Mitsubishi PEAD-RP·GA, PKA-RP·FAL(2), PEAD-RP·EA(2), PKA-RP·GAL, PLA-RP35BA Technical Data Book

...
TECHNICAL DATA BOOK
CONTENTS
1. REFERENCE SERVICE MANUAL ············································· 2
2. SPECIFICATIONS ······································································ 3
3. OUTLINES AND DIMENSIONS ···············································10
4. WIRING DIAGRAM ··································································· 18
5. REFRIGERANT SYSTEM DIAGRAM ······································ 28
7. CORRECTION FACTORS ························································ 31
8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ·········· 32
9. AIR FLOW DA TA ······································································35
10. NOISE CRITERION CURVES ··················································45
11. OPTIONAL PARTS ············································································51
<Indoor unit>
[Model names]
R410A
PLA-RP·BA(2) PEAD-RP·EA(2) PEAD-RP·GA PKA-RP·GAL PKA-RP·FAL(2)
<Outdoor unit> [Model names]
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
PUHZ-HRP71/100VHA PUHZ-HRP100/125YHA PUHZ-HRP71/100VHA2 PUHZ-HRP100/125YHA2
September 2008
INVERTER
Zubadan
No. OCS11
REVISED EDITION-A
• Please void OCS11.
Revision :
PLA-RP
•BA2 and PUHZ-HRP
•HA2 are added in REVISED EDITION-A.
• Some descriptions have been modified.
2
For information on service, please refer to the service manual as follows.
Model name Service Ref. Service
Manual No.
PLA-RP35/50/60/100/125BA PLA-RP71/100/125BA2
PLA-RP35/50/60/100/125BA(1).UK/BA#2.UK PLA-RP71/100/125BA2.UK
OCH412 OCB412
PKA-RP35/50GAL PKA-RP35/50GAL(#1)
OC330
PKA-RP60/100FAL PKA-RP50FAL2
PKA-RP60/100FAL(#1) PKA-RP50FAL2(#1)
OC331
PEAD-RP50/60/71/125EA
PEAD-RP50/60/71/125EA(#1).UK
HWE0521
PEAD-RP35/100EA2
PEAD-RP35/100EA2(#1).UK
PEAD-RP60/71/100GA PEAD-RP60/71/100GA(#1).UK
HWE0506
1-2. OUTDOOR UNIT
Model name Service Ref. Service
Manual No.
OCH425 OCB425
PUHZ-HRP71/100VHA
PUHZ-HRP71/100VHA
PUHZ-HRP100/125YHA
PUHZ-HRP100/125YHA
PUHZ-HRP71/100VHA2
PUHZ-HRP71/100VHA2
PUHZ-HRP100/125YHA2
PUHZ-HRP100/125YHA2
1-1. INDOOR UNIT
1
REFERENCE SERVICE MANUAL
3
2
SPECIFICATIONS
2-1. CEILING CASSETTE TYPE
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW Total input kW EER Energy label class SHF
Heating Capacity Btu/h
kW Total input kW COP Energy label class Booster heater kW
Power supply Phase
Cycle Hz Voltage V Breaker size A
Indoor unit Air flow CMM
(Low-Medium2-Medium1-High)
CFM External pressure Pa Sound level
dB(A)
(Low-Medium2-Medium1-High)
External finish (Panel) Dimension W : mm Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch Weight kg Unit (Panel) lbs Field drain pipe O.D. mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
dB(A)
Sound level at heating
dB(A) External finish Dimension W : mm
D : mm H : mm
W : inch
D : inch H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
Height difference
m
Length
m
PLA-RP71BA2 PLA-RP100BA2
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2
24,200 34,100
7.1 ( 4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 )
1.94 2.44
3.66 4.10 AA
0.73 0.74
27,300 38,200
8.0 ( 4.5 - 10.2 ) 11.2 ( 4.5 - 14.0 )
1.90 2.54
4.21 4.41 AA
-­1
50
230
32 40
14 - 16 - 18 - 21
495 - 565 - 635 - 740
20 - 23 - 26 - 30
710 - 810 - 920 - 1060
0
32 - 34 - 37 - 4028 - 30 - 32 - 34
White Munsell 6.4Y 8.9/0.4
840 (950) 840 (950)
298 (35)258 (35)
33-1/16 (37-3/8) 33-1/16 (37-3/8)
10-3/16 (1-3/8) 11-3/4 (1-3/8)
23 (6)
51 (13)
27 (6)
60 (13)
