Mitsubishi PKA-RP1.6GAL, PKA-RP2GAL Service Manual

Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT -TYPE, AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
2004
No.OC305
Series PKA
Indoor unit [Model names]
PKA-RP1.6GAL
PKA-RP2GAL
Wall Mounted
[Service Ref.]
PKA-RP1.6GAL PKA-RP2GAL
Indoor unit
Model name indication
R407C/R410A
CONTENTS
1. COMBINATION OF INDOOR AND OUTDOOR UNITS···2
2. SAFETY PRECAUTION·······································3
3. PART NAMES AND FUNCTIONS ·······················6
4. SPECIFICATIONS················································8
5. DATA···································································11
6. OUTLINES AND DIMENSIONS·························26
7. WIRING DIAGRAM ············································27
REFRIGERANT SYSTEM DIAGRAM
9. TROUBLE SHOOTING ······································29
10. DISASSEMBLY PROCEDURE ··························39
11. PARTS LIST ·······················································42
12. OPTIONAL PARTS ························BACK COVER
This manual dose not cover
outdoor uniits. When servicing tthem, please refer to service manual OC261 REVISED EDITION-B, OC285, OC294 REVISED EDITION-A, OC298 and this manual in a set.
······················28
Remote controller
Page 2
1
Outdoor unit [OC294
REVISED EDITION-A]
Heat pump type
PUHZ-RP
Outdoor unit [OC285]
Heat pump type
PUH-P
(R407C Fixed speed)
(R407C Fixed speed)
(R410A Inverter)
Outdoor unit [OC298]
Cooling only type
PU-P
2VHA
1.6VHA
Indoor unit
PKA-RP1.6GAL PKA-RP2GAL
Heat pump without electric heater or Cooling only
1.6VGAA
2VGAA
1.6VGAA
2VGAA
Indoor unit
PKA-RP1.6GAL
PKA-RP2GAL
Heat pump type
PUH-P
Cooling only type
PU-P
Heat pump without electric heater or Cooling only
VGAA.UK VGAA1.UK
YGAA.UK YGAA1.UK
VGAA.UK VGAA1.UK
YGAA.UK YGAA1.UK
VGAA.UK VGAA1.UK
YGAA.UK YGAA1.UK
VGAA.UK VGAA1.UK
YGAA.UK YGAA1.UK
Indoor unit
PKA-RP1.6GAL
PKA-RP2GAL
Outdoor unit [OC261 REVISED EDITION-B
]
1.6 2 1.6 2
COMBINATION OF INDOOR AND OUTDOOR UNITS
2
Page 3
2 SAFETY PRECAUTION
Do not use the existing refrigerant piping.
The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit.
Use “low residual oil piping”
If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.
Use ESTR , ETHER or HAB as the lubricant to coat flares and flange connection parts.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Use liquid refrigerant to seal the system.
If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
Do not use a refrigerant other than R407C.
If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration.
Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration.
Store the piping to be used during installation indoors with keep both ends sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Gravimeter
Unit
CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R407C
[1] Cautions for service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
3
Page 4
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1 Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2 Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3 Electronic scale 4 Gas leak detector ·Use the detector for R134a or R407C. 5 Adapter for reverse flow check. ·Attach on vacuum pump. 6 Refrigerant charge base. 7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8 Refrigerant recovery equipment.
4
Page 5
CAUTIONS RELATED TO NEW REFRIGERANT
Use new refrigerant pipes.
Make sure that the inside and outside of refrige­rant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections.
In case of using the existing pipes for R22, be careful with the followings.
· Change flare nut to the one provided with this product. Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas cylinder.
If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrige­rant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera­nt will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterio­ration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com­pressor.
If large amount of mineral oil enter, that can cause deterio­ration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Cautions for units utilizing refrigerant R410A
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
5
Page 6
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No. Specifications
1 Gauge manifold ·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2 Charge hose ·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3 Electronic scale 4 Gas leak detector ·Use the detector for R134a, R407C or R410A. 5 Adaptor for reverse flow check ·Attach on vacuum pump. 6 Refrigerant charge base 7 Refrigerant cylinder ·Only for R410A Top of cylinder (Pink)
8 Refrigerant recovery equipment
specifications
Cylinder with syphon
. (UNF1/2)
3 PART NAMES AND FUNCTIONS
Indoor Unit
Air intake
Guide vane
Filter
Air outlet
Air intake grille
Auto vane
6
Page 7
Wireless remote controller
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK
TEST RUN
˚C
AMPM
AMPM
VANE CONTROL button
Used to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF button
The unit is turned ON and OFF alternately each time the button is pressed.
LOUVER button
This switch the horizontal fan motion ON and OFF.
(Not available for this model.)
MODE SELECT button
Used to switch the operation mode between cooling, drying, blowing, heating and auto mode.
CHECK-TEST RUN button
Only press this button to perform an inspec­tion check or test operation. Do not use it for normal operation.
FAN SPEED SELECT button
Used to change the fan speed.
TIMER display
Displays when in timer operation or when setting timer.
button
SET TEMPERATURE button sets any desired room temperature.
CLOCK display
Displays the current time.
“ ” “ ” display
Displays the order of timer operation.
“ ” “ ” display
Displays whether timer is on or off.
w In case the outdoor unit is cool only type,
the heating and auto mode not available.
Buttons used to set the “hour and minute” of the current time and timer settings.
h and min buttons
display
SET TEMP. display indicates desired temper­ature set.
display
FAN SPEED display indicates which fan speed has been selected.
display
The vertical direction of air flow is indicated.
display
Blinks when model is selected.
display
Lights up while transmission to the indoor unit is mode using switches.
display
CHECK&TEST RUN display indicates that the unit is being checked or test-run.
display
OPERATION MODE display Operation mode display indicates which op­eration mode is in effect.
TIMER CONTROL buttons
AUTO STOP (OFF timer): when this switch is set, the air conditioner will be au­tomatically stopped at the preset time. AUTO START (ON timer): when this switch is set, the air conditioner will be automatical­ly started at the preset time.
MODEL SELECT
CHECK
TEST RUN
When cover is open.
7
Page 8
4
Cooling
15,700
4,600(2,300~5,400)
1.63
0.07
0.33
0.40
Heating
15,400
4,500(2,500~6,200)
1.40
0.07
0.33
0.40
Single phase, 50Hz, 220-230-240V
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(320-355-390-425)
0(direct blow)
Wireless remote controller & built-in
36-38-41-43
26(1)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
PUHZ-RP2VHA
PKA-RP2GAL
PKA-RP2GAL
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
Function Capacity Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow(Lo-Mi2-Mi1-Hi)
External static pressure Operation control & Thermostat Noise level(Lo-Mi2-Mi1-Hi) Unit drain pipe O.D. Dimensions
Weight
W
D H
INDOOR UNIT
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
4. Above data based on indicated voltage Indoor Unit Single phase 230V 50Hz Outdoor Unit Single phase 230V 50Hz
2. Guaranteed operating range Upper limit
Lower limit Upper limit Lower limit
Indoor D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C
D.B. 28˚C D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C D.B. 21˚C, W.B. 15˚C D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref.
OUTDOOR UNIT
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
3. Guaranteed voltage 198~264V, 50Hz
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
Function Capacity Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow(Lo-Mi2-Mi1-Hi)
External static pressure Operation control & Thermostat Noise level(Lo-Mi2-Mi1-Hi) Unit drain pipe O.D. Dimensions
Weight
W D H
INDOOR UNIT
PKA-RP1.6GAL
PKA-RP1.6GAL
Cooling
12,300
3,600(1,600~4,500)
1.03
0.07
0.33
0.40
Heating
14,000
4,100(1,600~5,200)
1.27
0.07
0.33
0.40
Single phase, 50Hz, 220-230-240V
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(320-355-390-425)
0(direct blow)
Wireless remote controller & built-in
36-38-41-43
26(1)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
PUHZ-RP1.6VHA
Service Ref.
OUTDOOR UNIT
SPECIFICATIONS
4-1. Heat pump type (1)
8
Page 9
4-2. Heat pump type (2)
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
Function Capacity Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow(Lo-Mi2-Mi1-Hi)
External static pressure Operation control & Thermostat Noise level(Lo-Mi2-Mi1-Hi) Unit drain pipe O.D. Dimensions
Weight
W
D H
INDOOR UNIT
PKA-RP1.6GAL
PKA-RP1.6GAL
Cooling
15,200
4,450
1.70
0.07
0.33
0.40
Heating
16,900
4,950
1.79
0.07
0.33
0.40
Single phase, 50Hz, 220-230-240V
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(320-355-390-425)
0(direct blow)
Wireless remote controller & built-in
36-38-41-43
26(1)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
Service Ref.
OUTDOOR UNIT
PUH-P1.6VGAA PUH-P1.6VGAA.UK / PUH-P1.6YGAA.UK PUH-P1.6VGAA
1.UK / PUH-P1.6YGAA1.UK
Item
Function Capacity Total input
Service Ref.
Power supply(phase, cycle, voltage)
External finish Heat exchanger Fan Fan(drive) x No.
INDOOR UNIT
Operation control & Thermostat Noise level(Lo-Mi2-Mi1-Hi) Unit drain pipe O.D. Dimensions
Weight
OUTDOOR UNIT
Notes1. Rating Conditions (ISO T1)
2. Guaranteed operating range
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage Indoor Unit Single phase 230V 50Hz Outdoor Unit 3 phase 400V 50Hz
Input Running current Starting current
Fan motor output Airflow(Lo-Mi2-Mi1-Hi) External static pressure
Service Ref.
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
K/min(CFM)
W
D H
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C
D.B. 28˚C D.B. 17˚C
Service Ref.
Btu/h
W
kW
kW
A A
kW
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
Indoor
PKA-RP2GAL
Cooling
18,300
5,350
2.33 Single phase, 50Hz, 220-230-240V
0.07
0.33
0.40
Wireless remote controller & built-in
Outdoor
D.B. 46˚C
D.B. -5˚C D.B. 24˚C, W.B. 18˚C D.B. -11˚C, W.B. -12˚C
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
9
PUH-P2VGAA PUH-P2VGAA.UK / PUH-P2YGAA.UK PUH-P2VGAA
PKA-RP2GAL
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
9-10-11-12(320-355-390-425)
0.030
0(direct blow)
36-38-41-43
26(1)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
1.UK / PUH-P2YGAA1.UK
Heating
21,200
6,200
2.34
0.07
0.33
0.40
Page 10
4-3. Cooling only type
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.)
kg(lbs)
Function Capacity Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input Running current
Starting current External finish Heat exchanger Fan Fan(drive) x No.
Fan motor output
Airflow(Lo-Mi2-Mi1-Hi)
External static pressure Operation control & Thermostat Noise level(Lo-Mi2-Mi1-Hi) Unit drain pipe O.D. Dimensions
Weight
W
D H
INDOOR UNIT
PKA-RP1.6GAL
Cooling
15,200
4,450
1.70
PKA-RP1.6GAL
Single phase, 50Hz, 220-230-240V
0.07
0.33
0.40
Munsell 0.70Y 8.59/0.97
Plate fin coil
Line flow (direct) x 1
0.030
9-10-11-12(320-355-390-425)
0(direct blow)
Wireless remote controller & built-in
36-38-41-43
26(1)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
Service Ref.
OUTDOOR UNIT
PU-P1.6VGAA PU-P1.6VGAA.UK / PU-P1.6YGAA.UK PU-P1.6VGAA
1.UK / PU-P1.6YGAA1.UK
Item
Function Capacity Total input
Service Ref.
Power supply(phase, cycle, voltage)
External finish Heat exchanger Fan Fan(drive) x No.
INDOOR UNIT
Operation control & Thermostat Noise level(Lo-Mi2-Mi1-Hi) Unit drain pipe O.D. Dimensions
Weight
OUTDOOR UNIT
Notes1. Rating Conditions (ISO T1)
2. Guaranteed operating range
3. Guaranteed voltage 198~264V, 50Hz
4. Above data based on indicated voltage
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
Input Running current Starting current
Fan motor output Airflow(Lo-Mi2-Mi1-Hi) External static pressure
Service Ref.
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Refrigerant piping length (one way) : 5m (16ft)
Cooling
Upper limit Lower limit
Indoor Unit Single phase 230V 50Hz Outdoor Unit 3 phase 400V 50Hz
Service Ref.
