Mitsubishi PCH-3GKHAFT, PCH-5GKHSAFT, PKH-1.6FKHAFT, PKH-3FKHAFT, PLH-1.6KKHCFT Service Manual

...
Page 1
This service manual covers the modification. Refer the following service manuals for further information. INDOOR UNIT [Service Ref.] [Service manual No.] PLH-1.6KKHC No.OC123 PLH-3GKHB No.OC096 PLH-5GKHSB PKH-1.6FKHA
3 No.OC130
PKH-3FKHA
2
PCH-3GKHA No.OC135 PCH-5GKHSA
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
CONTENTS
1. CHANGE POINT···································2
2. SAFETY PRECAUTION ·······················3
3. COMBIINATION OF INDDOR AND OUTDOOR UNITS ································5
4. SPECIFICATIONS·································6
5. WIRING DIAGRAM·····························14
6.
REFRIGERANT SYSTEM DIAGRAM
······17
7. PARTS LIST········································20
1997
Indoor unit [Model names] [Service Ref.]
Outdoor unit
Ceiling CassettesSeries PLH
R407C
No.OC159
The Slim Line. From Mitsubishi Electric.
PLH-1.6KKHCFT PLH-1.6KKHCFT PLH-3GKHBFT PLH-3GKHBFT PLH-5GKHSBFT PLH-5GKHSBFT
Ceiling SuspendedSeries PCH
PCH-3GKHAFT PCH-3GKHAFT PCH-5GKHSAFT PCH-5GKHSAFT
Wall MountedSeries PKH
PKH-1.6FKHAFT PKH-1.6FKHAFT PKH-3FKHAFT PKH-3FKHAFT
PUH-1.6VKAFT PUH-1.6VKAFT PUH-3VKAFT PUH-3VKAFT PUH-5YKSAFT PUH-5YKSAFT
Page 2
2
1 CHANGE POINT
Differentia with the standard type.
1.1.Indoor unit
1) PLH-KKHCFT Series Type
PLH-KKHCFT PLH-KKHC
Items
Refrigerant Heat exchanger
Use low residual oil piping
Coppaer piping for refrigerant
R407C R22
2) PLH-GHKBFT Series Type
PLH-GHHBFT PLH-GKHB
Items
Refrigerant Heat exchanger Capillaly tube
3GKHBFT 5GKHSBFT
Use low residual oil piping
{4.0O{2.2–L850mm {4.0O{2.6–L690mm
Coppaer piping for refrigerant
{4.0O{2.0–L400mm {4.0O{2.0–L350mm
R407C R22
3) PCH-GHKAFT Series Type
PCH-GKHAFT PCH-GKHA
Items
Refrigerant Heat exchanger Capillaly tube
3GKHBFT 5GKHSBFT
Use low residual oil piping
{4.0O{2.2–L400mm {4.0O{2.8–L860mm
Coppaer piping for refrigerant
{4.0O{2.0–L280mm {4.0O{2.4–L270mm
R407C R22
4) PKH-FHKAFT Series Type
PKH-FKHAFT PKH-FKHA
Items
Refrigerant Heat exchanger Capillaly tube
3FKHAFT only
Use low residual oil piping {4.0O{2.0–L740mm
Coppaer piping for refrigerant {4.0O{2.0–L500mm
R407C R22
4) PKH-FHKAFT Series Type
PKH-FKHAFT PKH-FKHA
Items
Refrigerant Heat exchanger
Compressor
Capillaly tube
Filter dryer
Ball valve
High pressure switch Solnoid valve
Charge plug Refrigerant charge Rear guard 4 way valve Controller board
1.6VKAFT 3VKAFT 5YKSAFT 3GVKAFT only
1.6VKAFT
3VKAFT 5YKSAFT
1.6VKAFT 3VKAFT
1.6VKAFT only
1.6VKAFT only
Use low residual oil piping RE247VFC NE52VND ZR61KCETED {4.0O{2.0–L940mm Attachment to outside of the unit. (Packing in same package) Self-containing unit Self-containing unit
·
Change of rubber materials.
·Change the oil to coat flare nut. Addition Valve diameter {1.8 Valve diameter {1.8 Change of rubber material.
2.3kg Change the rear guard form. Change of specification. Additions of the connector for 63H2.
Coppaer piping for refrigerant RH247VFC NH52VND ZR61KCTE5 {4.0O{2.0–L1,070mm
Valve diameter {2.0 Valve diameter {2.0
2.2kg
R407C R22
– –
Page 3
3
2 SAFETY PRECAUTION
Cautions for devices that use R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
· Use “low residual oil piping”.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerator oil will result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use Suniso 4GS or 3GS (small amount) as the refrigerator oil to coat flares and flange connection parts.
-The refrigerator oil used with the air conditioner is highly hygroscopic. If it is used, water may be mixed in and deterioration
of the refrigerator oil may result.
· Use liquid refrigerant to seal the system.
-If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
Page 4
4
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 35kgf/cm
2
or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 52kgf/cm
2
or over.
3 Electronic scale 4 Gas leak detector ·Use the detector for R134a or R407C. 5 Adapter for reverse flow check. ·Attach on vacuum pump. 6 Refrigerant charge base. 7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
[2] Notice on repair service
·After recovering the all refrigerator in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After complete the repair service, recharge the cycle with the specified amount of the liquid refrigerant.
Page 5
5
3 COMBINATION OF INDOOR AND OUTDOOR UNITS
Indoor unit Outdoor unit
Service Ref.
PLH-GKH(S)BFT PLH-KKHCFT PCH-GKH(S)AFT PKH-FKHAFT
OC096 OC123 OC135 OC130
Service
Manual No.
1.6
VKAFT
3
VKAFT
5
YKAFT
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct enclosure from the bomb.
·Comfirm that R407C bomb on the market are syphon pipe.
·Leave the syphon pipe bomb raising and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerator in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After complete the repair service, recharge the cycle with the specified amount of the liquid refrigerant.
Gravimeter
Unit
Page 6
6
SPECIFICATIONS4
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
mmAq,Pa
kW
dB(A) mm,(in.) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kW
A A
kW
kW
K
/min(CFM
)
dB(A) mm,(in.) mm,(in.) mm,(in.)
kg,(lbs)
kg,(lbs) mm,(in.) mm,(in.)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle,voltage)
Input Running current
Starting current External finish Heat exchanger
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain conn. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Input
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices Heat exchanger
Fan(drive) x No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge Pipe size O.D.
Connection method
Between the indoor & outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PLH-1.6KKHCFT
Cooling
15,000
4,400
1.59
0.15
0.64
0.70
UNIT : 660(26) UNIT : 660(26) UNIT : 253(10)
UNIT : 19(42)[20(44)]
1.44
6.74
Heating
15,900[20,600]
4,650[6,050]
1.51[3.20]
0.10[1.50]
0.45[6.28]
0.50[6.91]
PANEL : 760(30) PANEL : 760(30)
PANEL : 30(1-1/8)
PANEL : 3.7(8)[3.7(8)]
1.41
6.60
W
D H
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
PLH-1.6KKHCFT
Single, 50Hz, 220-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan [direct) x 1
0.030
13-16(460-565)
0(direct blow)
[1.4]
Remote controller & built-in
32-37
32(1-1/4)
PUH-1.6VKAFT
Single, 50Hz, 220-240V
33
Munsell 5Y 7/1
Capillary tube
Hermetic
RH247VFC
1.2
Line start
Inner thermostat, High pressure switch
Plate fin coil
Propeller (direct) x 1
0.065
45(1,590)
Reverse cycle
49
870(34-1/4)
295+24 (11-5/8 and 1)
650 (25-5/8)
53(117)
R407C
2.3(5.1)
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 40m Max. 40m
4.1.Indoor unit
Page 7
7
Service Ref.
Power supply(phase, cycle,voltage)
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain conn. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input Running current Starting current
Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive) x No. Fan motor output Airflow
Charge
W D H
W D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Models
Btu/h
W
kW
kW
A A
kW
K/ min (CFM)
Pa(mmAq)
kW
dB(A) mm,(in) mm,(in) mm,(in) mm,(in) kg,(lbs)
kW
A A
kW
kW
K/ min (CFM)
dB(A) mm,(in) mm,(in) mm,(in) kg,(lbs)
kg,(lbs) mm,(in) mm,(in)
PLH-3GKHBFT
Cooling
26,300
7,700
3.57
Heating
28,700[35,800]
8,400[10,500]
3.59[5.69]
0.16
0.72
1.00
0.16[2.26]
0.72[9.5]
1.00[9.8]
UNIT : 820(32-1/4) UNIT : 820(32-1/4) UNIT : 258(10-1/8)
UNIT : 29(64)
PANEL : 950(37-3/8) PANEL : 950(37-3/8)
PANEL : 65(2-9/16)
PANEL : 7(16)
3.41
4.96/15.58 58/37
3.43
5.04/5.61 58/37
PLH-3GKHBFT
Single, 50Hz, 220-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.050
14-18(495-640)
0(direct blow)
[2.1]
Remote controller & built-in
32-39
30(1-1/4)
PUH-3VKAFT
Single, 50Hz, 220-240V/3, 50Hz, 380-415V(4wires)
Munsell 5Y 7/1
Capillary tube
Hermetic
NE-52VND
2.2/2.4
Line start
w1
Plate fin coil
Propeller (direct) x1
0.085
50(1764)
Reverse cycle
52
870(34-1/4)
295+24 (11-5/8 add 1)
850(34-1/4)
75(165)
R407C
3.2(7.1)
9.52 (3/8)
15.88(5/8) Flared Flared
Max. 50m Max. 50m
w1 V…Internal Thermostat, HP switch
Y…Anti-phase protector, thermal relay, thermal switch, HP switch
Page 8
8
Service Ref.