32
1-1/4
100
3,530
51 52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
120 265
15.88 5/8
9.52 3/8
Max. 30 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32°C, W.B. 23°C
D.B. 46°C
Lower limit
D.B. 19°C, W.B. 15°C D.B. -5°C *
Heating
Upper limit
D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit
D.B. 17°C
D.B. -25°C, W.B. -25°C
4. Above data are based on the indicated voltage.
* If optional air protect guide is installed : D.B.-18°C
Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz
4
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW Total input kW EER Energy label class SHF
Heating Capacity Btu/h
kW Total input kW COP Energy label class Booster heater kW
Power supply Phase
Cycle Hz Voltage V Breaker size A
Indoor unit Air flow CMM
(Low-Medium2-Medium1-High)
CFM External pressure Pa Sound level
dB(A)
(Low-Medium2-Medium1-High)
External finish (Panel) Dimension W : mm Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch Weight kg Unit (Panel) lbs Field drain pipe O.D. mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
dB(A)
Sound level at heating
dB(A) External finish Dimension W : mm
D : mm H : mm
W : inch
D : inch H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
Height difference
m
Length
m
PLA-RP100BA2 PLA-RP125BA2
PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
34,100 42,700
10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 )
2.50 3.79
4.00 3.30 AA
0.74 0.71
38,200 47,800
11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 )
2.60 3.57
4.31 3.92 AA
-­3
50
400
16
20 - 23 - 26 - 30 22 - 25 - 28 - 31
710 - 810 - 920 - 1060 780 - 880 - 990 - 1090
00
32 - 34 - 37 - 40 34 - 36 - 39 - 41
White Munsell 6.4Y 8.9/0.4
840 (950) 840 (950)
298 (35) 33-1/16 (37-3/8) 33-1/16 (37-3/8)
11-3/4 (1-3/8)
27 (6)
60 (13)
32
1-1/4
100
3,530
51 52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
134 295
15.88 5/8
9.52 3/8
Max. 30 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32°C, W.B. 23°C
D.B. 46°C
Lower limit
D.B. 19°C, W.B. 15°C D.B. -5°C *
Heating
Upper limit
D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit
D.B. 17°C
D.B. -25°C, W.B. -25°C
4. Above data are based on the indicated voltage.
* If optional air protect guide is installed : D.B.-18°C
Indoor unit Single phase 230V 50Hz
3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz)
5
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW Total input kW EER Energy label class SHF
Heating Capacity Btu/h
kW Total input kW COP Energy label class Booster heater kW
Power supply Phase
Cycle Hz Voltage V Breaker size A
Indoor unit Air flow CMM
(Low-Medium2-Medium1-High)
CFM External pressure Pa Sound level
dB(A)
(Low-Medium2-Medium1-High)
External finish (Panel) Dimension W : mm Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch Weight kg Unit (Panel) lbs Field drain pipe O.D. mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
dB(A)
Sound level at heating
dB(A) External finish Dimension W : mm
D : mm H : mm
W : inch
D : inch H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
Height difference
m
Length
m
PLA-RP100BA PLA-RP100BA PLA-RP125BA
PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA
34,100 34,100 42,700
10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 ) 12.5 ( 5.5 - 14.0 )
3.02 3.02 3.87
3.31 3.31 3.23 AAA
0.74 0.74 0.71
38,200 38,200 47,800
11.2 ( 4.5 - 14.0 ) 11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 )
3.10 3.10 3.88
3.61 3.61 3.61 AAA
---
13
50 50
230 400
32 16
20 - 23 - 26 - 30 22 - 25 - 28 - 31
710 - 810 - 920 - 1060 780 - 880 - 990 - 1090
00
32 - 34 - 37 - 40 34 - 36 - 39 - 41
White Munsell 6.4Y 8.9/0.4
840 (950) 840 (950)
298 (35) 33-1/16 (37-3/8) 33-1/16 (37-3/8)
11-3/4 (1-3/8)
25 (6)
55 (13)