Btu/h
W
kW
kW
A A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
W
D H
D.B. 35˚C, W.B. 22.5˚C D.B. 19˚C, W.B. 15˚C
mm(in.) mm(in.) mm(in.)
kg(lbs)
Indoor
Outdoor
D.B. 46˚C
D.B. -5˚C
PKA-RP2GAL
Cooling
18,300
5,350
2.33
Single phase, 50Hz, 220-230-240V
Wireless remote controller & built-in
PU-P2VGAA PU-P2VGAA.UK / PU-P2YGAA.UK PU-P2VGAA1.UK / PU-P2YGAA1.UK
10
PKA-RP2GAL
0.07
0.33
Munsell 0.70Y 8.59/0.97
9-10-11-12(320-355-390-425)
0.40
Plate fin coil
Line flow (direct) x 1
0.030
0(direct blow)
36-38-41-43
26(1)
990(39)
235(9-1/4)
340(13-3/8)
16(35)
Page 11
5
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
0.74
0.62
0.50
0.82
0.70
0.58
0.90
0.78
0.66
0.54
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.94
0.82
0.70
1.00
1.00
0.90
0.78
1.00
1.00
0.98
0.86
1.00
1.00
1.00
0.94
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA 3,564 3,816 4,104 3,564 3,816 4,104 3,564 3,816 4,104 4,374 3,564 3,816 4,104 4,374 3,564 3,816 4,104 4,374 3,564 3,816 4,104 4,374 3,564 3,816 4,104 4,374 3,564 3,816 4,104 4,374 3,564 3,816 4,104 4,374
SHC(W)
2,637 2,366 2,052 2,922 2,671 2,380 3,208 2,976 2,709 2,362 3,493 3,282 3,037 2,712 3,564 3,434 3,201 2,887 3,564 3,587 3,356 3,062 3,564 3,816 3,694 3,412 3,564 3,816 4,022 3,762 3,564 3,816 4,104 4,112
SHF P.C.
0.82
0.84
0.87
0.82
0.84
0.87
0.82
0.84
0.87
0.89
0.82
0.84
0.87
0.89
0.82
0.84
0.87
0.89
0.82
0.84
0.87
0.89
0.82
0.84
0.87
0.89
0.82
0.84
0.87
0.89
0.82
0.84
0.87
0.89
CA
3,456 3,708 4,014 3,456 3,708 4,014 3,456 3,708 4,014 4,284 3,456 3,708 4,014 4,284 3,456 3,708 4,014 4,284 3,456 3,708 4,014 4,284 3,456 3,708 4,014 4,284 3,456 3,708 4,014 4,284 3,456 3,708 4,014 4,284
SHC(W)
2,257 2,299 2,007 2,834 2,596 2,328 3,110 2,892 2,649 2,313 3,387 3,189 2,970 2,656 3,456 3,337 3,131 2,827 3,456 3,486 3,291 2,999 3,456 3,708 3,613 3,342 3,456 3,708 3,934 3,684 3,456 3,708 4,014 4,027
SHF
0.74
0.62
0.50
0.82
0.70
0.58
0.90
0.78
0.66
0.54
0.998
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.94
0.82
0.70
1.00
1.00
0.90
0.78
1.00
1.00
0.98
0.86
1.00
1.00
1.00
0.94
P.C.
0.87
0.89
0.91
0.87
0.89
0.91
0.87
0.89
0.91
0.94
0.87
0.89
0.91
0.94
0.87
0.89
0.91
0.94
0.87
0.89
0.91
0.94
0.87
0.89
0.91
0.94
0.87
0.89
0.91
0.94
0.87
0.89
0.91
0.94
P.C.
0.92
0.95
0.97
0.92
0.95
0.97
0.92
0.95
0.97
1.00
0.92
0.95
0.97
1.00
0.92
0.95
0.97
1.00
0.92
0.95
0.97
1.00
0.92
0.95
0.97
1.00
0.92
0.95
0.97
1.00
0.92
0.95
0.97
1.00
SHC(W
) 2,478 2,221 1,953 2,745 2,507 2,265 3,013 2,794 2,578 2,255 3,281 3,081 2,890 2,589 3,348 3,224 3,047 2,756 3,348 3,367 3,203 2,923 3,348 3,582 3,515 3,257 3,348 3,582 3,828 3,591 3,348 3,582 3,906 3,925
CA
3,348 3,582 3,906 3,348 3,582 3,906 3,348 3,582 3,906 4,176 3,348 3,582 3,906 4,176 3,348 3,582 3,906 4,176 3,348 3,582 3,906 4,176 3,348 3,582 3,906 4,176 3,348 3,582 3,906 4,176 3,348 3,582 3,906 4,176
SHF
0.74
0.62
0.50
0.82
0.70
0.58
0.90
0.78
0.66
0.54
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.65
1.00
0.94
0.82
0.70
1.00
1.00
0.90
0.78
1.00
1.00
0.98
0.86
1.00
1.00
1.00
0.94
DATA
5-1. PERFORMANCE DATA
COOLING CAPACITY(1) PKA-RP1.6GAL / PUHZ-RP1.6VHA
(230V)
CA : Capacity (W) SHC(W) : Sensible heat capacity P.C. : Power consumption (kW) SHF : Sensible heat factor
11
Page 12
COOLING CAPACITY(2)
Outdoor intake air D.B.(°C)
35 40 45
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
0.74
0.62
0.50
0.82
0.70
0.58
0.90
0.78
0.66
0.54
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.94
0.82
0.70
1.00
1.00
0.90
0.78
1.00
1.00
0.98
0.86
1.00
1.00
1.00
0.94
0.99
1.01
1.04
0.99
1.01
1.04
0.99
1.01
1.04
1.06
0.99
1.01
1.04
1.06
0.99
1.01
1.04
1.06
0.99
1.01
1.04
1.06
0.99
1.01
1.04
1.06
0.99
1.01
1.04
1.06
0.99
1.01
1.04
1.06
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA 3,204 3,456 3,744 3,204 3,456 3,744 3,204 3,456 3,744 4,032 3,204 3,456 3,744 4,032 3,204 3,456 3,744 4,032 3,204 3,456 3,744 4,032 3,204 3,456 3,744 4,032 3,204 3,456 3,744 4,032 3,204 3,456 3,744 4,032
SHC(W)
2,371 2,143 1,872 2,627 2,419 2,172 2,884 2,696 2,471 2,177 3,140 2,972 2,771 2,500 3,204 3,110 2,920 2,661 3,204 3,249 3,070 2,822 3,204 3,456 3,370 3,145 3,204 3,456 3,669 3,468 3,204 3,456 3,744 3,790
SHF P.C. CA
3,060 3,348 3,600 3,060 3,348 3,600 3,060 3,348 3,600 3,888 3,060 3,348 3,600 3,888 3,060 3,348 3,600 3,888 3,060 3,348 3,600 3,888 3,060 3,348 3,600 3,888 3,060 3,348 3,600 3,888 3,060 3,348 3,600 3,888
SHC(W)
2,264 2,076 1,800 2,509 2,344 2,088 2,754 2,611 2,376 2,100 2,999 2,879 2,664 2,411 3,060 3,013 2,808 2,566 3,060 3,147 2,952 2,722 3,060 3,348 3,240 3,033 3,060 3,488 3,528 3,344 3,060 3,348 3,600 3,655
SHF
0.74
0.62
0.50
0.82
0.70
0.58
0.90
0.78
0.66
0.54
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.94
0.82
0.70
1.00
1.00
0.90
0.78
1.00
1.00
0.98
0.86
1.00
1.00
1.00
0.94
P.C.
1.06
1.09
1.11
1.06
1.09
1.11
1.06
1.09
1.11
1.14
1.06
1.09
1.11
1.14
1.06
1.09
1.11
1.14
1.06
1.09
1.11
1.14
1.06
1.09
1.11
1.14
1.06
1.09
1.11
1.14
1.06
1.09
1.11
1.14
P.C.
1.15
1.17
1.19
1.15
1.17
1.19
1.15
1.17
1.19
1.22
1.15
1.17
1.19
1.22
1.15
1.17
1.19
1.22
1.15
1.17
1.19
1.22
1.15
1.17
1.19
1.22
1.15
1.17
1.19
1.22
1.15
1.17
1.19
1.22
SHC(W)
2,158 1,942 1,692 2,391 2,192 1,963 2,624 2,443 2,233 1,983 2,858 2,694 2,504 2,277 2,916 2,819 2,640 2,424 2,916 2,944 2,775 2,570 2,916 3,132 3,046 2,864 2,916 3,132 3,316 3,158 2,916 3,132 3,384 3,452
CA 2,916 3,132 3,384 2,916 3,132 3,384 2,916 3,132 3,384 3,672 2,916 3,132 3,384 3,672 2,916 3,132 3,384 3,672 2,916 3,132 3,384 3,672 2,916 3,132 3,384 3,672 2,916 3,132 3,384 3,672 2,916 3,132 3,384 3,672
SHF
0.74
0.62
0.50
0.82
0.70
0.58
0.90
0.78
0.66
0.54
0.98
0.86
0.74
0.62
1.00
0.90
0.78
0.66
1.00
0.94
0.82
0.70
1.00
1.00
0.90
0.78
1.00
1.00
0.98
0.86
1.00
1.00
1.00
0.94
PKA-RP1.6GAL / PUHZ-RP1.6VHA
(230V)
CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
12
Page 13
COOLING CAPACITY(3)
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
1.00
1.00
0.96
0.84
1.30
1.33
1.37
1.30
1.33
1.37
1.30
1.33
1.37
1.40
1.30
1.33
1.37
1.40
1.30
1.33
1.37
1.40
1.30
1.33
1.37
1.40
1.30
1.33
1.37
1.40
1.30
1.33
1.37
1.40
1.30
1.33
1.37
1.40
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA
4,554 4,876 5,244 4,554 4,876 5,244 4,554 4,876 5,244 5,589
4,554 4,876 5,244 5,589 4,554 4,876 5,244 5,589 4,554 4,876 5,244 5,589 4,554 4,876 5,244 5,589 4,554 4,876 5,244 5,589
4,554 4,876 5,244 5,589
SHC(W)
2,915 2,536 2,098 3,279 2,926 2,517 3,643 3,316 2,937 2,459 4,008 3,706 3,356 2,906
4,190 3,901 3,566 3,130 4,372 4,096 3,776 3,353 4,554 4,486 4,195 3,801 4,554 4,876 4,615 4,248
4,554 4,876 5,034 4,695
SHF P.C. CA
4,416 4,738 5,129 4,416 4,738 5,129 4,416 4,738 5,129 5,474 4,416 4,738 5,129 5,474 4,416 4,738 5,129 5,474 4,416 4,738 5,129 5,474 4,416 4,738 5,129 5,474 4,416 4,738 5,129 5,474 4,416 4,738 5,129 5,474
SHC(W)
2,826 2,464 2,052 3,180 2,843 2,462 3,533 3,222 2,872 2,409 3,886 3,601 3,283 2,846 4,063 3,790 3,488 3,065 4,239 3,980 3,693 3,284 4,416 4,359 4,103 3,722 4,416 4,738 4,514 4,160 4,416 4,738 4,924 4,598
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
1.00
1.00
0.96
0.84
P.C.
1.38
1.40
1.43
1.38
1.40
1.43
1.38
1.40
1.43
1.48
1.38
1.40
1.43
1.48
1.38
1.40
1.43
1.48
1.38
1.40
1.43
1.48
1.38
1.40
1.43
1.48
1.38
1.40
1.43
1.48
1.38
1.40
1.43
1.48
P.C.
1.46
1.50
1.53
1.46
1.50
1.53
1.46
1.50
1.53
1.58
1.46
1.50
1.53
1.58
1.46
1.50
1.53
1.58
1.46
1.50
1.53
1.58
1.46
1.50
1.53
1.58
1.46
1.50
1.53
1.58
1.46
1.50
1.53
1.58
SHC(W)
2,738 2,380 1,996 3,080 2,746 2,396 3,422 3,112 2,795 2,348 3,765 3,479 3,194 2,775 3,936 3,662 3,394 2,988 4,107 3,845 3,594 3,202 4,278 4,211 3,993 3,628 4,278 4,577 4,392 4,055 4,278 4,577 4,791 4,482
CA
4,278 4,577 4,991 4,278 4,577 4,991 4,278 4,577 4,991 5,336 4,278 4,577 4,991 5,336 4,278 4,577 4,991 5,336 4,278 4,577 4,991 5,336 4,278 4,577 4,991 5,336 4,278 4,577 4,991 5,336 4,278 4,577 4,991 5,336
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
1.00
1.00
0.96
0.84
PKA-RP2GAL / PUHZ-RP2VHA
(230V)
CA : Capacity (W) SHC(W) : Sensible heat capacity P.C. : Power consumption (kW) SHF : Sensible heat factor
13
Page 14
COOLING CAPACITY(4)
Outdoor intake air D.B.(°C)
35 40 45
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA
4,094 4,416 4,784 4,094 4,416 4,784 4,094 4,416 4,784 5,152 4,094 4,416 4,784 5,152
4,094 4,416 4,784 5,152 4,094 4,416 4,784 5,152
4,094 4,416 4,784 5,152 4,094 4,416 4,784 5,152 4,094 4,416 4,784 5,152
SHC(W)
2,620 2,296 1,914 2,948 2,650 2,296 3,275 3,003 2,679 2,267 3,603 3,356 3,062 2,679
3,766 3,533 3,253 2,885 3,930 3,709 3,444 3,091
4,094 4,063 3,827 3,503 4,094 4,416 4,210 3,916 4,094 4,416 4,593 4,328
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
1.00
1.00
0.96
0.84
P.C.
