is 10 times more hygroscopic than the conventional oil. The probability of a machine failure if water infiltrates is higher than with conventional refrigerant oil.
2. A flux generally contains chlorine. A residual flux in the refrigerant circuit may generate sludge.
Note:
Commercially available antioxidants may have adverse effects on the equipment due to its residue, etc. When
applying non-oxide brazing, use nitrogen.
Page 8
–6–
[5] Airtightness Test
No changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407C leakage.
Halide torch R22 leakage detector
Items to be strictly observed:
1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipment’s airtightness, taking temperature variations into account.
2. When investigating leakage locations using a refrigerant, be sure to use R407C.
3. Ensure that R407C is in a liquid state when charging.
Reasons:
1. Use of oxygen as the pressurized gas may cause an explosion.
2. Charging with R407C gas will lead the composition of the remaining refrigerant in the cylinder to change and this refrigerant can then not be used.
Note:
•A leakage detector for R407C is sold commercially and it should be purchased.
[6] Vacuuming
1. Vacuum pump with check valve A vacuum pump with a check valve is required to prevent the vacuum pump oil from flowing back into the refrigerant circuit when the vacuum pump power is turned off (power failure). It is also possible to attach a check valve to the actual vacuum pump afterwards.
2. Standard degree of vacuum for the vacuum pump Use a pump which reaches 0.5 Torr (500 MICRON) or below after 5 minutes of operation. In addition, be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil. If the vacuum pump is not properly maintained, the degree of vacuum may be too low.
3. Required accuracy of the vacuum gauge Use a vacuum gauge that can measure up to 5 Torr. Do not use a general gauge manifold since it cannot measure a vacuum of 5 Torr.
4. Evacuating time
•Evacuate the equipment for 1 hour after -755 mmHg (5 Torr) has been reached.
After envacuating, leave the equipment for 1 hour and make sure the that vacuum is not lost.
5. Operating procedure when the vacuum pump is stopped In order to prevent a backflow of the vacuum pump oil, open the relief valve on the vacuum pump side or loosen the charge hose to drawn in air before stopping operation.
The same operating procedure should be used when using a vacuum pump with a check valve.
NO
NO
Page 9
–7–
[7] Charging of Refrigerant
R407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.
For a cylinder with a syphon attached For a cylinder without a syphon attached
Cylinder color identification R407C-Gray Charged with liquid refrigerant
R410A-Pink
Reasons:
1. R407C is a mixture of 3 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is charged with R407C gas, then the refrigerant whose evaporation temperature is closest to the outside temperature is charged first while the rest of refrigerants remain in the cylinder.
Note:
In the case of a cylinder with a syphon, liquid R407C is charged without turning the cylinder up side down. Check the
type of cylinder before charging.
Cylin-
der
Cylin-
der
Valve
Valve
Liquid
Liquid
Page 10
–8–
Cooling Heating
18,000 20,400
20.9 23.7
3N~ 380/400/415 V 50 Hz
7.27 7.17
13.0 12.8
Propeller fan × 1
185
0.38
Hermetic
5.5
0.05 (240V)
R407C/FVC68D
Steel plate painting with polyester powder
(MUNSELL 5Y8/1 or similar)
1,715(H) × 990(W) × 840(L)
3.3
Overcurrent protection/Thermal switch
ø12.7 Flare / ø25.4 Flange
PEH-RP200MYA
56
215
Indoor: 15 °CWB~24 °CWB Indoor: 15°CDB~27 °CDB
Outdoor: -5 °CDB~46 °CDB
Outdoor: -12 °CWB~18 °CWB
2 SPECIFICATIONS
Specifications of air-source heat pump type packaged air conditioner
(Outdoor unit)
Model name PUH-P200MYA Quantity
Capacity
kcal/h
kW
Power source
Power input kW
Current A
Type x Quantity
Fan Airflow rate m3/min
Motor output kW
Type
Compressor Motor output kW
Crankcase heater kW
Refrigerant/Lubricant
External finish
External dimension mm
High pressure protection MPa
Compressor/Fan
Refrigerant piping diameter Liquid/Gas mm
Indoor unit
Noise level dB (A)
Net weight kg
Operating temperature range
Notes:
1. Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor: 27 °CDB/19 °CWB Outdoor: 35
°
CDB
Heating Indoor: 20 °CDB Outdoor: 7
°
CDB/6 °CWB
Pipe length: 7.5m Height difference: 0m
2. Works not included: Installation/Foundation work, Electrical connection work, Duct work, Insulation work, Power source switch, and other items not specified in this specifications.
Protection
device
Page 11
–9–
Cooling Heating
22,400 26,200
26.0 30.5
3N~ 380/400/415V 50Hz
9.02 8.62
16.0 15.4
Propeller fan × 1
185
0.38
Hermetic
7.5
0.05 (240V)
R407C/FVC68D
Steel plate painting with polyester powder
(MUNSEL 5Y8/1 or similar)
1,715(H) × 990(W) × 840(L)
3.3
Overcurrent protection/Thermal switch
ø12.7 Flare / ø28.6 Flange
PEH-RP250MYA
57
220
Indoor: 15 °CWB~24 °CWB Indoor: 15 °CDB~27 °CDB
Outdoor: -5 °CDB~46 °CDB Outdoor: -12 °CWB~18 °CWB
Specifications of air-source heat pump type packaged air conditioner
(Outdoor unit)
Model name PUH-P250MYA Quantity
Capacity
kcal/h
kW
Power source
Power input kW
Current A
Type x Quantity
Fan Airflow rate m3/min
Motor output kW
Type
Compressor Motor output kW
Crankcase heater kW
Refrigerant/Lubricant
External finish
External dimension mm
High pressure protection MPa
Compressor/Fan
Refrigerant piping diameter Liquid/Gas mm
Indoor unit
Noise level dB (A)
Net weight kg
Operating temperature range
Notes:
1. Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor: 27 °CDB/19 °CWB Outdoor: 35 °CDB Heating Indoor: 20 °CDB Outdoor: 7 °CDB/6 °CWB
Pipe length: 7.5 m Height difference: 0 m
2. Works not included: Installation/Foundation work, Electrical connection work, Duct work, Insulation
work, Power source switch, and other items not specified in this specifications.
Protection
device
Page 12
–10–
3 EXTERNAL DIMENSIONS
• Models PUH-P200MYA/P250MYA
65
60
84
100 251
234
60 75
194
10048
80 40
121
50
6 5
840
910
15
880
15
990
215
215
560
1715
225
1490
413
55
190
149
40
70
16531
80
79
55
378
160
25
198
237
8073
Service panel
4-14X20 holes
<For mounting
anchor bolt M8>
(Field supply)
Plane view
Rear view
Left side view
Front view
Right side view
Refrig. service
valve (liquid)
φ
12.7<flare> Refrig. service
valve(gas)
<flange>
φ
38.1 Knockout hole
<Bottom side hole for
the power supply>
φ
38.1 Knockout hole <Left side hole for
the power supply>
Knockout hole
<Front side hole for
the power supply and
control wiring>
φ
38.1 Knockout hole <Right side hole for
the power supply>
φ
25.4 Knockout hole
<Bottom side hole for
the control wiring>
φ
25.4 Knockout hole <Left side hole for
the control wiring>
φ
25.4 Knockout hole <Right side hole for
the control wiring>
Knockout hole
Left piping hole
Knockout hole
Front piping hole
Knockout hole
Pressure gauge
(for option)
Knockout hole
Rear piping hole
(It is necessary
for the option)
Connecting pipe
8 :
φ
25.4<brazed>
10 :
φ
28.6<brazed>
Note 1
Note 2
Note 3
Knockout hole
Bottom piping hole
Cross section X-X
Cross section Y-Y
X
X
Y
Y
Air outlet
Air
inlet
Air
inlet
<Accessory>
• Refrigerant connecting pipe ......................................
1pc.
(The connecting pipe is fixed with the unit)
•Packing for connecting pipe ......................................
1pc.
(It is attached control box cover)
• Conduit mounting plate
(Painted the same color as the unit body)
φ
27 ............................................................................
1pc.
φ
34 ............................................................................
1pc.
φ
40 ............................................................................
1pc.
•Tapping screw 4 x 12 ..............................................
4pcs.
Note: 1. Please leave a space under the outdoor unit for
the piping when you connected the piping from
the bottom.
(Please be careful not to close the hole of the
bottom plate by the basement.)
2. It is possible to change to
φ
27 or
φ
34 by selecting
the conduit mounting plate.
3. The hole size can be selected to
φ
27 or
φ
34 or
φ
40 by selecting the conduit mounting plate.
Page 13
–11–
4 ELECTRICAL WIRING DIAGRAM
[1] Outdoor Unit
• Model PUH-P200MYA/P250MYA
Symbol Name
F1, F2 FUSE (15A 250VAC CLASS T)
F01~F04 FUSE (6.3A 250VAC CLASS F)
F10~F30 FUSE (6.3A 250VAC CLASS F)
51C OVER CURRENT RELAY (COMPRESSOR)
52C MAGNETIC CONTACTOR (COMPRESSOR)
63L PRESSURE SWITCH (LOW PRESSURE)
63H1 PRESSURE SWITCH (HIGH PRESSURE)
63H2 PRESSURE SWITCH (FOR CONTROL)
MC COMPRESSOR MOTOR
MF FAN MOTOR (OUTDOOR)
TR TRANSFORMER
X1 AUXILIARY RELAY (FOR 16, 20HP)
LED 1 LED (FOR SERVICE)
X01~X05 AUXILIARY RELAY (MAIN BOARD)
CN2,CN20~28
CN3,34,30,3N,3S
CN4,40,51~53,81
CONNECTOR MAIN BOARD
CNFC1, FG, S3
CNMT,VMNT
Symbol Name
SW1~SW5 SWITCH (MAIN BORD)
21S4 4-WAY VALVE
SV1 SOLENOID VALVE
CH CRANK CASE HEATER (COMPRESSOR)
LEV ELECTRINIC EXPANSION VALVE
TH1 LIQUID TEMP.
TH2 THERMISTOR DISCHARGE TEMP.
TH3 COND./EVA. TEMP.
TB1 POWER SOURCE TERMINAL BLOCK
TB3, 4 OUTDOOR/INDOOR CONNECTION TERMINAL BLOCK
TB8 TERMINAL BLOCK (FOR 16, 20HP)
C11, C12 CONNECTOR (FAN MOTOR)
C14 CONNECTOR (63H2)
CAFAN, CNFC2
CONNECTOR (F. C. BOARD)
CNPO
CNOUT1, 2
CONNECTOR (N, F. BOARD)
CNIN
Note :
1. Be sure to apply earth work to the unit. (Use the earth terminal of TB1.)
2. The dotted lines show field wiring.
3. Color of earth wire is yellow and green twisting.
4. This motor (*1) includes auto reset type internal thermostat.
5. Indoor and outdoor connecting wires (*2) are made with polarities, make sure matching wiring and terminal.
6. SW5 (*3) is shown PUH-P250MYA set­ting. In case of PUH-P200MYA setting is shown as below.
Caution :
1. To protect compressor from abnormal cur­rent, over current relays is installed. There­fore, do not change factory set value of over current relays.