32 1-1/4 100
3,530
52
53
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8 120 134 265 295
15.88 5/8
9.52 3/8
Max. 30 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32°C, W.B. 23°C
D.B. 46°C
Lower limit
D.B. 19°C, W.B. 15°C D.B. -5°C *
Heating
Upper limit
D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit
D.B. 17°C
D.B. -25°C, W.B. -25°C
4. Above data are based on the indicated voltage.
* If optional air protect guide is installed : D.B.-18°C
Indoor unit Single phase 230V 50Hz
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz(HRP100, 125Y : 342~457V, 50Hz)
6
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW Total input kW EER Energy label class SHF
Heating Capacity Btu/h
kW Total input kW COP Energy label class Booster heater kW
Power supply Phase
Cycle Hz Voltage V Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM External pressure Pa Sound level
dB(A)
(Low-High)
External finish (Panel) Dimension W : mm Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch Weight kg Unit (Panel) lbs Unit drain pipe O.D.
Outdoor unit Air flow CMM
CFM
Sound level at cooling
dB(A)
Sound level at heating
dB(A) External finish Dimension W : mm
D : mm H : mm
W : inch
D : inch H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
Height difference
m
Length
m
PEAD-RP71EA PEAD-RP100EA2
PUHZ-HRP71VHA PUHZ-HRP100VHA
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2
24,200 34,100
7.1 (4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 )
2.15 3.06
3.30 3.27 AA
0.83 0.86
27,300 38,200
8.0 ( 4.5 - 10.2 ) 11.2 ( 4.5 - 14.0 )
2.34 3.10
3.42 3.61 BA
-­1
50
230
32 (VHA)/ 40 (VHA2)32
20 - 25 33.5 - 42
706 - 883 1183 - 1483
70 70
37-41 44-50
Galvanized sheets
1175 1415
740 325
46-1/8 55-11/16
29-1/8
12-13/16
44 65 97 143
R1 (External thread)
100
3,530 52 (VHA)/ 51 (VHA2) 53 (VHA)/ 52 (VHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
120 265
15.88 5/8
9.52 3/8
Max. 30 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32°C, W.B. 23°C
D.B. 46°C
Lower limit
D.B. 19°C, W.B. 15°C D.B. -5°C *
Heating
Upper limit
D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit
D.B. 17°C
D.B. -25°C, W.B. -25°C
4. Above data are based on the indicated voltage.
* If optional air protect guide is installed : D.B.-18°C
Indoor unit Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz
2-2. CEILING-CONCEALED TYPE
7
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW Total input kW EER Energy label class SHF
Heating Capacity Btu/h
kW Total input kW COP Energy label class Booster heater kW
Power supply Phase
Cycle Hz Voltage V Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM External pressure Pa Sound level
dB(A)
(Low-High)
External finish (Panel) Dimension W : mm Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch Weight kg Unit (Panel) lbs Unit drain pipe O.D.