1.56
1.61
1.65
1.56
1.61
1.65
1.56
1.61
1.65
1.68
1.56
1.61
1.65
1.68
1.56
1.61
1.65
1.68
1.56
1.61
1.65
1.68
1.56
1.61
1.65
1.68
1.56
1.61
1.65
1.68
1.56
1.61
1.65
1.68
CA
3,910 4,278 4,600 3,910 4,278 4,600 3,910 4,278 4,600 4,968 3,910 4,278 4,600 4,968 3,910 4,278 4,600 4,968 3,910
4,78 4,600 4,968 3,910 4,278 4,600 4,968 3,910 4,278 4,600 4,968 3,910 4,278 4,600 4,968
SHC(W)
2,502 2,225 1,840 2,815 2,567 2,208 3,128 2,909 2,576 2,186 3,441 3,251 2,944 2,583 3,597 3,594 3,312 2,981 3,754 3,594 3,312 2,981 3,910 3,936 3,680 3,378 3,910 4,278 4,048 3,776 3,910 4,278 4,416 4,173
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
1.00
1.00
0.96
0.84
P.C.
1.68
1.73
1.76
1.68
1.73
1.76
1.68
1.73
1.76
1.81
1.68
1.73
1.76
1.81
1.68
1.73
1.76
1.81
1.68
1.73
1.76
1.81
1.68
1.73
1.76
1.81
1.68
1.73
1.76
1.81
1.68
1.73
1.76
1.81
P.C.
1.82
1.86
1.89
1.82
1.86
1.89
1.82
1.86
1.89
1.92
1.82
1.86
1.89
1.92
1.82
1.86
1.89
1.92
1.82
1.86
1.89
1.92
1.82
1.86
1.89
1.92
1.82
1.86
1.89
1.92
1.82
1.86
1.89
1.92
SHC(W)
2,385 2,081 1,730 2,683 2,401 2,076 2,981 2,721 2,421 2,064 3,279 3,042 2,767 2,440 3,428 3,202 2,940 2,628 3,577 3,362 3,113 2,815 3,726 3,682 3,459 3,191 3,726 4,002 3,805 3,566 3,726 4,002 4,151 3,941
CA
3,726 4,022 4,324 3,726 4,002 4,324 3,726 4,002 4,324 4,692 3,726 4,002 4,324 4,692 3,726 4,002 4,324 4,692 3,726 4,002 4,324 4,692 3,726 4,002 4,324 4,692 3,726 4,002 4,324 4,692 3,726 4,002 4,324 4,692
SHF
0.64
0.52
0.40
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
1.00
1.00
0.96
0.84
PKA-RP2GAL / PUHZ-RP2VHA
(230V)
CA : Capacity (W) SHC(W) : Sensible heat capacity P.C. : Power consumption (kW) SHF : Sensible heat factor
14
Page 15
COOLING CAPACITY(5)
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA
4,406 4,417 5,073 4,406 4,717 5,073 4,406 4,717 5,073 5,407 4,406 4,717 5,073 5,407 4,406 4,717 5,073 5,407 4,406 4,717 5,073 5,407 4,406 4,717 5,073 5,407
4,406 4,717 5,073 5,407 4,406 4,717 5,073 5,407
SHC(W)
2,952 2,594 2,181 3,304 2,972 2,587 3,657 3,349 2,993 2,541 4,009 3,726 3,399 2,974 4,185 3,915 3,602 3,190 4,361 4,104 3,805 3,406 4,406 4,481 4,211 3,839
4,406 4,717 4,616 4,271 4,406 4,717 5,022 4,704
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
1.00
1.00
0.99
0.87
P.C.
1.36
1.39
1.43
1.36
1.39
1.43
1.36
1.39
1.43
1.46
1.36
1.39
1.43
1.46
1.36
1.39
1.43
1.46
1.36
1.39
1.43
1.46
1.36
1.39
1.43
1.46
1.36
1.39
1.43
1.46
1.36
1.39
1.43
1.46
CA
4,272 4,584 4,962 4,272 4,584 4,962 4,272 4,584 4,962 5,296 4,272 4,584 4,962 5,296 4,272 4,584 4,962 5,296 4,272 4,584 4,962 5,296 4,272 4,584 4,962 5,296 4,272 4,584 4,962 5,296 4,272 4,584 4,962 5,296
SHC(W)
2,862 2,521 2,134 3,204 2,888 2,530 3,546 3,254 2,927 2,489 3,888 3,621 3,324 2,913 4,058 3,804 3,523 3,124 4,229 3,988 3,721 3,336 4,272 4,354 4,118 3,760 4,272 4,584 4,515 4,183 4,272 4,584 4,912
4,607
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
1.00
1.00
0.99
0.87
P.C.
1.44
1.46
1.50
1.44
1.46
1.50
1.44
1.46
1.50
1.55
1.44
1.46
1.50
1.55
1.44
1.46
1.50
1.55
1.44
1.46
1.50
1.55
1.44
1.46
1.50
1.55
1.44
1.46
1.50
1.55
1.44
1.46
1.50
1.55
P.C.
1.52
1.56
1.60
1.52
1.56
1.60
1.52
1.56
1.60
1.65
1.52
1.56
1.60
1.65
1.52
1.56
1.60
1.65
1.52
1.56
1.60
1.65
1.52
1.56
1.60
1.65
1.52
1.56
1.60
1.65
1.52
1.56
1.60
1.65
SHC(W)
2,773 2,435 2,076 3,104 2,789 2,462 3,435 3,144 2,849 2,426 3,766 3,498 3,235 2,839 3,932 3,675 3,428 3,046 4,097 3,852 3,621 3,252 4,139 4,206 4,007 3,665 4,139 4,428 4,394 4,078 4,139 4,428 4,780 4,491
CA
4,139 4,428 4,828 4,139 4,428 4,828 4,139 4,428 4,828 5,162 4,139 4,428 4,828 5,162 4,139 4,428 4,828 5,162 4,139 4,428 4,828 5,162 4,139 4,428 4,828 5,162 4,139 4,428 4,828 5,162 4,139 4,428 4,828 5,162
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
1.00
1.00
0.99
0.87
PKA-RP1.6GAL / PUH-P1.6VGAA
PUH-P1.6VGAA.UK PUH-P1.6YGAA.UK PUH-P1.6VGAA1.UK PUH-P1.6YGAA1.UK PU-P1.6VGAA PU-P1.6VGAA.UK PU-P1.6YGAA.UK PU-P1.6VGAA1.UK PU-P1.6YGAA1.UK
(230V)
CA : Capacity (W) SHC(W) : Sensible heat capacity P.C. : Power consumption (kW) SHF : Sensible heat factor
15
Page 16
COOLING CAPACITY(6) PKA-RP1.6GAL / PUH-P1.6VGAA
PUH-P1.6VGAA.UK PUH-P1.6YGAA.UK PUH-P1.6VGAA1.UK PUH-P1.6YGAA1.UK PU-P1.6VGAA PU-P1.6VGAA.UK PU-P1.6YGAA.UK PU-P1.6VGAA1.UK PU-P1.6YGAA1.UK
Indoor
Intake air
D.B.(°C)
20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
Indoor
Intake air
W.B.(°C)
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA 3,961 4,272 4,628 3,961 4,272 4,628 3,961 4,272 4,628 4,984 3,961 4,272 4,628 4,984 3,961 4,272 4,628 4,984 3,961 4,272 4,628 4,984 3,961 4,272 4,628 4,984 3,961 4,272 4,628 4,984 3,961 4,272 4,628 4,984
SHC(W)
2,654 2,350 1,990 2,970 2,691 2,360 3,287 3,033 2,731 2,342 3,604 3,375 3,101 2,741 3,762 3,546 3,286 2,941 3,921 3,717 3,471 3,140 3,961 4,058 3,841 3,539 3,961 4,272 4,211 3,937 3,961 4,272 4,582 4,336
Outdoor intake air D.B.(°C)
35 40 45
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
1.00
1.00
0.99
0.87
P.C.
1.63
1.67
1.72
1.63
1.67
1.72
1.63
1.67
1.72
1.75
1.63
1.67
1.72
1.75
1.63
1.67
1.72
1.75
1.63
1.67
1.72
1.75
1.63
1.67
1.72
1.75
1.63
1.67
1.72
1.75
1.63
1.67
1.72
1.75
CA 3,783 4,139 4,450 3,783 4,139 4,450 3,783 4,139 4,450 4,806 3,783 4,139 4,450 4,806 3,783 4,139 4,450 4,806 3,783 4,139 4,450 4,806 3,783 4,139 4,450 4,806 3,783 4,139 4,450 4,806 3,783 4,139 4,450 4,806
SHC(W)
2,534 2,276 1,914 2,837 2,607 2,270 3,139 2,938 2,626 2,259 3,442 3,269 2,982 2,643 3,593 3,435 3,160 2,836 3,745 3,600 3,338 3,028 3,783 3,932 3,694 3,412 3,783 4,139 4,050 3,797 3,783 4,139 4,406 4,181
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
1.00
1.00
0.99
0.87
P.C.
1.75
1.80
1.84
1.75
1.80
1.84
1.75
1.80
1.84
1.89
1.75
1.80
1.84
1.89
1.75
1.80
1.84
1.89
1.75
1.80
1.84
1.89
1.75
1.80
1.84
1.89
1.75
1.80
1.84
1.89
1.75
1.80
1.84
1.89
CA 3,605 3,872 4,183 3,605 3,872 4,183 3,605 3,872 4,183 4,539 3,605 3,872 4,183 4,539 3,605 3,872 4,183 4,539 3,605 3,872 4,183 4,539 3,605 3,872 4,183 4,539 3,605 3,872 4,183 4,539 3,605 3,872 4,183 4,539
SHC(W)
2,415 2,129 1,799 2,703 2,439 2,133 2,992 2,749 2,468 2,133 3,280 3,058 2,803 2,496 3,424 3,213 2,970 2,678 3,568 3,368 3,137 2,860 3,605 3,678 3,472 3,223 3,605 3,872 3,807 3,586 3,605 3,872 4,141 3,949
SHF
0.67
0.55
0.43
0.75
0.63
0.51
0.83
0.71
0.59
0.47
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
0.99
0.87
0.75
0.63
1.00
0.95
0.83
0.71
1.00
1.00
0.91
0.79
1.00
1.00
0.99
0.87
(230V)
P.C.
1.90
1.94
1.97
1.90
1.94
1.97
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
1.90
1.94
1.97
2.01
CA : Capacity (W) SHC(W) : Sensible heat capacity P.C. : Power consumption (kW) SHF : Sensible heat factor
16
Page 17
COOLING CAPACITY(7) PKA-RP2GAL / PUH-P2VGAA
PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2VGAA1.UK PUH-P2YGAA1.UK PU-P2VGAA PU-P2VGAA.UK PU-P2YGAA.UK PU-P2VGAA1.UK PU-P2YGAA1.UK
Indoor
Intake air
D.B.(°C)
20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
Indoor
Intake air
W.B.(°C)
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA 5,297 5,671 6,099 5,297 5,671 6,099 5,297 5,671 6,099 6,500 5,297 5,671 6,099 6,500 5,297 5,671 6,099 6,500 5,297 5,671 6,099 6,500 5,297 5,671 6,099 6,500 5,297 5,671 6,099 6,500 5,297 5,671 6,099 6,500
SHC(W)
3,178 2,722 2,196 3,602 3,176 2,684 4,025 3,629 3,171 2,600 4,449 4,083 3,659 3,120 4,661 4,310 3,903 3,380 4,873 4,537 4,147 3,640 5,297 4,990 4,635 4,160 5,297 5,444 5,123 4,680 5,297 5,671 5,611 5,200
Outdoor intake air D.B.(°C)
20 25 30
SHF
0.60
0.48
0.36
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
P.C.
