CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR UP TO 30m PIPING LENGTH AT SHIPMENT.
The unique refrigerant circuit and a large accumulator always control the optimal refrigerant level regardless of the length
(50m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems.
Therefore, it is completely eliminated. This unique system improves the quality and reliability of the work done. It also helps
to speed up the installation work.
3
4DATA
1. REFILLING REFRIGERANT CHARGE (R-22 : kg)
Models
PUH-1VKA1·UK
PUH-1.6VKA·UK
PUH-1.6VKA
1·UK
PUH-2VKA·UK
PUH-2VKA
1·UK
PUH-2.5VKA·UK
PUH-2.5VKA
1·UK
PUH-3VKA·UK
PUH-3VKA
1·UK
PUH-3YKA·UK
PUH-3YKA
1
·UK
PUH-4YKSA·UK
PUH-4YKSA
1
·UK
PUH-5YKSA·UK
PUH-5YKSA
1
·UK
PUH-6YKSA·UK
PUH-6YKSA
1
·UK
5m
1.7
1.5
1.5
2.1
2.5
2.5
3.5
4.7
4.3
10m
1.7
1.7
1.7
2.3
2.7
2.7
3.6
4.8
4.4
15m
1.8
1.8
1.8
2.4
2.8
2.8
3.8
5.0
4.6
2. COMPRESSOR TECHNICAL DATA
Outdoor unit
Compressor Model
Winding
Resistance
(Ω)
at 20˚C
U-V
(
R-C
U-W
(
S-C
W-V
PUH-1VKA1·UK
RH173VFC
)
)
2.85
5.55
—
PUH-1.6VKA ·UK
PUH-1.6VKA
1
RH247VFC
2.00
4.55
—
Refrigerant piping length (one way)
20m
1.8
1.9
1.9
2.5
2.9
2.9
3.9
5.1
4.7
PUH-2VKA·UK
PUH-2VKA
·UK
NH38VMD
1.05
2.23
—
25m
1.9
2.1
2.1
2.7
3.1
3.1
4.1
5.3
4.9
PUH-2.5VKA·UK
1
PUH-2.5VKA
·UK
NH41VMD
1.03
2.22
—
30m
1.9
2.2
2.2
2.8
3.2
3.2
4.2
5.4
5.0
1
·UK
PUH-3VKA
35m
—
2.3
2.3
2.9
3.3
3.3
4.4
5.6
5.2
PUH-3VKA·UK
1
·UK
NH52VND
0.83
2.03
—
40m
—
2.4
2.4
3.0
3.4
3.4
4.5
5.7
5.3
45m
—
—
—
3.1
3.6
3.6
4.6
5.9
5.5
PUH-3YKA·UK
PUH-3YKA
1
·UK
NH52YDA
3.60
3.60
3.60
50m
—
—
—
3.3
3.7
3.7
4.8
6.0
5.6
PUH-4YKSA·UK
PUH-4YKSA
1
·UK
NH56YDA
3.50
3.50
3.50
Outdoor unit
Compressor Model
Winding
Resistance
(Ω)
at 25˚C
1-T3
T
T2-T
T3-T
PUH-5YKSA/5YKSA
ZR61K3-TFD
2.53-2.91
3
1
2.53-2.91
2.53-2.91
1
·UK
PUH-6YKSA/6YKSA1·UK
ZR68KC-TFD
2.31
2.31
2.31
4
5OUTLINES AND DIMENSIONS
10010
1000For 10 units or less
200
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
The upper side must be open.
Outdoor Unit-Necessary surrounding clearance
200
10
10
10
Note:Allow adequate
upper clearance
100
500
500
Service space
Front opening
Handle
for moving
138
95
Rear piping hole
23
33
Rear fresh
air intake
Side air intake
724(1)295(11-5/8)
Outlet guide
installation hole
302
Air intake
Air intake
Air outlet
870(34-1/4)
185
(7-9/32)
185
(7-9/32)
500(19-11/16)
330(13)
362(14-1/4)
1715
39.5 27.5
Terminal block for indoor and outdoor unit connection
Terminal block for power line and Ground terminal
Handle for moving
77
524
339
282
297
444
650 (25-5/8)
4060524
Service panel
Refrigerant-pipe flared
connection
[15.88 3/8F
Refrigerant-pipe flared
connection
[9.52 3/8F
Knock out hole
for front piping
(refrigerant,drainage
and wiring)
Knock out hole
for right piping
(refrigerant,drainage
and wiring)
R
20
R20
60
120
4553
25 max.