(*3)
14
SW5
ON
OFF
63H1
63L
CN23
1
3
CN22
1
3
CN21
1
3
CN26
1
3
5
CN25
1
3
CN53
1
3
CN52
1
3
5 6
CNFC1
1
6
CN20
L1
7
F01
N
F04
L2
F02
L3
1
F03
X1
INDOOR UNIT
TB4
S1 S2 S3
(3P)
(3P)
(3P)
(5P)
(3P)
(3P)
(6P)
(6P)
(7P)
3
RED
51C
52C
RED
TB1
L1
L2 L3 N PE
POWER SUPPLY 3N~PE 380/400/415V 50HZ
MC
WHITE WHITE
BLACK
BLACK
(*1)
MF
13 1
C11
(3P)
35
1
CNFAN
(5P)
CNFC2
F. C . BOARD
CNPO
(5P)
CNOUT1
BLUE
5
3
11
(5P)
1
F10
3
F20
5
F30
7
CNIN
(7P)
GREEN/YELLOW
F1
F2
PE
CIRCUIT BREAKER (FIELD SUPPLY) PUH-P200MYA-EU : 50A PUH-P250MYA-EU : 60A
3
(6P)
CNOUT2
N.F.BOARD
TB3
C12
(3P)
1
6
3
(3P)
S1 S2 S3
SV1
51C
52C
52C
PE
TO INDOOR UNIT CONNECTING WIRES (*2) (POLER)
21S4
TB8
CH
OUT OUT ININ
CNVMNT
(3P)
X04
X01
X02
X05
CNFG
(3P)
1
CNMNT
(5P)
(*3)
O
OFF
4
1
SW5
O
OFF
SW3
X03
LED1
Transmission Circuit
CNS3
(3P)
OUTDOOR UNIT CONTROL BOX
TH1
TH2
LEV
1
212
2
CN2
CN40 CN4CN3
(2P)
(6P)
1
SW4
3
2
(2P) (2P)
O
OFF
16
SW1
O
OFF
1
6
SW2
CN34
CN28
(3P)
3
1
1
TR
DC power supply
(3P)
TH3
3
1
CN3D (3P)
CN3S (3P)
CN3N (3P)
CN24 (3P)
CN27 (3P)
CN81 (3P)
CN51 (5P)
1
X1
3
1
63H2
2
3
1
1
C14
(2P)
Page 14
–12–
Indoor Units
PEH-RP*MYA PLH-P*KAH, PLH-P*AAH PLA-P*KA, PLA-P*AA PEHD-P*EAH, PEAD-P*EA PCH-P*GAH, PCA-P*GA PKH-P*GALH, PKH-P*FALH PKA-P*GAL, PKA-P*FAL PSH-P*GAH, PSA-P*GA
Indoor Units
PEH-RP*MYA PLH-P*KAH, PLH-P*AAH PLA-P*KA, PLA-P*AA PEHD-P*EAH, PEAD-P*EA PCH-P*GAH, PCA-P*GA PKH-P*GALH, PKH-P*FALH PKA-P*GAL, PKA-P*FAL PSH-P*GAH, PSA-P*GA
Multi distributor pipes (Option)
25 : 25 : 25 : 25
2HP+2HP
+2HP+2HP
2.5HP+2.5HP+
2.5HP+2.5HP –
SDT-1111SA-E
[2] Skelton of Indoor/Outdoor Connection
(1) Applicable combinations of 8 & 10HP [PUH-P200MYA/P250MYA]
(2) System
Indoor units
Distributor
Remote controller
Outdoor unit
Pipe work
Transmission line
3-core cable
Distributor
Remote controller
Outdoor unit
Pipe work
Transmission line
3-core cable
Indoor unit
Remote controller
Outdoor unit
Pipe work
Pipe work
Transmission line
3-core
*4-core cable
cable 3-core *cable
Indoor units
Twin
TripleSingle
Single
8HP
– –
10HP
– –
50 : 50
4HP+4HP
5HP+5HP
SDD-50WSA-E
33 : 33 : 33
2.5HP+2.5HP +2.5HP
3HP+3HP
+3HP
SDT-111SA-E
25 : 25 : 50
2HP+2HP
+4HP
2.5HP+2.5HP +5HP
SDT-112SA-E
20 : 40 : 40
1.6HP+3HP +3HP
2HP+4HP
+4HP
SDT-122SA-E
PUH-P250MYA PUH-P200MYA
Four
Distributor
Remote controller
Outdoor unit
Pipe work
Transmission line
3-core cable
Indoor units
*
indicates applicable HP
* Two outdoor units connected when using
PEH-P400·500MYA, therefore 4-core cable required in order to send and receive alternate defrost signal.
Outdoor unit
Indoor Units PEH-P*MYA Indoor Unit PEH-P*MYA
16HP
20HP
– – – –
– – – –
– – – –
– – – –
– – – –
Page 15
–13–
380 400 415 380 400 415
50 50 50 50 50 50
27/19 27/19 27/19 20/– 20/– 20/–
35/– 35/– 35/– 7/6 7/6 7/6
7.5 7.5 7.5 7.5 7.5 7.5
7.9 7.9 7.9 7.9 7.9 7.9
13.0 13.0 13.0 12.8 12.8 12.8
7.27 7.27 7.27 7.17 7.17 7.17
11.9 11.9 11.9 11.7 11.7 11.7
1.1 1.1 1.1 1.1 1.1 1.1
1.12 1.12 1.12 1.12 1.12 1.12
0.65 0.65 0.65 0.65 0.65 0.65
2.11 2.11 2.11 1.91 1.91 1.91
0.48 0.48 0.48 0.40 0.40 0.40
75 75 75 70 70 70
666000
46 46 46 0 0 0
35 35 35 30 30 30
5 Technical Data of PUH-P200MYA/P250MYA to Meet LVD
[1] Standard Operation Data
(1) PUH-P200MYA
Operating condition
Operating condition Cooling Heating
Voltage V
Power source frequency Hz
Indoor air condition (DB/WB) °C
Outdoor air condition (DB/WB) °C
Piping length m
Refrigerant charge kg
Current A
Input kW
Compressor current A
Fan current A
Current A
Input kW
Discharge pressure MPa
Suction pressure MPa
Discharge refrigerant temperature °C
Suction refrigerant temperature °C
Liquid pipe temperature
(at piping sensor)
°C
Compressor shell bottom temperature °C
Outdoor unit
Indoor unit
Refrigerant circuit
Electrical characteristics
380 400 415 380 400 415
50 50 50 50 50 50
27/19 27/19 27/19 20/– 20/– 20/–
35/– 35/– 35/– 7/6 7/6 7/6
7.5 7.5 7.5 7.5 7.5 7.5
8.4 8.4 8.4 8.4 8.4 8.4
16.0 16.0 16.0 15.4 15.4 15.4
9.02 9.02 9.02 8.62 8.62 8.62
14.9 14.9 14.9 14.3 14.3 14.3
1.1 1.1 1.1 1.1 1.1 1.1
1.64 1.64 1.64 1.64 1.64 1.64
0.94 0.94 0.94 0.94 0.94 0.94
2.22 2.22 2.22 1.75 1.75 1.75
0.50 0.50 0.50 0.38 0.38 0.38
80 80 80 65 65 65
888-1-1-1
48 48 48 0 0 0
30 30 30 20 20 20
(2) PUH-P250MYA
Operating condition
Operating condition Cooling Heating
Voltage V
Power source frequency Hz
Indoor air condition (DB/WB) °C
Outdoor air condition (DB/WB) °C
Piping length m
Refrigerant charge kg
Current A
Input kW
Compressor current A
Fan current A
Current A
Input kW
Discharge pressure MPa
Suction pressure MPa
Discharge refrigerant temperature °C
Suction refrigerant temperature °C
Liquid pipe temperature
(at piping sensor)
°C
Compressor shell bottom temperature °C
Outdoor unit
Indoor unit
Refrigerant circuit
Electrical characteristics
Note: The values listed above indicate that when connected with the indoor unit PEH-RP200MYA as representative data.
Note: The values listed above indicate that when connected with the indoor unit PEH-RP250MYA
as representative data.
Page 16
(3) PUH-P200MYA×2 units
V 380 415 380 415
Hz 50 50 50 50
°C 27/19 27/19 20/– 20/–
°C 35/– 35/– 7/6 7/6
m 7.5 7.5 7.5 7.5
kg 7.9 7.9 7.9 7.9
Current A 13.0 13.0 12.8 12.8
Input kW 7.27 7.27 7.17 7.17
Compressor Current A 11.9 11.9 11.7 11.7
Fan current A 1.1 1.1 1.1 1.1
Current A 4.5 4.1 4.5 4.1
Input kW 2.30 2.30 2.30 2.30
MPa 2.11 2.11 1.81 1.81
MPa 0.52 0.52 0.40 0.40
°C75 75 70 70
°C6 6 0 0
°C46 46 0 0
°C35 35 30 30
Note: The values listed above indicate that when connected with the indoor unit PEH-P400MYA as representative data.
*1: Value for one outdoor unit.
(4) PUH-P250MYA×2 units
V 380 415 380 415
Hz 50 50 50 50
°C 27/19 27/19 20/– 20/–
°C 35/– 35/– 7/6 7/6
m 7.5 7.5 7.5 7.5
kg 8.4 8.4 8.4 8.4
Current A 16.0 16.0 15.4 15.4
Input kW 9.02 9.02 8.62 8.62
Compressor Current A 14.9 14.9 14.3 14.3
Fan current A 1.1 1.1 1.1 1.1
Current A 5.1 4.7 5.1 4.7
Input kW 2.50 2.50 2.50 2.50
MPa 2.22 2.22 1.75 1.75
MPa 0.50 0.50 0.38 0.38
°C80 80 65 65
°C8 8 -1 -1
°C48 48 0 0
°C30 30 20 20
Note: The values listed above indicate that when connected with the indoor unit PEH-P500MYA as representative data.
*1: Value for one outdoor unit.
Cooling Heating
Electrial characterristics
Outdoor unit
*1
Indoor unit
Refrigerant circuit
Discharge pressure
Suction pressure
Discharge refrigerant temperature
Suction refrigerant temperature
Liquid pipe temperature (at piping sensor)
Compressor shell bottom temperature
Cooling Heating
Operating condition
Operating condition
Voltage
Power source frequency
Indoor air condition(DB/WB)
Outdoor air condition(DB/WB)
Piping length
Refrigerant charge
*1
Indoor air condition(DB/WB)
Refrigerant circuit
Discharge pressure
Suction pressure
Discharge refrigerant temperature
Suction refrigerant temperature
Liquid pipe temperature (at piping sensor)
Compressor shell bottom temperature
Outdoor air condition(DB/WB)
Operating condition
Outdoor unit
*1
Piping length
Refrigerant charge
*1
Operating conditionElectrial characterristics
Indoor unit
Voltage
Power source frequency
–14–
Page 17
–15–
[2] Cooling Capacity Curves
• PUH-P200MYA/P250MYA
[3] Heating Capacity Curves
• PUH-P200MYA/P250MYA
-5 -3 -1 1 3 5 7 9 11 13 15171921232527293133353739414345
22
20
18
16
0.6
0.8
1
1.2
1.4
Capacity ratio
-5 -3 -1 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45
22 20
18 16
0.7
0.9
1.1
1.22
Input ratio
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
15 20
25
0.6
0.8
1
1.2
1.4
Capacity ratio
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
25
20
15
0.6
0.8
1
1.2
1.4
Input ratio
Indoor inlet air wet
bulb temp. <˚CWB>
inlet air wet
bulb temp. <˚CWB>
Indoor
Indoor inlet air dry
bulb temp. <˚CDB>
Indoor inlet air dry
bulb
temp. <˚CDB>
Outdoor air
temperature
<˚CWB>
Outdoor air temperature
<˚CWB>
Outdoor air temperature
<˚CDB>
Outdoor air
temperature
<˚CDB>
Page 18
–16–
[4] Capacity Reduction Ratio due to Changes in Piping Length
(1) Cooling capacity
(2) Heating capacity
(3) Calculation formula of equivalent piping length
PUH-P200MYA
PUH-P250MYA
Model name
Equivalent piping length
~
30m 30 ~ 50m 50 ~70m
1.0 0.995 0.99
PUH-P200MYA Equivalent piping length (m) = Actual piping length (m) + (0.47 × Number of bend)
PUH-P250MYA Equivalent piping length (m) = Actual piping length (m) + (0.5 × Number of bend)
6 1.0
4 0.98
2 0.88
0 0.85
-2 0.86
-4 0.89
-6 0.92
-8 0.92
-10 0.92
(4) Reduction ratio by frosting
Outdoor unit inlet wet bulb temperature
Heating capacity reduction ratio
(°CWB)
Capacity ratio
Equivalent piping length (m)
0 10 20 30 40 50 60 70
0.8
0.9
1
PUH-P200MYA
Capacity ratio
Equivalent piping length (m)
0 10 20 30 40 50 60 70
0.8
0.9
1
PUH-P250MYA
Page 19
–17–
[5] Center of Gravity (Outdoor unit)
PUH-P200MYA
PUH-P250MYA
XYZ
330 350 490 215
300 330 510 220
Item
Model name
Center of gravity (mm)
Net weight
(kg)
(1) Caution for Lifting
Suspending spot
Protection pad
Name plate
Indicates the unit front side.
Hanger rope (Over 7m × 2)
Service panel
X
Y
Z
Compressor position
Center of gravity
G
Inclining to the right front side of unit.
2-point,front and rear
Warning
Must be durable against unit weight. For the lifting of unit for movement, please be sure to suspend at four points, and not to give any shock to unit.
Never apply two-point lifting as it is dangerous.
Use pads properly to prevent the scratching of external panel caused by contact with sling.
Fasten here properly to prevent unit from slipping off from the sling at lifting.
Lift unit slowly by suspending rope uniformly so that the rope will not slip off or unit will not incline seriously.
Be careful that unit may fall down if the rope is not in a proper position as the center or gravity of unit is being inclined.
Below 40˚
Page 20
–18–
[6] NC Curve (Outdoor unit)
(1) Octave Band Analysis
1) PUH-P200MYA
2) PUH-P250MYA
Note: The measuring point is 1m from the bottom of the unit (1m from the front of the unit).
Note:
The measuring point is 1m from the bottom of the unit (1m from the front of the unit).
20
µPa
20
µPa
Measurement condition
1m
A
1m
B
Sound pressure level in anechoic room
56 dB (A)
63Hz63125Hz59250Hz56500Hz551000Hz502000Hz454000Hz428000Hz
39
70
60
50
40
30
20
OCTAVE BAND PRESSURE LEVEL< dB> 0dB =
Approximate minimum audible limit on continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES <Hz>
NC60
NC50
NC30
NC20
(dB)
NC40
Measurement condition
1m
A
1m
B
Sound pressure level in anechoic room
57 dB (A)
63Hz63125Hz60250Hz56500Hz561000Hz512000Hz474000Hz448000Hz
40
70
60
50
40
30
20
OCTAVE BAND PRESSURE LEVEL< dB> 0dB =
Approximate minimum audible limit on continuous noise
10
63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCIES <Hz>
(dB)
NC60
NC50
NC40
NC30
NC20
Page 21
–19–
• PUH-P200MYA/P250MYA Detail of Electrical Parts Box
(with cover removed) (with Main Board Panel removed)
6 SERVICE DATA
[1] Appearance of Equipment
MAIN BOARD
Power source terminal block
Te rminal block for outdoor/indoor control wiring connection
F. C. BOARD
N. F. BOARD
Overcurrent relay <51C>
Magnetic contactor for compressor <52C>
Transformer
Te r minal block for defrosting signal
Relay for defrosting signal receiving <X1>
• PUH-P200MYA/P250MYA (with cover removed)
Outdoor unit heat exchanger
Compressor
Electrical parts box
Ball valve for refrigerant piping connection <Liquid side> Flare Ball valve for refrigerant piping connection <Gas side> Flange
Page 22
–20–
• PUH-P200MYA/P250MYA (Detail of machine room)
Accumulator
Electric expansion valve (LEV)
Thermistor <Discharge temp.> TH2
Thermistor <Condenser/evaporator temp.> TH3
(At the back of the heat exchanger panel (header cover). When this screw is removed, the header cover is removed.)