Power supply(phase, cycle,voltage)
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain conn. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
Input Running current Starting current
Fan(drive) x No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive) x No. Fan motor output Airflow
Charge
W
D H
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Function
Capacity
Total input
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Models
Btu/h
W
kW
kW
A A
kW
K/ min (CFM)
Pa(mmAq)
kW
dB(A) mm,(in) mm,(in) mm,(in) mm,(in) kg,(lbs)
kW
A A
kW
kW
K/ min (CFM)
dB(A) mm,(in) mm,(in) mm,(in) kg,(lbs)
kg,(lbs) mm,(in) mm,(in)
PLH-5GKHSBFT
Cooling
41,300 12,100
4.55
Heating 45,700[56,000] 13,400[16,400]
4.77[7.77]
0.28
1.27
1.50
0.28[3.28]
1.27[13.8]
1.50[14.0]
UNIT : 1340(52-3/4)
UNIT : 820(32-1/4) UNIT : 258(10-1/8)
UNIT : 45(99)
PANEL : 1470(57-7/8)
PANEL : 950(37-3/8)
PANEL : 65(2-9/16)
PANEL :10(22)
4.27
6.90 53
4.49
7.34 53
PLH-5GKHSBFT
Single, 50Hz, 220-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 2
0.050+0.050
24-33(850-1165)
0(direct blow)
[3.0]
Remote controller & built-in
36-43
30(1-1/4)
PUH-5YKSAFT
3, 50Hz, 380-415V(4wire)
Munsell 5Y 7/1
Capillary tube
Hermetic
ZR61KCE-TFD
3.5
Line start
Internal thermostat, Anti-phasa protector, Thermal switch, HP switch
Plate fin coil
Propeller (direct) x2
0.085+0.085 95(3550)
Reverse cycle
55
970(38-3/16)
345+24(13-9/16 add 1)
1258(49-1/2)
114(251)
R407C
5.4(11.9)
9.52(3/8)
19.05(3/4) Flared Flared
Max. 50m Max. 50m
Page 9
9
Rating Conditions (JIS B8616)
Service Ref.
Power supply
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Crankcase heater Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side Outdoor side Height difference Piping length
Input Running current Starting current
Fan(drive))No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive))No. Fan motor output Airflow
Charge
dB(A) mm,(in) mm,(in) mm,(in) mm,(in) kg,(lbs)
W
D H
Function
Total input
Capacity
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor 35: DB, 22.5: WB 21: DB, 15.5: WB
27: DB 20: DB
Outdoor 46: DB
-5: DB
21: DB, 15.5: WB
-8.5: DB, -9.5: WB
2. Guaranteed operating range
W
dB(A) mm,(in) mm,(in) mm,(in) kg,(lbs)
W
D H
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
A A
kW
kg,(lbs)
kW
K/min <CFM>
kW
K/min <CFM>
Pa(mmAq)
kW
mm,(in) mm,(in)
Liquid Gas
PCH-3GKHAFT PCH-4GKHSA1
Cooling
25,600
7,500
3.28
0.13
0.55
1.27
0.13 (2.23)
0.55 (9.30)
1.27 (10.02)
0.16
0.70
1.48
0.16 (2.86)
0.70 (11.95)
1.48 (12.73)
Heating
29,000 (36,200)
8,500 (10,600)
3.07 (5.17)
Cooling
34,100 10,000
3.36
Heating 35,700 (44,900) 10,450 (13,150)
3.35(6.05)
PCH-3GKHAFT
Single phase. 50Hz. 220-240V
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Sirocco (direct) 3
PCH-4GKHSA
1
0.07
14 -18 <494-635>
0.09
20 -25 <706-883>
0 (direct blow)
(2.1)
210 (8-1/4) 270 (10-5/8)
(2.7)
Remote controller & built-in
37 - 43 40 - 45
26 (1)
1,310 ( 51-9/16 )
680 (26-3/4)
36 (79)
PUH-3VKAFT
39.5 (87)
PUH-4YKSA
3
NH52YDA
2.2 / 2.4
NH56YDA
2.7
Propeller (direct) 1
0.085
50 (1,764)
Propeller (direct) 2
0.065 + 0.065 95 (3,350)
850 (33-7/16)
75 (165)
1,258 (49-1/2)
94 (207)
Max. 50m Max. 50m
38 52
38 54
3.2 (7.1)
9.52 (3/8)
15.88 (5/8)
4.2 (9.2)
9.52 (3/8)
19.05 (3/4)
VKA...1phase, 50Hz, 220-240V
Reverse cycle
R407C
870 <34-1/4>
295 + 24 <11-5/8 add 1>
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
VKA...Inner thermostat. High-pressure switch YKA...Anti-phase protector, Thermal relay, Thermal switch, High-pressute switch
Plate fin coil
3.15
13.82 / 5.16 58 / 37
2.94
12.89 / 4.81 58 / 37
3.20
5.24 40
3.19
5.22 40
Flared Flared
Notes1. Rating Conditions (JIS B8616)
Cooling : Indoor : 27:(80
o
F)DB. 19:(66oF)WB
Outdoor : 35:(95
o
F)DB. 24:(75oF)WB
Heating : Indoor : 20:(68
o
F)
Outdoor : 7:(45
o
F)DB. 6:(43oF)WB.
Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
Page 10
10
Rating Conditions (JIS B8616)
Service Ref.
Power supply
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain connection O.D.
Dimensions
Weight
Service Ref.
Power supply
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Crankcase heater Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Indoor side Outdoor side Height difference Piping length
Input Running current Starting current
Fan(drive))No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Starting current
Model Motor output Starter type Protection devices
Fan(drive))No. Fan motor output Airflow
Charge
dB(A) mm,(in) mm,(in) mm,(in) mm,(in)
kg,(lbs)
W
D H
Function
Total input
Capacity
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Indoor 35: DB, 22.5: WB 21: DB, 15.5: WB
27: DB 20: DB
Outdoor 46: DB
-5: DB
21: DB, 15.5: WB
-8.5: DB, -9.5: WB
2. Guaranteed operating range
W
dB(A) mm,(in) mm,(in) mm,(in)
kg,(lbs)
W
D H
INDOOR UNITOUTDOOR UNIT
REFRIGERANT
PIPING
Item
Service Ref.
Btu/h
W
kW
kW
A A
kW
A A
kW
kg,(lbs)
kW
K/min <CFM>
kW
K/min <CFM>
Pa(mmAq)
kW
mm,(in) mm,(in)
Liquid Gas
PCH-5GKHSAFT PCH-6GKHSA1
Cooling
42,300 12,400
4.45
0.24
1.06
2.20
0.24 (3.24)
1.06 (13.56)
2.20 (14.70)
0.24
1.06
2.20
0.24 (3.24)
1.06 (13.56)
2.20 (14.70)
Heating 47,400 (57,700) 13,900 (16,900)
4.40 (7.40)
Cooling
49,500 14,500
4.97
Heating 51,200 (61,400) 15,000 (18,000)
4.82 (7.82)
PCH-5GKHSAFT
Single phase. 50Hz. 220-240V
PCH-6GKHSA
1
Munsell 0.70Y 8.59 / 0.97
Plate fin coil
Sirocco (direct)4
0.15
27 -34 <953-1,200>
0 (direct blow)
(3.0)
Remote controller & built-in
41-46 42-48
26 (1)
1,620 (63-3/4)
680 (26-3/4) 270 (10-5/8)
46 (101)
PUH-5YSAFT
48 (106)
PUH-6YKSA
2
ZR61KC-ETED
3.5
ZR68KC-TFD
4.0
0.085 + 0.085 95 (3,350)
0.10 + 0.10
100 (3,530)
114 (251) 117 (258)
55 56
5.4 (11.9) 5.0 (11.0)
3 phases. 50Hz. 380-415V (4 wires)
Reverse cycle
38
R407C
970 (38-3/16)
345 + 24 (13-9/16 add 1)
1,258 (49-1/2)
Munsell 5Y 7/1
Capillary tube
Hermetic
Line start
Anti-phase protector, Internal thermostat, Thermal switch, High-pressure switch
Plate fin coil
Propeller (direct)2
4.21
6.89 53
4.16
6.81 53
4.73
7.74 74
4.58
7.50 74
9.52 (3/8)
19.05 (3/4) Flared Flared
Max. 50m Max. 50m
Notes1. Rating Conditions (JIS B8616)
Cooling : Indoor : 27:(80
o
F)DB. 19:(66oF)WB
Outdoor : 35:(95
o
F)DB. 24:(75oF)WB
Heating : Indoor : 20:(68
o
F)DB.
Outdoor : 7:(45
o
F)DB. 6:(43oF)WB.
Refrigerant piping length (one way) : 5m(16ft)
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 3 phase 415V 50Hz
Page 11
11
Item Function
Capacity
Total input
Service Ref.
Power supply(phase,cycle,voltage)
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain connection. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Input Running current Starting current
Fan(drive) No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Staring current
Model Motor output Starter type Protection devices
Fan(drive)No. Fan motor output Airflow
Charge
Service Ref.
W
D H
W
D H
Liquid Gas Indoor side Outdoor side Height difference Piping length
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
W
Btu/h
kW
kW
A A
kW
m
3
/X<CFM>
Pa(mmAq)
kW
>(A) A,<in.> A,<in.> A,<in.> A,<in.>
kg,<lbs>
>(A) A,<in.> A,<in.> A,<in.>
A,<in.> A,<in.>
kg,<lbs>
kg,<lbs>
kW
A A
kW
kW
m
3
/X,<CFM>
PKH-1.6FKHAFT
Cooling Heating
4,500 4,650(6,050)
15,350 15,900(20,600)
1.51
0.07
0.32
0.40
PKH-1.6FKHAFT
Single, 50Hz, 220-240V
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow(direct) 1
0.030
10-13<353-459>
0<direct blow>
1.4
Remote controller & built-in
36-43
20<13/16>
1,250<49-3/16>
200<7-7/8>
300<11-13/16>
18<40>
PUH-1.6VKAFT
Single, 50Hz, 220-240V
1.411.44
6.606.74
33
Munsell 5y 7/1
Capillary tube
Hermetic
RE247VFC
1.2
Line start
Internal thermostat, HP switch
Plate fin coil
Propeller (direct) 1
0.065
45<1,590>
Reverse cycle
49
870<34-1/4>
295+24<11-5/8 add 1>
650<25-5/8>
53<117>
R-407C
2.3<5.1>
9.52<3/8>
15.88<5/8> Flared Flared
Max. 40m Max. 40m
1.48(2.88)
0.07(1.47)
0.32(6.15)
0.40(6.23)
Note. Rating Conditions (JIS B 8616)
Cooling : Indoor : 27°C (80°C) DB, 19°C (66°F) WB
Outdoor : 35°C (95°F) DB, 24°C (75°F) WB
Heating : Indoor : 20°C (68°F)
Outdoor : 7°C (45°F) DB, 6°C (43°F) WB
Page 12
12
Item Function
Capacity
Total input
Service Ref.