Knock out holes for
power line 2-[27
Standard bolt length
65
Front right piping holes-
detail figures
80
17
42
45
12
R6
104
33
Bottom
piping hole
2-U-shaped
notched
holes
Drain hole
Drain hole
2-12o23 Oval holes
(standard bolt M10)
Handle for moving
PUH-1VKA·UK,PUH-1.6VKA·UK,PUH-2VKA·UK Unit : mm (inch)
PUH-1.6VKA1·UK,PUH-2VKA1·UK
5
10010
1000For 10 units or less
200
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
The upper side must be open.
Outdoor Unit-Necessary surrounding clearance
200
10
10
10
Note:Allow adequate
upper clearance
100
500
500
Service space
Front opening
Handle
for moving
138
95
Rear piping hole
23
33
Rear fresh
air intake
Side air intake
724(1)295(11-5/8)
Outlet guide
installation hole
302
Air intake
Air intake
Air outlet
870(34-1/4)
185
(7-9/32)
185
(7-9/32)
500(19-11/16)
330(13)
362(14-1/4)
1715
39.5 27.5
Terminal block for indoor and outdoor unit connection
Terminal block for power line and Ground terminal
Handle for moving
179524
441
337
352
403
553
850(33-7/16)
4060524
Service panel
Refrigerant-pipe flared
connection [15.88 5/8F
Refrigerant-pipe flared
connection [9.52 3/8F
Knock out hole
for front piping
(refrigerant,drainage
and wiring)
Knock out hole
for right piping
(refrigerant,drainage
and wiring)
R
20
R20
60
120
4553
25 max.
Knock out holes for
power line 2-[27
Standard bolt length
65
Front right piping holes-
detail figures
80
17
42
45
12
R6
104
33
Bottom
piping hole
2-U-shaped
notched
holes
Drain hole
Drain hole
2-12o23 Oval holes
(standard bolt M10)
Handle for moving
PUH-2.5VKA·UK,PUH-3VKA·UK,PUH-3YKA·UKUnit : mm (inch)
PUH-2.5VKA1·UK,PUH-3VKA1·UK,PUH-3YKA1·UK
6
PUH-4YKSA·UKUnit : mm (inch)
PUH-4YKSA1·UK
4553
300
Note:Allow adequate
upper clearance
10
Front opening
10
Outdoor Unit-Necessary surrounding clearance
1715
185
(7-9/32)
100
500
Service space
500
10
Terminal block for
indoor and outdoor
unit connection
362(14-1/4)
330(13)
39.5 27.5
Terminal block for power line
and Ground terminal
Service panel
Handle
for moving
Refrigerant-pipe flared
1258(49-1/2)
959
Knock out holes for
60
connection [19.05 3/4F
Refrigerant-pipe flared
connection [9.52 3/8F
Knock out hole
for front piping
403
382
power line 2-[27
120
(refrigerant,drainage
and wiring)
104
R20
20
R
Knock out hole
for right piping
(refrigerant,
57
52
Bottom
39
drainage and wiring)
25 max.
80
R6
piping hole
2-U-shaped
Standard bolt length
65
Front right piping holes-
detail figures
17
12
notched
holes
Air intake
500(19-11/16)
185
(7-9/32)
Air intake
300
1000For 10 units or less
The upper side must be open.
870(34-1/4)
302
Air outlet
Outlet guide
724(1)295(11-5/8)
installation hole
Side air intake
52461
585
Handle for moving
Rear fresh
air intake
345
2-12o23 Oval holes
(standard bolt M10)
83524
4060524
Drain hole
33
23
Drain hole
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
15010
Handle
for moving
Rear piping hole
95
138
7
PUH-5YKSA·UK,PUH-6YKSA·UKUnit : mm (inch)
15010
1000For 10 units or less
300
Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
Outdoor Unit-Necessary surrounding clearance
The upper side must be open.