Thermistor <Liquid temp.> TH1
4-way valve
Pressure switch
(63H2)
Pressure switch
(63H1)
Solenoid valve(SV1)
Pressure switch (63L)
Check joint (low pressure)
Check joint (high pressure)
Page 23
–21–
[2] Refrigerant Circuit
Flare connection
Flange connection
Brazing connection
Cooling operation
Heating operation
<
<
[3] Limitation of Refrigerant Piping Length
PUH-P200,250
PUH-P200,250
PUH-P200,250
L 50 m H 40 m
L + a + b 70 m L + a, L + b 50 m a – b  ≤ 8 m H 40 m, h 1 m
L + a + b + c 70 m L + a, L + b, L + c 50 m a – b, b – c , c – a ≤ 8 m H 40 m, h 1 m
L + a + b + c + d 70 m L + a, L + b, L + c, L + d 50 m a – b , b – c , c – d,d – a 8 m H 40 m, h 1 m
(3) Triple
(1) Single (2) Twin
(4) Four
PUH-P200,250
*
* Two outdoor units must be connected when using PEH-P400·500MYA.
Total bends are 15 units, and max. bends are 8 units within L + a, L + b, L + c and L +
d.
Indoor units
Indoor heat exchanger
Outdoor unit
Service port
Ball valve
Strainer
Service port
Low pressure switch (Protection)
Solenoid valve
Strainer
High pressure switch (Protection)
High pressure switch (Control)
Muffler
Outdoor heat exchanger
Service port
Accumulator
Service port
Strainer
Multiple-distributor
Ball valve
H
L
Compressor
a
h
H
Electric expansion valve
Capillary tube
b
L
a
h
H
b
c
L
a
h
H
b
c
L
d
Page 24
–22–
[4] Refrigerant Piping
[5] Refrigerant Charge
Model Gas pipe Liquid pipe
PUH-P200MYA ø25.4 ø 12.7
PUH-P250MYA ø
28.58 ø 12.7
35, 50, 60, 71 ø 15.88 ø9.52
100, 125 ø19.05 ø 9.52
200
ø
25.4 (ø 12.7)
250
400
500
ø28.58
ø25.4 × 2 ø12.7 × 2
ø12.7 × 2
ø28.58 × 2
ø
12.7
Outdoor unit
Indoor unit
[6] Operation Rage
-5 46
Outdoor air temperature (°CDB)
24
15
Indoor air temperature (
°CWB)
-12 18
Outdoor air temperature (°CWB)
27
15
Indoor
air temperature (
°CDB)
Additional
* 1
refrigerant charge
0.026× L + 0.014 × (
a + b + c + d) + 1.7(kg)
Amount of refrigerant
at ex-factory
R407C 6.0 kg
R407C 6.5 kg
L: Main section actual length
a + b + c + d: Join section actual length
The value of calculation result at the second decimal place must be rounded up to the first decimal place.
(e.g. 2.22 kg must be rounded up to 2.3 kg) * 1 : For amount of total indoor units
Model
PUH-P200MYA
PUH-P250MYA
Cooling Heating
* 1
0.026× L + 0.014 × ( a + b + c + d) + 1.7(kg)
ø 9.52
* Use the reducer that is provided when using the size of the liquid pipe that is parenthesized in the table.
Page 25
–23–
7 CONTROL
[1] Composition of Control
1.
Function block diagram
3N~ 380/400/415 V 50 Hz
outdoor
indoor
Electrical
terminal block
Indoor/outdoor
connection terminal
Indoor/outdoor
connection terminal
block
block
Fuse
Fuse
Fuse
Transformer
microcomputer
Communication
circuit
DC/DC
converter
LED1
<Power>
DC5V for
12V
Magnetic
contractor
Fuse
Semiconductor relay
Fan control
Over current relay
4-way valve, LEV, solenoid valve, crankcase heater
Outdoor fan
Semiconductor relay
Compressor
Louver
Vane
Drain pump
Others
Remote
controller
terminal block
Remote controller
terminal block
Remote controller
Current
detection
LED2 LED3
<Supply power>
DC5V
5V
<Indoor/outdoor units communication>
Key input
LCD
Send/receive
Communication
circuit
Fan control
Indoor fan
Page 26
–24–
[2] Control specifications
(1) Protection functions
1) The main protection devices for the outdoor unit are: a) High pressure protection (63H1) b) Compressor overcurrent protection (51C) c) Liquid temp thermistor trouble (TH1) d) Discharge temperature protection (TH2 118 °C) e) Discharge temp thermistor trouble (TH2) f) Condenser/evaporater temp thermistor trouble (TH3) g) Low pressure protection (63L)
2) When tripping of a detection device is sensed, the check mode is entered and the compressor is stopped. (After 3 minutes, the compressor restarts.) Thereafter, the compressor is stopped when the specified number of check modes or greater is sensed within the check time.
3) Check mode is released by stopping operation, changing the operation mode, or check mode time up. A check mode is also released by stopping of operation by remote controller.
4) Detected check mode history (newest) and abnormality history (last 2 times) are memorized and are displayed on the segment by circuit board DIP switch setting. The operation mode when the newest abnormality was generated, the thermistor temperature (TH1,2,3), and the thermostat ON time can also be displayed.
(2) Compressor, 4-way valve, and crankcase heater control
1) Determines the operation mode and operates the compressor based on the indoor/outdoor communication or M­NET communication data.
2) Compressor control has a function which prevents the compressor from restarting within 3 minutes.
3) The 4-way valve is always ON during heating (except during defrosting). In other modes, it is OFF. However, when the operation mode was changed from heating to stop, the 4-way valve is turned off 10 minutes after the compres­sor was stopped.
4) While the compressor is stopped, the crankcase heater remains ON. (OFF while the compressor is operating.)
5) When the operation mode is changed while the compressor is operating, the compressor stops and 3 minutes later restarts in the new mode.
Protection functions
a) High pressure protection
(63H1)
b) Compressor overcurrent
protection (51C)
c) Liquid temp thermistor
trouble (TH1)
d) Discharge temperature
protection (TH2
118 °C)
e) Discharge temp ther-
mistor trouble (TH2)
f) Condenser/evaporater
temp thermistor trouble (TH3)
g) Low pressure protection
(63L)
Operation value
3.3 MPa
P200MYA: 22 A P250MYA: 27 A
Less than -39 °C or greater than 88 °C
Greater than 118 °C
Less than 0 °C or greater than 216 °C
Less than -39 °C or greater than 88 °C
0 MPa
Detection condition
Compressor operating
Compressor operating
Compressor operating except for 10 minutes at end of defrosting and 7 minutes while compressor starting
Compressor operating
Compressor operating except for 10 minutes at end of defrosting and 5 minutes while compressor starting Compressor operating except for 10 minutes at end of defrosting and 7 minutes while compressor starting Compressor operating except for defrosting, 10 minutes at end of defrosting
Number of
check modes
0
1 time
1 time
2 times
1 time
1 time
2 times
Check time
30 minutes
30 minutes
30 minutes
30 minutes
30 minutes
30 minutes
> =
Page 27
–25–
(3) Fan control
Controls the fan speed based on the piping temperature (TH1) to perform cooling at low outdoor temperatures and heating at high outdoor temperatures.
1) Control at cooling a) When the compressor stops, the fan stops (fan output=0%). b) When the power is turned on, or when the compressor is restated after it has been stopped for 30 minutes or
longer, the piping temperature ( TH1) determines the fan output.
When TH 25˚C Fan output = 100 % When TH < 25˚C Fan output = 60 %
c) When the compressor is restarted within 30 minutes after it has been stopped, the fan step before the compres-
sor was stopped is selected. However, when the fan output was under 30% when the fan was stopped, 30% is
selected. d) When the mode was changed from heating to cooling, the fan step conforms to item 2. e) Two minutes after the fan is started, the fan step (number of units) is controlled every 30 seconds based on the
piping temperature (TH1). f) When TH1 reaches 50˚C or higher, or when the control high pressure switch (63H2) tripped, the fan output
becomes 100%. g) Fan output while the compressor is operating is within the 20% to 100% range.
•FAN step The following expression determines the next fan step count nj+1: nj + 1 = nj + nj nj: Current fan step, nj: Displacement step amount nj control
• If nj + 1 100% nj + 1 = 100%
• If nj + 1 20% nj + 1 = 20%
• If TH1 50 °C or 63H2 is “OFF” nj + 1=100%
FAN nj Outputs are all %.
* In the night mode, the maximum value of nj is 80%. (When TH1 < 50˚C)
Target condensation temperature 31 °C
Condensation temperature TH1
20 nj < 50 50 ≤≤ nj 100
Current
output
t > 49 °C
5
10
t = 49
t > 46
3
4
~
~
~
~
~
~
~
~
~
t = 46
t > 43
2
3
t = 43
t > 40
2
2
t = 40
t > 36
2
2
t = 36
t > 33
2
2
t = 33
t > 29
0
0
t = 29
t > 26
-2
-2
t = 26
t > 23
-2
-2
t = 23
t > 20
20
-3
-4
t
20 ˚C
-5
-10
Page 28
–26–
T = 17
T > 15
-3
~
~
~
~
~
~
~
~
~
2) Control at heating a) When the compressor is stopped and during defrosting, the fan is stopped. b) When the power is turned on, or when the compressor is restarted after being stopped for 30 minutes or longer,
the piping temperature (TH1) determines the fan step.
TH1 > 8˚C Fan output = 60% TH1 8˚C Fan output = 100%
c) When the compressor is restarted within 30 minutes, the fan step is the step before the compressor was stopped. d) When the mode is changed from cooling to heating, the fan step conforms to item b). e) When returning from defrosting, the fan step is the step before defrosting. f) Two minutes after the fan was restarted, the fan step is controlled every 30 seconds based on the piping
temperature (TH1).
g) When TH1 is -5˚C or lower, the fan output is made 100%.
•FAN step The following expression determines the next fan step count nj + 1: nj + 1 = nj + nj nj: Current fan step, nj: Displacement step amount nj control
• If nj + 1 100% nj + 1 = 100%
• If nj + 1 20% nj + 1 = 20%
• If TH1 < -5 °C nj + 1=100%
FAN nj Outputs are all %.
(4) Defrosting control
1) When the following conditions are satisfied, defrosting starts: a) When the integrated compressor operation time has exceeded T
1 (initial setting 50 minutes) and the piping
temperature (TH1) is below -10˚C
b) When the integrated compressor ˚C
Piping differential temperature TH1 = TH10 - TH1
2) The defrosting prohibit time T
1 is set as following based on the defrosting time T2:
Note: T
1 is reset at the end of defrosting, or by cooling ON command.
Note: When the compressor was stopped during defrosting, T1 = 20 minutes is set to recognize the stop as
defrosting end.
3) During defrosting, all the outdoor fans are stopped and the bypass solenoid valve (SV1) is turned ON and the 4-way valve (21S4) is turned OFF.
4) When the following conditions are satisfied, defrosting ends: a) T
2 2 mins TH1 30°C
b) 2 < T
2 < 15 minutes TH1 ≤ 8°C continuous 2 minutes
c) T
2 =15 minutes
5) When
6) When using PEH-P400·500MYA, alternate defrosting is possible after sending and receiving each respective outdoor unit defrost signal.
the fan and 4-way valve (21S4) are turned ON at the end of defrosting, the heating mode is reset. Two
minutes after defrosting reset, the bypass solenoid valve (SV1) turns OFF.
Target evaporation temperature 10 °C
Evaporation temperature TH1
20 nj + 1 100
Current
output
T > 19 °C
-10
T = 19
T > 17
-4
T = 15
T > 13
-2
T = 13
T > 11
-2
T = 11
T > 8
0
T = 8
T > 6
2
T = 6
T > 4
2
T = 4
T > 2
3
T = 2
T > 0
4
T 0˚C
10
Current piping temperature
Piping temperature 10 minutes after starting or 10 minutes after returning from defrosting
T
2 3 (minutes) T1 60 (minutes)
3 < T2 < 15 40 T
2
= 15
30
Page 29
–27–
(6) Electronic expansion valve (LEV)
1) Initial processing after power turned on
After the power is turned on, full close processing is performed as initial drive processing. a) A 2200 pulses down is output from power on. b) At the end of 2200 pulse down output, 60 pulses up is output. c) Sixty pulses up output ends initial processing. At this point, the valves are fully closed.