1.86
1.90
1.96
1.86
1.90
1.96
1.86
1.90
1.96
2.00
1.86
1.90
1.96
2.00
1.86
1.90
1.96
2.00
1.86
1.90
1.96
2.00
1.86
1.90
1.96
2.00
1.86
1.90
1.96
2.00
1.86
1.90
1.96
2.00
CA 5,136 5,511 5,965 5,136 5,511 5,965 5,136 5,511 5,965 6,367 5,136 5,511 5,965 6,367 5,136 5,511 5,965 6,367 5,136 5,511 5,965 6,367 5,136 5,511 5,965 6,367 5,136 5,511 5,965 6,367 5,136 5,511 5,965 6,367
SHC(W)
3,082 2,645 2,147 3,492 3,086 2,625 3,903 3,527 3,102 2,547 4,314 3,968 3,579 3,056 4,520 4,188 3,818 3,311 4,725 4,408 4,056 3,565 5,136 4,849 4,534 4,075 5,136 5,290 5,011 4,584 5,136 5,511 5,488
5,093
SHF
0.60
0.48
0.36
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
P.C.
1.97
2.00
2.05
1.97
2.00
2.05
1.97
2.00
2.05
2.12
1.97
2.00
2.05
2.12
1.97
2.00
2.05
2.12
1.97
2.00
2.05
2.12
1.97
2.00
2.05
2.12
1.97
2.00
2.05
2.12
1.97
2.00
2.05
2.12
4,976 5,323 5,805 4,976 5,323 5,805 4,976 5,323 5,805 6,206 4,976 5,323 5,805 6,206 4,976 5,323 5,805 6,206 4,976 5,323 5,805 6,206 4,976 5,323 5,805 6,206 4,976 5,323 5,805 6,206 4,976 5,323 5,805 6,206
CA
SHC(W)
2,985 2,555 2,090 3,383 2,981 2,554 3,781 3,407 3,018 2,482 4,179 3,833 3,483 2,979 4,378 4,046 3,715 3,227 4,577 4,259 3,947 3,475 4,976 4,684 4,412 3,972 4,976 5,110 4,876 4,468 4,976 5,323 5,340 4,965
SHF
0.60
0.48
0.36
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
(230V)
P.C.
2.09
2.14
2.19
2.09
2.14
2.19
2.09
2.14
2.19
2.26
2.09
2.14
2.19
2.26
2.09
2.14
2.19
2.26
2.09
2.14
2.19
2.26
2.09
2.14
2.19
2.26
2.09
2.14
2.19
2.26
2.09
2.14
2.19
2.26
CA : Capacity (W) SHC(W) : Sensible heat capacity
P.C. : Power consumption (kW) SHF : Sensible heat factor
17
Page 18
COOLING CAPACITY(8) PKA-RP2GAL / PUH-P2VGAA
PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2VGAA1.UK PUH-P2YGAA1.UK PU-P2VGAA PU-P2VGAA.UK PU-P2YGAA.UK PU-P2VGAA1.UK PU-P2YGAA1.UK
Indoor
Intake air
D.B.(°C)
20 20 20 22 22 22 24 24 24 24 26 26 26 26 27 27 27 27 28 28 28 28 30 30 30 30 32 32 32 32
34 34 34 34
Indoor
Intake air
W.B.(°C)
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA 4,762 5,136 5,564 4,762 5,136 5,564 4,762 5,136 5,564 5,992 4,762 5,136 5,564 5,992 4,762 5,136 5,564 5,992 4,762 5,136 5,564 5,992 4,762 5,136 5,564 5,992 4,762 5,136 5,564 5,992 4,762 5,136 5,564 5,992
SHC(W)
Outdoor intake air D.B.(°C)
35 40 45
2,857 2,465 2,003 3,238 2,876 2,448 3,619 3,287 2,893 2,397 4,000 3,698 3,338 2,876 4,190 3,903 3,561 3,116 4,381 4,109 3,784 3,356 4,762 4,520 4,229 3,835 4,762 4,931 4,674 4,314 4,762 5,136 5,119 4,794
SHF
0.60
0.48
0.36
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
P.C.
2.24
2.30
2.35
2.24
2.30
2.35
2.24
2.30
2.35
2.40
2.24
2.30
2.35
2.40
2.24
2.30
2.35
2.40
2.24
2.30
2.35
2.40
2.24
2.30
2.35
2.40
2.24
2.30
2.35
2.40
2.24
2.30
2.35
2.40
CA 4,548 4,976 5,350 4,548 4,976 5,350 4,548 4,976 5,350 5,778 4,548 4,976 5,350 5,778 4,548 4,976 5,350 5,778 4,548 4,976 5,350 5,778 4,548 4,976 5,350 5,778 4,548 4,976 5,350 5,778 4,548 4,976 5,350 5,778
SHC(W)
2,729 2,388 1,926 3,092 2,786 2,354 3,456 3,184 2,782 2,311 3,820 3,582 3,210 2,773 4,002 3,781 3,424 3,005 4,184 3,980 3,638 3,236 4,548 4,378 4,066 3,698 4,548 4,776 4,494 4,160 4,548 4,976 4,922 4,622
SHF
0.60
0.48
0.36
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
P.C.
2.40
2.47
2.52
2.40
2.47
2.52
2.40
2.47
2.52
2.59
2.40
2.47
2.52
2.59
2.40
2.47
2.52
2.59
2.40
2.47
2.52
2.59
2.40
2.47
2.52
2.59
2.40
2.47
2.52
2.59
2.40
2.47
2.52
2.59
CA 4,334 4,655 5,029 4,334 4,655 5,029 4,334 4,655 5,029 5,457 4,334 4,655 5,029 5,457 4,334 4,655 5,029 5,457 4,334 4,655 5,029 5,457 4,334 4,655 5,029 5,457 4,334 4,655 5,029 5,457 4,334 4,655 5,029 5,457
SHC(W)
2,600 2,234 1,810 2,947 2,607 2,213 3,293 2,979 2,615 2,183 3,640 3,351 3,017 2,619 3,813 3,537 3,219 2,838 3,987 3,724 3,420 3,056 4,334 4,096 3,822 3,492 4,334 4,468 4,224 3,929 4,334 4,655 4,627 4,366
SHF
0.60
0.48
0.36
0.68
0.56
0.44
0.76
0.64
0.52
0.40
0.84
0.72
0.60
0.48
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
1.00
0.88
0.76
0.64
1.00
0.96
0.84
0.72
1.00
1.00
0.92
0.80
(230V)
P.C.
2.60
2.66
2.70
2.60
2.66
2.70
2.60
2.66
2.70
2.75
2.60
2.66
2.70
2.75
2.60
2.66
2.70
2.75
2.60
2.66
2.70
2.75
2.60
2.66
2.70
2.75
2.60
2.66
2.70
2.75
2.60
2.66
2.70
2.75
CA : Capacity (W) SHC(W) : Sensible heat capacity P.C. : Power consumption (kW) SHF : Sensible heat factor
18
Page 19
HEATING CAPACITY (1)
PKA-RP•GAL / PUHZ-RP•VHA
Indoor
Service Ref.
PKA-RP1.6GAL
PKA-RP2GAL
NOTE: CA: Capacity (W) P.C.: Power consumption (kW)
intake are D.B. (˚C)
15 20 25 15 20 25
-10 -5 0 5 10 15
CA 2,604 2,501 2,419 2,858 2,745 2,655
P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
0.75
2,829
0.81
2,706
0.86
2,624
0.83
3,105
0.90
2,970
0.95
2,880
0.83
0.89
0.97
0.91
0.98
1.06
Outdoor intake air W.B. (:)
3,157 2,993 2,870 3,465 3,285 3,150
HEATING CAPACITY (2)
PKA-RP•GAL / PUH-P•VGAA PUH-P•VGAA.UK PUH-P•YGAA.UK
1.UK PUH-P•YGAA1.UK
Outdoor intake air W.B. (:)
P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.
1.06
1.15
1.22
1.38
1.50
1.59
3,416 3,267 3,168 4,278 4,092 3,968
1.16
1.25
1.36
1.52
1.64
1.78
3,812 3,614 3,465 4,774 4,526 4,340
Service Ref.
PKA-RP1.6GAL
PKA-RP2GAL
Indoor intake are D.B. (˚C)
15 20 25 15 20 25
PUH-P•VGAA
-10 -5 0 5 10 15
CA 3,143 3,020 2,921 3,937 3,782 3,658
0.95
1.03
1.12
1.05
1.13
1.23
1.34
1.45
1.58
1.76
1.90
2.06
4,141 3,998 3,772 4,545 4,388 4,140
5,000 4,826 4,554 6,262 6,045 5,704
1.14
1.23
1.31
1.26
1.36
1.44
1.61
1.74
1.84
2.11
2.27
2.41
4,674 4,510 4,346 5,130 4,950 4,770
5,643 5,445 5,247 7,068 6,820 6,572
1.27
1.37
1.47
1.40
1.51
1.62
1.79
1.93
2.07
2.34
2.53
2.70
5,207 5,023 4,838 5,715 5,513 5,310
6,287 6,064 5,841 7,874 7,595 7,316
(230V)
1.37
1.47
1.58
1.51
1.62
1.74
(230V)
1.93
2.08
2.23
2.53
2.71
2.91
NOTE: CA: Capacity (W) P.C.: Power consumption (kW)
19
Page 20
1.4
1.2
1.0
15
20 25
25 20
15
0.8
0.6
0.4
1.4
1.2
1.0
0.8
0.6
0.4
-12 -10 -5 0 5 10 15
INDOOR D.B.(°C)
INDOOR D.B.(°C)
OUTDOOR W.B.(°C)
CAPACITY (RATIO)TOTAL INPUT (RATIO)
Correcting the capacity line influenced by frosting Not correcting the capacity line influenced by frosting
In some cases, heating operation cannot be conducted with the maximum frequency in the area below the slanting line.
In some cases, heating operation cannot be conducted with the maximum frequency in the area above the slanting line.
1.4
1.2
1.0
0.8
10
22 20 18 16
22
20
18 16
20 30 46400-5
1.2
1.0
0.8
0.6
0.4
INDOOR W.B.(°C)
CAPACITY (RATIO)TOTAL INPUT (RATIO)
INDOOR W.B.(°C)
OUTDOOR D.B.(°C)
5-2. PERFORMANCE CURVE
1.4
1.2
1.0
15
20 25
25 20
15
0.8
0.6
0.4
1.4
1.2
1.0
0.8
0.6
0.4
-12 -10 -5 0 5 10 15
INDOOR D.B.(°C)
INDOOR D.B.(°C)
OUTDOOR W.B.(°C)
CAPACITY (RATIO)TOTAL INPUT (RATIO)
Correcting the capacity line influenced by frosting Not correcting the capactiy line influenced by frosting
1.4
1.2
1.0
0.8
10
22 20 18 16
22
20
18 16
20 30 46400-5
1.2
1.0
0.8
0.6
0.4
INDOOR W.B.(°C)
CAPACITY (RATIO)TOTAL INPUT (RATIO)
INDOOR W.B.(°C)
OUTDOOR D.B.(°C)
PKA-RP•GAL / PUHZ-RP•VHA
Cooling performance curve(50Hz)
Heating performance curve(50Hz)
PKA-RP•GAL / PUH-P•VGAA PUH-P•VGAA.UK PUH-P•YGAA.UK
PU-P•VGAA PU-P•VGAA.UK PU-P•YGAA.UK
PUH-P•VGAA
1.UK PUH-P•YGAA1.UK
PU-P•VGAA1.UK PU-P•YGAA1.UK
Cooling performance curve(50Hz)
Heating performance curve(50Hz)
20
Page 21
5-3. Correction factors
PKA-RP•GAL / PUHZ-RP•VHA
Cooling capacity correction factors
Service Ref.
PKA-RP1.6GAL
5m
1.00
10m
0.992
20m
0.976
Refrigerant piping length (one way)
30m
0.962
40m
0.949
50m
0.936
55m
0.930
60m
70m
80m
PKA-RP2GAL
Heating capacity correction factors
Service Ref.
PKA-RP1.6GAL PKA-RP2GAL
PKA-RP•GAL / PUH-P•VGAA PUH-P•VGAA.UK PUH-P•YGAA.UK
Cooling capacity correction factors
Service Ref.