Handle
for moving
138
95
Rear piping hole
23
33
Rear fresh
air intake
Side air intake
724(1)345(13-9/16)
Outlet guide
installation hole
352
Air intake
Air intake
Air outlet
970(38-3/16)
185
(7-9/32)
185
(7-9/32)
600(23-5/8)
380(14-31/32)
412(16-1/4)
1715
39.5 27.5
Terminal block for
indoor and outdoor
unit connection
Terminal block for power line
and Ground terminal
300
10
10
10
Note:Allow adequate
upper clearance
150
500
500
Service space
Handle for moving
52461
585
83524
345
382
403
959
1258(49-1/2)
9060524
Service panel
Handle
for moving
Refrigerant-pipe flared
connection [19.05 3/4F
Refrigerant-pipe flared
connection [9.52 3/8F
Knock out hole
for front piping
(refrigerant,drainage
and wiring)
Knock out hole
for right piping
(refrigerant,
drainage and wiring)
R
20
R20
60
120
4553
25 max.
Knock out holes for
power line 2-[27
Standard bolt length
65
Front right piping holes-
detail figures
80
17
52
57
12
R6
104
39
Bottom
piping hole
2-U-shaped
notched
holes
Drain hole
Drain hole
2-12o23 Oval holes
(standard bolt M10)
Front opening
PUH-5YKSA1·UK,PUH-6YKSA1·UK
8
6WIRING DIAGRAM
RED
N
E
BLU
1
230V
ORN
RED
4
3
WHT
RED
ORN
BLU
WHT
WHT
WHT
2
X11X12X13
1234
CN2
63H1
BRN
3
1
X13X14
X14
SV
RED
RED
21R
21S4
21
S4
RED
RED
MF
ORN
C1
RED
52C
R
T
W
U
BLU
WHT
BLU
C2
S
C
MC
R
63H1
BRN
BRN
GRN/YLW
T
ORN
YLW
1
2
TB3
A
RED AC12.3V
BRN AC12.3V
RED
YLW
BLK
BLK
RED
240V
220V
4
1234
CN4T
CN3
2
3
12
SW3
SW2
O.B
LED
SW1
TO INDOOR UNIT
CONNECTING WIRES
DC 12V (polar)
TB1
POWER SUPPLY
~(1PHASE)
220—240V 50Hz
ON
OFF
LD7
LD1
LD2
LD3
LD4
LD5
LD6
LD8
F
5
RT
X11X12
CN4
TRF52C
WHT
WHT
GRY
GRY
A
B
52C
HC
CH
ZNR
R/1 S/2 T/3
BLU BLU
YLW
YLW
YLW
YLW
BLU
FC
26C
63H2
51CM
MF2
MF1
PUH-1VKA·UK,PUH-1.6VKA·UK
SYMBOL
HC
C1
C2
FC<O.B
>
F<O.B
21S4
21R
LD1~LD8
CRANKCASE HEATER
FAN MOTOR CAPACITOR
COMPRESSOR CAPACITOR
>
FAN CONTROLLER
FUSE(6A
R.V COIL
BYPASS VALVE COIL
LED(CHECK, SERVICE)
NAME
)
SYMBOL
MC
MF
O.B
SW1·2·3<O.B
T
TB1,3
RT
X11<O.B>
COMPRESSOR MOTOR(INNER THERMOSTAT)
NAME
FAN MOTOR (INNER THERMOSTAT)
OUTDOOR CONTROLLER BOARD
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
—
wWhen power supply is 220V
YELLOW
240V
ORANGE
RED
230V
220V
WHITE
PUH-2VKA·UK,PUH-2.5VKA·UK,PUH-3VKA·UK
B
52C
A
GRY
GRY
N
E
A
RED
BLK
RED
BLK
GRN/YLW
52C
RED
C2
BLU
BLUBLU
5
MF2
RED
LED
O.B
LD8
LD7
LD6
LD5
LD4
LD3
LD2
63H1
YLW
YLW
YLW
YLW
BRN
BRN
HC
WHT
WHT
BLK
BLK
RED
RED
S
C
R
BLU
WHT
BLU
W
U
T
R
WHT
WHT
220V
230V
240V
RED
ORN
YLW
T
AC12.3V
AC
12.3V
BRN
BRN
RED
RED
C1
ORN
RED
BLU
WHT
ORN
BLU
WHT
F.C
MF1
R
ST
26C
63H1
51CM
F
ZNR
CH52C21S4TRFSV
X11X12X13X14
4
123
CN4T
4
1234
CN4
TH
LD1
CN2
CN3
1
2
3
12
ON
OFF
SW3
SW2
SW1
TB3
TB1
BRN
ORN
YLW
3
2
1
POWER SUPPLY
~(1PHASE)
220—240V 50Hz
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
MF
1
2
4
3
MC
21R
21
S4
X11X12X13X14
SYMBOL
CN3(O.B
)
CN4T(O.B
HC
C1
C2
)
FC(O.B
)
F(O.B
LD1-LD8(O.B
CONNECTOR (CONNECTING)
WIRES INDOOR/OUTDOOR
)
CONNECTOR(TRANSFORMER)
CRANKCASE HEATER
FAN MOTOR CAPACITOR
RUN CAPACITOR FOR MC
FAN CONTROLLER
FUSE(6A
)
LED(CHECK,SERVICE)
NAME
)
SYMBOL
MC
MF
O.B
21R
SW1·2·3(O.B
T
TB1,3
TH
X11(O.B
)
COMPRESSOR
FAN MOTOR
OUTDOOR CONTROLLER BOARD
BYPASS VALVE SOLENOID COIL
NOTE : If the operation of the protection device stops to function. then check the display flashes.