Outdoor unit Air flow CMM
CFM
Sound level at cooling
dB(A)
Sound level at heating
dB(A) External finish Dimension W : mm
D : mm H : mm
W : inch
D : inch H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
Height difference
m
Length
m
PEAD-RP100EA2 PEAD-RP125EA
PUHZ-HRP100YHA PUHZ-HRP125YHA PUHZ-HRP100YHA2 PUHZ-HRP125YHA2
34,100 42,700
10.0 ( 4.9 - 11.4 ) 125. ( 5.5 - 14.0 )
3.06 3.89
3.27 3.21 AA
0.86 0.82
38,200 47,800
11.2 ( 4.5 - 14.0 ) 14.0 ( 5.0 - 16.0 )
3.10 3.88
3.61 3.61 AA
-­3
50
400
16
33.5 - 42 33.5 - 42
1183 - 1483 1183 - 1483
70 70
44 - 50 44 - 50
Galvanized sheets
1415
740 325
55-11/16
29-1/8
12-13/16
65
143
R1 (External thread)
100
3,530 52 (YHA)/ 51 (YHA2) 53 (YHA)/ 52 (YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
134 295
15.88 5/8
9.52 3/8
Max. 30 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32°C, W.B. 23°C
D.B. 46°C
Lower limit
D.B. 19°C, W.B. 15°C D.B. -5°C *
Heating
Upper limit
D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit
D.B. 17°C
D.B. -25°C, W.B. -25°C
4. Above data are based on the indicated voltage.
* If optional air protect guide is installed : D.B.-18°C
Indoor unit Single phase 230V 50Hz
3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage Indoor unit:198~264V, 50Hz Outdoor unit:342~457V, 50Hz
8
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW Total input kW EER Energy label class SHF
Heating Capacity Btu/h
kW Total input kW COP Energy label class Booster heater kW
Power supply Phase
Cycle Hz Voltage V Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM External pressure Pa Sound level
dB(A)
(Low-High)
External finish (Panel) Dimension W : mm Unit (Panel) D : mm
H : mm
W : inch
D : inch
H : inch Weight kg Unit (Panel) lbs Unit drain pipe O.D. mm
inch
Outdoor unit Air flow CMM
CFM
Sound level at cooling
dB(A)
Sound level at heating
dB(A) External finish Dimension W : mm
D : mm H : mm
W : inch
D : inch H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
Height difference
m
Length
m
PEAD-RP71GA PEAD-RP100GA PEAD-RP100GA
PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA
PUHZ-HRP71VHA2 PUHZ-HRP100VHA2 PUHZ-HRP100YHA2
24,200 34,100 34,100
7.1 ( 4.9 - 8.1 ) 10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 )
2.15 3.08 3.08
3.30 3.25 3.25 AAA
0.83 0.86 0.86
27,300 38,200 38,200
8.0 ( 4.5 - 10.2 ) 11.2 ( 4.5 - 14.0 ) 11.2 ( 4.5 - 14.0 )
2.34 3.28 3.28
3.42 3.41 3.41 BBB
--­13
50 50
230 400
32 (VHA)/ 40 (VHA2)32 16
20-25 26.5-33 706-883 935-1165 10/50/70 10/50/70
35-38/37-41/37-43 40-43/42-45/42-46
Galvanized sheets
1171 1411
740 275
46-1/8 55-9/16
29-1/8
10-13/16 42 50 93 111
R1 (External thread)
1-1/4
100
3,530 52 (VHA, YHA)/ 51 (VHA2, YHA2) 53 (VHA, YHA)/ 52 (VHA2, YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8 120 134 265 295
15.88 5/8
9.52 3/8
Max. 30 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32°C, W.B. 23°C
D.B. 46°C
Lower limit
D.B. 19°C, W.B. 15°C D.B. -5°C *
Heating
Upper limit
D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit
D.B. 17°C
D.B. -25°C, W.B. -25°C
4. Above data are based on the indicated voltage.
* If optional air protect guide is installed : D.B.-18°C
Indoor unit Single phase 230V 50Hz
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz(HRP100Y : 342~457V, 50Hz)
9
Model name Indoor unit
Outdoor unit
Cooling Capacity Btu/h
kW Total input kW EER Energy label class SHF
Heating Capacity Btu/h
kW Total input kW COP Energy label class Booster heater kW
Power supply Phase
Cycle Hz Voltage V Breaker size A
Indoor unit Air flow CMM
(Low-High)
CFM External pressure Pa Sound level
dB(A)
(Low-High)
External finish (Panel) Dimension W : mm
Unit (Panel) D : mm
H : mm
W : inch
D : inch H : inch
Weight kg
Unit (Panel) lbs
Field drain pipe I.D.
