Mitsubishi PC-2GJA1, PC-2.5GJA1, PC-3GJA1, PC-4GJSA1, PC-5GJSA1 Service Manual

...
SPLIT-TYPE, COOLING AIR CONDITIONERS
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER
MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
TECHNICAL & SERVICE MANUAL
No. OC134
REVISED EDITION-A
Series PC
Indoor unit [
Model names]
PC-2GJA PC-2.5GJA PC-3GJA PC-4GJSA PC-5GJSA PC-6GJSA
INDOOR UNIT
Ceiling Suspended
[Service Ref.]
PC-2GJA1 PC-2.5GJA1 PC-3GJA1 PC-4GJSA1 PC-5GJSA1 PC-6GJSA1
This manual does not cover the following outdoor units. When serving them, please refer to the service manual No.OC127(REVISED EDITION-A) .
[Service Ref.] PU-2VJA2 PU-2NJA1 PU-2.5VJA2 PU-2.5NJA1
PU-5YJSA PU-5TJSA PU-6YJSA
PU-6TJSA
PU-3NJA1 PU-3YJA3 PU-3VJA2 PU-4TJSA2 PU-4VLJSA2 PU-4YJSA3
CONTENTS
1. FEATURES ···········································2
2. PART NAMES AND FUNCTIONS········4
3. SPECIFICATIONS ·································6
4. DATA·····················································9
5. OUTLINES AND DIMENSIONS··········12
6. WIRING DIAGRAM ·····························17
REFRIGERANT SYSTEM DIAGRAM
8. OPERATION FLOW-CHART··············20
9. MICROPROCESSOR CONTROL·······23
10. TROUBLE SHOOTING·······················29
11. DISASSEMBLY PROCEDURE···········30
12. PARTS LIST········································35
13. OPTIONAL PARTS ·····························46
······18
Revision:
PC-5GJSA1,PC-6GJSA1
are added.
The first edition has been par-
tially modified.
Please destroy OC134.
REMOTE CONTROLLER
1
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
FEATURES
Series PC
Ceiling Suspended
Indoor unit
Service Ref. PC-2GJA
1 5,600/5,400 19,100/18,400
Cooling Capacity (50 / 60Hz)
W Btu/h
PC-2.5GJA1 6,500/7,000 22,200/23,900 PC-3GJA1 7,200/7,800 24,600/26,600 PC-4GJSA1 9,800/10,800 33,400/36,800 PC-5GJSA1 12,400/13,500 42,300/46,100 PC-6GJSA1 14,600/15,200 49,800/51,900
Note: Rating condition
Indoor : 27°C D.B., 19°C W.B. Outdoor : 35°C D.B., 24°C W.B.
Remote controller
1. ADVANCED REMOTE CONTROLLER
(1) Ultra-thin 12mm (1/2”) remote controller
The streamelined, square controller is designed to blend with any inte­rior. Also, the sophisticated microprocessor allows you to easily carry out a wide range of operations.
(2) Attractive LED display
Every operation condition is indicated on the LED display.
(3) Simultaneous display of set temperature and room temperature
The set temperature is indicated by continuous light and the room tem­perature is indicated by a flashing light. In this way, accurate tempera­ture conditions are always available at a glance and fine temperature regulation is possible.
(4) Convenient 12-hour ON-OFF timer
The timer switches on and off automatically at the times you set. Once the timer is set, the remaining time is shown on the LED display.
(5) Self-diagnostic feature indicates faults instantly
If a problem occurs, the unit will stop operating and the temperature display will change to a self-diagnosis indicator, which shows the loca­tion of the trouble.
(6) Useful memory feature for storing instructions
The previous set value is memorized so that constant temperature control can be achived. For example, if a power fail­ure occurs, the temperature will not have to be readjusted afterwards.
(7) Cables between remote controller and indoor unit
The polar, 12-core type remote controller cables makes installation simple and troublefree. Also, the cables can be extended up to 50m. (optional)
2
1. AIR OUTLET
New PC series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane) instead of 2 (horizontal, and down flows).
2. EASY TO CLEAN ; FLOCKLESS VANE
With our original air current control mechanism, a flockless vane is newly adapted. The flockless vane prevents the condensation on the vane. By changing the vane to the flockless type, the unit can be cleaned much easier with mild household detergent.
B
Flockless vane
A
Air outlet
Protruding portion A
Unifies the air speed with the vane.
Protruding portion B
Sending the air to the upper area of the vane
Prevents the air comes from outside the unit
+
=
3. NEW MATERIALS FOR BETTER OIL RESISTANCE
We have changed the materials of grill, filer, fan and fan casing from ABS to P.P. (polypropylene) for better oil resistance. As a result, oil crazing is cut in half.
4. SIMPLIFIED INSTALLATION WORK (DIRECT SUSPENDING METHOD)
Simplified the installation work by changing the suspending method to the direct suspending method (suspending the unit directly from the suspension fixture). In this way, the unit can be attached to the suspension fixture without removing the installation parts off (Only the side cover is removed). This method is much simpler than the ¨One-time installation method¨.
5. IMPROVING EFFICIENCY OF PIPING WORK
New PC series models have 1 air outlet (auto vane switching of horizontal air flow / down flow by switched by auto vane) instead of 2 (horizontal, and down flows).
1 Removed the knockout work by separating the piping space
from the air outlet for efficiency of the piping work.