CAUTIONS FOR SERVICING
●
Connect the lead wires according to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Since LD8 lights when normal power is furned ”ON”, check the power supply with the ON or OFF LD8.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used,
change the wiring connection in the following procedure.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
(
when both Nos.1 and 2 of are ”OFF”
Output display (light
SW3
)
Pipe sensor short/open
TH overheat protecyion
Defective input
)
Check display (flash
—
—
—
—
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
wWhen power supply is 220V
YELLOW
ORANGE
RED
240V
230V
220V
WHITE
11
PUH-2VKA1·UK,PUH-2.5VKA1·UK,PUH-3VKA1·UK
A2
52C
A1
GRY
GRY
N
L
TB1
RED
BLU
RED
BLU
GRN/YLW
52C
RED
C2
BLU
BLUBLU
5
MF2
RED
LED
O.B
LD8
LD7
LD6
LD5
LD4
LD3
LD2
63H1
YLW
YLW
YLW
YLW
BRN
BRN
HC
WHT
WHT
BLU
BLU
RED
RED
S
C
R
BLU
WHT
BLU
T2/6
T1/2
L3/5
L1/1
WHT
WHT
220V
230V
240V
RED
ORN
YLW
T
AC12.3V
AC
12.3V
BRN
BRN
RED
RED
C1
ORN
RED
BLU
WHT
ORN
BLU
WHT
F.C
MF1
R
ST
26C
63H1
51CM
F
ZNR
CH52C21S4TRFSV
X11X12X13X14
4
123
CN4T
4
1234
CN4
TH
LD1
CN2
CN3
1
2
3
12
ON
OFF
SW3
SW2
SW1
TB3
BRN
ORN
YLW
3
2
1
POWER SUPPLY
~(1PHASE)
220—240V 50Hz
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
MF
1
2
4
3
MC
21R
21
S4
X11X12X13X14
SYMBOL
CN3(O.B
)
CN4T(O.B
HC
C1
C2
FC(O.B
F(O.B
)
)
LD1-LD8(O.B
CONNECTOR (CONNECTING)
WIRES INDOOR/OUTDOOR
)
CONNECTOR(TRANSFORMER)
CRANKCASE HEATER
FAN MOTOR CAPACITOR
RUN CAPACITOR FOR MC
FAN CONTROLLER
FUSE(6.3A
)
LED(CHECK,SERVICE)
NAME
)
SYMBOL
MC
MF
O.B
21R
SW1·2·3(O.B
T
TB1,3
TH
X11(O.B
)
COMPRESSOR
FAN MOTOR
OUTDOOR CONTROLLER BOARD
BYPASS VALVE SOLENOID COIL
NOTE : If the operation of the protection device stops to function. then check the display flashes.