PKA-RP1.6GAL PKA-RP2GAL
1.00
5m
1.00
1.00
PU-P•VGAA PU-P•VGAA.UK PU-P•YGAA.UK
0.985
10m
0.997
0.997
PUH-P•VGAA
PU-P•VGAA1.UK PU-P•YGAA1.UK
5m 10m 20m 30m 40m 50m
1.00
1.00
0.957
20m
0.991
0.991
Refrigerant piping length(one way)
0.993
0.993
0.978
0.978
0.931
Refrigerant piping length (one way)
30m
0.985
0.985
1.UK PUH-P•YGAA1.UK
0.961
0.961
0.908
40m
0.979
0.979
0.948
0.948
0.886
50m
0.973
0.973
— —
0.876
55m
0.970
0.970
60m
— —
70m
— —
80m
— —
Heating capacity correction factors
Service Ref.
PKA-RP1.6GAL PKA-RP2GAL
5m 10m 20m 30m 40m 50m
1.00
1.00
Refrigerant piping length(one way)
0.998
0.998
0.993
0.993
0.988
0.988
0.983
0.983
— —
21
Page 22
5-4. STANDARD OPERATION DATA
Service Ref.
Mode Capacity Input
Indoor unit Service Ref.
Phase , Hz Volts Amperes
Outdoor unit Service Ref.
Phase , Hz Volts Amperes
Discharge pressure
Suction pressure
Discahrge temperature
Condensing temperature
Suction temperature
Ref.pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
BF
SHF
W
kW
˚C
˚C ˚C
˚C ˚C
D.B.
D.B.
W.B.
D.B.
W.B.
˚C ˚C ˚C
m
MPa MPa
Outdoor
side
Indoor side Refrigerant circuit Electrical circuit Total
Cooling Heating Cooling Heating
PKA-RP1.6GAL PKA-RP2GAL
PKA-RP1.6GAL
1 , 50
230
PUHZ-RP1.6VHA
1 , 50
230
PKA-RP2GAL
1 , 50
230
PUHZ-RP2VHA
1 , 50
230
3,600
1.03
0.33
4.29
70 46 15
5 27 19
14.8 35 24
0.84
0.11
4,100
1.27
0.33
5.36
81 48
2
5 20 15
38.3 7 6
— —
4,600
1.63
0.33
6.98
76 49
3
5 27 19
13.3 35 24
0.74
0.13
4,500
1.40
0.33
5.95
82 53
2
5 20 15
40.2 7 6
— —
2.68
1.01
3.05
0.73
2.89
0.79
3.18
0.72
Heat pump type (1)
The unit of pressure has been changed to Mpa on tha international system of unit (Sl system). The converted score against tha traditional unit system can be gotten according to the formula below. 1(Mpa) = 10.2(kgf/ff)
22
Page 23
Heat pump type (2)
Service Ref.
Mode Capacity Input
W
kW
Indoor unit Service Ref.
Phase , Hz Volts Amperes
Outdoor unit Service Ref.
Phase , Hz Volts Amperes
Discharge pressure
Suction pressure
Discahrge temperature
Condensing temperature
Suction temperature
Ref.pipe length
MPa MPa
˚C ˚C ˚C
m
PKA-RP1.6GAL PKA-RP2GAL
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
1.70
0.33
2.37
2.11
0.53 80 49
8 5
3 , 50
400
4,950
1.79
0.33
5,350
2.33
0.33
PUH-P2VGAA PUH-P2VGAA.UK PUH-P2VGAA
2.51
10.80
2.10
0.47
2.38
0.48 77 47
2 5
6,200
PKA-RP2GAL
1 , 50
230
10.85
88 53
4 5
5,350
2.34
2.33
1 , 50
230
0.33
0.33
PUH-P2YGAA.UK
1.UK
PUH-P2YGAA1.UK
3.37
95 55
2.38
0.48 88 53
1 5
4 5
2.56
0.44
6,200
2.34
0.33
3 , 50
400
3.39
2.56
0.44 95 55
1 5
4,450
1.70
4,950
4,450
1.79
PKA-RP1.6GAL
1 , 50
230
0.33
0.33
PUH-P1.6VGAA PUH-P1.6VGAA.UK PUH-P1.6VGAA
PUH-P1.6YGAA.UK
1.UK
PUH-P1.6YGAA1.UK
1 , 50
230
80 49
8.22
2.10
0.47 77 47
8 5
2 5
7.79
2.11
0.53
Intake air temperature
Discharge air
Indoor side Refrigerant circuit Electrical circuit Total
temperature
Intake air temperature
side
Outdoor
SHF
BF
W.B.
D.B. D.B.
W.B.
˚C ˚C ˚C ˚C ˚C
27 19
13.3 35 24
0.77
0.09
20 15
42.5 7 6
— —
27 19
13.3 35 24
0.77
0.09
20 15
42.5 7 6
— —
27 19
11.9 35 24
0.70
0.11
20 15
48.9
— —
27 19
11.9 35
7
24
6
0.70
0.11
20 15
48.9 7 6
— —
D.B.
The unit of pressure has been changed to Mpa on tha international system of unit (Sl system). The converted score against tha traditional unit system can be gotten according to the formula below. 1(Mpa) = 10.2(kgf/ff)
23
Page 24
Air flow m3/min Air speed m/sec Coverage range m (ft)
12
5.3
10(32.8)
PKA-RP1.6GAL
12
5.3
10(32.8)
PKA-RP2GAL
Service Ref.
Mode Capacity Input
Indoor unit Service Ref.
Phase , Hz Volts Amperes
Outdoor unit Service Ref.
Phase , Hz Volts Amperes
Discharge pressure
Suction pressure
Discahrge temperature
Condensing temperature
Suction temperature
Ref.pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
BF
SHF
W
kW
˚C
˚C ˚C
˚C ˚C
D.B.
D.B. W.B.
D.B. W.B.
˚C ˚C ˚C
m
MPa MPa
Outdoor
side
Indoor side Refrigerant circuit Electrical circuit Total
Cooling Cooling Cooling Cooling
PKA-RP1.6GAL PKA-RP2GAL
PU-P1.6VGAA PU-P1.6VGAA.UK PU-P1.6VGAA
1.UK
PU-P1.6YGAA.UK PU-P1.6YGAA1.UK
PU-P2VGAA PU-P2VGAA.UK PU-P2VGAA
1.UK
PU-P2YGAA.UK PU-P2YGAA1.UK
PKA-RP2GAL
1 , 50
230
PKA-RP1.6GAL
1 , 50
230
1 , 50
230
3 , 50
400
1 , 50
230
3 , 50
400
4,450
1.70
0.33
7.79
80 49
8
5 27 19
13.3 35 24
0.77
0.09
2.11
0.53
2.11
0.53
5,350
2.33
0.33
10.80
88 53
4
5 27 19
11.9 35 24
0.70
0.11
2.38 2.38
0.48
5,350
2.33
0.33
3.37
88 53
4
5 27 19
11.9 35 24
0.70
0.11
0.48
4,450
1.70
0.33
2.37
80 49
8
5 27 19
13.3 35 24
0.77
0.09
Cooling only type
The unit of pressure has been changed to Mpa on tha international system of unit (Sl system). The converted score against tha traditional unit system can be gotten according to the formula below. 1(Mpa) = 10.2(kgf/ff)
5-5. OUTLET AIR SPEED COVERAGE RANGE
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from the unit at the Hi notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furni­ture inside the room.
24
Page 25
5-6. NOISE CRITERION CURVES
UNIT
WALL
1m
1m
MICROPHONE
PKA-RP1.6GAL PKA-RP2GAL
90
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
20
10
APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NOTCH
Hi Mi1 Mi2
Lo
SPL(dB)
43 41 38 36
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
25
Page 26
6
BYOFF
ON STAND
HEATCOOL
OFF BY
ON STAND
COOL HEAT
ÅrÇoÇoÅqÅ@ëOñÅ@ÇeÇqÇnÇmÇs ÅrÇoÇoÅqÅ@ëOñÅ@ÇeÇqÇnÇmÇs
r.SLI
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
r.S
L
I
m m
MITSUBISHI ELECTRICMITSUBISHI ELECTRIC
Knock out hole for right piping
Refrigerant pipe.Drain pipe.
Wiring hole
21
Right side
Less than 15
70
245
60
235
Auto vane
Front view
Air intake
Air intake
Air intake
Air intake
198
53
340
715 225
340 80 280 233
990
21
Left side
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
60
70
245
(Necessary clearance for
Unit installation)
Right side
Allowing clearances
Front view
Less than 130
50 or more 150 or more
180 or more 30 or more
for bolts
Left-rear
piping hole
left-rear piping
R52.5
R52.5
Installation plate
balance point hole
Details of installation plate
49-[5hole
for tapping screw
Knock out hole for
right-rear piping
Right-rear
piping hole
Unit center
14-[14hole
Knock out hole for
425
420
170
190
210 230
0
322
0355580130
190
230
272
310
0
35
95
150
205
260
320
345
495
20 75 135 190 245 300 360
405
495
32
0
w1 Sleeves are available on the market.
w2 This size shows the lower end of through hole.
[90~[100[90
Through hole
Sleeve w1
1.6
.
2
Model
R52.5
R52.5
Gas pipe
Liquid pipe
Terminal block to
outdoor unit
Filter grip
Service panel
(Power supply access)
Gas pipe
Liquid pipe
1.6, 2
Model
(Flexible hose total length800)
(Right side piping
installation)
(Left side piping
installation)
Unit drain pipe O.D.20
Front view(to open the grille)
700
449
86
581 54
31 280
35
Knock out hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
12-Louvers(manual)
Air outlet
Lower side
80
50
395400
190
60
70 35
79
160 40
235
705
153
Refigerant Pipe flared connection
For PUHZ–RP type : 1/4F([6.35)
For PU(H)–P type : 3/8F([9.52)
Refigerant Pipe flared connection
For PUHZ–RP type : 1/2F([12.7)
For PU(H)–P type : 5/8F([15.88)
OUTLINES AND DIMENSIONS
INDOOR UNIT
PKA-RP1.6GAL PKA-RP2GAL
Unit : mm
26
Page 27
7
WIRING DIAGRAM
PKA-RP1.6GAL PKA-RP2GAL
INDOOR UNIT
MF
123
C
I.B
SWE SW1SW2 ON OFF
Manufacture Service board
P.B
F1
ZNR
I.B
CN2L CN32 CN41
SW1
SW2
SWE
X4 FC LED1 LED2
WHT
RED
BLK
X4
POWER CN03
(RED)
FAN (WHT)
FC
1
35
X4
D.SENSOR CN31
J14
J13
J12
J11
J21
J22
J23
J24
J15
(WHT)
SW1
J15J14J13J12J11
INDOOR POWER BOARD FUSE(4A) VARISTOR INDOOR CONTROLLER BOARD CONNECTOR(LOSSNAY) CONNECTOR(REMOTE SWITCH) CONNECTOR(HA TERMINAL-A) JUMPER WIRE(MODEL SELECTION) JUMPER WIRE(CAPACITY CORD) SWITCH(EMERGENCY OPERATION) RELAY(FAN MOTOR) FAN PHASE CONTROL POWER SUPPLY(I.B) POWER SUPPLY(R.B) TRANSMISSION(INDOOR-OUTDOOR)LED3
NAME SYMBOLSYMBOL
BRN
YLW
ORN
5
13 21
LED3 LED2 LED1
321
54321
ON OFF
WHT
BLK
POWER CN2D(WHT)
HEATER
CN24 (YLW)
21
MODELS
1.6GAL
TB4
TB5
TH1 ROOM TEMP.THERMISTOR
TH2
TH5
CN2S(WHT)
2
DC14V
1
F1
ZNR
3 2 1
CONT.BOARD CN02(WHT)
CN41
CN25
INTAKE
LIQUID
CN20
CN21
(RED)
(WHT)
12 12
TH1
TH2 TH5
CN2L
CN32
PIPE CN29 (BLK)
1
OUTDOOR CN01(BLU)
VANE CN6V (WHT)
WIRELESS CN90 (WHT)
REMOCON CN22 (BLU)
2
21
SW2
Manufacture
CAPACITOR(FAN MOTOR)C FAN MOTORMF VANE MOTORMV TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)(OPTION)
(0°C/15k",25°C/5.4k" DETECT) PIPE TEMP.THERMISTOR/LIQUID (0°C/15k",25°C/5.4k" DETECT) COND./EVA.TEMP.THERMISTOR (0°C/15k",25°C/5.4k" DETECT)
Service board
1ON432
J24J23J22J21
NAME SYMBOL
P.B
TB4
YLW ORN BRN
S1 S2 S3
TO OUTDOOR UNIT
1 2 3
]
6
MV
9
RU
RECEIVER
2 1
TRANSMISSION WIRES DC12V
TB5
Please set the voltage using the remote controller. For the setting method,please refer to the indoor unit Installation Manual.