2) Control contents
3) Normal LEV control
a) The operation frequency when the compressor is started (including after defrosting reset) determines the stan-
dard opening angle.
b) After a) above, sub cool (SC) shown below controls the LEV opening angle.
<Definition of SC> Cooling: SC = TH3 (outdoor unit)-TH1 (outdoor unit) Heating: SC = TH5 (indoor unit)-TH2 (indoor unit) * When there are multiple indoor units, the value of TH2 and TH5 is the average value of TH2 and TH5 of all
the indoor units. <LEV control> LEV is controlled so that SC is equal to SCm. SC < SCm: LEV opening angle is made smaller SC > SCm: LEV opening angle is made larger SC = SCm: LEV opening angle remains unchanged SCm = 5~15 (SCm is different with Indoor Units.)
4) Transient LEV control a) When outlet temperature (outdoor unit TH2) rises
When the outlet temperature (outdoor unit TH2) exceeds 115 °C, the LEV opening angle is made larger.
(7) Service functions
1) Abnormality history clear
a) When DIP SW1-2 is turned ON while the compressor is operating or stopped, the abnormality history is cleared.
(5) Bypass solenoid valve control (SV1)
1) Control at cooling
a) While the compressor is stopped, the solenoid valve is OFF. b) When the power is turned on, or when the compressor is restarted after it has been stopped for 30 minutes or
longer, if the liquid temperature (TH1) is 25˚C or higher then the solenoid valve turns ON for 2 minutes.
c) When the power is turned on, or when the compressor restarted after it has been stopped for 30 minutes or
longer, the solenoid valve turns ON for 5 minutes if the liquid temperature (TH1) is staying below 25˚C. d) The item b) or c) is applied to the mode change from heating to cooling. e) When the previous operation mode is cooling and the compressor restarted within 30 minutes after it’s stopping
by the tripping of 63H2, the solenoid valve turns ON for 2 minutes.
2) Control at heating a) While the compressor is stopped, the solenoid valve is OFF. b) When the power is turned on, or when the compressor restarted after it has been stopped for 30 minutes or
longer, the solenoid valve turns ON for 2 minutes if the liquid temperature (TH1) is staying above 8˚C.
c) When the power is turned on, or when the compressor restarted after it has been stopped for 30 minutes or
longer, the solenoid valve turns ON for 5 minutes if the liquid temperature (TH1) is staying below 8˚C. d) The item b) or c) is applied to the mode change from cooling to heating. e) When the control pressure switch (63H2) trips, the solenoid valve turns ON. f) If 63H2 resets 15 minutes after tripping, the solenoid valve turns OFF. g) During defrosting, the solenoid valve turns ON. h) When the previous operation mode is heating and the compressor restarted within 30 minutes after it’s stopping
by the tripping of 63H2, the solenoid valve turns ON for 2 minutes. i) When the previous operation mode is heating, and the compressor restarted within 30 minutes after the tripping
of 63L, the solenoid valve turns ON for 2 minutes.
At compressor starting At compressor stopping At defrosting Normal
LEV output opening angle
Initial opening angle
1000 pulses
2000 pulses (full close)
See next item
Opening angle control range
Approx. 1000 to 2000 pulses
– –
1000 to 1500 pulses
Page 30
–28–
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
OFF
ON
123456
01234
56789
10 11 12 13 14
15
[3] Function of switches and connectors (outdoor unit)
(1) Function of switches
1) Function of switches (Normal mode)
Switch
SW1 CN33 When
open
(Normal)
SW2
SW3
SW4
SW5
Switch effec-
tive timing
Running or
stopped
When power
turned on
Running or
stopped
stopped
stopped*
1
stopped
When power
turned on
When power
turned on
Operation by switch operation
ON OFF
––
Clear Normal
See pages 29 to 34.
Register Normal
Operate Stop
Heat Cool
Do Do not
Do not Do
Cooling only Heat pump
PUH-P250MYA PUH-P200MYA
Normal mode
SW3 = Unrelated
Kind of
switch
DIP SW
Tact SW
DIP SW
DIP SW
Pole
1
2
3
4
5
6
1 2 3 4 5 6
1 2 1
2
3
4
Function
None
Abnormality history clear
Refrigerant system
address setting
Self diagnosis
Mode input register
Trial run
Trial run mode switching
Inlet temp. re-reading
3-phase power source
detection
Cooling only switching
Model setting
Remarks
Function
None
Night mode
Defrosting end switching
Defrosting prohibit time
switching
None
Switch effec-
tive
timing
stopped
stopped
stopped
Switch
SW1 When CN33
shorted
(mode
switching)
Operation by switch operation
ON OFF
––
Night mode Normal mode
Fixed Training
––
Kind of
switch
DIP SW
Pole
1 2 3
4
5
6
*1 Trial run performs trail run processing by input change while stopped. (For details, see the trail run section) *2 Mode input is entered by SW3 OFFON change (___↑). Press and hold down SW3 for about 2 seconds. The set
mode can be registered according to the outdoor unit setting information on page 31.
2) Switch functions at set mode change
Note: After changing the mode by CN33 shorting (mode switching), return to the normal mode by opening CN33.
3) Connector function assignment
12 °C continuous 2 min­utes
8 °C continuous 2 min­utes
Set input mode
CN33 = short SW3 = ON*
2
Shows that Nos. 3, 4, 5 , and 6 of SW1 are ON.
Type
Connector
Connector
CN31 CN32 CN33
Function
Emergency operation
Function test
DIP switch mode switching
Operation by open/short
short open
Start Normal
Function mode Normal
Mode switching Normal
Switch effec-
tive timing
At initialization At initialization
stopped
Page 31
–29–
Display Check unit
0 Outdoor unit 1 Indoor unit 1 2 Indoor unit 2 3 Indoor unit 3 4 Indoor unit 4
Display Compressor 4-way valve Bypass solenoid valve
0– – 1– ON 2– ON – 3– ON ON 4ON – 5ON ON 6ON ON – 7ON ON ON
<Outdoor unit operation monitoring function>
The operation status and check code contents can be ascertained by means of the 2-digit number and symbol on digital display light emitting diode LED2 by operating DIP switch SW2.
<Description of operation of digital display light emitting diode (LED2)>
• When ON (normal operation): Displays the operation mode.
• When blinking (Operation stopped by tripping protection device): Displays the check mode
[Tens digit: Operation mode]
Display Operation mode
O stopped C Cooling/Dry H Heating
d Defrost
[Units digit: Relay output]
PUH-P8MYA/P10MYA
Display Check contents (at power on)
E8 Indoor-outdoor communication receive abnormal (outdoor unit) E9 Indoor-outdoor communication send abnormal (outdoor unit)
EA
Indoor/outdoor connection erroneous wiring, number of indoor units mismatch
Eb
Indoor/outdoor connection erroneous wiring (indoor unit power failure, disconnection)
Ed Serial communication abnormal (M-NET)
E0-E7 Communication other than outdoor unit abnormal
F8 Input circuit faulty
Display Check contents (operating)
U2 Compressor discharge temperature abnormal, CN23 short-circuit connector unplugged U3 Compressor discharge temp thermistor (TH2) open/short U4 Liquid temp thermistor (TH1), Condenser/evaporater temp thermistor (TH3) open/short U6 Compressor overcurrent protection trip (51C trip)
UE High pressure protection (63H1 trip)
UL Low pressure protection (63L trip) P1-P8 Indoor unit abnormal A0-A8 M-NET communication abnormal
SW2
LED2
ON
12 3 4 5 6
ON
OFF
(Load status)
Page 32
–30–
°C
°C
%
100 times
10 hours
5 pulses
Check mode 1 display method
bit 1 ..... Compressor discharge temperature
abnormal
bit 2 ..... Compressor discharge temp thermistor
abnormal (TH2)
bit 3 ..... CN23 short-circuit connector un-
plugged
bit 5 ..... Liquid temp thermistor abnormal (TH1)
SW2 setting Display contents Description of display Unit
Liquid temperature (TH1)
-39 ~88
-39 ~88
Discharge tempera­ture (TH2) 0 ~
~
~
~
~
216
FAN output 0 100
Number of compressor ON/OFF 0 999
~
~
0 999
~ ~ 0 999
~ 0 999
Compressor inte­grated operation time
Current check mode code 1
Current check mode code 2
LEV opening angle (/5) 0 400
(When 0 °C or lower, “–”and temperature are displayed alternately.) <Example> When -10,
every other second –
←→ 10
0 216 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 115,
every other second 1
←→ 15
0 100 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 100,
every other second 1
←→ 00
(When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 425,
every other second 4
←→ 25
(When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 245,
every other second 2
←→ 45
Check mode segment display method Segment and bit correspon­dence
Check mode 2 display method
bit 1 ..... Overcurrent trip (Comp)
bit 2 ..... Low pressure protection
0 400 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 200 ,
every other second 2
←→ 00
Self diagnosis by SW2
• PUH-P200MYA/P250MYA
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
bit 2 bit 3
bit 1
bit 5
bit 6 bit 7
bit 4
bit 8
Page 33
–31–
Newest check code Newest outdoor unit abnormality Check display
Operation mode when abnormality occurred
Liquid temperature (TH1) when abnor­mality occurred
- 39 ~
~
~
88
- 39 ~ 88
COMP discharge temperature (TH2) when abnormality occurred 0 216
Check code history (1) (newest) Abnormal unit No. and check code inverted display
Check code history (2) (One before newest) Abnormal unit No. and check code inverted display
Current thermostat ON time 0 999
Number of indoor units connected 0 4
When no check mode,“00” <Example> When piping thermistor abnormal U4
Operation mode when abnormally stopped <Example> Comp. only ON at cooling operation C4
(When 0 °C or lower, “–” and temperature are displayed alternately.) <Example> When -15,
every other second –
←→ 15
0 216 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 130,
every other second 1
←→ 30
When no abnormality history “0”, “←→”, “–”
When no abnormality history “0”, “←→”, “–”
0 999 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 245,
every other second 2
←→ 45
0 4
Code display
Code display
°C
°C
Code display
Code display
Minutes
Units
SW2 setting Display contents
Description of display
Unit
1 23456
ON
OFF
123 456
ON
OFF
123 456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
123 456
ON
OFF
~
~
~
~
Page 34
–32–
Outdoor unit capacity is displayed as function code.
Model name function code
PUH-P200MYA 20 PUH-P250MYA 25
-39 88
-39 88
-39 88
-39 88
-39 88
-39 88
-39 88
-39 88
(When 0 °C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
(When 0 °C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
(When 0 °C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
(When 0 °C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
8 39.5
8 39.5
When there are no indoor units, “00” is displayed.
17 30
17 30
When there are no indoor units, “00” is displayed.
Outdoor unit set information 1
Outdoor unit set information 2
Indoor unit piping temperature (TH2) Indoor 1
Indoor unit piping temperature (TH2) Indoor 2
Indoor unit piping temperature (TH2) Indoor 3
Indoor unit piping temperature (TH2) Indoor 4
Indoor intake tem­perature
Indoor set temperature
Code display
Code display
°C
°C
°C
°C
°C
°C
SW2 setting Display contents Description of display Unit
Outdoor unit set information 1 Function setting (display valves) 3-phase power source detection Do (1) Do not (0) Cooling only switching Cooling only (2) H/P (0) Night mode Night mode (1) Normal mode (0) Defrosting end time
12 °C continuous 2 minutes
(2)
8 °C continuous 2 minutes
(0)
Defrosting prohibit time Fixed (4) Training (0)
Tens digitUnits digit
Set information display values are added and displayed at each position.