CAUTIONS FOR SERVICING
●
Connect the lead wires according to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Since LD8 lights when normal power is furned ”ON”, check the power supply with the ON or OFF LD8.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used,
change the wiring connection in the following procedure.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
12
(
when both Nos.1 and 2 of are ”OFF”
)
SW3
Check display (flash
Pipe sensor short/open
TH overheat protecyion
Defective input
)
How to use SW1 and 2
●
)
—
—
—
—
—
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
wWhen power supply is 220V
YELLOW
ORANGE
RED
240V
230V
220V
WHITE
PUH-3YKA·UK
SYMBOL
CN3<O.B
CN4T<O.B
C
FC<O.B
F<O.B
HC
LD1-LD8<O.B
MC
MF
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220—415/240V 50Hz
>
CONNECTOR (CONNECTING
WIRES INDOOR/OUTDOOR)
>
CONNECTOR (TRANSFORMER)
FAN MOTOR CAPACITOR
>
FAN CONTROLLER
>
FUSE(6A
CRANKCASE HEATER
>
LED(CHECK,SERVICE)
COMPRESSOR
FAN MOTOR
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
)
1
2
3
TB3
RED
NAME
YLW
ORN
BRN
RED
BRN
BRN
AC
12.3V
AC12.3V
TB1
A1
A2
A3
N
E
T
O.B
SW1
SW2
SW3
4
GRN/YLW
12
YLW
ORN
RED
LED
OFF
ON
3
2
CN3
1
CN4T
LD1
LD2
123
240V
230V
220V
LD3
SYMBOL
O.B
SW1·2·3<O.B
T
TB1,3
TH
X11<O.B
X12<O.B
X13<O.B
X14<O.B
ZNR<O.B>
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTIONS FOR SERVICING
●
Connect the lead wires according to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “A2” or “A3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “A1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnoction procedure
In case of reverse rotation
Unit side
wiring
A1A2A3
Field wiring
Change thie side
123
wWhen power supply is 220V
YELLOW
ORANGE
RED
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Outdoor unit
terminal
WHITE
13
PUH-3YKA1·UK
SYMBOL
CN3<O.B
CN4T<O.B
C
FC<O.B
F<O.B
HC
LD1-LD8<O.B
MC
MF
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220—415/240V 50Hz
>
CONNECTOR (CONNECTING
WIRES INDOOR/OUTDOOR)
>
CONNECTOR (TRANSFORMER)
FAN MOTOR CAPACITOR
>
FAN CONTROLLER
>
FUSE(6.3A
CRANKCASE HEATER
>
LED(CHECK,SERVICE)
COMPRESSOR
FAN MOTOR
1
2
3
TB3
NAME
)
YLW
ORN
BRN
RED
RED
AC
12.3V
AC12.3V
BRN
BRN
TB1
L1
L2
L3
N
T
O.B
SW1
SW2
SW3
4
GRN/YLW
LED
12
3
2
1
CN4T
YLW
ORN
RED
OFF
ON
LD1
CN3
LD2
123
240V
230V
220V
LD3
4
LD4
LD5
RED
WHT
BLK
LD6
RED
RED
WHT
BLK
BLU
SYMBOL
O.B
SW1·2·3<O.B
T
TB1,3
TH
X11<O.B
X12<O.B
X13<O.B
X14<O.B
ZNR<O.B>
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTIONS FOR SERVICING
●
Connect the lead wires according to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnoction procedure
In case of reverse rotation
Unit side
wiring
L1L2L3
Field wiring
Change thie side
123
wWhen power supply is 220V
YELLOW
ORANGE
RED
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
14
Outdoor unit
terminal
WHITE
PUH-4YKSA·UK
SYMBOL
CN3<O.B
CN4T<O.B
C1,2
FC<O.B
F<O.B
HC
LD1-LD8<O.B
MC
MF1,2
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220 — 415/240V 50Hz
>
CONNECTOR (CONNECTING
WIRES INDOOR/OUTDOOR)
>
CONNECTOR (TRANSFORMER)
FAN MOTOR CAPACITOR
>
FAN CONTROLLER
>
FUSE(6A
CRANKCASE HEATER
>
LED(CHECK,SERVICE)
COMPRESSOR
FAN MOTOR
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
1
2
3
TB3
NAME
)
YLW
ORN
BRN
RED
RED
AC
12.3V
AC12.3V
BRN
BRN
TB1
A1
A2
A3
N
E
O.B
T
LED
SW1
SW2
SW3
12
3
2
1
CN4T
4
YLW
ORN
RED
GRN/YLW
OFF
ON
CN3
LD1
123
240V
230V
220V
LD2
LD3
LD4
4
SYMBOL
O.B
SW1·2·3<O.B
T
TB1,3
TH
X11<O.B
X12<O.B
X13<O.B
X14<O.B
ZNR<O.B>
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTIONS FOR SERVICING
●
Connect the lead wires according to the colo indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “A2” or “A3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “A1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Unit side
wiring
Field wiring
Change thie side
Power line reconnoction procedure
In case of reverse rotation
A1A2A3
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
123
and 2.)