Outdoor unit Air flow CMM
CFM Sound level at cooling
dB(A)
Sound level at heating
dB(A) External finish Dimension W : mm
D : mm H : mm
W : inch
D : inch H : inch
Weight kg
lbs
Refrigerant pipe size Gas side O.D. mm
inch
mm
inch
Liquid side O.D. mm
inch
Refrigerant pipe length
Height difference
m
Length
m
PKA-RP100FAL PKA-RP100FAL
PUHZ-HRP100VHA PUHZ-HRP100YHA
PUHZ-HRP100VHA2 PUHZ-HRP100YHA2
34,100 34,100
10.0 ( 4.9 - 11.4 ) 10.0 ( 4.9 - 11.4 )
2.93 2.93
3.41 3.41 AA
0.77 0.77
38,200 38,200
11.2 ( 4.5 - 14.0 ) 11.2 ( 4.5 - 14.0 )
3.10 3.10
3.61 3.61 AA
--
13
50 50
230 400
32 (VHA)/ 40 (VHA2) 16
22 - 28
780 - 990
0
41 - 46
White Munsell 3.4Y 7.7/0.8
1680
235 340
66-1/8
9-1/4
13-3/8
28 62 20
13/16
100
3,530
52
(VHA, YHA)/ 51 (VHA2, YHA2)
53 (VHA, YHA)/ 52 (VHA2, YHA2)
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8 120 134 265 295
15.88 5/8
9.52 3/8
Max. 30 Max. 75
NOTE: 1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27°C (80°F) W.B. 19°C (66°F) Outdoor : D.B. 35°C (95°F) W.B. 24°C (75°F) Heating Indoor : D.B. 20°C (68°F) Outdoor : D.B. 7°C (45°F) W.B. 6°C (43°F) Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range Indoor Outdoor
Cooling
Upper limit
D.B. 32°C, W.B. 23°C
D.B. 46°C
Lower limit
D.B. 19°C, W.B. 15°C D.B. -5°C *
Heating
Upper limit
D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit
D.B. 17°C
D.B. -25°C, W.B. -25°C
4. Above data are based on the indicated voltage.
* If optional air protect guide is installed : D.B.-18°C
Indoor unit Single phase 230V 50Hz
V:Single phase 230V 50Hz, Y:3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage 198~264V, 50Hz(HRP100Y : 342~457V, 50Hz)
10
3
OUTLINES AND DIMENSIONS
37728460
()
Ceiling hole
Branch duct hole
Drain pipe connected to VP-25
Ceiling
Grille
Drain hole
Models
Auto vane (Air outlet)
Air intake grille
Ceiling
Cut out hole
Cut out hole
Cut out hole
Burring hole pitch
Burring hole pitch
Burring hole
Burring hole
Power supply wire, Indoor unit/Outdoor unit connecting wire entry
Indoor unit/Outdoor unit connecting terminal block
Indoor power supply terminal block(Option part)
Control wire entry
Air intake hole
Air intake hole
Air outlet hole
Air outlet hole
Connected the attached flexible pipe or socket.
Keep approximately 10 to 15mm space between unit ceiling and ceiling slab.