MODELS
2GAL
OFF
RU RECEIVING UNIT
LED1 LED(RUN INDICATOR) LED2 SW1
CN2 TB6
9
CNB
BZ
LED2
LED1 SW1SW2
R.B
CN2
W.B
21
TB6
SW2
Manufacture Service board
J24J23J22J21
WIRELESS REMOTE CONTROLLER BOARDW.B
BUZZERBZ
LED(HOT ADJUST) SWITCH(HEATING ON/OFF) SWITCH(COOLING ON/OFF)SW2 REMOTE CONTROLLER BOARD(OPTION)R.B CONNECTOR(PROGRAM TIMER)
TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE)
NAME
1ON432
OFF
NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities,make wiring matching terminal numbers(S1,S2,S3).
3.Make sure that the main power supply of the booster heater is independent.
4.Symbols used in wiring diagram above are, [Self-diagnosis]
An explanation of the wireless remote controller self checking operations,check codes,buzzer sounds and LED signals are given below. For check codes and symptom see the table below please.
1.Press the CHECK button twice continuously.
· CHECK begins to light and refrigerant address display "00" begins to blink.
· Start this operation from the status of remote controller display turned off.
2.Press the TEMP , buttons.
· Set the refrigerant address of the indoor unit that is to be self-diagnosed.
· Set the refrigerant address of outdoor unit by outdoor unit dip switch "SW1". (Refer to installation manual of outdoor unit for the detail.)
Check code
U0~UL F1~F9 E6~EF
Operation lamp
P1
1SEC.FLASHo1
P2
1SEC.FLASHo2
P6
1SEC.FLASHo6
P8
1SEC.FLASHo8
P9
1SEC.FLASHo2 (0.4+0.4)SEC.FLASHo1
DIFFERENT FROM ABOVE
----
OFF
FFFF
OFF
Buzzer sound Single beepo1 Single beepo2 Single beepo6 Single beepo8 Single beepo2 Double beepo1
Sounds other than above No sound Triple beep
:Connector, :Terminal (block).
3.While pointing the remote controller toward the unit's receiver, press the h button.
· The check code will be indicated by the number of times that the buzzer sounds from the receiver section and the number of blinks of the operation lamp.
4.While pointing the remote controller toward the unit's receiver, press the ON/OFF button.
· Self-check mode is canceled.
Abnormality of room temperature thermistor(TH1). Abnormality of pipe temperature thermistor/Liquid(TH2). Freezing /overheating protection is working. Abnormality of pipe temperature. Abnormality of pipe temperature thermistor/ Cond./Eva.(TH5). Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
Abnormality of signal transmission between indoor unit and outdoor unit ("EE" indicates abnormality of combination). No trouble generated in the past. No corresponding unit.
Symptom
27
Page 28
8
Pipe temperature thermistor/liquid (TH2)
Distributor with strainer #50
Condenser/evaporator temperature thermistor (TH5)
Room temperature thermistor (TH1)
Refrigerant flow in cooling Refrigerant flow in heating
Strainer #50
Strainer #50
Heat exchanger
Refrigerant GAS pipe connection (Flare)
Refrigerant LIQUID pipe connection (Flare)
REFRIGERANT SYSTEM DIAGRAM
PKA-RP1.6GAL PKA-RP2GAL
Unit : mm
28
Page 29
9 TROUBLESHOOTING
Unit conditions at service
Error code
Actions to be taken for service (summary)
The inferior phenomenon is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “Self-diagnosis action table” (Page 31).
Identify the cause of the inferior phenomenon and take a corrective action according to “Trouble shooting by inferior phenomena” (Page 34).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service. 3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom. 2Identify the cause of the inferior phenomenon and take
a corrective action according to “Trouble shooting by inferior phenomena” (Page 34). 3Continue to operate unit for the time being if the cause is not ascertained. 4There is no abnormality in electrical components, controller boards, remote controller etc.
9-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service and the inferior phenomenon reoccurrence at field are summarized in the table below. Check the contents below before investigating details.
29
Page 30
Inspected unit
Check code
P1 P2 P4 P5 P6 P8 P9
E4, E5
Beep output
beep O 1 time beep O 2 times beep O 4 times beep O 5 times beep O 6 times beep O 8 times beep O 2 times Other than above
Operation LED 1 sec. O 1 time 1 sec.O 2 times 1 sec.O 4 times 1 sec.O 5 times 1 sec.O 6 times 1 sec.O 8 times 1 sec.O 2 times Other than above
Indoor unit
Inspected unit
Check code
F1–F9 U0–UP E6–EE
No check code
(normal)
Beep output
beep beep O 1 time
Other than above
No output
beep beep beep
Operation LED (0.4sec+0.4sec)
O 1 time
Other than above
Lights off
Lights off
Outdoor
unit
No check code (mistake of match­ing with refrigerant
address)
9-2. Malfunction-diagnosis method by remote controller
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK display
Temperature button
CHECK button
Refrigerant address display
HOUR button
ON/OFF button
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
<Malfunction-diagnosis method at maintenance service>
[Procedure]
1. Press the CHECK button twice.
• "CHECK" lights, and refrigerant address "00" flashes.
• Check that the remote controller's display has stopped before continuing.
2. Press the temperature buttons.
• Select the refrigerant address of the indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1).
(For more information, see the outdoor unit installation manual.)
3. Point the remote controller at the sensor on the indoor unit and press the HOUR button.
• If an air conditioner error occurs, the indoor unit's sensor emits an intermit­tent buzzer sound, the operation light flashes, and the error code is output. (It takes 3 seconds at most for error code to appear.)
4. Point the remote controller at the
• The check mode is cancelled.
sensor on the indoor unit and press the ON/OFF button.
Malfunction diagnosis can be performed only for refrigerant system control-
ling wireless units.
30
Page 31
9-3. SELF-DIAGNOSIS ACTION TABLE
Error Code
P1
P2
Meaning of error code and detection method Abnormality of room temperature
thermistor (TH1)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating operation. Short: 90: or more Open: -40: or less
Abnormality of pipe temperature thermistor/Liquid (TH2)
1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.)
2 Constantly detected during cooling,
drying, and heating (except defrosting) operation. Short: 90: or more Open: -40: or less
Note: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Cause
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN20) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective indoor controller
board.
1 Defective thermistor
characteristics.
2 Contact failure of connector
(CN21) on the indoor controller board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring.
4 Defective refrigerant circuit is
causing thermistor temperature of 90: or more or -40: or less.
5 Defective indoor controller board.
Countermeasure
13 Check resistance value of thermistor. 0: ······15.0k" 10: ····9.6k" 20: ····6.3k" 30: ····4.3k" 40: ····3.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor breaking of wire or contact failure can be detected. 2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to page 37. Turn the power on again and check restart after inserting connector again.
4 Check room temperature display on remote
controller. Replace indoor controller board if there is abnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
13 Check resistance value of thermistor. For characteristics, refer to (P1) above. 2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to page 37. Turn the power on and check restart after inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in test run mode. If there is exclusive difference with actual pipe <liquid> temperature, replace indoor controller board.
P4
P5
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds continuously. Turn off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnormality. (The unit returns to normal operation,
if it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature
- room temperature <-10deg (Except defrosting)
• When pipe <liquid> temperature or room temperature is short/open temperature.
• During drain pomp operation.
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pomp is abnormal if the condition
above is detected during suspensive abnormality.
3 Constantly detected during drain pomp
operation.
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN31) on the indoor controller board. (Insert failure).
3 Breaking of wire or contact
failure of drain sensor wiring.
4 Defective indoor controller board.
1 Malfunction of drain pump 2 Defective drain
Clogged drain pump Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from lead wire.
• Clogged filter is causing wave of drain.
4 Defective indoor controller board.
Turn the power off, and on again to operate after check.
13 Check resistance value of thermistor. 0: ······6.0k" 10: ····3.9k" 20: ····2.6k" 30: ····1.8k" 40: ····1.3k" 2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to page 37. Turn the power on again and check restart after inserting connector again.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited, and abnormality reappears.
Turn the power off, and on again to operate after check.
1 Check if drain-up machine works. 2 Check drain function. 3 Check the setting of lead wire of drain sensor
and check clogs of the filter.
4 Replace indoor controller board if drain
pump operates with the line of drain sensor connector CN31-1 and 2 is short-circuited and abnormality reappears. Refer to page 37.
Turn the power off, and on again to operate after check.
31
Page 32
Error Code
123456
ON OFF
123456
ON OFF
123456
ON OFF
123456
ON OFF
A-Control Service Tool SW2 setting
Temperature display of indoor liquid pipe Indoor 1
Temperature display of indoor liquid pipe Indoor 2
Temperature display of indoor condenser/ evaporator pipe Indoor 1
Temperature display of indoor condenser/ evaporator pipe Indoor 2
P6
P8
Meaning of error code and detection method Freezing/overheating protection is
working
1 Freezing protection (Cooling mode)
The unit is in six-minute resume prevention mode if pipe <liquid or condenser/evap-
(Cooling or drying mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Low-load (low temperature)
orator> temperature stays under
-15: for three minutes, three minutes after the compressor started. Abnormal if it stays under -15: for three minutes again within 16 minutes after six-minute
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
resume prevention mode.
2 Frost abnormality (Only for the combination
with inverter-type outdoor unit) Suspensive abnormal if unit operates in frost prevention mode (below) for 9 minutes or more. After that, when frost prevention mode is released and
5 Overcharge of refrigerant 6 Defective refrigerant circuit
compressor restarts its operation, unit is not detected as abnormal if compressor keeps operating for 20 minutes continuously and abnormal if compressor stops operating within 20 minutes and unit operates in frost prevention mode for more than 9 minutes again. (Not abnormal if unit stops operating in frost prevention
(Heating mode)
1 Clogged filter (reduced airflow) 2 Short cycle of air path 3 Over-load (high temperature)
mode within 9 minutes) <Frost prevention mode> If pipe <liquid or condenser-evaporator> temperature is 2: or below when 16 minutes has passed after compressor starts operating, unit will start operating
4 Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
in frost prevention mode which stops compressor operation. After that, when pipe <liquid or condenser/evaporator> temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
5 Overcharge of refrigerant 6 Defective refrigerant circuit
3 Overheating protection (Heating mode)
The units is in six-minute resume prevention mode if pipe <condenser /
7 Bypass circuit of outdoor unit
evaporator> temperature is detected as over 74: after the compressor started. Abnormal if the temperature of over 74: is detected again within 10 minutes after six-minute resume prevention mode.
Abnormality of pipe temperature
1 Slight temperature difference
<Cooling mode> Detected as abnormal when the pipe tem­perature is not in the cooling range 3 min­utes later of compressor start and 6 min­utes later of the liquid or condenser/evapo­rator pipe is out of cooling range. Note 1) It takes at least 9 min. to detect. Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : Indoor pipe temperature
2 Converse connection of
(TH2 or TH5) – intake temperature (TH1) [ -3 deg
TH: Lower temperature between: liquid
3 Converse wiring of indoor/
pipe temperature and condenser/ evaporator temperature
4 Defective detection of indoor
<Heating mode> When 10 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is
5 Stop valve is not opened
detected as abnormal when condenser/evaporator pipe temperature is not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrosting mode is over)
Heating range : 3 deg [ (Condenser/
Evaporator temperature(TH5) – intake temperature(TH1))
Cause
operation beyond the tolerance range
defective.
(clogs)
operation beyond the tolerance range
defective.
(clogs) is defective.
between indoor room temperature and pipe <liquid or condenser / evaporator> temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe <liquid or condenser /
evaporator> thermistor
• Defective refrigerant circuit
extension pipe (on plural units connection)
outdoor unit connecting wire (on plural units connection)
room temperature and pipe <condenser / evaporator> temperature thermistor
completely.
32
Countermeasure
(Cooling or drying mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's winding.
Measure the output voltage of fan's connector (FAN) onthe indoor controller board.
WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to page 37.
56 Check operating condition of refrigerant
circuit.