Power supply(phase,cycle,voltage)
External finish Heat exchanger
Booster heater Operation control & Thermostat Noise level(Low-High) Cond. drain conn. O.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor unit
Input Running current Starting current
Fan(drive) No. Fan motor output Airflow(Low-High) External static pressure
Input Running current Staring current
Model Motor output Starter type Protection devices
Fan(drive)No. Fan motor output Airflow
Charge
Service Ref.
W
D H
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping lenghth
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
W
Btu/h
kW
kW
A A
kW
m
3
/X<CFM>
Pa(mmAq)
kW
>(A) A,<in.> A,<in.> A,<in.> A,<in.>
kg,<lbs>
>(A) A,<in.> A,<in.> A,<in.>
A,<in.> A,<in.>
kg,<lbs>
kg,<lbs>
kW
A A
kW
kW
m
3
/X<CFM>
PKH-3FKHAFT
Cooling Heating
7,900 9,100(11,200)
27,000 31,000(38,200)
3.25
0.095
0.44
0.80
PKH-3FKHAFT
Single, 50Hz, 220-240V
Munsell 3.4Y 7.7/0.8(White)
Plate fin coil
Line flow(direct) 2
0.040
15-20<530-706>
0(direct blow)
2.1
Remote controller & built-in
35-43
20<13/16>
1,400<55-1/8>
235<9-1/4>
340<13-3/8>
26<57>
PUH-3VKAFT
Single, 50Hz, 220-240V/3
2.94/2.943.15/3.15
12.89/4.8113.82/5.16
58/37
Munsell 5Y 7/1
Capillary tube
Hermetic
NE52VND
2.2
Line start
Internal thermostat, HP switch/Thermal relay, thermal switch
Plate fin coil
Propeller (direct) 1
0.085
50<1,764>
Reverse cycle
52
870(34-1/4)
295+24<11-5/8 add 1>
850<33-7/16>
75<165>
R-407C
3.2<7.1>
9.52<3/8>
15.88<5/8> Flared Flared
Max. 50m Max. 50m
3.04(5.14)
0.095(2.195)
0.44(9.19)
0.80(9.55)
Note. Rating Conditions (JIS B 8616)
Cooling : Indoor : 27°C (80°C) DB, 19°C (66°F) WB
Outdoor : 35°C (95°F) DB, 24°C (75°F) WB
Heating : Indoor : 20°C (68°F)
Outdoor : 7°C (45°F) DB, 6°C (43°F) WB
Page 13
13
1. REFILLING REFRIGERANT CHARGE (R-22 : kg)
PUH-1.6VKAFT PUH-3VKAFT PUH-5YKSAFT
5m
1.6
2.5
4.7
Service Ref.
Refrigerant piping length (one way)
10m
1.8
2.7
4.8
15m
1.9
2.8
5.0
20m
2.0
2.9
5.1
25m
2.2
3.1
5.3
30m
2.3
3.2
5.4
35m
2.4
3.3
5.6
40m
2.5
3.4
5.7
45m
3.6
5.9
50m
3.7
6.0
2. COMPRESSOR TECHNICAL DATA at 20˚C
at 25˚C
Winding
Resistance
(!)
U-V
(
R-C
)
U-W
(
S-C
)
W-V
Compressor Model
RE247VFC NE52VND
Winding
Resistance
(!)
ZR61KCETED
T1-T2
T2-T3
T3-T1
Compressor Model
4.2.Outdoor unit
Page 14
14
5 WIRING DIAGRAM
PUH-1.6VKAFT
Main functions of LED
(
when both Nos.1 and 2 of are “OFF”
)
NOTE : If the operation stops to function of the protection device, the check display flashes.
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
Since LD8 lights when normal power is turned “ON”, check the power supply with the “ON” or “OFF” LD8.
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection in the following procedure.
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
How to use SW1 and 2
Pressing erases the past check contents loaded on the microcomputer.
The output display (light) remains lit during operation but pressing displays the past check contents in flashing mode. Pressing the switch again returns to output display (light).
SW3
SW1
SW2
LED No.
LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
Output display (light
) Compressor indoor command Heating indoor command 63H1 ON
Compressor ON Outdoor fan ON
4-way valve ON Bypass valve ON Crankcase heater ON
Check display (flash
) – –
Pipe sensor short/open 63H2 functions
– –
RT overheat protection Defective input
CAUTIONS FOR POWER SUPPLY WIRING
CAUTION FOR SERVICING
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
SYMBOL MC MF C1 C2 RT HC 52C 21S4 21R
NAME COMPRESSOR OUTDOOR FAN MOTOR (INNER THERMOSTAT) FAN MOTOR CAPACITOR COMPRESOR CAPACITOR PIPE TEMP. THERMISTOR CRANKCASE HEATER CONTACTOR 4-WAY VALVE SOLENOID COIL BYPASS VALVE SOLENOID COIL
SYMBOL TB1,3 63H1 63H2 O.B ZNR<O.B
>
F<O.B
>
FC<O.B
>
X11<O.B
>
T
NAME TERMINAL BLOCK CONTROL HIGH PRESSURE SWITCH PROTECT HIGH PRESSURE SWITCH OUTDOOR CONTROLLER BOARD SURGE ABSORBER FUSE(6.3A
)
FAN CONTROLLER CRANKCASE HEATER RELAY TRANSFORMER
SYMBOL
X12<O.B
>
X13<O.B
>
X14<O.B
>
X16 SW1,2,3<O.B
>
LD1-LD8<O.B
>
NAME COMPRESSOR RELAY SOLENOID COIL RELAY SOLENOID COIL RELEY HIGH PRESSURE RELAY CHECK,SERVICE SELECT SWITCH CHECK,SERVICE LED
TO INDOOR UNIT CONNECTING WIRES DC 12V (polar)
POWER SUPPLY ~/N(1phase) 220V-240V 50Hz
1
YLW
2
ORN
3
BRN
TB3
BRN AC12.3V
RED AC12.3V
O.B
SW1 SW2 SW3
12
3
CN3
2 1
CN4T
YLW
240V
ORN
230V
RED
220V
T
TB1
L N
GRN/YLW
LD1
OFF ON
LD2
1234
LD3
4
LED
LD4
LD5
LD6
RED
RED BLU
RT
CN2
LD7
LD8
X14
TRF 52C
SV
WHT
WHT
RED
21R
RED BLU
52C
L1/1
L3/5
BLU
T1/2
T3/6
X13X14
21S4
BLU
21 S4
GRY
BLU WHT RED
GRY
52C
X16
X11X12
A1
A2
GRY
7
8
6
C2
WHT
X16
WHT
CH
CN4
HC
GRY
2
GRY
RED
X11X12X13
ZNR
63H2
1234
F
R/1 S/2 T/3
R
C
MC
S
63H1
BLU BLU
BRN
BRN5YLW
63H1
YLW
YLW
YLW
FC
BLU
26C
63H2
51CM
MF
VLT
BLU WHT RED ORN
VLT
MF2
MF1
1 X16
5
BLU
WHT
4
RED
3 2
C1
1
ORN
When power supply is 220V
RED WHITE
220V
ORANGE
YELLOW
230V
240V
Page 15
15
PUH-3VKAFT
Main functions of LED
(
when both Nos.1 and 2 of are “OFF”
)
NOTE : If the operation stops to function of the protection device, the check display flashes.
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
Since LD8 lights when normal power is turned “ON”, check the power supply.
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection in the following procedure.
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
How to use SW1 and 2
Pressing erases the past check contents loaded on the microcomputer.
The output display (light) remains lit during operation but pressing displays the past check contents in flashing mode. Pressing the switch again returns to output display (light).
SW3
SW1
SW2
LED No.
LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
Output display (light
) Compressor indoor command Heating indoor command 63H1 ON
Compressor ON Outdoor fan ON
4-way valve ON Bypass valve ON Crankcase heater ON
Check display (flash
) – –
Pipe sensor short/open 63H2 functions
– –
TH overheat protection Defective input
CAUTIONS FOR POWER SUPPLY WIRING
CAUTION FOR SERVICING
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
SYMBOL MC MF C1 C2 TH HC 52C 21S4 21R
NAME COMPRESSOR OUTDOOR FAN MOTOR (INNER THERMOSTAT) FAN MOTOR CAPACITOR COMPRESOR CAPACITOR PIPE TEMPERATURE THERMISTOR CRANKCASE HEATER CONTACTOR 4-WAY VALVE SOLENOID COIL BYPASS VALVE SOLENOID COIL
SYMBOL TB1,3 63H1 63H2 O.B ZNR<O.B
>
F<O.B
>
FC<O.B
>
X11<O.B
>
T
NAME TERMINAL BLOCK CONTROL HIGH PRESSURE SWITCH PROTECT HIGH PRESSURE SWITCH OUTDOOR CONTROLLER BOARD SURGE ABSORBER FUSE(6.3A
)
FAN CONTROLLER CRANKCASE HEATER RELAY TRANSFORMER
SYMBOL
X12<O.B
>
X13<O.B
>
X14<O.B
>
X16 SW1,2,3<O.B
>
LD1-LD8<O.B
>
CN3<O.B
>
CN4T<O.B
>
NAME COMPRESSOR RELAY SOLENOID COIL RELAY SOLENOID COIL RELEY HIGH PRESSURE RELAY CHECK,SERVICE SELECT SWITCH CHECK,SERVICE LED CONNECTING WIRES INDOOR/OUTDOOR CONNECTOR TRANSFORMER CONNECTOR
TO INDOOR UNIT CONNECTING WIRES DC 12V
POWER SUPPLY ~/N(1phase) 220V-240V 50Hz
1
YLW
2
ORN
3
BRN
TB3
RED
RED
AC12.3V
AC
12.3V
TB1
L N
BRN BRN
T
GRN/YLW
O.B
SW1 SW2 SW3
4
YLW ORN RED
LED
12 3 2 1
LD1
OFF ON
CN3
CN4T
240V 230V 220V
BLU
LD7
LD6
LD5
LD4
LD3
LD2
CN2
123
4
RED
WHT
WHT
TH
LD8
RED
21R
SV
RED
RED BLU
1234
CN4
X12X13X14
X11
X11X12X13X14
A1
A2
GRY
7 8
WHT
6
BLU WHT RED
WHT
X16
C2
CH
GRY
HC
GRY 2
RED
ZNR
63H2
C
TRF
BLU
BLU
L1/1
L3/5
21S4
21 S4
GRY
52C
52C
GRY
52C
X16
T1/2
T2/6
YLW
F. C
MF2
MF1
5
BLU
VLT
VLT
YLW
YLW
1
X16
5
C1
WHT BLU RED ORN
WHT
3
BLU
4
RED
MF
2
ORN
1
26C
63H2
63H1
51CM
ST
F
R
YLW
BRN
BRN
BLUBLU
63H1
R
MC
S
When power supply is 220V
RED WHITE
220V
ORANGE
YELLOW
230V
240V
Page 16
16
PUH-5YKSAFT
Main functions of LED
(
when both Nos.1 and 2 of are “OFF”
)
NOTE : If the operation stops to function of the protection device, the check display flashes.