Branch duct hole
Fresh air intake hole
Ceiling hole
Suspension bolt pitch
Suspension bolt pitch
Remote controller terminal block
Suspension bolt M10 or W3/8
(7.5)(7.5)
605
+35
- 5
620
DEFROST/STAND BY lamp
Receiver
Operation lamp
In case of standard grille : PLP-6BA / PLP-6BAMD
In case of wireless remote controller : PLP-6BALM
Auto Grille Air intake grille up/down discharge
Emergency operation switch<Cooling>and Emergency Up/Down switch<Up>
160
160
500
500
597
83
36
950
8336
950
597
A
17
+5
0
B35
190
156
105
140
50~70
160
840
150
90
C
D
840
187.5
20~45
860~910
20~45
810
20~45
860~910
20~45
24
160
++
+
+
+
+
+
+
+
M
M
M
M
120
120
:175
:125
167
158
Vane motor
2
1
Drain pump clean hole and Drain emergency drainage hole
130
100
70
155
350
90 100 100 90
BACDE
241 258
80
87
74
400
298
85 77
440
281
2
1
Refrigerant pipe
···:6.35 Flared connection
···1/4 inch
Refrigerant pipe
···:9.52 Flared connection
···3/8 inch
Refrigerant pipe
···:12.7 Flared connection
···1/2 inch
Refrigerant pipe
···:15.88 Flared connection
···5/8 inch
Refrigerant pipe
:6.35 / :9.52
Flared connection 1/4 inch / 3/8 inch (compatible)
PLA-RP35/50BA
PLA-RP60BA
PLA-RP71BA
PLA-RP100,125,140BA
PLA-RP71BA2
PLA-RP100,125BA2
Detail drawing of fresh air intake hole
Detail connecting of branch duct(Both aspects)
3-:2.8
14-:2.8
:150
:100
Emergency operation switch<Heating>and Emergency Up/Down switch<Down>
In case of Auto-Grille : PLP-6BAJ
Suspension bolt lower edge
170
+
Ceiling
Air intake grille
Max. 4.0m
L.L Filter
Ceiling
Grille
Indoor unit
1500mm or more
1000mm
or more
3000mm or more
1800mm or more
from floor
For high attachment
Indoor unit
Obstacle
Floor
Note 1. Please choose the Grille from a standard grille or Auto-Grille.
2. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE). Drain pump is included. Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions + marked on the figure.
3) The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.
INDOOR UNIT PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP100BA PLA-RP125BA PLA-RP71BA2 PLA-RP100BA2 PLA-RP125BA2
Unit : mm
11
PEAD-RP35EA2 PEAD-RP50EA PEAD-RP60EA
PEAD-RP71EA PEAD-RP100EA2 PEAD-RP125EA
2
1
3 4 5 6 7
Refrigerant piping flare connection (liquid : F copper tube):HP Refrigerant piping flare connection (gas :G copper tube):LP Drain R1(External thread) Electrical parts box Drain Pump (Option) Drain Pipe (Option) ... Flexible joint VP-25(I.D.
:
32)
Filter
R407C Outdoor unit : 9.52
F
R410A Outdoor unit : 6.35 +
R407C Outdoor unit : 9.52 +
Outdoor unit (SUZ) : 6.35
EDCBA
804830
-
305772
Model
RP60
R407C Outdoor unit : 15.88
G
R410A Outdoor unit : 12.7 +
15.88
104410702902801012
RP35,50
+ Initial setting
2
1
3
4
Air inlet
Air outlet
Access door
55
50~150
81
197
Service space:500 or more
Keep duct-work length 850mm or more. Be sure to apply the air filter near the air inlet grille.
5
6
75
44
18
365~465
B 81
10
56 355
7
159
243
Air outlet
Air inlet
7
Lifting bolt hole
(1422)
10-:3 (RP35,50) 12-:3 (RP60)
In case of rear inlet
In case of bottom inlet
10-:3 (RP35,50) 12-
:
3 (RP60)
D
30
C
10
81BC
A
450
450
10-:3 (RP35,50) 12-
:
3 (RP60)
176
40
288
256
3.5
3.5
10
109
179
10
35
24
30640
30
21
277
80 45
282
13
13E
A
61 227
29
85
40
176
10
15
3.5
256
BC 81
10
81
A
Set
R407C outdoor unit : 19.05158416104704601552RP140
15.8810441070290
F
R410A Outdoor unit : 15.88 +
EDCBA
12841310370360
2801012
1252
Model
RP100,125
RP71
+ Initial s
etting
7
44
243
308
323
75
6
5
13
Refrigerant piping flare connection (liquid :9.52 copper tube):HP Refrigerant piping flare connection (gas :F copper tube):LP Drain R1 (External thread) Electrical parts box Drain Pump (Option) Drain Pipe (Option) ... Flexible joint VP25(I.D.:32) Filter
Service space:500 or more
81
365~465
197
81
50~150
55
29
Access door
Air outlet
Air inlet
4
3
1
2
7
6
5
4
3
2
1
113
307
122
12-:3
(14x22)
Lifting bolt hole
45
Set
210
12-:3
450
450
140
282
680
3.5
3.5
30
319
261
181
40
30
A
CB
81
10
375
10
80
C B81
A
E13
30D
20
35
30
1053 169
Keep duct-work length 850mm or more.