(Heating mode)
1 Check clogs of the filter. 2 Remove shields.
4 Measure the resistance of fan motor's
winding. Measure the output voltage of fan's connector (FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to page 37.
5~7Check operating condition of refrigerant
circuit.
1~4 Check pipe <liquid or condenser /
evaporator> temperature with room temperature display on remote controller and outdoor controller circuit board. Pipe <liquid or condenser / evaporator> temperature display is indicated by setting SW2 of outdoor controller circuit board as follows.
Conduct temperature check with outdoor controller circuit board after connecting
(
‘A-Control Service Tool(PAC-SK52ST)’.
23Check converse connection of extension
pipe or converse wiring of indoor/outdoor unit connecting wire.
)
Page 33
Error Code
123456
ON OFF
123456
ON OFF
A-Control Service Tool SW2 setting
Temperature display of indoor condenser/ evaporator pipe Indoor 1
Temperature display of indoor condenser/ evaporator pipe Indoor 2
P9
Meaning of error code and detection method
Abnormality of pipe temperature ther­mistor / Condenser-Evaporator (TH5)
1 The unit is in three-minute resume pro-
tection mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within three min­utes. (The unit returns to normal opera­tion, if it has normally reset.)
2 Constantly detected during cooling, dry-
ing, and heating operation (except defrosting) Short: 90: or more Open: -40: or less
1 Defective thermistor 2 Contact failure of connector
3 Breaking of wire or contact 4 Temperature of thermistor is
5 Defective indoor controller
Cause
characteristics (CN29) on the indoor controller
board. (Insert failure) failure of thermistor wiring. 90: or more or -40: or less
caused by defective refrigerant circuit.
board.
Countermeasure
13 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN29)
on the indoor controller board. Refer to page 37. Turn the power on and check restart after inserting connector again.
4 Operate in test run mode and check pipe
<condenser / evaporator> temperature with outdoor controller circuit board. If pipe <condenser / evaporator> temperature is exclusively low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective.
5 Operate in test run mode and check pipe
<condenser / evaporator> temperature with outdoor control circuit board. If there is exclusive difference with actual pipe <condenser / evaporator> temperature replace indoor controller board. There is no abnormality if none of above comes within the unit. Turn the power off and on again to operate.
In case of checking pipe temperature with outdoor controller circuit board, be sure to connect A-control service
(
tool (PAC-SK52ST).
)
E4
E5
E6
E7
Remote controller signal receiving error
1 Abnormal if indoor controller board can
not receive normally any data from remote controller or from other indoor controller board for three minutes.
2 Indoor control board cannot receive any
signal from remote controller for two minutes.
Remote controller transmitting error
1 Abnormal if indoor controller board cannot
check the blank of transmission path for three minutes.
2 Abnormal if indoor controller board cannot
finish transmitting 30 times consecutively.
Indoor/outdoor unit communication error (Signal receiving error)
1 Abnormal if indoor controller board
cannot receive any signal normally for six minutes after putting the power on.
2 Abnormal if indoor controller board
cannot receive any signal normally for three minutes.
3 Consider the unit abnormal under the
following condition: When two or more indoor units are connected to one outdoor unit, indoor controller board cannot receive a signal for three minutes from outdoor controller circuit board, a signal which allows outdoor controller circuit board to transmit signals.
Indoor/outdoor unit communication error (Transmitting error)
Abnormal if “1” receiving is detected 30 times continuously though indoor controller board has transmitted “0”.
1 Contact failure at transmission
wire of remote controller
2 All remote controllers are set
as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board.
3 Defective transmitting receiving
circuit of remote controller
4 Defective transmitting receiving
circuit of indoor controller board.
5 Noise has entered into the
transmission wire of remote controller.
1 Defective transmitting receiving
circuit of indoor controller board.
2 Noise has entered into the
transmittion wire of remote controller.
1 Contact failure, short circuit or,
mis-wiring (converse wiring) of indoor/outdoor unit connecting wire
2 Defective transmitting receiving
circuit of indoor controller board
3 Defective transmitting receiving
circuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
1 Defective transmitting receiving
circuit of indoor controller board
2 Noise has entered into power
supply.
3 Noise has entered into outdoor
control wire.
33
1 Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2 Set one of the remote controllers “main”.
If there is no problem with the action above.
3 Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem. Put the power off, and on again to check. If abnormality generates again, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller. c) When “RC E3” is displayed, d) When “ERC 00-06” is displayed, [ c),d)Noise may be causing abnormality. ]
If the unit is not normal after replacing
indoor controller board in group control, indoor controller board of address “0” may be abnormal.
12 Turn the power off, and on again to
check. If abnormality generates again, replace indoor controller board.
Check LED display on the outdoor control
circuit board. (Connect A-control service tool, PAC-SK52ST.) Refer to EA-EC item if LED displays EA-EC.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or outdoor unit. Check all the units in case of twin triple indoor unit system.
2-4 Turn the power off, and on again to
check. If abnormality generates again, replace indoor controller board or outdoor controller circuit board.
Other indoor controller board may have
defective in case of twin triple indoor unit system.
1-3 Turn the power off, and on again to
check. If abnormality generates again, replace indoor controller board.
Page 34
9-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Note: Refer to the manual of outdoor unit for the detail of remote
controller.
Phenomena
(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is also off.
1 Power supply of 220~240V is not supplied to outdoor
unit.
2 Defective outdoor controller circuit board.
3 Power supply of 220~240V is not supplied to indoor
unit.
4 Defective indoor power board.
5 Defective indoor controller board.
Cause
Countermeasure
1 Check the voltage of outdoor power
supply terminal block (L, N)
• When AC 220~240V is not detected. Check the power wiring to outdoor unit and the breaker.
• When AC 220~240V is detected. —Check 2 (below).
2 Check the voltage between outdoor
terminal block S1 and S2.
• When AC 220~240V is not detected. Check the fuse on outdoor controller circuit board (10A). Check the wiring connection.
• When AC 220~240V is detected. —Check 3 (below).
3 Check the voltage between indoor terminal
block S1 and S2.
• When AC 220~240V is not detected. Check indoor/outdoor unit connecting wire for mis-wiring.
• When AC 220~240V is detected. —Check 4 (below).
4 Check voltage output from CN2S on indoor
power board (DC14V). Refer to page 38.
• When no voltage is output. Check the fuse on indoor power board. Check the wiring connection.
• When output voltage is between 12V and 16V. —Check 5 (below).
5 Check the wiring connection between
indoor controller board and indoor power board. If no problems are found, indoor controller board is defective.
(2)LED2 on indoor controller board
is blinking.
(3)Upward/downward vane
performance failure
• When LED1 on indoor controller board is lit.
1 Mis-setting of refrigerant address for outdoor unit
(There is no unit corresponding to refrigerant address “0”.)
• When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit.
Mis-wiring of remote controller wires Under twin triple indoor unit system, 2 or more indoor units are wired together.
1 Refrigerant address for outdoor unit is wrong or not
set.
Under grouping control system, there are some units whose refrigerant address is 0.
2 Short-cut of remote controller wires 3 Defective remote controller
1 The vane is not downward during defrosting and
heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOLprotection function)
2 Vane motor does not rotate.
• Defective vane motor
• Breaking of wire or connection failure of connector
3 Upward/downward vane does not work.
• The vane is set to fixed position.
1 Reconfirm the setting of refrigerant
address for outdoor unit
Set the refrigerant address to “0”. (For grouping control system under which 2 or more outdoor units are connected, set one of the units to “0”.) Set refrigerant address using SW1 (3-6) on outdoor controller circuit board.
Check indoor/outdoor unit connecting wire for connection failure. Check the connection of remote controller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units. 1 Check the setting of refrigerant address
in case of grouping control system.
If there are some units whose refrigerant addresses are 0 in one group, set one of the units to 0 using SW1 (3-6) on outdoor controller circuit board.
23 Remove remote controller wires and
check LED2 on indoor controller board.
• When LED2 is blinking, check the short-cut of remote controller wires.
• When LED2 is lit, connect remote controller wires again and:
if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
1 Normal operation (The vane is set to hor-
izontal regardless of remote control.)
2 Check 2 (left).
• Check the vane motor. (Refer to “How to check the parts”.)
• Check for breaking of wire or connec­tion failure of connector.
3 Normal operation (Each connector on
vane motor side is disconnected.)
34
Page 35
9-5. EMERGENCY OPERATION
Mode
Cooling
Heating
Set temperature
Fan speed
Airflow direction
24: High
Downward (70deg)
24: High
Horizontal (30deg)
wEmergency operation will be performed as follows.
Receiving section
Power lamp
Defrosting • Initial heating lamp
Emergency switch(Heat)
Emergency switch(Cool)
COOL
ON
O F F
HEAT
STAND
BY
9-5-1. When wireless remote controller troubles or its battery is exhausted
1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor unit.
2. To start operation
• Cooling Operation·······Press (Cooling) switch.
Heating Operation·······Press (Heating) switch.
wWhen the unit starts operating, the power lamp is lit.
3. To stop operation
• Press either emergency operation switch (cooling/heating).
9-5-2. When wired remote controller or indoor unit micro computer troubles
1. If there is not any other wrong when trouble occures, emergency operation starts as the indoor controller board switch (SWE) is set to ON. During the emergency operation the indoor unit is as follows;
(1) Indoor fan high speed operation
2. When emergency operating for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit
emergency operation are necessary.
3. Check items and notices as the emergency operation
(1) Emergency operation cannot be used as follows;
• When the outdoor unit is something wrong.
• When the indoor fan is something wrong.
• When drain over flow protected operation is detected during self-diagnosis. (Error code : P5)
(2) Emergency operation will be serial operation by the power supply ON/OFF.
ON/OFF or temperature, etc. adjustment is not operated by the remote controller.
(3) Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emer-
gency operation. (4) Cool emergency operation must be within 10 hours at most. It may cause heat exchanger frosting in the indoor unit. (5) After completing the emergency operation, return the switch setting, etc. in former state. (6) Since vane does not work at emergency operation, position the vane manually and slowly.
35
Page 36
1
1
2
2
3
3
Red
White
Black
Relay connector
Protector OPEN : 125i 5: CLOSE : 79i 15:
4
5
2
361
Orange
Red Pink
Yellow Brown Blue
M
Parts name Check points
Measure the resistance between the terminals using a tester. (Winding temperature 20:)
Fan motor (MF)
Abnormal
Open or short
Red–Black
White–Black
Motor terminal
or
Relay connector
RP1.6 , RP2
120.5"
111.3"
Normal
Open or short
Abnormal
Brown–Yellow
Brown–Blue
Red–Orange
Red–Pink
Connector
Normal
186~214"
Measure the resistance between the terminals using a tester. (Surrounding temperature 20:~30:)
Vane motor (MV)
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Room temperature thermistor (TH1)
Pipe temperature thermistor/liquid(TH2)
Condenser/evaporator temperature thermistor (TH5)
Normal
4.3k"~9.6k"
Abnormal
Open or short
9-6. How to check the parts PKA-RP1.6GAL PKA-RP2GAL
<Thermistor Characteristic graph>
Thermistor for lower temperature
Thermistor R0=15k±3% Fixed number of B=3480K ± 2%
Rt=15exp { 3480( ) }
0: 15k 10: 9.6k 20: 6.3k 25: 5.4k 30: 4.3k 40: 3.0k
•Room temperature thermistor(TH1)
•Pipe temperature thermistor/liquid(TH2)
•Condenser/evaporator temperature thermistor(TH5)
1
273+t
1
273
36
50
40
30
20
Resistance (K")
10
0
< Thermistor for lower temperature >
-20 -10 0 10 20 30 40 50 Temperature (:)
Page 37
9-7. TEST POINT DIAGRAM
9-7-1. Indoor controller board PKA-RP1.6GAL PKA-RP2GAL
CN6V Vane motor output (MV)
LED1 Power supply (I.B)
LED2 Power supply (R.B)
LED3 Transmission (Indoor/outdoor)
+
CN03 Connect to the indoor power board (CN02) Between 1 to 3 220~240V AC Between 3 to 5 0~24V DC (Indoor/outdoor transmission)
}
CN32 Connector (Remote switch)
CN90 Connect to the wireless remote controller board (CNB)
CN2D Connect to the indoor power board (CN2S) 12~16V DC
}
+
CN22 Connect to the terminal block(TB5) (Remote controller connecting wire) (10~16V DC)
}
+
CN21 Pipe temperature thermistor/Liquid (TH2)
CN20 Room temperature thermistor (TH1)
CN2L Connector (LOSSNAY)
CN41 Connector (HA terminal-A)
CN31 Drain sensor (DS)
CN29 Condenser/evaporator temperature thermistor (TH5)
+
CN25
}
Humidifier output
(12~16V DC)
FAN Fan motor output (MF) Between 1 to 5 100~240V AC
Jumper wire J41, J42 Pair number setting with wireless remote controller
Jumper wire J11~J15 Model setting
Jumper wire J21~J24 Capacity setting
SWE Emergency operation
37
Page 38
J11~J15
(SW1)
Open/short of jumper wire
Functions
Jumper wire
Model settings
Capacity settings
Pair number setting with wireless remote controller
Heater-less
Models : PKA-RP1.6, RP2
Remarks
J11 J12 J13 J14 J15
Models
RP1.6
RP2
J21 J22 J23 J24
J21~J24
(SW2)
J41 J42
0 1 2
3 ~ 9
Wireless remote
controller setting
Control PCB setting
J41 J42
<Settings at time of factory shipment> Wireless remote controller: 0 Control PCB: (for both J41 and J42) Four pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (' ' in the table indicates the jumper line is disco­nnected.)