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection in the following procedure.
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
How to use SW1 and 2
Pressing erases the past check contents loaded on the microcomputer.
The output display (light) remains lit during operation but pressing displays the past check contents in flashing mode. Pressing the switch again returns to output display (light).
SW3
SW1
SW2
LED No.
LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8
Output display (light
) Compressor indoor command Heating indoor command 63H1 ON
Compressor ON Outdoor fan ON
4-way valve ON Bypass valve ON Crankcase heater ON
Check display (flash
) Auti-phase detect Missing-phase detect Pipe sensor short/open 63H2 functions
26C functions RT overheat protection Defective input
CAUTIONS FOR POWER SUPPLY WIRING
CAUTION FOR SERVICING
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
SYMBOL MC MF1,2 C1,2 TH HC 49C 52C 21S4 21R X16
NAME COMPRESSOR OUTDOOR FAN MOTOR (INNER THERMOSTAT) FAN MOTOR CAPACITOR
PIPE TEMPERATURE THERMISTOR
CRANKCASE HEATER INTERNAL THERMOSTAT FOR MC CONTACTOR 4-WAY VALVE SOLENOID COIL BYPASS VALVE SOLENOID COIL HIGH PRESSURE RELAY
SYMBOL TB1,3 63H1 63H2 26C O.B ZNR<O.B
>
F<O.B
>
FC<O.B
>
X11<O.B
>
T
NAME TERMINAL BLOCK CONTROL HIGH PRESSURE SWITCH PROTECT PRESSURE SWITCH DIS.CHARGE THERMAL SWITCH OUTDOOR CONTROLLER BOARD SURGE ABSORBER FUSE(6.3A
)
FAN CONTROLLER CRANKCASE HEATER RELAY TRANSFORMER
SYMBOL
X12<O.B
>
X13<O.B
>
X14<O.B
>
CN3<O.B
>
CN4T<O.B
>
SW1,2,3<O.B
>
LD1-LD8<O.B
>
51CM<O.B
>
NAME COMPRESSOR RELAY SOLENOID COIL RELAY SOLENOID COIL RELEY CONNECTING WIRES INDOOR/OUTDOOR CONNECTOR TRANSFORMER CONNECTOR CHECK,SERVICE SELECT SWITCH CHECK,SERVICE LED JUMPER CONNECTOR
TO INDOOR UNIT CONNECTING WIRES DC 12V
POWER SUPPLY 3N~(3phase 4wires) 380/220V-415/240V 50Hz
YLW
1
ORN
2
BRN
3
TB3
RED
RED
AC
12.3V
AC12.3V
BRN BRN
TB1
L1 L2 L3
N
LED
O.B
SW1 SW2 SW3
12 3 2 1
CN4T
4
YLW
ORN
RED
T
GRN/YLW
OFF ON
CN3
LD1
240V
230V 220V
LD5
LD4
LD3
LD2
123
4
13
52C 14
RED WHT BLU
TH
LD8
LD7
LD6
CN2
SV
RED
RED
21R
RED
WHT
WHT
RED WHT BLK BLU
L2/3 L3/5
52C
1234
CN4
X11X12X13X14
X11X12X13X14
63H1
RST
F
TRF
T1/2L1/1 T2/4 T3/6
BLU
21S4
BLU
21 S4
52C
GRY
GRY
A1
52C
A2
GRY
X16
ZNR
CH
BLK
BLK
HC
GRY
7
2
6
63H2
X16
8
GRY
RED WHT BLU
26C
63H2
51CM
5
BRN
BRN
63H1
49C
T1 T2 T3
VLT
MC
F.C
MF2
MF1
BLK
BLK
VLT
1
X16
26C
5
C1
C2
WHT BLU RED ORN
WHT BLU BRN YLW
WHT
3
BLU
4
RED
2
ORN
1
WHT
3
BLU
4
RED
2
ORN
1
MF1
MF2
Power line reconnection procedure In case of reverse rotation
Unit side wiring
Field wiring
Change thie side
L1L2L3
123
charge 2 out of 1. 2 and 3.
(This example shows reconnection of 1 and 2.)
When power supply is 220V
RED WHITE
220V
ORANGE
YELLOW
230V
240V
Outdoor unit terminal
Page 17
17
6 REFRIGERANT SYSTEM DIAGRAM
PKH-1.6FKHAFT/PUH-1.6VKAFT PKH-3FKHAFT/PUH-3VKAFT
Unit : mm
Indoor heat exchanger
Indoor coil thermistor (RT2)
Distributor with strainer
PLH-1.6 (O.D.3.2 I.D.1.6-r630)
Restrictor valve
Refrigerant pipe (option)
9.52mm( 3.8") (with heat insulator)
Ball valve (with service port)
Indoor unit
Strainer
Refrigerant pipe (option)
15.88mm( 5/8") (with heat insulator)
Flexible tube
Flared connection
Ball valve
Strainer
4-way valve
Oil separator
Service port
High pressure control switch
Outdoor unit
Outdoor heat exchanger
Outdoor coil thermistor (TH)
Bypass valve
Restrictor valve
Capillary
tube
Strainer
Compressor
Accumulator
Refrigerant flow in cooling Refrigerant flow in heating
R.V.coil Heating ON Cooling OFF
PUH-1.6 (O.D.3.2 I.D.1.8 -R600)
Capillary tube
High pressure protect switch
Service port
PLH-1.6KKHCFT/PUH-1.6VKAFT
Indoor unit
Indoor heat exchanger
Strainer
Indoor coil thermistor (RT1)
Distributor with strainer
PKH-1.6 (O.D.3.2 I.D.1.6-r700) PKH-3 (O.D.4.0 I.D.2.2-r740)
Restrictor valve
Capillary tube
Refrigerant pipe (option)
15.88mm( 5/8") (with heat insulator)
Flexible tube
Flared connection
Refrigerant pipe (option)
9.52mm( 3.8") (with heat insulator)
Ball valve
Strainer
Service port
Accumulator
Ball valve (with service port)
High pressure
Oil separator
4-way valve
Compressor
High pressure control switch
PUH-1.6 (O.D.3.2 I.D.1.8 -r600)
PUH-3 (O.D.4.0 I.D.2.4 -r940)
control switch
Service port
Outdoor unit
Outdoor heat exchanger
Bypass valve
Restrictor
valve
Strainer
Outdoor coil thermistor (TH)
Capillary tube
Page 18
18
Indoor unit
Indoor heat exchanger
Refrigerant pipe (option)
15.88
mm( 5/8")
(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Service port
Service port
High pressure control switch
High pressure proted switch
Outdoor unit
Outdoor heat exchanger
Thermistor
TH
Capillary tube
Restrictor valve
PUH-3 4.0 2.4- 940
Strainer
Bypass valve
Compressor
Accumulator
Ball valve (with service port)
Refrigerant pipe (option)
9.52
mm( 3/8")
(with heat insulator)
Capillary tube
Restrictor valve
Distributor with strainer
Thermistor TH2
Strainer
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
<R.V.coil> Heating ON Cooling OFF
Unit : mm
O.D. I.D. Length
O.D. I.D. Length
2.2- 850 PLH-3 4.0
Thermal switch
Indoor unit
Indoor heat exchanger
Refrigerant pipe (option)
19.05
mm( 3/4")
(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Service port
Service port
High pressure control switch
High pressure proted switch
Outdoor unit
Outdoor heat exchanger
Thermistor TH
Capillary tube
Restrictor valve
Strainer
Bypass valve
Compressor
Accumulator
Ball valve (with service port)
Refrigerant pipe (option)
9.52
mm( 3/8")
(with heat insulator)
Capillary tube
Distributor with strainer
Thermistor RT2
Strainer
Flared connection
PLH-5 4.0 2.6- 690
Capillary tube
O.D. I.D. Length
O.D. I.D. Length
PUH-5 ( 4.0 2.4- 840) 2
Restrictor valve
PLH-3GKHBFT/PUH-3VKAFT
PLH-5GKHSBFT/PUH-5YKSAFT
Page 19
19
Indoor unit
Indoor heat exchanger
Refrigerant pipe (option)
15.88
mm( 5/8")
(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Service port
Service port
High pressure control switch
Outdoor unit
Outdoor heat exchanger
Outdoor coil thermistor
(RT)
Capillary tube
Restrictor valve
Strainer
Bypass valve
Compressor
Accumulator
Ball valve (with service port)
Refrigerant pipe (option)
9.52
mm( 3/8")
(with heat insulator)
Capillary tube
Restrictor valve
Distributor with strainer
Indoor coil thermistor RT2
Indoor coil thermistor RT2
Strainer
Flared connection
<R.V.coil> Heating ON Cooling OFF
PCH-3(O.D.4.0 I.D.2.2-R400)
Thermal switch
Indoor unit
Indoor heat exchanger
Refrigerant pipe (option)
19.05
mm( 3/4")
(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Service port
Service port
High pressure control switch
Outdoor unit
Outdoor heat exchanger
Capillary tube
Restrictor valve
Strainer
Bypass valve
Compressor
Accumulator
Ball valve (with service port)
Refrigerant pipe (option)
9.52
mm( 3/8")
(with heat insulator)
Capillary tube
Distributor with strainer
Strainer
Flared connection
PCH-5 O.D.4.0 I.D.2.8-R860
Capillary tube
PUH-5 (O.D.4.0 I.D.2.4-R840) 2
Restrictor valve
Refrigerant flow in cooling Refrigerant flow in heating
Unit : mm
PUH-3(O.D.4.0 I.D.2.4-R940)
Outdoor coil thermistor
(RT)
High pressure protect switch
High pressure protect switch
(O.D.4.0 ✕ I.D.3.0-R200)
PCH-3GKHAFT/PUH-3VKAFT
PCH-5GKHSAFT/PUH-5YKSAFT
Page 20
20
7 PARTS LIST
PANEL PARTS PLH-1.6KKHCFT
7
6
No. Part No. Part Name Specification
1
T7W 560 003
2
R01 29H 500
3
R01 29H 691
4
R01 29H 061 5 6
T7W 14K 200
7
T7W 556 305
AIR OUTLET GRILLE AIR FILTER INTAKE GRILLE HINGE GRILLE HANGER REMOTE CONTROLLER REMOTE CONTROLLER CABLE
12m
Q'ty/set
PLH-1.6
KKHCFT
1 1 1 2 1 1 1
Remarks
(Drawing No.)