Be sure to apply the air filter near the air inlet grille.
Unit : mm
12
PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA
Unit : mm
Model A B C D E
7
7
9
8
9.52
9.52
15.88
15.88
8
10
FG H J
RP60
RP71
RP100
1125
1125
1365
1090
1090
1330
1050
1050
1290
1012
1012
1252
840
840
1080
Outdoor unit(SUZ) : 6.35
Other outdoor unit : 9.52
*
R410A Outdoor unit : 15.88 *
R407C Outdoor unit : 19.05
*
Initial setting
13
PKA-RP35GAL PKA-RP50GAL Unit : mm
Knockout hole for
right piping
Refrigerant pipe.
Drain pipe.
Wiring hole
21
Right side
Less than 15
70
245
60
235
Auto vane
Front view
Air intake
Air intake
Air intake
Air intake
198
53
340
715 225
340 80 280 233
990
21
Left side
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
60
70
245
(Necessary clearance for
unit installation)
Right side
Allowing clearances
Front view
Less than 130
50 or more 150 or more
180 or more 30 or more
for bolts
Left-rear
piping hole
left-rear piping
R52.
5
R52.5
Installation plate
balance point hole
Details of installation plate
49-:5hole
for tapping screw
Knockout hole for
right-rear piping
Right-rear
piping hole
Unit center
14-:14hole
Knockout hole for
425
420
170
190
210 230
0
322
0355580130
190
230
272
310
0
35
95
150
205
260
320
345
495
20
75
135
190
245
300
360
405
495
32
0
+1 Sleeves are available on the market.
+2 This size shows the lower end of through hole.
:90~:100:90
Through hole
Sleeve +1
35, 50
Model
R52.5
R52.5
Gas pipe
Liquid pipe
Terminal block for
Terminal block to
outdoor unit
Filter grip
Service panel
(Power supply access)
(Flexible hose total length800)
(Right side piping
installation)
(Left side piping
installation)
Unit drain pipe O.D.20
Front view(to open the grille)
700
449
86
581 54
31 280
35
Knockout hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
12-Louvers(manual)
Air outlet
Lower side
80
50
395400
190
60
70 35
79
160 40
235
705
power supply
(Heater (PKH-P35, 50GALH only))
153
GAS SIDE
LIQUID SIDE
RP35, 50
P35, 50
:6.35
:9.52
:12.7
:15.88
:9.52—:15.88
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
: Initial flare nut size
14
PKA-RP50FAL2 Unit : mm PKA-RP60FAL
235
45
235
45
235
45
235
62.5
13
58
42
340
197
To p
Front
Right side
Left side
1400
1090
Air intake
235
C
Knockout hole for right piping
Refrigerant pipe. Drain pipe
Knockout hole for left piping
Drain hose for left-hand side piping
Drain hose
Lower side
Auto vanes
(Gas pipe)
Drain hose O.D.20
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe :9.52(3/8F) Gas pipe :15.88(5/8F)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knockout hole for wiring
25
1110
183
240
B
1120
552
55 120
107 111
Air outlet
552
Air outlet
Louvers (manual)
Under panel Removable at left-hand side piping
Knockout hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
12-ø6 hole for tapping screw
66-ø6 hole for tapping screw
Wall fixture
Unit center
32-ø12 hole for bolt
225
18
18
91
900
990
455
285
245
19
240 280 314
610
90
Drainage range on left-hand side
Drainage range on right-hand side
10 91=(910)
180
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Display section
Receiving section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
GAS SIDE
LIQUID SIDE
RP50
:6.35 :9.52
:15.88
:12.7
:9.52
:15.88
:90
RP60,71 / P60,71
+1 Sleeves are available on the market.