(Marks in the table below) Jumper wire ( : Short : Open) DIP switch ( : ON : OFF)
9-7-2. Indoor power board PKA-RP1.6GAL PKA-RP2GAL
CN02 Connect to the indoor controller board (CN03) Between 1 and 2 0~24V DC (Indoor/Outdoor transmission) Between 2 and 3 220~240V AC
CN2S Connect to the indoor controller
board (CN2D)
}
+
(12~16V DC)
+
}
+
}
CN01 Connect to the Terminal Block (TB4) (Indoor/outdoor connecting line) Between 1 and 2 220~240V AC Between 2 and 3 0~24V DC (Indoor/outdoor transmission)
Fuse 4A/250V
9-8. FUNCTIONS OF JUMPER WIRE
Each function is controlled by the jumper wire on control p.c. board. For service parts, J11- J15 and J21-J24, DIP switches (SW1 and SW2) are equipped with jumper wire.
38
Page 39
10
DISASSEMBLY PROCEDURE
PKA-RP1.6GAL PKA-RP2GAL
OPERATION PROCEDURE
1. REMOVE THE LOWER SIDE OF THE INDOOR UNIT FROM THE INSTALLATION PLATE.
(1) Remove the left / right corner box of the indoor unit. (2) Hold and pull down the lower and both ends of the indoor
unit, and remove the section from the square hole. (Refer to the figure 2.1) Or remove the front panel and push the section down by using hexagonal wrench ,etc. from the front side. (Refer to the figure 2.2).
(3) Unhook the top of the indoor unit from the back plate catch.
(Figure 2.2)
PHOTOS & ILLUSTRATION
(Figure 1)
(Figure2.1)
Hook
Hook
Square hole
2. REMOVING THE FRONT PANEL.
(1) Open the front grille. (2) Remove the terminal block cover with a screw. (3) Remove the screw 3caps then remove the set 3screws. (4) After removing the lower side of the front panel a little,
remove it as pulling toward upper.
3. REMOVING THE INDOOR CONTROLLER BOARD.
(1) Remove the terminal block cover. (2) Remove the front panel. (see the photo 1) (3) Remove the electrical parts box(2screws). (4) Remove the electrical parts box cover(1screw). (5) Disconnect the connector on the controller board and
remove the controller board by Pulling up the hook of the controller case. w To smooth works, hang the side hooks of the electrical
parts box on the hook of the motor cover. (see the photo 3)
Up
Down
(Figure 3)
(Photo 1)
Front panel
(Photo 2)
Motor cover
Electrical parts box hook w
Square hole
Terminal block cover
Front grille
Set screw
Set screw
Electrical parts box
Set screw
39
(Photo 3)
Hook
Control board
Controller case
Electrical parts box
Page 40
OPERATION PROCEDURE
PHOTOS & ILLUSTRATION
4. REMOVING THE POWER BOARD
(1) Remove the front panel.(see the photo 1) (2) Remove the electrical parts box(2screws).(see the photo 2) (3) Disconnect the whole connector in the control board. (4) After lifting the controller case with pressing it’s convex
section, remove the controller case and the control board
simultaneously.(see the photo 3) (5) Disconnect the connector in the power board. (6) Remove the power board.
5. REMOVING THE VANE MOTOR
(1) Disconnect the connector CN6V on the indoor controller
board.
(2) Remove the 2screws of the vane motor, disconnect the
lead wire and remove the vane motor from the shaft.
6. REMOVING THE THERMISTOR
(1) Removing the room temperature thermistor TH1.
1Disconnect the connector CN20<red> on the indoor
controller board.
2Remove the room temperature thermistor from the holder. (2) Removing the pipe temperature thermistor TH2.
1Disconnect the connector CN21<white> on the controller
board.
2Remove the pipe temperature thermistor with set to the pipe. (3) Removing the indoor coil temperature thermistor TH5.
1Disconnect the connector CN29<black> on the indoor con-
troller board.
2Remove the gas pipe thermistor with set to the pipe.
(Photo 4)
(Photo 5)
Nozzle assemble
Van motor
(Photo 6)
Pipe temperature thermistor
Room temperature thermistor
Power board
Electrical parts box
Set screws
Lead wire
Condenser /evaporator temperature thermistor
Electrical parts box
7. REMOVING THE NOZZLE ASSEMBLE
(1) Disconnect the connector CN6V on the controller board. (2) Disconnect the lead wire of the vane motor. (3) Remove the corner cover. (4) Pull the drain hose out from the nozzle assemble. (5) Unhook the hook of the lower nozzle assemble and
pull the nozzle assemble toward you,then remove the nozzle assemble by sliding it down.
8. REMOVING THE ELECTRICAL PARTS BOX
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Disconnect the vane motor connector. (4) Disconnect the fan motor connector from the fan motor. (5) Remove the liquid / gas pipe thermistor.(see the photo 6) (6) Remove the electrical parts box (2screws).
(Photo 7)
Nozzle assemble
(Photo 8)
Pipe temperature thermistor
Hook
Fan motor connector
Drain hose
Corner cover
Vane motor connector
Electrical parts box
40
Page 41
OPERATION PROCEDURE PHOTOS & ILLUSTRATION
9. REMOVING THE FAN MOTOR.
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Remove the electrical parts box.(see the photo 8) (4) Remove the nozzle assemble.(see the photo 7) (5) Remove the fan motor leg fixing 3screws. (6) Unscrew the set screws using by alankey and remove it by
sliding the fan motor to right.
(7) Remove the 4screws and remove the motor cover from the
fan motor leg.
10. REMOVING THE LINE FLOW FAN
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Remove the electrical parts box.(see the photo 8) (4) Remove the nozzle assembly.(see the photo 7) (5) Remove the fan motor.(see the photo 9) (6) Remove the pipe fixture with 2screws.(see the photo12) (7) Remove the left / right screws of the heat exchanger and
pull the left-hand side up.
(8) Remove the 2screws by sliding it toward you remove the
fixture(fixing bearing). w The fan motor is removable first , when the fan removing
is hard.
w When resetting the fan to the fan motor.
Locate and fix the shaft after installing the fan.
(Photo 9)
Set
screw
(Photo 10)
Motor cover
Fan motor
(Photo11)
Heat exchanger
Set screws
Fixture (fixing bearing)
Motor cover
Fan motor
screws
motor leg
11. REMOVING THE HEAT EXCHANGER
(1) Remove the terminal block cover. (2) Remove the front panel.(see the photo 1) (3) Remove the electrical parts box.(see the photo 8) (4) Remove the corner box. (5) Remove the nozzle assemble.(see the photo 7) (6) Remove the 2screws and the pipe fixture. (7) Remove the 2screws and heat exchanger.
12. REMOVING the SIGNAL RECEIVING P.C. BOARD
(1) Remove the terminal block cover. (2) Disconnect the connector <yellow> for the wireless remote
controller. (3) Remove the front panel.(see the photo 1) (4) Remove the 2screws and signal receiving p.c. board cover. (5) Remove the signal receiving p.c. board.
(Photo 12) Heat
exchanger
Set screw
(Photo 14)
Set screws
(Photo 15)
Pipe fixture
Signal receiving p.c. board cover
Set screws
Front panel
Front panel
41
Signal receiving p.c. board
Page 42
11 PARTS LIST
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
BACK PLATE CORNER COVER UNDER COVER FRONT PANEL SCREW CAP VANE SLEEVE FRONT GRILLE AIR FILTER AUTO VANE RECEIVING UNIT CORNER COVER BOX ASSEMBLY WIRELESS REMOTE CONTROLLER WIRELESS REMOTE CONTROLLER DOOR WIRELESS REMOTE CONTROLLER HOLDER
No.
Parts No.
Parts Name
Specifications
1 1 1 1 3 1 1 2 1 1 1 1 1 1 1
Q'ty/set
PKA-RP1.6GAL PKA-RP2GAL
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Recom­mended
Q'ty
Unit
Amount
Price
R01 07Y 808 R01 09Y 658 R01 07Y 623 R01 89Y 651 R01 07Y 096 R01 07Y 092 R01 07Y 691 R01 A16 500 R01 07Y 002 R01 24K 658 R01 07Y 658 R01 07Y 635 T7W E06 714 R01 E01 049 R01 E00 075
RU
STRUCTURAL PARTS PKA-RP1.6GAL PKA-RP2GAL
4
5
6
1
2
3
12
11
7
8
9
10
13
14 15
42
Page 43
ELECTRICAL PARTS PKA-RP1.6GAL PKA-RP2GAL
5
1
4
3
2
33
32
6
9
7
10
11
12
No. Parts No. Parts Name
1
T7W E50 480
2
R01 07Y 114
3
R01 07Y 102
4
R01 005 103
5
R01 07Y 106
6
T7W A00 675
7
R01 07Y 524
8
R01 07Y 527
9
T7W E13 530
10
R01 09Y 038
11
R01 07Y 038
12
R01 07Y 059
13
R01 E02 223
14
R01 50J 317
15
R01 07Y 135
16
R01 07Y 105
17
T7W A01 762 18 19
T7W E13 716 20
R01 588 255 21
T7W E36 310 22 23 24
T7W E01 313 25
T7W E00 239 26 27 28
R01 E32 202 29
T7W E05 202 30
T7W E06 202 31
R01 07Y 130 32
T7W E02 457 33
T7W E01 457
— —
— —
HEAT EXCHANGER LINE FLOW FAN BEARING MOUNT SLEEVE BEARING BEARING SUPPORT FAN GUARD DRAIN PLUG DRAIN HOSE NOZZLE GUIDE VANE GUIDE VANE ARM VANE MOTOR WIRERLESS ADAPTER CONTROLLER BOARD MOTOR COVER RUBBER MOUNT FAN MOTOR TERMINAL COVER TERMINAL BLOCK CAPACITOR INDOOR CONTROLLER BOARD CONTROLLER COVER CONTROLLER CASE POWER BOARD FUSE ELECTRICAL PARTS COVER SENSOR HOLDER CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR ROOM TEMPERATURE THERMISTOR PIPE TEMPERATUER THERMISTOR MOTOR SUPPORT FLARE NUT FLARE NUT
8
10
13
Specifications
PM4V30-K
3P(S1, S2, S3)
2.0= 440V
250V 4A
1/2 1/4
1
17
16
15
14
Q'ty/set
PKA-PR1.6GAL PKA-RP2GAL
1 1 1 1 1 1 1 1 1 4
10
2 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
31
29
27
28
18
Remarks
(Drawing No.)
(BG02V195H10)
(BG02V194H05)
(BG25B573H06)
(BG00V196G41) (RG25C546H06)
30
19
Wiring
Diagram
Symbo
l
MV
W.B
MF
TB4
C
I.B
P.B
F1
TH5 TH1 TH2
26
25
20
Recom­mended
Q'ty
21
Unit
24
23
22
Price
Amount
43
Page 44
12 OPTIONAL PARTS
12-1. Wired Remote Controller (with terminal bed).
Part No. PAR-20MAAT-E
12-2. Program Timer
Part No. PAC-SC32PTA
12-3. Remote Sensor
Part No. PAC-SE41TS-E
12-4. Remote Operation Adapter
Part No. PAC-SF40RM-E
12-5. Remote ON/OFF Adapter
Part No. PAC-SE55RA-E
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
cCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in May 2004 No.OC305 PDF 9 Made in Japan
New publication, effective May 2004 Specifications subject to change without notice
Loading...