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
~
~
~
~
~
~
~
~
~
~
~
~
Page 35
–33–
Indoor unit control status Indoor 1, 2
Indoor unit control status Indoor 3, 4
Condenser/evaporater temperature (TH3)
Outdoor unit control status
Discharge super heat SHd 0 216 Cooling: Outdoor TH2 -
Outdoor TH3
Heating: Outdoor TH2
- Indoor TH3 (Average)
Sub cool Sc 0 130 Cooling: Outdoor TH3
- Outdoor TH1
Heating: Indoor TH3
(Average) ­Indoor TH2 (Average)
Target sub cool step N 1 5
-39 88 (When 0 °C or lower, “–”and temperature are displayed alternately.) <Example> When -10,
every other second –
←→ 10
0 216 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 150,
every other second 1
←→ 50
0 130 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 100,
every other second 1
←→ 00
1 5
°C
°C
°C
SW2 setting Display contents Description of display Unit
Indoor unit No.1 Indoor unit No.3
Indoor unit No.2 Indoor unit No.4
Control mode
Indoor unit
Ordinary
Hot adjustment
Defrosting
Heater ON
Freeze prevention
Surge prevention
Compressor OFF
Display
0 1 2 3 4 5 6 7
Outdoor unit
← ← ← ← ← ← ← ←
Control mode display system
Control mode display system
Indoor unit No.1 Indoor unit No.3 Outdoor unit
Indoor unit No.2 Indoor unit No.4
Control mode
Indoor unit
Ordinary
Hot adjustment
Defrosting
Heater ON
Freeze prevention
Surge prevention Compressor OFF
Display
0 1 2 3 4 5 6 7
Outdoor unit
← ← ← ← ← ← ← ←
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
ON
OFF
~
~
~
~
~
~
~
Page 36
–34–
Communication de­mand capacity 0 255
Abnormal thermistor display 1 3, –
FAN output at abnor­mal stop 0 100
LEV opening angle (/5) at abnormal stop 0 400
Outdoor Condenser/ evaporater temp tem­perature at abnormal stop
-39 88
Discharge super heat SHd at abnormal stop 0 216 Cooling: Outdoor TH2-
Outdoor TH3
Heating: Outdoor TH2-
Indoor TH3 (average)
Sub cool Sc at abnor­mal stop 0 130 Cooling: Outdoor TH3-
Outdoor TH1
Heating: Indoor TH3
(average) -In­door TH2 (av­erage)
0 255 When communication demand not set: 100% (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 100,
every other second 1
1
←→ 00
1 3, – 1: Outdoor liquid temp thermistor (TH1) 2: Outdoor discharge temp thermistor (TH2) 3: Outdoor condenser/evaporater temp thermistor (TH3) –: No abnormal thermistor
0 100 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 100,
every other second
←→ 00
0 400 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 200,
every other second 2
←→ 00
-39 88 (When 0 °C or lower, “–”and temperature are displayed alternately.) <Example> When -10,
every other second –
←→ 10
0 216 (When 100 °C or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 150,
every other second
←→ 50
0 130 (When 100 °C or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 100,
every other second 1
1
←→ 00
%
%
5 pulses
°C
°C
°C
SW2 setting Display contents
Description of display
Unit
1 23456
ON
OFF
1 23456
ON
OFF
123456
ON
OFF
123456
ON
OFF
123456
ON
OFF
1 23456
ON
OFF
123456
ON
OFF
~
~
~
~
~
~
~
~
~
~
~
~
~
~
Page 37
–35–
Thermostat ON time up to abnormal stop 0 999
LEV regular control count n 1 5
Indoor unit condenser/ evaporater temp tem­perature (TH3) Indoor 1
Indoor unit condenser/ evaporater temp tem­perature (TH3) Indoor 2
Indoor unit condenser/ evaporater temp tem­perature (TH3) Indoor 3
Indoor unit condenser/ evaporater temp tem­perature (TH3) Indoor 4
0 999 (When 100 or higher, 100s digit and 10s and units digits are displayed alternately.) <Example> When 245,
every other second 2
←→ 45
1 5
-39 88
-39 88
-39 88
-39 88
-39 88
-39 88
-39 88
-39 88
(When 0 ˚C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
(When 0 ˚C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
(When 0 ˚C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
(When 0 ˚C or lower, “–”and temperature are displayed alternately.) When there are no indoor units, “00” is displayed.
Minutes
˚C
˚C
˚C
˚C
SW2 setting Display contents
Description of display
Unit
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
1 23456
ON
OFF
~
~
~
~
~
~
~
~
~
~
~
~
Page 38
–36–
[4] Simple parts check method
• PUH-P200MYA/P250MYA
Part name
Thermistor (TH1) <Liquid temperature detection> Thermistor (TH2) <Discharge temperature detection> Thermistor (TH3) <Condenser/ evaporater temperature detection>
Fan motor
Compressor
Thermal protector trip temperature 135 ±5˚C : ON 88 ±5˚C : OFF
Judgment instructions
Disconnect the connector and measure the resistance value with a multimeter. (Ambient temperature 10 ˚C to 30 ˚C)
Measure the resistance value across the terminals with a multimeter. (Winding temperature 20 ˚C)
Measure the resistance value across the terminals with a multimeter. (Winding temperature 20 ˚C)
Normal
4.3 k~9.6 k
160 k~410 k
Abnormal
Open or short
(Based on thermistor characteristic table (next page))
TH1, 3
TH2
White
Blue
Black
Normal
45.5
Abnormal
Open or short
Motor lead wire
Between 2 phases
Normal
PUH-P200MYA
Each phase 1.574
PUH-P250MYA
Each phase 1.263
Abnormal
Open or short
Open or short
Red
Page 39
–37–
[5] Reference Data
<Thermistor characteristic table>
Low temperature thermistor Thermistor <Liquid temperature detection> (TH1)
Thermistor <Condenser/evaporater temperature detection> (TH3)
Thermistor <Liquid temperature detection> (TH1) Thermistor <Condenser/evaporater temperature detection> (TH3) Thermistor Ro = 15 kΩ ± 3 % B constant = 3,460 kΩ ± 2 %
Rt = 15 exp {3,460 (–––––– – ––––)}
0 °C: 15 k 10 °C: 9.7 k 20 °C: 6.4 k 25 °C: 5.3 k 30 °C: 4.3 k 40 °C: 3.1 k
11
273 + t 273
Resistance
High temperature thermistor Thermistor <Discharge temperature detection> (TH2)
Thermistor (Discharge temperature detection) (TH2) Thermistor R120 = 7.465 kΩ ± 2 % B constant = 4,057 kΩ ± 2 %
Rt = 7.465 exp {4,057 (–––––– – ––––)}
20 °C: 250 k 70 °C: 34 k 30 °C: 160 k 80 °C: 24 k 40 °C: 104 k 90 °C: 17.5 k 50 °C: 70 k 100 °C: 13.0 k 60 °C: 48 k 110 °C: 9.8 k
11
273 + t 393
<Low temperature thermistor>
<High temperature thermistor>
Temperature
Resistance
Temperature
50
40
30
20
10
0
25
-20 -10 10 20 30 40 50 600
20
15
10
5
0
90 100 110 120
Page 40
–38–
[6] Troubleshooting of each part
(1) LEV
1) Overview of LEV operation LEV (electronic expansion valve) receives pulse signals from the outdoor unit main circuit board and drives a valve by means of a servomotor. The valve opening angle changes in proportion to the number of pulses. <Outdoor controller board and LEV>
<Pulse signal output and valve operation>
The output pulses change in the following order: Valve closing 1 → 2 → 3 → 4 → 1 Valve opening 4 → 3 → 2 → 1 → 4 *1. When the LEV opening angle is not changed, all output
phases turn OFF.
2. When the output misses a phase or remains ON, the mo­tor cannot rotate smoothly and makes a clacking sound and vibrates.
White
Red
Orange
Blue
Brown
Yellow
Brown
Red
Blue
Yellow
White
Connector Outdoor controller board CN40
Drive circuit
Output (phase)
No.
ø1 ø2 ø3 ø4
Output state
1234 ON OFF OFF ON ON ON OFF OFF
OFF ON ON OFF OFF OFF ON ON
LEV opening and closing operations
* When the power is turned on, to register the valve posi-
tion, a 2200 pulses valve close signal is output and is al­ways set to point A .
If the valve moves smoothly, the LEV will not generate a sound or vibration, but at E A and when the valve is locked, a sound louder than the sound generated by missing phase, etc. will be generated.
* Generation of sound can be checked by placing the tip of
a screwdriver against the valve and your ear against the handle.
Valve opening angle (flow)
Valve closing
Valve opening
Increased throttling region (80 - 100 pulses)
Full open 2000 pulses
Pulse count
D
C
A
E
B
Page 41
–39–
2) Judgment method and probable trouble mode
3) Electronic expansion valve motor replacement instructions
1. Description of construction
1.1 A lock nut connects the motor to the valve body.
1.2 The motor consists of a motor rotating section, rotation transmission gear section, and a driver which converts rotation to linear motion.
1.3 The valve body consists of a valve assembly, which moves up and down, and an orifice. A bellows at the top of the valve body block isolates the refrigerant circuit from the atmosphere side. Therefore, the motor is not exposed to the refrigerant.
2. Principle of operation
2.1 Pulses output from the control circuit board are sequentially supplied to four coils and the motor is rotated. The motor can be rotated in either clockwise or counterclockwise by changing the order in which the pulses are supplied.
2.2 The gear section reduces the motor speed to 1/30 and supplies the motor rotation to the motor output shaft.
2.3 The motor output shaft is threaded and is used as a driver.
2.4 The up and down motion of the end of the driver moves the valve assembly of the valve body up and down and controls the flow by changing the distance between the orifice and the bottom end of the valve.
Trouble mode
Microcomputer drive cir­cuit faulty
LEV mechanism locked
LEV motor coil open or shorted
Connector connection in­correct, or contact faulty
Judgment method
(1)Disconnect the control circuit board connector, and con-
nect the check LED shown below.
When the mains power is turned on, a pulse signal is out­put for 10 seconds. If the LED remains OFF or ON, the drive circuit is abnor­mal. (1)When the LEV is in the locked state and driven, the mo-
tor races. At this time, a soft clicking sound is generated. When this sound is generated both when closing and
when opening, the mechanism is abnormal. Measure the resistance between the coils (red-white, red­orange, brown-yellow, brown-blue) with a multimeter. If 150 Ω ±10%, the coil is normal. (1)Visually check for loose connector terminals and check
the color of the lead wires.
(2) Disconnect the control circuit board connector and
check the continuity with a multimeter.
Remedy
When drive circuit is faulty, re­place control circuit board.
Replace LEV
Replace LEV coil
Check continuity of faulty point
Valve assembly
Motor
Driver
Lock nut
Refrigerant circuit
V
alve
body
Orifice
Bellows
Page 42
–40–
3. Work precautions
3.1 Do not apply abnormal force to the motor.
3.2 Do not use a motor that has been dropped.
3.3 Do not remove the cap until immediately before start­ing work.
3.4 Do not wipe off the molybdenum.
3.5 Do not remove the packing.
3.6 Do not coat the lock nut with a substance other than the specified lock tight, grease, etc.
4. Replacement instructions
4.1 Stop the air conditioner from the remote controller. After confirming that the air conditioner has stopped, turn off the outdoor unit power.
4.2 Get two wrenches. Hold the flat part of the body with one wrench and loosen the lock nut with the other wrench. The lock nut loosens when turned counterclockwise as viewed from the motor. Always use two wrenches. Do not hold the motor with one hand and try to loosen the lock nut with only one wrench.
4.3 When the lock nut is turned several turns, it will disengage from the threads and the motor can be removed.
4.4 Get the replacement motor. The replacement motor is limited to a motor whose driver end position has been set at the factory for replacement use. (The driver end of factory set parts does not stick out.) Use of a motor whose driver end position is not set is related to erroneous valve flow control or no operation.
4.5 During replacement work, be sure that dirt, foreign matter, or water does not enter the part where the motor and valve body separate. (Since the part exposed by separation corresponds to the mechanical part of the valve.) Do not damage the connecting part with the tools. After removing the motor, 1
blow out the body bellows section with N2 gas, etc. to remove the water clinging to the inside and 2 after fan stop processing of the pertinent unit in the motor removed state, dry the bellows section by performing the cooling operation for 30 minutes.
4.6 Remove the cap of the replacement motor and butt the bottom of the motor against the top of the valve body and hold it so that both are aligned and connect the motor to the valve body with the lock nut.
Coat the entire periphery of the threaded part with screw lock. Be sure that the screw lock does not enter the interior. If a defect occurs during replacement work, do not use the motor, instead use a new replacement motor.
4.7 After tightening the lock nut 2 to 3 turns by hand, hold the flat part of the body with one wrench and tighten to the prescribed torque with a torque wrench. Tighten to a torque of 15N·m (150kgf·cm) (Control value 15 ±1N·m (150 ± 10 kgf·cm)) If tightened too tight, the flare nut may break during use.
4.8 When tightening the lock nut, hold the motor with your hand, etc. so that strong rotation torque and bending load are not applied.
4.9 The difference of the relative positions of the motor and body after assembly has no affect on the valve control and open/close mechanism. Do not try to forcefully position the motor and valve body to correct “displacement” after tightening of the lock nut due to the difference in the positional relationship between the motor and valve body before and after assembly.
Fixing with the clip may be impossible due to motor section defor­mation, but fixing of the piping is sufficient and fixing by clip is un­necessary.
4.10 Connect the connector. At this time, be sure not to pull the lead wires forcefully. Also, firmly insert the connector up to the lock and check that it cannot not be easily disconnected.
4.11Turn on the outdoor unit power and operate the air conditioner from the remote controller and confirm that there are no abnormalities.
Rotation direction “displacement” is OK.
Motor
Packing
Molybdenum
Cap
Page 43
–41–
[7] Emergency operation
1) When the following check displays occur at the outdoor unit, or when the wired remote controller or indoor unit microcomputer fails, if there are no other defects, emergency operation is possible by shorting the connector (CN31) on the outdoor controller board.
• Abnormalities that allow emergency operation
2) Check items and precautions when performing emergency operation a) In addition to the abnormalities above, check the outdoor unit for any abnormalities. (When there is an abnor-
mality other than the above, emergency operation is impossible.)
b) Check the operating range. (For U4 display)
Since the outdoor fan always operates at full speed at emergency operation, do not operate the air conditioner outside the range shown below.
Operation outside this range may cause com­pressor trouble.
c) When performing emergency operation, set the outdoor unit after setting the emergency operation switch (SWE)
on the indoor controller board. For the indoor emergency operation method, refer to the indoor unit wiring diagram.
d) A power failure causes emergency operation to become continuous operation. ON/OFF, temperature adjust-
ment and other operations cannot be performed from the remote controller. (When a PEH-RP200MYA or RP250MYA indoor unit is connected, check that the special indoor unit power is turned on, then start emergency operation.)
e) Since cool air is discharged from the indoor unit, when the outdoor unit starts the defrosting operation during
heating emergency operation, do not operate the air conditioner for a long time. f) You can perform cooling emergency operation up to 10 hours. The indoor unit heat exchanger may freeze. g) At the end of emergency operation, always return the switch settings, etc. to their original state.