Use the current nuts meeting the pipe size of the outdoor unit.
Sleeve +1
Through hole
:90~ :100
Available pipe size
: Initial flare nut size
15
PKA-RP100FAL Unit : mm
235
45
235
45
235
45
235
45
235
62.5
13
58
42
340
197
To p
Front
Right side
Display section
Receiving section
Power lamp
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Left side
1680
1370
Air intake
235
C
Knockout hole for right piping
Knockout hole for left piping
Drain hose for left-hand side piping
Drain hose
Drain hose
Lower side
Auto vane
(Gas pipe)
Bolt
Gas pipe
15
(Liquid pipe)
Liquid pipe
A
30
32
39
98
37
74
439
100
30
37
74
4
2980
280
3030
18430
60
10
39
37
65
100
AB C
Knockout hole for wiring
25
1110
183
240
B
1400
55 120
102 111
694
Air outlet
694
Air outlet
Louvers (manual)
Under panel
(Removable at left-hand side piping)
Knockout hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping openingRange for left rear piping opening
12-ø6 hole for tapping screw
84-ø6 hole for tapping screw
Wall fixture
Unit out line
Unit center
41-ø12 hole for bolt
295 225
18
18
91
900
1270
595
285
245
19
240 280 314
750
90
Drainage range on right-hand side
13 91=(1183)
180
Drainage range on left-hand side
Terminal block for heater (PKH only)
Terminal block for indoor/outdoor connecting line
Drain hose O.D.20
:Initial flare nut size
GAS SIDE
LIQUID SIDE
RP100
:9.52 :15.88 :19.05
P100
:9.52
:19.05
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
16
Handle for moving
Side Air Intake
Front piping cover
Rear piping cover
Terminal connection
Left···Power supply wiring
Right···Indoor/Outdoor wiring
Earth terminal
Service panel
Handle for moving
1
2
Air Discharge
Rear Air Intake
Side Air Intake
···Refrigerant GAS pipe connction (FLARE)W15.88(5/8 inch)
···Refrigerant LIQUID pipe connection (FLARE)W 9.52(3/8 inch)
+1 ···Indication of STOP VALVE connection location.
Example of Notes
Piping Knockout Hole Details
600175 175
330
417
42
66
53 56
45
(19)
28 370
2-U Shaped notched holes
(Foundation Bolt M10)
2-12 x 36 Oval holes
(Foundation Bolt M10)
Installation Feet
30
45 40
65
92
27 55
23 73 63
Rear piping hole
(Knockout)
Rear trunking hole
(Knockout)
Power supply wiring hole
(2-
W
27Knockout)
W
92
19 55
92
75
40
73 63 23
27 92
Right piping hole
(Knockout)
Right trunking hole
(Knockout)
Power supply wiring hole
(2-
W
27Knockout)
W
92
92
65
45
40
27 55
23
73 63
Front piping hole
(Knockout)
Front trunking hole
(Knockout)
Power supply wiring hole
(2-
W
27Knockout)
W
92
14514522030 145
81 219
71
71
Bottom piping hole
(Knockout)
Drain hole
(5-W33)
1350
23
950
A
+1 447
+1 443
371 635
322
Handle for moving
HRP·VHA
HRP·YHA
1,079
A
930
Air intake
Rear Air Intake
Handle for moving
Handle for moving
Over
Over
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
front, right, rear and below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS
2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
Dimensions of space needed
for service access are
shown in the below diagram.
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
30
FOUNDATION
10
500
500
150
Service space
FREE
Over 10mm
Over 10mm
Ove
r 150mm
Ove
r 1000mm
OUTDOOR UNIT Unit : mm PUHZ-HRP71VHA PUHZ-HRP100VHA PUHZ-HRP100YHA PUHZ-HRP125YHA