wWhen power supply is 220V
YELLOW
ORANGE
RED
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Outdoor unit
terminal
WHITE
15
PUH-4YKSA1·UK
SYMBOL
CN3<O.B
CN4T<O.B
C1,2
FC<O.B
F<O.B
HC
LD1-LD8<O.B
MC
MF1,2
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220 — 415/240V 50Hz
>
CONNECTOR (CONNECTING
WIRES INDOOR/OUTDOOR)
>
CONNECTOR (TRANSFORMER)
FAN MOTOR CAPACITOR
>
FAN CONTROLLER
>
FUSE(6.3A
CRANKCASE HEATER
>
LED(CHECK,SERVICE)
COMPRESSOR
FAN MOTOR
1
2
3
TB3
YLW
ORN
BRN
RED
RED
AC12.3V
NAME
)
BRN
BRN
AC
12.3V
TB1
L1
L2
L3
N
O.B
T
LED
SW1
SW2
SW3
12
3
2
1
CN4T
4
YLW
ORN
RED
GRN/YLW
OFF
ON
CN3
LD1
123
240V
230V
220V
LD2
LD3
4
LD4
RED
WHT
BLK
LD5
LD6
RED
RED
WHT
BLK
BLU
LD7
CN2
RED
WHT
WHT
SYMBOL
O.B
SW1·2·3<O.B
T
TB1,3
TH
X11<O.B
X12<O.B
X13<O.B
X14<O.B
ZNR<O.B>
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTIONS FOR SERVICING
●
Connect the lead wires according to the colo indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Unit side
wiring
Field wiring
Change thie side
Power line reconnoction procedure
In case of reverse rotation
L1L2L3
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
123
and 2.)
wWhen power supply is 220V
YELLOW
ORANGE
RED
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
16
Outdoor unit
terminal
WHITE
PUH-5YKSA·UK
SYMBOL
MC
MF1,2
C1,2
TH
HC
49C
52C
21S4
21R
T
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220—415/240V 50Hz
COMPRESSOR
FAN MOTOR
FAN MOTOR CAPACITOR
OUTDOOR COIL THERMISTOR
CRANKCASE HEATER
INTERNAL THERMOSTAT FOR MC
COMPRESSOR CONTACTOR
R.V COIL
BYPASS VALVE COIL
TRANSFORMER
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTION FOR SERVICING
●
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “A2” or “A3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “A1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnoction procedure
In case of reverse rotation
Unit side
wiring
A1A2A3
Field wiring
Change thie side
123
wWhen power supply is 220V
YELLOW
ORANGE
RED
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Outdoor unit
terminal
WHITE
17
PUH-5YKSA1·UK
SYMBOL
MC
MF1,2
C1,2
TH
HC
49C
52C
21S4
21R
T
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220—415/240V 50Hz
COMPRESSOR
FAN MOTOR
FAN MOTOR CAPACITOR
PIPE TEMP. THERMISTOR
CRANKCASE HEATER
INTERNAL THERMOSTAT FOR MC
COMPRESSOR CONTACTOR
4-WAY VALVE SOLENOID COIL
BYPASS VALVE SOLENOID COIL
TRANSFORMER
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTION FOR SERVICING
●
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnoction procedure
In case of reverse rotation
Unit side
wiring
L1L2L3
Field wiring
Change thie side
123
wWhen power supply is 220V
YELLOW
ORANGE
RED
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
18
Outdoor unit
terminal
WHITE
PUH-6YKSA·UK
SYMBOL
MC
MF1,2
C1,2
TH
HC
49C
52C
21S4
21R
T
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220—415/240V 50Hz
COMPRESSOR
FAN MOTOR
FAN MOTOR CAPACITOR
OUTDOOR COIL THERMISTOR
CRANKCASE HEATER
INTERNAL THERMOSTAT FOR MC
COMPRESSOR CONTACTOR
R.V COIL
B.V COIL
TRANSFORMER
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTION FOR SERVICING
●
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “A2” or “A3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “A1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnoction procedure
In case of reverse rotation
Unit side
wiring
A1A2A3
Field wiring
Change thie side
123
wWhen power supply is 220V
YELLOW
ORANGE
RED
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Outdoor unit
terminal
WHITE
19
PUH-6YKSA1·UK
SYMBOL
MC
MF1,2
C1,2
TH
HC
49C
52C
21S4
21R
T
TO INDOOR UNIT
CONNECTING WIRES
DC 12V
POWER SUPPLY
3N~(3PHASE 4WIRES)
380/220—415/240V 50Hz
COMPRESSOR
FAN MOTOR
FAN MOTOR CAPACITOR
PIPE TEMP. THERMISTOR
CRANKCASE HEATER
INTERNAL THERMOSTAT FOR MC
COMPRESSOR CONTACTOR
4-WAY VALVE SOLENOID COIL
BYPASS VALVE SOLENOID COIL
TRANSFORMER
NOTE : If the operation stops to function of the protection device, the check display flashes.