(BG88H096H01)
Wiring
Diagram
Symbol
R.B
Recom-
mended
Q'ty
Unit
Price
Amount
Page 21
21
1 2 3 4 5 6 7 8 9
10
R01 29H 002 R01 29H 085 R01 29H 223 R01 29H 063
T7W 33K 063
R01 29H 056 R01 29H 047 T7W 560 258 R01 29H 040 R01 29H 041
4 1 1 1 1 1 8 1 1 1
MV
H
<3/SET>
AUTO VANE AIR GUIDE VANE MOTOR SPRING JOINT 1 SPRING JOINT PUSH BUTTON VANE SUPPORT CORD HEATER GRILLE GEAR (RIGHT) GRILLE GEAR (LEFT)
240V 28.2W
No. Part No. Part Name Specification
Q'ty/set
Price
Unit
Amount
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
PLH-1.6
KKHCFT
PANEL PARTS PLH-1.6KKHCFT
Page 22
22
11
12 13
14
15
37
20
22
3032
34
29 31 33
28
27
26
19
18
7
6
3
4
35
8
9
10
5
1
2
36
24
23
25
16
FUNCTIONAL PARTS PLH-1.6KKHCFT
21
Page 23
23
1 2 3 4 5 6 7 8 9
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
— — — — —
T7W E00 762
R01 29H 105
— R01 41N 114 T7W E00 300 T7W E01 300
R01 32K 706
R01 046 700 R01 08K 202 R01 41N 523
T7W E00 355 R01 W28 266 R01 W28 527 T7W E12 480
R01 E00 529
— T7W 521 716 T7W 517 716 T7W 515 716 R01 29H 255
T7W 58K 310
T7W 520 239 T7W 580 799
R01 J07 202
— R01 71G 215
T7W 29H 675
R01 08K 097 R01 A48 524 R01 71N 241
R01 20J 303
MF1
H
H FS1 26H
RT2
DP DS
TB2 TB4 TB5
C1
I.B
F.IN
T
RT1
88H
(BG02Y348G06) (BG00T672G08) (BG00T672G09) (BG00T672G10) (BG00T673G02)
(BG00T718G06)
(BG00T713G05) (BG00T712G06)
(BG25J542H04)
(BG00L601G22) (BG00A662G18)
BASE LEG LEG LEG LEG FAN MOTOR MOTOR MOUNT INNER COVER TURBO FAN HEATER ELEMENT HEATER ELEMENT THERMAL FUSE THERMAL SWITCH INDOOR COIL THERMISTOR DRAIN SOCKET DRAIN PUMP DRAIN SENSOR DRAIN HOSE HEAT EXCHANGER DRAIN PAN CORNER COVER COVER (DRAM) TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK CAPACITOR CONTROLLER CASE INDOOR CONTROLLER BOARD FUSE TRANSFORMER ROOM TEMPERATURE THERMISTOR BELL MOUTH ELECTRICAL PARTS COVER RELAY FAN GUARD SPL WASHER DRAIN PLUG SENSOR HOLDER INSULATOR
PAI-V30F
467W 240V 700W 240V 77"C 250V 10A OFF42"C ON32"C
3P(L,N,;) 3P(1,2,3) 2P(1,2)
2.5#F 400V
250V 6.3A
LY2F DC12V
No.
Part No. Part Name Specification
Q'ty/set
Price
Unit Amount
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
10
KKHCFT
PLH-1.6
1 1 1 1 1 1 3 1 1 3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Part numbers that are cicled are not shown in the figure.
Page 24
24
No. Parts No. Parts Name
Specification
Q'ty / set
PLH-3
GKHBFT
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit Amount
Price
1 2 3 4 5 6 7 8
AIR OUTLET GRILLE AIR FILTER INTAKE GRILLE HANGER G GRILLE CATCH FILTER CATCH SHUTTER PLATE PANEL SCREW
PANEL 1
1 1 1 2 2 1 1
T7W 700 003 R01 W28 500 R01 W28 691 R01 W28 098 R01 W28 054 R01 029 054 R01 W28 083 R01 W28 673
PANEL PARTS PLH-3GKHBFT
Part numbers that are circled are not shown in the figure.
Page 25
25
No. Parts No. Parts Name
Specification
Q'ty / set
PLH-3
GKHBFT
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit Amount
Price
1 2 3 4 5 6 7 8 9
AUTO VANE(2) AUTO VANE(3) AIR GUIDE(1) AIR GUIDE(2) AIR GUIDE(3) AIR GUIDE(4) VANE MOTOR VANE JOINT VANE BUSHING
2 2 1 1 1 1 1 4 8
MV
R01 W29 002 R01 W30 002 R01 W28 085 R01 W28 086 R01 W28 087 R01 W28 088 T7W 700 223 R01 W28 063 R01 W28 064
PANEL PARTS PLH-3GKHBFT
8
9
2
9
8
9
1
9
8
7
9
4
2
6
9
5
9
3
8
Page 26
26
FUNCTIONAL PARTS PLH-3GKHBFT
37
Page 27
27
No. Parts No. Parts Name Specifications
Q'ty/set
PLH-3
GKHBFT
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit Amount
Price
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
BASE DRAM (1) DRAM (2) FAN MOTOR TURBO FAN LEG HEATER ELEMENT THERMAL FUSE THERMAL SWITCH INDOOR COIL THERMISTOR DRAIN SOCKET DRAIN PUMP DRAIN SENSOR HEAT EXCHANGER DRAIN PAN TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK RELAY TRANSFORMER RUN CAPACITOR INDOOR CONTROLLER BOARD FUSE CONTROLLER CASE BELL MOUTH
ROOM TEMPERATURE THERMISTOR
DRAIN HOSE ELECTRICAL BOX ELECTRICAL BOX REMOTE CONTROLLER REMOTE CONTROLLER CABLE MOTOR LEG RUBBER MOUNT SPL WASHER DRAIN PLUG FAN GUARD SENSOR HOLDER
1 1 1 1 1 4 3 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 1 1 1
(BG00C305G25) (BG00A102G10) (BG00A101G09)
(DB00H01G02)
(BG25B226H03) (BG00A894G06)
(BG00D221G19) (BG00D221G09)
MF1
H1
FS1,2
26H
RT2
DP DS
TB2 TB4 TB5
88H
T C1 I.B
F<I.B>
RT1
R,B
PM6V50-LA
240V 700W 250V 96"C 10A OFF 42"C ON 32"C
3P(L,N,;) 3P(1,2,3) 2P(1,2) JC-1A DC 12V
3+ 400V
250V 6.3A
12m
— —
— T7W 703 762 R01 W46 114
— T7W 705 300 R01 P02 706 R01 046 700 R01 W28 202 R01 K01 523 T7W 11K 355 R01 W28 266 T7W E10 480 R01 W28 529
T7W 519 716 T7W 518 716 T7W 515 716 R01 71G 215
T7W 700 799 R01 W28 255 T7W 57K 310
T7W 520 239
— R01 J01 202 R01 W28 527
— T7W 14K 200
T7W 556 305 R01 W46 130 R01 W28 105
R01 08K 097
R01 A48 524 T7W 11K 675
R01 005 533
Part numbers that are circled are not shown in the figure.
Page 28
28
FUNCTIONAL PARTS PLH-5GKHSBFT
38
Page 29
29
PLH-5
No. Parts No. Parts Name Specifications
GKHSBFT
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Price
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
26
27 28 29 30 31 32 33 34 35 36 37 38
BASE DRAM (1) DRAM (2) SEPARATOR FAN MOTOR TURBO FAN LEG HEATER ELEMENT THERMAL FUSE THERMAL SWITCH INDOOR COIL THERMISTOR DRAIN SOCKET DRAIN PUMP DRAIN SENSOR HEAT EXCHANGER DRAIN PAN TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK RELAY TRANSFORMER RUN CAPACITOR INDOOR CONTROLLER BOARD FUSE INDOOR CONTROLLER CASE BELL MOUTH BELL MOUTH
ROOM TEMPERATURE THERMISTOR
DRAIN HOSE ELECTRICAL BOX ELECTRICAL BOX REMOTE CONTROLLER REMOTE CONTROLLER CABLE MOTOR LEG RUBBER MOUNT SPL WASHER FAN GUARD DRAIN PLUG SENSOR HOLDER
1 1 1 2 2 2 4 3 2 2 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 2 6 2 2 1 1
(BG00C305G26) (BG00A102G10) (BG00A101G09) (BG00C324G07)
(DB00H010G02)
(BG25B226H03) (BG00C894G06) (BG00C894G07)
(BG00D220G13) (BG00D221G09)
MF1,2
H1
FS1,2
26H
RT2
DP DS
TB2 TB4 TB5
88H
T
C1,2
I.B
F<I.B>
RT1
R,B
PM6V50-LA
240V 1000W 250V 98"C 15A OFF 42"C ON 32"C
3P(L,N,;) 3P(1,2,3) 2P(1,2) JC-1A DC 12V
3+ 400V
250V 6.3A
12m
— — —
— T7W 703 762 R01 W46 114
— T7W 709 300 T7W 509 706 R01 046 700 R01 W28 202 R01 K01 523 T7W 11K 355 R01 W28 266 T7W E11 480 R01 W50 529 T7W 518 716 T7W 519 716 T7W 515 716 R01 71G 215
T7W 700 799 R01 W28 255 T7W 57K 310
T7W 520 239
— —
— R01 J01 202 R01 W28 527
— T7W 14K 200
T7W 556 305 R01 W46 130 R01 W28 105
R01 08K 097
T7W 11K 675
R01 A48 524 R01 005 533
Part numbers that are circled are not shown in the figure.