3) Emergency operation contents a) The operation mode operates according to the contents set (cooling or heating) by SW4-2. b) The fan operation condition is always 100% operation. c) The operation mode display flashes every other second.
Display Check contents
U4
Liquid temp thermistor (TH1) open or shorted
Condenser/evaporater temp thermistor (TH3) open or shorted E8 Indoor-outdoor communication receive abnormal (outdoor unit) E9 Indoor-outdoor communication send abnormal (outdoor unit)
E0 - E7 Communication other than outdoor unit abnormal
Operation range (outdoor unit intake temperature)
Cooling geater than 20 °C
Heating less than 10 °
C
Page 44
–42–
4) Emergency operation method
* Before starting, recheck that the trouble allows
emergency operation.
*1 Only when PEH-RP200, RP250, P400, P500MYA indoor
unit connected.
*1. When PEH-RP200, RP250, P400, P500MYA indoor unit
is connected, first turn off the outdoor unit power, then turn off the indoor unit power.
5)
Emergency operation release method
Start
Piping work complete?
NO
YES
Check that mains power is OFF
Turn on emergency operation switch (SWE) on indoor controller board
Short CN31 (emergency operation connector) on outdoor controller board
Set operation mode (cooling or heating) with SW4-2 on outdoor board (SW4-1 not used)
SW4
OFF ON
1
Cooling Heating
2
Turn on indoor power *1
Turn on mains power
Check that emergency operation starts, and that operation mode display flashes
a)
Turn off mains power. (Outdoor, indoor) *1
b)
Turn off emergency operation switch (SWE) on indoor controller board
c)
Open CN31 (emergency operation connector) on outdoor controller board
d)
Set SW4-2 as shown below
SW4
e)
Turn on mains power
OFF ON
1
2
Page 45
–43–
[8] Self-diagnosis and troubleshooting
<Abnormality detected at power on>
Abnormal­ity display
None
EA
Eb
EC
F1
F2
Meaning of abnormality display and abnormality troubleshooting
Indoor/outdoor connection erro­neous wiring, too many indoor units (5 or more)
1. Outdoor controller board automati­cally recognizes the number of connected indoor units. However, when the number of connected in­door units cannot be set due to er­roneous indoor/outdoor connec­tion, erroneous wiring, etc. even after 4 minutes have elapsed since the power was turned on, an ab­normality is recognized.
2. When the outdoor controller board identified “5 or more” connected in­door units, an abnormality is rec­ognized.
Indoor/outdoor connection erro­neous wiring
The outdoor controller board auto­matically sets the unit No. of the in­door units. However, when the unit No. of the indoor units cannot be set due to indoor/outdoor connection er­roneous wiring even after 4 minutes has elapsed since the power was turned on, an abnormality is recog­nized.
Start-up time over
When start-up processing does not end even through 4 minutes has elapsed since the power was turned on, an abnormality is recognized.
Reverse phase detected
Missing phase detected
Cause
(1) Voltage not applied to outdoor unit ter-
minal block TB1.
a. Power supply circuit breaker not
closed.
b. Power supply terminals connection
faulty, or disconnected.
c. Missing phase (R or S phase)
(2) No electricity at controller board power
supply connector.
a. Power supply connector contact
faulty.
b. Te r minal R/1 or S/2 on controller
board disconnected.
(3) Outdoor unit controller board faulty.
a. Blown fuse on controller board. b. Part faulty.
(1) Indoor/outdoor connection wire con-
tact faulty or erroneous wiring.
(2) Indoor/outdoor connection wire diam-
eter or wiring length outside specifi­cation.
(3) Five or more indoor units connected
to outdoor unit.
(4) Outdoor controller board send/receive
circuit faulty.
(5) Indoor controller board send/receive
circuit faulty.
(6) Noise has entered on power supply
or indoor/outdoor connection wire.
(1) Indoor/outdoor connection wire con-
tact faulty, or erroneous wiring.
(2) Indoor/outdoor connection wire diam-
eter or wiring length outside specifi­cation.
(3) Outdoor controller board send/receive
circuit faulty.
(4) Indoor controller board send/receive
circuit faulty.
(5) Noise has entered on power supply
or indoor/outdoor connection wire.
(1) Indoor/outdoor connection wire con-
tact faulty.
(2) Indoor/outdoor connection wire diam-
eter or wiring length outside specifi­cation.
(3) Noise has entered on power supply
or indoor/outdoor connection wire.
Power supply reverse phase connection.
Power supply missing phase.
Judgment method and remedy
(1)
a. Check power supply circuit breaker. b. Check power supply terminal block
connections.
c. Check power supply terminal block
connections.
(2)
a. Check power supply connector board
connections.
(3)
a. Replace fuse. b. Replace controller board.
(However, when cannot be repaired even through the check above was carried out.)
(1) Check if indoor unit or outdoor unit in-
door/outdoor connection wire discon­nected or loose. Also check polarity.
(2) Check indoor/outdoor wire diameter
and wiring length. Outdoor-indoor: Max. 50m Indoor-indoor (span): Max. 30m Also check that VVF and other flat cables are connected in S1, S2, S3 or­der. (S2 in the middle)
(3) Check number of indoor units con-
nected to outdoor unit.
(4) Check by turning power off and on.
If abnormality is displayed again, re­place outdoor controller board or indoor controller board.
* LED3 of the indoor controller board
flashes when communication is being performed.
(1) Check power supply terminal block
connections.
(2) Replace controller board
(However, when cannot be repaired even though check above was carried out.)
Page 46
–44–
<Abnormality detected during unit operation: Outdoor unit>
Abnormal­ity display
U2
U3
U4
U6
UE
Meaning of abnormality display and abnormality troubleshooting
Discharge temperature abnormal
When the discharge thermistor tem­perature (TH2) exceeds 118 °C while the compressor is operating, an ab­normality is recognized.
49C trip (CN23 connector discon­nected)
When connector CN23 opens while the compressor is operating, an ab­normality is recognized.
Discharge temp thermistor (TH2) open or shorted.
When an open (0 °C or lower) or short (216 °C or higher) is detected while the compressor is operating, an abnormality is recognized. (Detection is disabled for 5 minutes at compressor starting.)
Liquid temp thermistor (TH1) or condenser/evaporater temp ther­mistor (TH3) open or shorted.
When an open (-39 °C or lower) or short (88 °C or higher) is detected while the compressor is operating, an abnormality is recognized. (Detection is disabled for 7 minutes beginning from 10 seconds after the compres­sor starts and for 10 minutes after return from defrosting.)
Compressor overcurrent trip
When the current value reaches the overload set value or higher while the compressor is operating, an abnor­mality is recognized.
P200MYA ..............................
..............................
22 A
P250MYA 27 A
High pressure abnormal (63H1 trip)
Detected (3.3
+0
-0.15
MPa) by 63H1 trip
while compressor is operating.
63H1: Pressure switch (high pres-
sure)
OFF: 3.3 MPa
Cause
(1) Compressor overheating due to insuf-
ficient refrigerant.
(2) Thermistor faulty. (TH2) (3) Outdoor controller board faulty.
(1) Shorting connector CN23 on outdoor
controller board dislodged or contact faulty.
(1) Connector (CN3) dislodged or con-
nect faulty.
(2) Thermistor faulty.
(3) Outdoor controller board faulty.
(1) Connector (TH1: CN2, TH3: CN4) dis-
lodged or contact faulty.
(2) Thermistor faulty.
(3) Outdoor controller board faulty.
(1) Overload operation exceeding unit us-
age range limit. (2) Power supply terminal voltage low. (3) Power supply missing phase. (4) Compressor motor faulty. (5) Compressor locked. (6) Connector (CN22) on outdoor control-
ler board dislodged or contact faulty. (7) 51C disconnected or contact faulty.
(1) Started with ball valve closed. (2) Connector (CN21) on outdoor control-
ler board dislodged or contact faulty. (3) 63H1 disconnected or contact faulty. (4) Indoor filter clogged. Power reset de-
tected during heating overload opera-
tion (Heating). (5) Low indoor unit air flow (heating). (6) Low outdoor unit air flow (cooling). (7) Part faulty.
Judgment method and remedy
(1) Check input super heat.
Check for refrigerant leakage and check piping length. Charge with additional refrigerant.
(2)(3)
Turn off power and restart operation and check if U3 is displayed within 8 minutes. When U3 is displayed, carry out U3 pro­cessing. (Do not replace board at U2 display only.)
(1) Repair shorting connector.
(1) Check connector contact and ther-
mistor wire.
(2) Check thermistor resistance value, or
check temperature by microcomputer. (Check using SW2 self-diagnosis func­tion.) See page 37.
(3) Replace outdoor controller board.
(Replace board after sufficiently check­ing 1 and 2.)
(1) Check connector contact and ther-
mistor wire.
(2) Check thermistor resistance value or
check temperature by microcomputer. (Check using SW2 self-diagnosis func­tion.) See to page 37.
(3) Replace outdoor controller board.
(Replace board after sufficiently check­ing 1 and 2)
(1) Check usage conditions.
(Check for short cycle operation.) (2) Check power supply voltage. (3) Check wiring for breaks and faulty con-
tact. (4) Check motor winding resistance (See
page 36.) (5) Replace compressor. (6)(7)
After checking connections, restart and
check operation.
(1) Check if ball valve is fully open. (2)(3)
Repair connector. (4) Check indoor filter. (5) Check flow duct static pressure and for
faulty fan motor. (6) Check for faulty outdoor fan motor. (7)
Replace pressure switch.
Page 47
–45–
Abnormal­ity display
UL
EO
E3
E8
E9
EF
Meaning of abnormality display and abnormality troubleshooting
Low pressure abnormal (63L trip)
Detected by tripping of 63L while the compressor is operating. (Ignored during defrosting and for 10 minutes at defrosting return.) 63L: Pressure switch (low pressure) OFF: 0 MPa
Remote controller communica­tions receive abnormal (remote controller).
1) When transmission from refriger­ant address “0” IC is not received normally even once in 3 minutes, an abnormality is recognized.
2) When a sub remote controller does not receive even one signal in 2 minutes, an abnormality is recognized.
Remote controller communication send abnormal (remote controller)
1) When the remote controller can not confirm that the transmission circuit is idle in 6 seconds, an ab­normality is recognized.
2) When the remote controller can­not complete 30 continuous trans­missions, an abnormality is rec­ognized.
Indoor-outdoor communication receive abnormal (Outdoor unit)
When the outdoor controller can not receive normally even once in 3 minutes, an abnormality is rec­ognized.
Indoor-outdoor communication send abnormal (Outdoor unit)
1) When the outdoor controller detectes reception of 30 consecu­tive “0” even through “1” was re­ceived, an abnormality is recog­nized.
2) When the outdoor controller can not confirm that the transmission circuit is idle in 3 minutes, an er­ror is recognized.
Check code undefined
Displayed when an undefined check code is received.
Cause
(1) Started with ball valve closed. (2) Connector (CN27) on outdoor control-
ler board open or contact faulty. (3) 63L disconnected or contact faulty. (4) Part faulty.
(1) Remote controller send/receive
circuit faulty. (2) Refrigerant address “0” indoor control-
ler board send/receive circuit faulty. (3) Noise entered on remote controller
transmission line.
(1) Remote controller send/receive circuit
faulty. (2) Noise entered on remote controller
transmission line.
(1) Indoor/outdoor connection wire con-
tact faulty. (2) Outdoor controller board send/receive
circuit faulty. (3) Indoor controller board send/receive
circuit faulty. (4) Noise entered on indoor/outdoor con-
nection wire.
(1) Outdoor controller board send/receive
circuit faulty. (2) Noise entered at power supply. (3) Noise entered on indoor/outdoor con-
nection wire.
(1) Noise entered on remote controller
transmission line. (2) Noise entered on indoor/outdoor con-
nection wire.
Judgment method and remedy
(1) Check if ball valve fully open. (2)(3) Repair connector.
(4) Replace pressure switch.
Perform remote controller diagnosis. Ta ke the following action based on the di­agnosed result: a) [RC OK] display
Remote controller normal. Turn power off and on and check. If “H0” remains on for 4 minutes or longer, replace indoor controller board.
b) [RC NG] display
Replace remote controller.
c) [RC E3] display
[ERC00-66]
(1) Check for disconnected or loose indoor
unit or outdoor unit indoor/outdoor con­nection wire.
(2)~(4)
Turn power off and on and check. If abnormality displayed again, replace indoor controller board or outdoor con­troller board.
(1)(2)(3)
Turn power off and on and check. If abnormality displayed again, replace indoor controller board or outdoor con­troller board.
(1)(2)
Turn power off and on and check. If abnormality displayed again, replace indoor controller board or outdoor con­troller board.
Noise, etc. probable
cause.
  
Page 48
–46–
<Abnormality detected during unit operation: Indoor unit>
Abnormal­ity display
P1
P2
P4
Meaning of abnormality display and abnormality troubleshooting
Intake sensor abnormal
1) If thermistor open or short is de­tected and the compressor enters the 3 minutes restart prevention mode and does not return to nor­mal after 3 minutes, an abnormal­ity is recognized. (If returned, returns to normal op­eration.)