CAUTION FOR SERVICING
●
Connect the lead wires accordling to the color indication of sticker on the compressor terminal.
CAUTIONS FOR POWER SUPPLY WIRING
●
Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor
operation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power
is turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side)
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
w
Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
in the following procedure.
)
Check display (flash
—
—
How to use SW1 and 2
●
)
Pressing erases the past check contents loaded on the
microcomputer.
●
The output display (light) remains lit during operation but
pressing displays the past check contents in flashing
mode. Pressing the switch again returns to output display
(light).
SW1
SW2
Power line reconnoction procedure
In case of reverse rotation
Unit side
wiring
L1L2L3
Field wiring
Change thie side
123
wWhen power supply is 220V
YELLOW
ORANGE
RED
Change 2 out of 1.
2 and 3.
(This example shows
reconnection of 1
and 2.)
240V
230V
220V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Refrigerant flow in cooling
Refrigerant flow in heating
PUH-1VKA·UK
Unit : mm
PUH-1.6/2/2.5/3VKA·UK
1.6/2/2.5/3VKA
1
·UK
3YKA·UK
3YKA
1
·UK
21
Indoor unit
Outdoor unit
Indoor
heat
exchanger
Thermistor
TH2
Strainer
Flexible tube
Service
port
Accumulator
Ball valve
Strainer
Compressor
Refrigerant pipe
(option)
19.05A({3/4")
(with heat insulator)
Refrigerant pipe
(option)
9.52A({3/8")
(with heat insulator)
Ball valve
(with service port)
Strainer
Bypass
valve
Restrictor
valve
4-way valve
Oil
separator
Service
port
High pressure
Control switch
Outdoor heat exchanger
Thermistor
TH
Capillary tube
PUH-5
....
(O.D.4.0OI.D.2.4-R840)O2
PUH-6
....
(O.D.4.0OI.D.2.4-R1200)O2
Distributor
with
strainer
Restrictor valve
Capillary
tube
Flared
connection
THERMAL
SWITCH
Capillary tube
PUH-4YKSA·UK
Indoor unit
Outdoor unit
Indoor
heat
exchanger
Thermistor
(TH2)
Strainer
Flexible tube
Service
port
Accumulator
Ball valve
Strainer
Compressor
Refrigerant pipe
(option)
19.05A({3/4")
(with heat insulator)
Refrigerant pipe
(option)
9.52A({3/8")
(with heat insulator)
Ball valve
(with service port)
Strainer
Bypass
valve
Restrictor
valve
4-way valve
Oil separator
Service
port
High pressure
Control switch
Outdoor heat exchanger
Thermistor
TH3
Capillary
tube
(O.D.3.2OI.D.2.0-R820)O2pcs
Distributor
with
strainer
Restrictor
valve
Capillary
tube
Flared
connection
Refrigerant flow in cooling
Refrigerant flow in heating
PUH-4YKSA1·UK
Unit : mm
PUH-5YKSA·UK,PUH-6YKSA·UK
PUH-5YKSA
22
1
·UK,PUH-6YKSA1·UK
8DISASSEMBLY PROCEDURE
Model:PUH-4/5/6YKSA·UK
OPERATING PROCEDUREPHOTOS
1. Removing the electrical parts
(1)
Remove the 3 screws at the front and 2 screws at the
rear of the top panel.