Page 30
30
PANEL PARTS PLH-5GKHSBFT
Part numbers that are circled are not shown in the figure.
No. Parts No. Parts Name
Specification
Q'ty / set
PLH-5
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit Amount
Price
1 2 3 4 5 6 7 8
AIR OUTLET GRILLE AIR FILTER INTAKE GRILLE HANGER G GRILLE CATCH FILTER CATCH SHUTTER PLATE PANEL SCREW
PANEL 1
2 2 2 4 4 1 1
T7W 800 003 R01 W50 500 R01 W50 691 R01 W28 098 R01 W28 054 R01 029 054 R01 W50 083 R01 W28 673
GKHSBFT
Page 31
31
No. Parts No. Parts Name
Specification
Q'ty / set
GKHSBFT
PLH-5
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit Amount
Price
1 2 3 4 5 6 7 8
9 10 11
AUTO VANE (L1) AUTO VANE (L2) AUTO VANE (2) AUTO VANE (3) AIR GUIDE (L1) AIR GUIDE (L2) AIR GUIDE (3) AIR GUIDE (4) VANE MOTOR VANE JOINT VANE BUSHING
1 1 1 1 1 1 1 1 1 4 8
MV
R01 W50 002 R01 W51 002 R01 W29 002 R01 W28 002 R01 W50 085 R01 W50 086 R01 W28 087 R01 W28 088 T7W 700 223 R01 W28 063 R01 W28 064
PANEL PARTS PLH-5GKHSBFT
Page 32
32
STRUCTURAL PART
PCH-3GKHAFT
16
11
13
14 12
27
15
10
24
17
1
5
22252619
7
369
4
23
18
2
8
Page 33
33
No.
Parts No. Parts Name
Specifications
PCH-3
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
RIGHT SIDE PANEL LEFT SIDE PANEL L.L. FILTER REAR PANEL FRONT PANEL GRILLE ASSY UNDER PANEL GRILLE HINGE GRILLE CATCH RIGHT SIDE BOX LEFT SIDE BOX GUIDE VANE ASSY-6R. GUIDE VANE ASSY-6L. GUIDE VANE ASSY-6C. AUTO VANE VANE MOTOR RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSECOVER SIDE PLATE-R. SIDE PLATE-L. SERVICE PANEL BEAM(GA) REAR SUPPORT VANE SUPPORT
1 1 2 1 1 2 1 4 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 2
(BG02H454H08) (BG02H454H04) (BG02R321G06)
MV
Remarks
(Drawing No.)
R01 17J 661 R01 17J 662 R01 17J 500 R01 29J 676 R01 29J 651 R01 17J 691 R01 29J 669 R01 17J 061 R01 17J 054 R01 17J 067 R01 17J 068 R01 17J 085 R01 18J 086 R01 29J 087 R01 29J 002 R01 29J 223 R01 17J 808 R01 17J 809 R01 17J 070 R01 17J 523 R01 17J 072 R01 18J 665 R01 18J 666 R01 17J 668
— —
GKHAFT
Page 34
34
STRUCTURAL PART PCH-5GKHSAFT
20
14 16 12 29 13 11
17
10 24
15
26
1
27
28
21
3
5
79
8
18
4
25
2
6
19
Page 35
35
No.
Parts No. Parts Name
Specifications
Q'ty / set Price
Wiring
PCH-5
GKHSAFT
Remarks
(Drawing No.)
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
R01 35J 661
1
R01 35J 662
2
R01 41J 669
3
R01 41J 676
4
R01 17J 500
5
R01 18J 500
6
R01 17J 691
7
R01 18J 691
8
R01 17J 054
9
R01 41J 651
10
R01 41J 085
11
R01 42J 086
12
R01 43J 087
13
R01 35J 223
14
R01 35J 067
15
R01 35J 068
16
R01 41J 002
17
R01 17J 061
18
R01 17J 808
19
R01 17J 809
20
R01 17J 070
21
R01 17J 523
22
R01 17J 072
23
R01 35J 665
24
R01 35J 666
25
R01 17J 668
26 27 28 29
— — —
RIGHT SIDE PANEL LEFT SIDE PANEL UNDER PANEL REAR PANEL L.L. FILTER L.L. FILTER GRILLE ASSY GRILLE ASSY GRILLE CATCH FRONT PANEL GUIDE VANE ASSY-5R. GUIDE VANE ASSY-5L. GUIDE VANE ASSY-5C. VANE MOTOR RIGHT SIDE BOX LEFT SIDE BOX AUTO VANE GRILLE HINGE RIGHT LEG LEFT LEG WIRELESS BOARD CASE JOINT SOCKET DRAIN HOSE COVER SIDE PLATE-R. SIDE PLATE-L. SERVICE PANEL BEAM(GA) REAR SUPPORT VANE SUPPORT
1 1 1 1 2 1 2 1 4 1 1 1 2 1
MV
1 1 1 4 1 1 1 1 1 1 1 1 3 1 3
(BG17H464H08) (BG02H454H04)
(BG02R805G04)
Page 36
36
No. Parts No. Parts Name Specifications
PCH-3
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4 5 6 7 8
9 10 11
12
13 14 15 16 17 18 19 20 21 22
FAN MOTOR FAN JOINT SHAFT (FAN) SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN CASING HEATER ELEMENT THERMAL SWITCH THERMAL FUSE INSULATOR INSULATOR INDOOR COIL THERMISTOR ROOM TEMPERATURE
THERMISTOR HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
1 1 1 1 1 2 1 3 3 1 1 1 3 1 1 1 1 1 1 1 2 1 1
MF
H
26H
FS1,2
RT2 RT1
Remarks
(Drawing No.)
T7W 30J 762 R01 29J 116 R01 29J 100 R01 705 103 R01 29J 130 R01 29J 114 R01 33J 114 R01 17J 110 T7W 30J 300 R01 46K 700 T7W 23J 706 R01 20J 303 R01 30J 303 R01 17J 202 R01 18J 202 T7W E08 480 R01 29J 529 R01 17J 524 R01 29J 145 T7W 20J 675 T7W 21J 675 T7W 18J 675 R01 43E 126
DC9C4P70MS
80V 700W OFF:50: ON:35: 110" 15A 250V
GKHAFT
9
13
15
11
10
6
8
21
16
20
3
19
7
17
4·18
14
2
1
5
22
12
FAN AND HEATER PARTS PCH-3GKHAFT
Page 37
37
17
10
12
4·20
9
23
8
22
18
7
21
19
24
11
6
25
2
3
1
5
16
13
14
15
FAN AND HEATER PARTS PCH-5GKHSAFT
No.
Parts No. Parts Name Specifications
1
T7W 43J 762
2
R01 29J 116
3
R01 29J 100
4
R01 705 103
5
R01 41J 130
6
R01 41J 114
7
R01 39J 114
8
R01 35J 114
9
R01 35J 110
10
R01 17J 202
11
R01 18J 202
12
T7W 43J 300
13
R01 46K 700
14
T7W 23J 706
15
R01 20J 303
16
R01 36J 303
17
T7W E09 480
18
R01 41J 529
19
R01 17J 524
20
R01 35J 145
21
T7W 25J 675
22
T7W 23J 675
23
T7W 24J 675
24
T7W 26J 675
25
R01 43E 126
FAN MOTOR FAN JOINT SHAFT SLEEVE BEARING MOTOR LEG SIROCCO FAN SIROCCO FAN SIROCCO FAN CASING INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMISTOR HEATER ELEMENT THERMAL SWITCH THERMAL FUSE INSULATOR INSULATOR HEAT EXCHANGER DRAIN PAN ASSY DRAIN PLUG BEARING SUPPORT FAN GUARD FAN GUARD FAN GUARD FAN GUARD PIECE (MOTOR)
D10B4P150MS
80V 1000W OFF:50: ON:35: 110" 15A 250V
Q'ty / set Price
PCH-5
GKHSAFT
Remarks
(Drawing No.)
1
Wiring
Diagram
Symbol
MF
Recom-
mended
Q'ty
Unit
Amount
1 1 1 1 1 1 2 4 1 1 3 1 1
RT2 RT1
H 26H FS1
1 6 1 1 1 1 1 2 1 1 1
Page 38
38
No.
Parts No. Parts Name
Specifications
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Unit
Amount
Q'ty / set Price
1 2 3 4
5
6 7 8
9 10 11 12
CONTROLLER BOARD FUSE TRANSFORMER CONTROL BOX RUN CAPACITOR RUN CAPACITOR TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK BOX COVER REMOTE CONTROLLER REMOTE CONTROLLER CORD RELAY
(BG00N015G14)
(BG02A804G13)
3
1 1 1 1 1
1 1 1 1 1 1 1
5
1 1 1 1
1 1 1 1 1 1 1 1
I.B
F1,2
T
C C
C TB2 TB4
R.B
250V 6.3A
4MF. 440V 6MF. 440V 3P (L,N, ) 3P (1,2,3) 2P (1,2)
10m
JC-1A DC12V
Remarks
(Drawing No.)
T7W 71J 310 T7W 520 239
T7W 23J 260
­T7W 39J 255 T7W 43J 255 T7W 521 716 T7W 517 716 T7W 512 716
­T7W 14K 200 R01 08K 305 R01 71G 215
GKHAFT GKHSAFT
5
12
3
2
1
6
7
8
4
10
11
9
ELECTRICAL PARTS PCH-3GKHAFT PCH-5GKHSAFT
Page 39
39
STRUCTURAL PARTS PKH-1.6FKHAFT
1
10
4
10
4
3
25
11
6
7
8
9
3
3
Part No.
Specifi-
cation
No.