2) Always detected during cool, dry, and heat operations. Short: 90 °C or higher Open: -40 °C or lower
Piping sensor abnormal
1) If thermistor short or open is de­tected and the compressor enters the 3 minutes restart prevention mode and does not return to nor­mal after 3 minutes, an abnormal­ity is recognized. (If returned, returns to normal op­eration.)
2) Always detected during cool, dry, and heat (except during defrost­ing) operation. Short: 90 °C or higher Open: -40 °C or lower
Drain sensor abnormal
1) If thermistor short or open continu­ously detected for 30 seconds, the compressor enters the check mode and turns off and the indoor fan turns off.
2) When another short or open is continuously detected for 30 sec­onds in the check mode, an ab­normality is recognized. (If returned, returns to normal op­eration.)
3) Always detected during cool, dry, and drain pump operation. Short: 90 °C or higher Open: -20 °C or lower
Cause
(1) Thermistor characteristics faulty. (2) Connector contact faulty.
(Insertion faulty)
(3) Thermistor wiring open or contact
faulty.
(4) Indoor controller board faulty.
(1) Thermistor characteristics faulty. (2) Connector contact faulty.
(Insertion faulty)
(3) Thermistor wiring open or contact
faulty.
(4) Faulty refrigerant circuit, etc. has
caused thermistor temperature to rise to 90 °C or higher or drop to -40 °C or lower.
(5) Indoor controller board faulty.
(1) Thermistor characteristics faulty. (2) Connector contact faulty.
(Insertion faulty)
(3) Drain sensor wiring open or contact
faulty.
(4) Indoor controller board faulty.
Judgment method and remedy
(1)~(3)
Check thermistor resistance value
0 °C ...... 15.0 k
10 °C ........ 9.7 k
20 °C ........ 6.4 k
30 °C ........ 5.3 k
40 °C ........ 3.1 k
Open or faulty contact can be detected by applying force (pulling, bending) to lead wire while measuring thermistor resistance.
(2) Check for connector faulty contact.
After reinserting connector, turn on power and recheck operation.
(4) Check remote controller room tempera-
ture display. If there is a difference between actual room temperature and displayed room temperature after checking that there are no problems at (1)~(3), replace in­door controller board. If there are no problems above, there are no abnormalities. Turn power off and on and operate.
(1)~(3)
Check thermistor resistance value. For characteristic, see above (P1).
(2) Check for connector faulty contact.
After reinserting connector, turn on power and recheck operation.
(4) Operate in trail run mode and check
piping temperature with remote control­ler. When piping temperature is abnor­mally low (cooling) or high (heating), refrigerant circuit is probably faulty.
(5) Check test run mode piping tempera-
ture with remote controller. If there is a difference between actual piping temperature and displayed pip­ing temperature when there are no ab­normalities at (1)~(4), replace indoor controller board. If there is no problem above, there are no abnormalities. Turn on power and operate.
(1)~(3)
Check thermistor resistance value.
0 °C .... 6.0 k
10 °C .... 3.9 k
20 °C .... 2.6 k
30 °C .... 1.8 k
40 °C .... 1.3 k
(2) Check connector for faulty contact.
After reinserting connector, turn on power and recheck operation.
(4) If abnormality reproduced by shorting
between drain sensor connector CN31 pins 1 and 2 and operating air condi­tioner, replace indoor controller board. If there are no problems above, there are no abnormalities. T
urn on power and operate.
Page 49
–47–
<Abnormality detected during unit operation: Indoor unit>
Abnormal­ity display
P5
P6
Meaning of abnormality display and abnormality troubleshooting
Drain overflow protection opera­tion
1) When the drain sensor thermistor overheats and the temperature rise is small, the compressor en­ters the check mode and is turned off and the indoor fan is turned off.
2) If the state above is detected again in the check mode, drain pump abnormality is recognized.
3) Always detected during drain pump operation.
Water leakage abnormality (PDH only)
1) When the drain sensor thermistor overheats and the temperature rise is small, the compressor en­ters the check mode and the drain pump is turned on for 6 minutes. (Detection: 1 time/hour)
2) If the state above is detected again within 12 hours after the check mode was entered, a wa­ter leakage abnormality is recog­nized.
3) Detected during stop, fan, and heat operation.
Freezing/excessive rise protection operation
1) Freezing protection When the piping temperature re­mains at -15 °C or lower for 3 min­utes after 3 minutes have elapsed since the compressor started, the compressor enters the 6 minutes restart prohibit mode and if the piping temperature again remains at -15 °C for 3 minutes within 16 minutes after 6 minutes restarting, an abnormality is recognized.
2) Excessive rise protection When a piping temperature rise to 70 °C or higher is detected af­ter the compressor starts, the compressor enters the 6 minutes restart prohibit mode. If a piping temperature rise up to 70 °C or higher is detected again within 10 minutes after 6 minutes restarting, an abnormality is recognized.
Cause
(1) Drain pump trouble. (2) Drain faulty.
Drain pump clogged. Drain pipe clogged.
(3) Water droplets on drain sensor.
Drain water waves created by trans­mission of drain water from lead wire, clogged filter, etc.
(4) Indoor controller board faulty.
(1) Water leaking from humidifier water
supply pipe. (2) Water droplets on drain sensor. (3) Indoor controller board faulty.
<Cool and dry> (1) Filter is clogged (insufficient air flow). (2) Air duct short cycle. (3) Low load operation (low temperature)
exceeding allowable range. (4) Indoor fan motor faulty. (5) Outdoor fan control faulty (intermedi-
ate period, winter). (6) Refrigerant overcharged. (7) Refrigerant circuit faulty (clogged).
<Heat> (1) Filter clogged (insufficient air flow) (2) Air duct short cycle. (3) Overload operation (high tempera-
ture) exceeding allowable range. (4) Indoor fan motor faulty. (5) Outdoor fan control faulty (intermedi-
ate period) (6) Refrigerant overcharged. (7) Refrigerant circuit faulty (clogged) (8) Outdoor unit bypass circuit faulty.
Judgment method and remedy
(1) Check drain up mechanism. (2) Check drain characteristic. (3) Check drain sensor lead wire arrange-
ment and check for filter clogging.
(4) If abnormality reproduced by shorting
between drain sensor connector CN31 pins 1 and 2 and operating air condi­tioner, replace indoor controller board. If there are no problems above, there are no abnormalities. Turn on the power and operate.
(1) Repair water leakage. (2) Check drain sensor lead wire arrange-
ment and check for filter clogging.
(3) If abnormality reproduced by shorting
between drain sensor connector CN31 pins 1 and 2 and operating air condi­tioner, replace indoor controller board. If there are no problems above, there are no abnormalities. Turn on power and operate.
<Cool and dry> (1) Check filter for clogging. (2) Remove obstruction. (4) Check fan motor operation and wind-
ing resistance. (5) Check outdoor fan motor operation. (6)(7)
Check refrigerant circuit operation.
<Heat> (1) Check filter for clogging. (2) Remove obstruction. (4) Check fan motor operation and wind-
ing resistance. (5) Check outdoor fan motor operation. (6)~(8)
Check refrigerant circuit operation.
Page 50
–48–
<Abnormality detected during unit operation: Indoor unit>
Abnormal­ity display
P8
E4
Meaning of abnormality display and abnormality troubleshooting
Piping temperature abnormal
<Cool> When the piping temperature stays outside the cooling area for 1 minute after 3 minutes have elapsed since the compressor was started, the in­door fan operates at low speed. If the piping temperature does not return to the cooling area after 5 minutes operation at low speed, an abnormal­ity is recognized. Note 1) It takes a minimum of 9 min-
utes for an abnormality to be detected.
Note 2) At dry operation, P8 abnor-
mality is not detected. <Heat> When the piping temperature falls outside the heating area and enters the ventilation area after compressor operation and the end of hot adjust, the indoor fan stops and the piping temperature does not return to the heating area within 20 minutes after 10 seconds have elapsed after it left the heating area, an abnormality is recognized. Note 3) It takes a minimum of 22
minutes and a maximum of
27 minutes for an abnormal-
ity to be detected. Note 4) Except during defrosting
(Detected again after de-
frosting return.)
Remote control communication re­ceive abnormal
1) When the indoor controller board
can not receive data normally from the remote controller or an­other indoor controller board even once in 3 minutes, an abnormal­ity is recognized.
2) When the indoor controller board
can not receive signals even once in 2 minutes, an abnormality is recognized.
Cause
(1) Indoor intake piping thermistor tem-
perature differential small.
- EInsufficient refrigerant
- EPiping thermistor holder dislodged.
- ERefrigerant circuit faulty.
(2) Extension piping (When multiple units
connected).
(3) Indoor/outdoor connection wire
(When multiple units connected).
(4) Indoor intake piping thermistor detec-
tion faulty.
(1) Remote controller transmission line
contact faulty.
(2) All remote controllers set as “sub”
remote controller.
(3) Remote controller send/receive circuit
faulty.
(4) Indoor controller board send/receive
circuit faulty.
(5) Noise entered on remote controller
transmission line.
Judgment method and remedy
(1) Operate in test run mode and check
piping temperature.
(2)(3)
Check extension piping or indoor/out­door connection wire.
(4) Check remote controller room tempera-
ture display and piping temperature in test run mode.
(1) Check if indoor unit or remote control-
ler transmission line disconnected or loose.
(2) Set one remote controller as “main”.
When there are no problems at the
above (3) Perform remote controller diagnosis. a) [RC OK] display
Remote controller normal. Check by turning power off and on. If the abnormality occurs again, replace indoor controller board.
b) [RC NG] display
Replace remote controller.
c) [RC E3] display
[ERC00-66] noise, etc. is probable cause.
Page 51
Normal boot-up completed.
Normal boot-up completed.
Normal boot-up completed.
No error occurs, therefore no countermeasures
possible.
No error occurs, therefore no countermeasures
possible.
No error occurs, therefore no countermeasures
possible.
Normal stoppage
Normal stoppage
Normal stoppage
No power to remote controller and so
inoperable.
Error can be confirmed at outdoor unit LED.
(1) Repair cable C Communication error detected at No.1 and No.2
system indoor unit due to remote controller
error, however, no error reported at remote
controller as inoperable during stoppage.
The outdoor unit for address 00 is no longer
connected to the system, and operation is not
possible as there is no power supply to the
remote controller. Error can be confirmed at
outdoor unit LED.
(1) Repair cable A.
[Emergency Repair]
(1)
Set to the No.2 address 00 and cut the power
to the No.1 outdoor unit. (single system
operation.) Change No.1 address to 01.
The outdoor unit for address 00 is no longer
connected to the system, and operation is not
possible as there is no power supply to the
remote controller, resulting in an error.
Unable to boot up system No.2 and error
detected at both the outdoor and indoor unit,
however, the remote controller cannot be used
during the stoppage, and therefore no error is
indicated. Error can be confirmed at outdoor unit
LED.
(No.1 system has booted up and therefore
operation is possible.)
(1) Repair cable B.
[Emergency Repair]
(1) Cut power to outdoor unit No.2.
Single system operation.
Error detected at both No.2 outdoor and indoor
unit, however, the remote controller cannot be
used during the stoppage, and therefore no
error is indicated.
Communication error detected at No.2 system
indoor unit, however, no error reported at
remote controller when D breakage occurs.
Error can be confirmed at outdoor unit LED.
(No.1 system has booted up and therefore
operation is possible.)
(1) Repair cable D Communication error detected at No.2 system
indoor unit, however, no error reported at
remote controller when D breakage occurs. No.2
system cannot be operated.
No error occurs, therefore no countermeasures
possible.
No error occurs, therefore no countermeasures
possible.
No error occurs, therefore no countermeasures
possible.
(1) Repair cable C
(1) Repair cable A.
[Emergency Repair]
(1)
Set to the No.2 address 00 and cut the power
to the No.1 outdoor unit. (single system
operation.) Change No.1 address to 01.
(1) Repair cable B.
[Emergency Repair]
(1) Cut power to outdoor unit No.2.
Single system operation.
(1) Repair cable C
Error Details Recommended Countermeasure Error Details Recommended Countermeasure
No No.1 system stoppage.
No.2 system error stoppage.
Remote controller indicates error, however,
remote controller operation is not possible other
than at stoppage. (Fan stoppage.)
No No.1 system stoppage.
No.2 system error stoppage.
Remote controller indicates error, however,
remote controller operation is not possible other
than at stoppage. (No fan stoppage.)
No.1 system error stoppage.
No No.2 system stoppage.
Remote controller indicates error, however,
remote controller operation is not possible other
than at stoppage. (No fan stoppage.)
Correct cause of error.
Correct cause of error.
Correct cause of error.
Communication error detected at No.1 and No.2
system indoor unit due to remote controller
error, and all systems stopped.
(1) Repair cable C
The outdoor unit for address 00 is no longer
connected to the system, and operation is not
possible as there is no power supply to the
remote controller, resulting in an error.
(1) Repair cable A.
[Emergency Repair]
(1) Set to the No.2 address and cut the power to
the No.1 outdoor unit. (single system
operation.) Change No.1 address to 01.
Error occurred at both No.2 system outdoor and
indoor unit and error occurs at remote controller.
Operation can be continued as no error has
occurred at system No.1, however, remote
controller operation is not possible other than at
stoppage. (No fan stoppage.)