(2)
Remove the top panel.
(3)
Remove the screw from the panel cover. Unhook the
catches from the side panel and pull the panel cover
toward you to remove.
(4)
Remove the screw from the service panel. Pull down
the service panel to unhook the catches. Pull the
service panel toward you to remove.
Photo 1
Photo 2
Screws
Panel cover
Run capacitor
52C relay
2. Removing the fan motors
(1)
Remove the 3 screws and the front panel.
Open the panel to a 45-degree angle and lift it to
remove. The panel is hooked by 3 catches on the left
side.
(2)
Remove the propeller nuts and the propellers.
(3)
Remove the 3 screws each and the fan motors.
Disconnect the lead connectors.
Screws
Photo 3
Propeller
nut
Motor support
Terminal block
Separator support place
High pressure
switch
Valve bed
PropellerCrankcase heater
23
OPERATING PROCEDUREPHOTOS
3. Removing the heat exchanger and the compressor
NOTE :When removing the panels, move them up and down
to unhook catches.
(1)
Remove the rear panel set screws : 2 screws at the
front, 1 screw on the side, and 3 screws at the rear.
(2)
Remove the valve bed.
(3)
Open the rear panel rearward to remove.
(4)
Remove the 4 screws of the right side panel and
remove it.
(5)
Remove the 3 screws of the rear guard and remove it.
(6)
Remove the 4screws of the separator support plate
and remove it.
(7)
Remove the 2 screws of the motor support and
remove it.
(8)
Remove the 5 screws of the valve bed. Lift the valve
bed to unhook the catches on both sides.
(9)
Remove the electrical parts box.
)
(
Disconnect the connectors of the high-pressure
10
switch, crankcase heater, shell thermo, and fan motor.
(11)
Remove the 2 screws of the separator and remove it.
(12)
Remove the 2 screws of the heat exchanger and
remove it.
(13)
Detach the welded points of the pipe.
(14)
Remove the 3 nuts of the compressor and remove it.
(15)
Detach the welded points of the suction pipe and
discharge pipe.
Photo 4
Screws
Screws
Photo 5
Heat exchanger
Accumulator
Photo 6
Charge plug
Ball valve
Accumulator
Accumulator
24
Compressor
9PARTS LIST
STRUCTURAL PARTS
PUH-1/1.6VKA·UK
PUH-1.6VKA1·UK
2
7
5
3
4
112
8105
No.
Part No.
(Drawing No.)
1
R01 A00 641
2
(Z004M203H10)
3
S70 020 668
4
S70 001 675
5
R01 A00 655
6
S70 020 661
7
R01 A00 662
8
(DG79R130H01)
9
(BC79G510H01)
10
R01 A00 682
11
R01 A00 658
12
R01 A00 698
13
S70 021 130
14
S70 020 686
Part name
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
LABEL (BRAND)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE
13 14611
Q'ty/set
Specification
(5O10)
PUH-1/1.6
VKA.UK
VKA1.UK
1
13
1
1
3
1
1
1
1
1
1
1
1
1
9
Remarks
Wiring
Diagram
Symbol
Recommended
Q'ty
Unit
Price
Amount
NOTE: When you need the following parts, please order to MCEUKA.
1The parts which parts number starts with “S”
Ex.) S70 020 668 FRONT PANEL
2The parts which drawing number is listed instead of parts number.
Ex.) (Z004M203H10) F.ST SCREW
3The parts which is not listed in the parts list.
25
STRUCTURAL PARTS
No.
Part No.
(Drawing No.)
Part name
Specification
Remarks
Unit
Amount
Wiring
Diagram
Symbol
Recom-
mended
Q'ty
Q'ty/set
PUH-2
VKA.UK
VKA1.UK
Price
1
2
3
4
5
6
7
8
9
10
11
12
13
14
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
LABEL (BRAND)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
LABEL (BRAND)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
LABEL (BRAND)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE
TOP PANEL
F.ST SCREW
FRONT PANEL
FAN GUARD
PANEL HANDLE
SERVICE PANEL
SIDE PANEL
LABEL (MITSUBISHI)
LABEL (BRAND)
REAR PANEL
PANEL COVER
REAR GUARD
MOTOR SUPPORT
BASE