Wiring
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
Q,ty/set
FKHAFT
1 2 3 4 5 6 7 8
9 10 11
R01 47J 651 R01 47J 500 R01 KV5 096 R01 A20 054 T7W 580 058 R01 KV5 658 R01 KV5 635 R01 KV5 808 R01 KV5 623
Part Name
FRONT PANEL AIR FILTER SCREW CAP FILTER CATCH SERVICE PANEL CORNER COVER BOX ASSEMBLY BACK PLATE UNDER COVER CATCH HOLDER PANEL CATCH
(
BC25R572H06
)
(
BC25G057H07
)
1 2 4 2 1 1 1 1 1 2 2
PKH-1.6
Page 40
40
Part No.
Specifica­tion
No.
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawin No.
)
Q,ty/set
PKH-1.6
FKHAFT
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
T7W 570 762 R01 KV5 114 R01 KV5 105 R01 KV5 106 R01 566 103 R01 KV5 102 R01 KV5 130 R01 KV5 530 R01 KW1 002 R01 KW2 002 R01 KV5 223 R01 KV5 527 T7W 70J 310 T7W 520 239 T7W 514 716
Part Name
FAN MOTOR
PK4V30KA
250V 6.3A
3P(L/N/;)
LINEFLOW FAN RUBBER MOUNT BEARING SUPPORT SLEEVE BEARING BEALING MOUNT MOTOR SUPPORT NOZZLE ASSEMBLY LEFT ROTARY VANE RIGHT ROTARY VANE VANE MOTOR DRAIN HOSE CONTROLLER BOARD FUSE TERMINAL BLOCK
1 1 2 1 1 1 1 1 1 1 1 1 1 2 1
MF
MV
I.B
F1<I.B>
TB2
FILTER
CHECK MODE
TEST RUN
241
( )
For 1.6,2FKHA2
1.6,2FKHA3,(FT)
( )
For 1.6,2FKHA
1.6,2FKHA1
ELECTRICAL PARTS PKH-1.6FKHAFT
22
37
18
20
6
521
33
19
16 17
38
14 15
30
35
31
29
1
34
36
7
13
12
26
27
10
32
40
39
24
25
3
2
11
9
28
8
4
42
Page 41
41
No.
Part No.
Part Name
Specific-
ation
Q,ty/set PKH-1.6
FKHAFT
Remarks
(
Drawing No.
Wiring
Diagram
)
Symbol
Recom-
mended
Q,ty
Unit
Price
Amount
16
T7W 512 716
17
T7W 517 716
18
R01 588 255
19
R01 J07 202
20
T7W 53J 799
21
T7W E06 480 T7W 54J 200
22
R01 12G 523
23
R01 KV5 135
24
R01 KV5 038
25
R01 KV5 059
26
R01 KV5 092
27
R01 KV5 048
28 29 30 31 32
T7W 581 300
33
R01 110 700
34
R01 A21 706
35 36
R01 71G 215
37
T7W 556 305
38
T7W 52J 675
39
T7W 51J 675
40
T7W B02 675
41
T7W 351 077
42
— — — —
TERMINAL BLOCK TERMINAL BLOCK RUN CAPACITOR THERMISTOR
2P(1/2)
3P(1/2/3)
2.0#F 440V
INDOOR COIL.ROOM TEMPERATURE
TRANSFORMER HEAT EXCHANGER REMOTE CONTROLLER DRAIN SOCKET MOTOR COVER GUIDE VANE ARM VANE SLEEVE CENTER SUPPORT CONTROLLER CASE WATER SHIELD CONTROL BOX COVER TERMINAL COVER HEATER ELEMENT
700W THERMAL SWITCH THERMAL FUSE
119˚C 10A 250V
INSULATOR RELAY REMOTE CONTROLLER CABLE
JC-1A DC 12V
12m FAN GUARD FAN GUARD FAN GUARD REMOTE CONTROLLER COVER
16
1 1 1 2 1
TB5 TB4
C
RT1 RT2
T 1 1
R.B 1 1
2 1 1 1 1 1 1
(
BG25B573H05
(
BG25B846H11
(
BG02A326G06
(
BG02B718H05
2 1 2 1
(
BA84D384H01
1
)
)
)
)
H
26H
FS<1.2>
)
88H 1 1 1 1
Page 42
42
FILTER
CHECK MODE
TEST RUN
241
ELECTRICAL PARTS PKH-3FKHAFT
5
1
3
31
10
7
21
18
322033
35 28 27
39
30 23 24
17
15 40
29
6
9
42
13
38
438 41 36
16
2
12
11
4
22
14
16
19
25
26
34
Part No.
Specification
No.
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
Q,ty/set
PKH-3
FKHAFT
1 2 3 4 5 6 7 8 9
R01 12G 220 R01 12G 105
— — —
R01 12G 115 R01 12G 114
R01 005 103 R01 12G 103
Part Name
FAN MOTOR RUBBER MOUNT MOTOR BAND MOTOR BAND MOTOR LEG RIGHT LINEFLOW FAN LEFT LINEFLOW FAN SLEEVE BEARING SLEEVE BEARING
1 2 1
1 1 1
1
1
1
MF
(
BG02H065H01
)
(
BG02H178H01
)
(
BG02A534G11
)
Page 43
43
No.
Part No.
Part Name
Specif­ication
Q,ty/set
PKH-3
FKHAFT
Remarks
(
Drawing No.
Wiring
Diagram
)
Symbol
Recom­mended
Q,ty
Unit
Price
Amount
R01 L15 102
10
R01 KV5 102
11 12 13 14
R01 12G 529
15
R01 12G 223 16 17 18
R01 12G 002
19
R01 12G 621
20
R01 12G 063
21
R01 KV5 527
22
T7W E07 480
23
T7W 71J 310
24
T7W 520 239
25 26 27
T7W 509 716
28
T7W 517 716
29 30
R01 588 255
31 32
T7W 50J 799 33
R01 06A 202 34
R01 22A 202 35
T7W 53J 200 36
R01 512 716 37
T7W 587 300 38
R01 230 700 39
R01 12G 706
R01 71G 215
40
T7W 556 305
41
T7W 53J 675
42 43
T7W 351 077
BEARING MOUNT BEARING MOUNT
BEARING BAND CENTER SUPPORT DRAIN PAN VANE MOTOR
GUIDE VANE GUIDE VANE(WITH HANDLE) ARM AUTO VANE CENTER COVER JOINT SHAFT DRAIN HOSE HEAT EXCHANGER CONTROLLER BOARD FUSE
CONTROLLER CASE CONTROLLER COVER
250V 6.3A
TERMINAL BLOCK TERMINAL BLOCK
TERMINAL COVER
3P(L/N/;)
3P(1/2/3)
RUN CAPACITOR TRANSFORMER
ROOM TEMPERATURE THERMISTOR
2.0#F 440V
INDOOR COIL THERMISTOR REMOTE CONTROLLER TERMINAL BLOCK HEATER ELEMENT
THERMAL SWITCH THERMAL FUSE RELAY REMOTE CONTROLLER CABLE FAN GUARD
2P(1/2)
240V 700W
70˚C OFF 50˚C ON
117˚C 10A 250V
JC-1A DC12V
12m
REMOTE CONTROLLER COVER
1 1 1 1 1 1
26
4 3 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 1 2 1 1 1 1
(
BG02L462H02
(
BG25A543H07
(
BG25J821H02
(
BG25J821H02
(
BG25H301H02
) )
) )
)
F1.2<I.B>
(
BG25B573H05
(
BG02A648G01
(
BG02J608H05
)
)
)
700W
FS1.2
MV
I.B
TB2 TB4
C
T RT1 RT2
R.B
TB5
H 26H
88H
Page 44
44
Part number that are circed is not shown in the figure.
Part No.
No.
Wiring
Diagram
Symbol
Recom­mended
Q,ty
Price
Unit
Amount
Remarks
(
Drawing No.
)
1 2 3 5 6 7 8
9 10 11
R01 12G 661 R01 12G 662 R01 12G 691 R01 12G 500 R01 12G 811 R01 12G 812 R01 12G 641 R01 12G 523 R01 12G 808
Part Name
RIGHT SIDE PANEL LEFT SIDE PANEL INTAKE GRILLE AIR FILTER NOSE UNDER PLATE TOP PLATE DRAIN SOKET BACK PLATE BOX ASSEMBLY
Specification
Q,ty/set
PKH-3
FKHAFT
1 1 2 4 1 1 1 1 1 1
(
BG00A593G91
)
STRUCTURAL PARTS PKH-3FKHAFT
11
1
5
7
6
3
108
2
Page 45
45
STRUCTURAL PARTS PUH-1.6VKAFT
1 2 3 4 5 6 7 8
9 10 11 12
14
13
R01 A00 641
R01 A00 668 R01 A00 675 R01 A00 655 R01 A00 661 R01 A00 662
R01 A00 682 R01 A00 658 T7W E00 698
R01 A00 686
Part No. SpecificationNo.
Wining
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
Part Name
TOP PANEL F.ST SCREW FRONT PANEL FAN GUARD PANEL HANDLE SERVICE PANEL SIDE PANEL LABEL (MITSUBISHI) REAR PANEL PANEL COVER
REAR GUARD MOTOR SUPPORT
BASE
LABEL (BRAND)
(510)
Q,ty/set
PUH-1.6
VKAFT
Remarks
(Drawing No.)
1
13
1 1 3 1 1 1 1
1
1
1 1 1
(ZOO4M203H10)
(DG79R130H01)
(BG00B020G55)
(BC79G510H01)
111
2
7
12 13 6 10
5 3
4
89
14
5
Page 46
46
STRUCTURAL PARTS PUH-3VKAFT
1 2 3 4 5 6 7 8
9 10 11 12 13 14
R01 A00 641
R01 A08 668 R01 A00 675 R01 A00 655 R01 A08 661 R01 A08 662
R01 A08 682 R01 A00 658 R01 A08 698
R01 A04 686
Part No. Part Name SpecificationNo.
Wining
Diagram
Symbol
Recom­mended
Q,ty
Price
Unit
Amount
TOP PANEL F.ST SCREW FRONT PANEL FAN GUARD PANEL HANDLE SERVICE PANEL SIDE PANEL LABEL (MITSUBISHI) REAR PANEL PANEL COVER REAR GUARD MOTOR SUPPORT BASE
(510)
Q,ty/set
VKAFT
Remarks
(Drawing No.)