(1) Repair cable B.
[Emergency Repair]
(1) Cut power to outdoor unit No.2.
Single system operation.
Communication error detected at No.2 system
indoor unit, however, no error reported at
remote controller when D breakage occurs.
Communication error detected at No.2 system
indoor unit, resulting in stoppage.
(1) Repair cable C
Error Details Recommended Countermeasure
Prior to power ON to boot-up Stoppage (power supplied) During Operation
Cable A
breakage,
reverse
connection
Wiring Errors
Cable B
breakage,
reverse
connection
Cable C
breakage,
reverse
connection
Cable D
breakage,
reverse
connection
No.1 system
error
No.2 system
error
51F error
Refrigerant
Related Errors
A
B
C
D
D
BA
C
No. 1 system indoor/outdoor unit transmission cable.
No. 2 system indoor/outdoor unit transmission cable.
Remote controller cable for board No.1 (communication of operation and control details).
Cable connecting No.1 and No.2 board (communication of operation and control details)
* Error countermeasures for PEH-P400·500MYA
Remote controller
Indoor unit
No.2 board
Outdoor unit No.1
Address: 00
Outdoor unit No.2
Address: 01
No.1 board
:::
:
–49–
Page 52
–50–
<Troubleshooting and repair by symptom>
Symptom and operation when normal
1. No remote controller display
2. Remote controller displays “PLEASE WAIT” unchanged.
3. When remote controller operation switch pressed, operation display appears but immediately disap­pears.
4. Does not beep and air conditioner does not operate even when oper­ated with wireless remote control­ler. (Operation display appears on wire­less remote controller.)
5. When operated with wireless re­mote controller, beeps but does not operate.
6. Remote controller display is normal and cooling operation is performed, but without any capacity (does not cool).
Cause
(1) DC14V is not supplied to remote con-
troller. (No power O display on liquid crystal panel.)
(2) DC14V is supplied to remote controller
but nothing is displayed.
- “PLEASE WAIT” not displayed
- “PLEASE WAIT” displayed
(1) Remote controller displays “PLEASE
WAIT” for maximum of 2 minutes for starting after power turned on.
(2) Indoor-remote controller communication
faulty.
(3) Outdoor-indoor communication faulty.
(1) Operation switch is disabled for approxi-
mately 30 seconds after function select operation from remote controller is re­leased.
(1) Wireless remote controller and indoor
controller board pair number setting mis­matched.
(2) Cause of item 1.
(1) Air conditioner does not operate for a
maximum of 2 minutes after the power is turned on.
(2) Set to local operation prohibit mode.
- Remote start/stop adapter is con­nected to CN32 on indoor controller board.
- Air conditioner is connected to MELANS and is set to local operation prohibit mode from centralized control­ler, etc.
(3) Cause of item 2.
(1) Insufficient refrigerant. (2) Filter clogged. (3) Outdoor unit heat exchanger clogged. (4) Air duct short cycle. (5) Outdoor unit bypass circuit faulty.
Symptom judgment and remedy
(1) Check LED2 on indoor controller board.
1)Steady light Check remote controller wire open or faulty contact.
2)Flashing Check for remote controller wire short.
3)Not lit Check outdoor controller refrigerant address.
(2) Make the following judgment:
- When “PLEASE WAIT” is not displayed, remote controller is faulty.
-
When “PLEASE WAIT” is displayed, see item 2.
(1) Normal operation. (2) Remote controller self-diagnosis. (3) When outdoor-indoor cannot communicate
“PLEASE WAIT” is displayed for a maximum 6 minutes. Check LED3 on indoor controller board.
1) Does not flash
Check indoor/outdoor connection cable for erroneous wiring. (S1 and S2 or S3 open)
2) Flashes
Indoor/outdoor connection cable is normal.
(1) Normal operation.
(1) Check pair number setting. (2) Item check of item 1.
(1) Normal operation. (2) Normal operation. (3) Item check of item 2.
(1) - When there is leakage, discharge tempera-
ture rises. Therefore, check by measuring temperature.
- Check for gas leakage from piping connec­tions, etc.
(2) Open intake grille and check filter. Clean filter,
and remove dust and dirt.
(3) - Since both indoor piping temperature and
outlet pressure rise when filter clogged, judge by measuring outlet pressure.
- Clean heat exchanger. (4) Remove obstruction. (5)
Check refrigerant circuit operation state.
Page 53
–51–
Symptom and operation when normal
7. Remote controller display is normal and heating operation is performed
but without any capacity (does no
t
heat).
Cause
(1) Insufficient refrigerant. (2) Refrigerant piping heat insulation insuf-
ficient. (3) Filter clogged. (4) Indoor unit heat exchanger clogged. (5) Air duct short cycle. (6) Outdoor unit bypass circuit faulty.
Symptom judgment and remedy
(1) - Since the discharge temperature rises when
there is leakage, judge by measuring the tem­perature.
- Check piping connections, etc. for gas leak­age.
(2) Check heat insulation. (3) Open intake grille and check filter.
Clean filter, and remove dust and dirt.
(4) - Since the indoor piping temperature and out-
let pressure rise when the heat exchanger is clogged, judge by measuring the outlet pres­sure.
- Clean heat exchanger.
(5) Remove obstruction. (6)
Check refrigerant circuit operation state.
Page 54
–52–
Erroneous wiring contents Remarks
Normal
wiring
Open
between S1
Open
between S2
Open
between S3
Remote control-
ler display
“ ” Power
supply mark
No display
No display
No display
Eb
No display
No display
No display
No display
No display
No display
No display
No display
No display
No display
No display
Eb
<Indoor/outdoor connection wire erroneous wiring and open symptoms>
Condition
Trial run
(relocation)
Trial run
relocation
Trial run
relocation
Trial run
relocation
Trial run
relocation
Trial run
relocation
Trial run
relocation
Trial run
relocation
Trial run
relocation
Indoor controller board
LED display
Outdoor controller
board LED display
OO
EA
(after 4 minutes)
Eb
(after 4 minutes)
EA
(after 4 minutes)
Eb
(after 4 minutes)
EA
(after 4 minutes)
Eb
(after 4 minutes)
EA
(after 4 minutes)
Eb
(after 4 minutes)
EA
(after 4 minutes)
Eb
(after 4 minutes)
EA
(after 4 minutes)
Eb
(after 4 minutes)
EA
(after 4 minutes)
Eb
(after 4 minutes)
EA
(after 4 minutes)
Eb
(after 4 minutes)
LED1
On
Off
Off
On
On
Off
Off
On
Off
On
Off
Off
Off
Off
Off
On
On
LED2
On
Off
Off
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
LED3
Flashing
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Indoor
side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Outdoor side
S1 S2 S3
Page 55
–53–
The test run can be carried out either from the outdoor unit or the indoor unit.
1. Check list
• After the installation, piping setup, and wiring of the indoor and outdoor units is complete, check that refrigerant is not leaking, the power and control wires are not loose, and the poles are not reversed. (When connecting model PEH-(R)P-MYA in particular, check that there is current in the separate power supply cable for the indoor unit.)
• Use a 500 V insulation resistance tester to make sure that the resistance between the power terminal and the ground is
1.0 Mor more. If it is less than 1.0 M, do not operate the unit. * Absolutely do not touch the tester to indoor/outdoor connection terminals S1, S2, and S3. An accident could occur.
• Make sure there is no malfunction in the outdoor unit. (If there is a malfunction, you can diagnose it using LED1 on the board.)
• Check that the ball valve is fully open on both the liquid and gas ends.
• Check the electrical power phase. If the phase is reversed, the fan may rotate in the wrong direction or stop, or unusual sounds may be produced.
• Starting at least 12 hours before the test run, send current through the crankcase heater. (If the current is running for a shorter period of time, damage to the compressor could result.)
After the above checks are complete, carry out the test run as indicated in the following outline.
2. Starting and finishing the test run
• Procedure from the indoor unit: carry out the test run as in the manual provided with the indoor unit.
• Procedure from the outdoor unit: start and stop the test run and set test run mode (cooling/heating) using the SW4 dip switches on the board.
a) Set test run mode (cooling/heating) using SW 4-2. b) The test run will begin when SW 4-1 is turned ON, according to the mode selected by SW 4-2. c) The test run is stopped when SW 4-1 is turned OFF.
Note: Test run mode cannot be stopped during operation by using SW 4-2. (If the operation mode is to be changed, first stop it using SW 4-1, then after changing the operation mode, start the test run again using SW 4-1.)
• If the 2-hour timer is set, the test run will stop automatically after 2 hours.
• During the test run, the room temperature display on the indoor unit will indicate the temperature of the indoor unit piping.
8 Test run
(1) Test run (For PUH-P200MYA/P250MYA)
cooling
run
<SW4>
heating
ON
1 2
stop
OFF
Page 56
–54–
(2) How to handle problems with the test run (For PUH-P200MYA/P250MYA)
Error code list: details
Error details
Remote controller communication – reception error Remote controller communication – transmission error Remote controller communication – reception error Remote controller communication – transmission error Communication between indoor and outdoor units – reception error Communication between indoor and outdoor units – transmission error Communication between indoor and outdoor units – reception error Communication between indoor and outdoor units – transmission error Indoor/outdoor connection wiring error, indoor unit overload (5 units or more) Indoor/outdoor connection wiring error (interference, loose) Excessive time in use Serial communication error Serial communication error Reverse phase, out of phase verification Faulty input circuit Duplicated M-NET address setting M-NET error in PH/W transmission M-NET bus busy M-NET communication error with P transmission M-NET error – no ACK M-NET error- no response Undefined error code Outlet temperature error CN23 Short-circuit Connector Unplugged Open/short in discharge temp thermistor Open/short in liquid temp or condenser/evaporater temp thermistor Compressor overcurrent interruption (51C operation) High pressure error (63H1 operation) Low pressure error (63L operation) Power synchronous idle circuit error Inlet sensor error Piping sensor error Drain sensor error Drain overflow protector operation Water leak error (PDH only) Freeze prevention operation Surge prevention operation Piping temperature error
MELANS
display 6831,6834 6832,6833 6831,6834 6832,6833 6740,6843 6841,6842 6840,6843 6841,6842
6844
6845 6846 0403 0403 4103 4115 6600 6602 6603 6606 6607 6608
undefined
1102 1108 5104 5105 4101 1302 1300 4115 5101 5102 2503 2502 2500 1503 1504
1110
Remote control-
ler display
E0 E3 E4 E5 E6 E7 E8 E9
EA
EB EC ED EE
F1
F8
A0
A2
A3
A6
A7
A8 EF U2 U2 U3 U4 U6 UE UL
F8
P1
P2
P4
P5
P5
P6
P6
P8
Problem location
Remote Controller Remote Controller
Indoor unit Indoor unit Indoor unit
Indoor unit Outdoor unit Outdoor unit
Outdoor unit
Outdoor unit Outdoor unit Outdoor unit
M-NET board
Outdoor unit Outdoor unit
M-NET board M-NET board M-NET board M-NET board M-NET board M-NET board
– Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
Page 57
–55–
Item
Operation mode/relay output
Outdoor unit control condition
Indoor unit control condition
Indoor unit control condition
Error code history 1 Error code history 2
Display contents
tens place O: stop
C: cooling H: heating d: defrosting
units place 1: SV1 Relay output = SV1 + 21S4 + 52C
2: 21S4 4: 52C
Ex. During cooling mode, when 52C and
SV1 are ON: C5 When an error occurs, the error code and error signal (*1) are displayed in alternation. Control mode display system
The error code (ex. U8, UA) and error indicator (*1) are displayed in alter­nation.
• Depending on the position of the SW2 switch on the outdoor unit board, the segments light up to indicate the running condition of the unit and the particulars of the check code.
SW2 setting
123456 000000
011110
010110
110110
011100 111100
*1 Display system for error indicator
The indicator corresponds to the following numbers
0 .......... Outdoor unit
1 .......... Indoor unit No.1
2 .......... Indoor unit No.2
3 .......... Indoor unit No.3
4 .......... Indoor unit No.4
Indoor unit No.1 Indoor unit No.3 Outdoor unit
Indoor unit No.2 Indoor unit No.4
(IC1) (IC2)
Control mode
Indoor unit
Ordinary
Hot adjustment
Defrosting
Heater ON
Freeze prevention
Surge prevention Compressor OFF
Display
0 1 2 3 4 5 6 7
Outdoor unit
(IC3) (IC4)
Page 58
New publication, effective Sep.2005
Specifications subject to change without notice.
The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series 9000 of the International Standard Organization (ISO) based on a review of quality warranties for the production of refrigeration and air conditioning equipment.
ISO Authorization System The ISO 9000 series is a plant authorization system relating to quality warranties as stipu­lated by the ISO. ISO 9001 certifies quality warranties based on the “design, development, production, installation and auxiliary services” for products built at an authorized plant.
The Air Conditioning & Refrigeration Systems Works acquired environmental management system standard ISO 14001 certification.
The ISO 14000 series is a set of standards applying to environmental protection set by the International Standard Organization (ISO). ISO 14001 certifies the plant’s environmental protection system and activities.
HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO 100-0005 TELEX J24532 CABLE MELCO TOKYO
Certificate Number FM33568
Certificate Number EC97J1227
Registered on March 10, 1998
HWE05180
Printed in Malaysia
Loading...