LABEL (BRAND)
1
13
1 1 1 3 1 1 1 1 1 1 1 1
(ZOO4M203H10)
(DG79R130H01)
(BG00B020G56)
(BC79G510H01)
PUH-3
1112
7
13 12 6 10
3
5
4
895
14
Page 47
47
STRUCTURAL PARTS PUH-5YKSAFT
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
R01 A14 641
— —
R01 A14 668 R01 A00 675 R01 A00 655 R01 A14 661 R01 A14 662
R01 A14 682 R01 A14 658 R01 A14 698
Part No. Part Name
Specification
No.
Wining
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
TOP PANEL F.ST SCREW FRONT PANEL FAN GUARD PANEL HANDLE SERVICE PANEL SIDE PANEL LABEL (MITSUBISHI) REAR PANEL PANEL COVER REAR GUARD MOTOR SUPPORT MOTOR PLATE
T7W E00 686
BASE
LABEL (BRAND)
(510)
Q,ty/set
Remarks
(Drawing No.)
1
13
1
3 1 1 1 1 1 1 1 1 1 1
2
(ZOO4M203H10)
(DG79R130H01)
(BG00B020G42)
(BG02C075H03)
(BC79G510H01)
YKSAFT
PUH-5
11213 112
7
3
14 5
4
5
89
10
9
15
Page 48
48
FUNCTIONAL PARTS PUH-1.6VKAFT
14
11
19
18 22 20
19
26
21 22
23
25
24
12
28
13
5
6
1
27
2
16
15
17
1047389
Page 49
49
Part numbers that are circled are not shown in the figure.
Part No. Part Name SpecificationNo.
Q,ty/set
PUH-1.6
VKAFT
Remarks
Wining
Diagram
Symbol
Recom-
mended
Q,ty
Unit
Price
Amount
1
T7W 271 763
2
R01 A00 115
3
T7W A05 315
4
T7W 520 239
5
T7W 509 716
6
T7W 516 716
7
T7W 251 799
8
R01 A00 255
9
T7W 737 723
10
T7W 249 708
11
R01 A00 208
12
T7W E00 428
13
T7W 106 242
14
R01 V39 490
15
T7W E00 403
16
T7W 250 242
17
R01 KL5 202
18
R01 L11 418
19
R01 56H 450
20
T7W 250 425 T7W A00 425
21
R01 A00 440
22
T7W E00 411
23
T7W E00 410
24
T92 660 610
25
T7W 249 236
26
T7W E00 413
27
R01 A04 408
28
R01 KL5 451
29
T7W A04 208
30
T7W 737 215
31
T7W E00 405
OUTDOOR FAN MOTOR PROPELLER FAN OUTDOOR CONTROLLER BOARD FUSE TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR CONTACTOR HIGH PRESSURE SWITCH SOLENOID VALVE SOLENOID COIL OIL SEPARATOR 4 -W AY V ALV E 4-WAY COIL OUTDOOR COIL THERMISTOR RESTRICTOR VALVE STRAINER CAPILLARY TUBE CAPILLARY TUBE ACCUMULLAOR BALL VALVE BALL VALVE COMPRESSOR CRANKCASE HEATER CHARGE PLUG HEAT EXCHANGER STRAINER HIGH PRESSUER SWITCH RELAY FILTER DRAIER
PA6V85-UH(1.6VKA2)
250V 6.3A 3P(L,N,;) 3P(1,2,3)
2.5+ 440V 35+ 420V S-U12 230V
OFF26kg/cm2 ON21kg/cm2
4 -W AY V ALV E
{3.2{1.8✕600mm
5/8˝ 3/8˝ RE247VFC 240V 30W
LY-2F 230VAC
1
MF 1 1
1 1 1 1 1 1 1 1
O.B
F<O.B>
TB1 TB3
T C1 C2
52C
63H1 1 1
21R 1 1 1 1
21S4
RT 1 1 1 1 1 1 1 1 1
MC
HC 2 1 1 1 1
63H2
X15
1
Page 50
50
FUNCTIONAL PARTS PUH-3VKAFT
11 16 15
13
17
14
12
10
21
18
29
1
2
251927 26 24 23 20
30
978 2145
6
283
1 2 3 4 5 6
T7W 271 763 R01 A00 115
T7W 520 239 T7W 509 716 T7W 516 716
Part No. Part Name SpecificationNo.
Wining
Diagram
Symbol
Recom-
mended
Q,ty
Price
Unit
Amount
OUTDOOR FAN MOTOR PROPELLER FAN
FUSE TERMINAL BLOCK TERMINAL BLOCK
250V 6.3A
3P(1,2,3)
3P(L,N,;)
PA6V85-UF(VKA,YKA) PA6V85-UH(VKA1,YKA1)
MF
T7W A05 315
OUTDOOR CONTROLLER BOARD
O.B
F(O.B)
TB3
TB1
Remarks
PUH-3
Q,ty/set
VKAFT
1 1
1 1
1
1
Page 51
51
Part numbers that are circled are not shown in the figure.
Part No. Part Name SpecificationNo.
7
T7W 251 799
8
R01 576 255
9
T7W 616 709
10
T7W E00 428
11
T7W 106 242
12
T7W E01 425
13
R01 L11 418
14
R01 A04 450
15
T7W E00 403
16
T7W 106 242
17
R01 KL5 202
18
R01 A08 451 T7W E00 413
19 20
T7W E02 413
21
R01 A08 440
22
R01 V39 490 T7W E01 411
23
T7W E00 410
24 25
T97 500 310
26
T7W A00 236
27
R01 A00 208
28
T7W 101 723
29
R01 A10 408
30
R01 A00 425
31
T7W A04 208
32
T7W 737 215 T7W E01 405
33
TRANSFORMER OUTDOOR FAN CAPACITOR CONTACTOR
3+ 440V
S-K25(S-N25)230V SOLENOID VALVE SOLENOID COIL CAPILLARY TUBE
{4.0{2.41070 RESTRICTOR VALVE STRAINER 4 -W AY V ALV E 4-WAY COIL OUTDOOR COIL THERMISTOR STRAINER CHARGE PLUG CHARGE PLUG ACCUMULATOR OIL SEPARATOR BALL VALVE BALL VALVE COMPRESSOR CRANKCASE HEATER HIGH PRESSURE SWITCH COMPRESSOR CAPACITOR
5/8˝
3/8˝
NE-52VND
240V 38W
OFF25.5kg/cm2 ON21kg/cm
60+ 400V HEAT EXCHANGER CAPILLARY TUBE
{2.5{0.61000 HIGH PRESSUER SWITCH RELAY
LY-2F 230VAC FILTER DRAIER
mm
mm
Q,ty/set
PUH-3
VKAFT
1 1 1
Remarks
Wining
Diagram
Symbol
T
C1
52C
Recom-
mended
Q,ty
Unit
Price
Amount
1 1
21R 1 1 1 1 1
1
21S4
RT 1 1
1 1 1 1
1 1 1
2
1 1
MC
HC
63H1
C2 1 1 1 1
63H2
X15
1
Page 52
52
FUNCTIONAL PARTS PUH-5YKSAFT
1 2 3 4 5 6
T7W 256 763 R01 A00 115
T7W 520 239 T7W 511 716 T7W 516 716
Part No. Part Name SpecificationNo.
Wining
Diagram
Symbol
Recom­mended
Q,ty
Price
Unit
Amount
OUTDOOR FAN MOTOR PROPELLER FAN
T7W A06 315
OUTDOOR CONTROLLER BOARD FUSE TERMINAL BLOCK TERMINAL BLOCK
S6V60FPK
250V6.3A 5P(1L,L2,L3,N,;) 3P(1,2,3)
Remarks
Q,ty/set
MF1,2
O.B
F<O.B>
TB1 TB3
YKSAFT
2 2 1 1 1 1
PUH-5
Part numbers that are circled are not shown in the figure.
14 15
17
18
18
20
2526 24 23
10
11
1
27
27
13 12
21
2
2
22
16
191 6 5 4 73 28 8 9
Page 53
53
Part numbers that are circled are not shown in the figure.
Part No. Part Name SpecificationNo.
7
T7W 251 799
8
R01 576 255
9
T7W 517 708
10
R01 A14 428
11
T7W 106 242
12
T7W E01 425
13
R01 993 418
14
R01 42L 450 T7W 258 403
15
T7W A01 242
16
R01 KN7 202
17
T7W E00 413
18
T7W E01 413 R01 A14 440
19
R01 A14 490
20
T7W E02 411
21
T7W E00 410
22 23
T97 510 510
24
R01 86H 201
25
T7W 010 236
26
R01 A00 208
27
T7W 555 408 T7W 737 215
28
R01 A00 425
29 30
T7W A04 208 T7W E02 405
31
TRANSFORMER FAN MOTOR CAPACITOR CONTACTOR
3+ 440V
S-K20(S-N20)230V SOLENOID VALVE SOLENOID COIL CAPILLARY TUBE
{4.0{2.4940 RESTRICTOR VALVE
STRAINER 4 -W AY V ALV E SOLENOID COIL OUTDOOR COIL THERMISTOR CHARGE PLUG CHARGE PLUG ACCUMULATOR OIL SEPARATOR BALL VALVE BALL VALVE
COMPRESSOR THERMOSTAT CRANKCASE HEATER HIGH PRESSURE SWITCH
3/4˝ 3/8˝
ZR61KCE-TFD CUT125˚C IN90˚C 240V 38W
OFF25.5kg/
HEAT EXCHANGER RELAY CAPILLARY TUBE
LY2F 230V 10A
{2.5{0.6✕1000 HIGH PRESSUER SWITCH FILTER DRAIER
cm2
ON21kg/
mm
cm
mm
Q,ty/set
PUH-5
YKSAFT
1 2 1
Remarks
Wining
Diagram
Symbol
T
C1,2
52C
Recom-
mended
Q,ty
Unit
Price
Amount
1 1
21R
2
2 1 1
1
1
21S4
RT 1 1 1 1
1 1 1
1 1
2
1
MC
26C
HC
63H1
2 1
X15 1 1
63H2
1
Page 54
Page 55
Page 56
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
cCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Issued in Dec. 1997. NO.OC157 28 Printed in Japan
New publication, effective Dec. 1997 Specifications subject to change without notice.