Side panel
L
G
G D
Open
L : Liquid pipe G: Gas pipe D: Drain pipe
U-cut
Back panel
L
D
Open
w Knockout work is needed for the top part. When optional
drain-up machine is installed, the refrigerant pipe exits out from the top.
2 Improved the flexibility by making it possible for drainage
pipe to exit not only from the right side back but also from the left side back.
Rubber plug
Insulation cover (attached)
Drain pipe (purchased locally)
Joint coupliy (attached)
Drain pan
Insulation cover
Band (attached)
w Please move the rubber plug for the unit to the right joint
when drainage pipe exits from the left side.
3
Air outlet
Intake grille
Air intake
Left/right guide vanes
Change the direction of airflow from the horizontal blower.
Long-life filter
Removes dust and foreigh matter from air coming in through the grille (Recommended cleaning interval : Approx, every 2,500 operating hours)
Up/down guide vanes
Change the direction of airflow from the vartical blower.
6. QUITENESS ; 43dB : PC-3GJA1(HIGH NOTCH)
Auto vane
Swing
Quiteness of the New PC series product is significant. It is because we have adapted the new shape air outlet and changed the air coures.
7. EASY MAINTENANCE ; NO MAINTENANCE NECESSARY FOR 2500 HOURS
The new long-life air filter can be used continuously 2500 hours without maintenance (at general office situation).
8. CHOICE OF FILTER
High performance filter can be purchased optionally for the special needs.
Locations Appropriate filter Capability Filter Maintenance How to attach to the unit
Busy shops etc···
Regular office, shops
High performance filter
Standard longlife filter
Weighing
method 70%
Weighing
method 30%
2500 hours
2500 hours
The filter can be used again after cleaning.
The filter can be used again after cleaning.
Remove the standard long life filter before attach this optional parts.
It is already attached to the unit
2
PART NAMES AND FUNCTION
Indoor (Main) Unit
4
Remote controller
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
TIMER / TEMP.
This button is used to change between display of room tem­peratue and display of remain­ing timer time durining “AUTO STOP” operation. Green lamps light in selected display mode.
Settings remain in effect until changed. Air conditioner can be operated by simply pushing ON/OFF button once settings have been made.
Display Panel Operating panel
ON / OFF button
Pushing button starts operation. Pushing again stops operation. Green lamp remains lit during operation.
MODE SELECT button
This button is used to change between cooling. ventilation and DRY(or heat­ing)operation modes.One of three green lamps light to indicate mode in effect.
Lamps display remaining timer time or room temper­ature.
Remaining timer time display
Lamps indicate time remaining until timer stops timed operation. Green lamps corresponding to remaining number of hours light.
Room Temperature display
Lamps display temperatue set­ings and actual room tempe­ratues.
Temperatue settings.
Green lamps light.
Temperatue in room.
Green lamps flash.
(Example display readings are for explanations only; actual dis­play readings will differ.)
Attention:
Pushing UP and DOWN buttons together for more than two seconds will initate “trial run” or “inspection” mode. Avoid pushing these buttons simultaneously during normal operation. Push ON / OFF button to cancel trial run or inspection mode if initiated by accident. All green lamps turn off when air conditioner is stopped. Avoid operation of buttons with fingernails or other sharp object. Sharp object may scratch operating panel.
*Heating operation mode is only available for models with built-in electric heater.
UP and DOWN buttons
Temperature control (While ”TEMP” green lamp is lit.) Use UP and DOWN buttons to set desired temper­ature between 18 and 29
o
C. Timed operation (While green “TIMER” lamp is lit.) Use UP and DOWN buttons to set timed operation between one and twelve hours.
FAN SPEED button
This button is used to change between low and high fan speeds. One of two green lamps lights to indicade fan speed in effect.
Swing Louver Button
Used to automatically disperse airflow vertically. Air is blown in one direction when louver is not turning. Lamp lights effect.
TIMER MODE button
Used for selecting timed starting or stopping.Green lamp light to indicate timer mode selected.
5
3
Service Ref.
External finish Fan motor output
Airflow Lo-Hi
External static pressure Operation control & Thermostat
Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w3 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
W
Btu/h
W
Btu/h
W
Btu/h
m/min
CFM
m/min
CFM
Pa(mmAq)
dB(A)
dB(A) mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM) K/min(CFM)
dB(A) mm(in.) mm(in.) mm(in.) kg(lbs.)
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz 60Hz
O.D.
W
D H
50/60Hz 50/60Hz
50Hz 60Hz
50/60Hz
W
D H
Munsell 0.70Y 8.59/0.97
0 (Direct blow)
Remote control & Built-in
Munsell 5Y 7/1
Capillary tube
295+24 (11-5/8 add 1)
9,800 33,400 10,800 36,800
9,300 31,700
3.49/4.47
PC-4GJSA
1
0.09
20-25
706-883
20-25
706-883
40-45
40-45
26 (1)
1310 (51-9/16)
680 (26-3/4) 270 (10-5/8)
37 (82)
w10 PU-4JSA-type
32/38
2.7/2.7
w7(V)/w6(Y,T)
0.065+0.065 95 (3352) 95 (3352)
54/55
870 (34-1/4)
1258 (49-1/2)
94 (207)
Cooling capacity w1
Cooling capacity w4 Total input (50/60Hz) w2
Item
Service Ref.
PC-4GJSA
1
7,200
24,600
7,800
26,600
6,500
22,200
3.30/3.60
PC-3GJA
1
0.07
14-18
494-635
14-18
494-635
37-43 37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
w9 PU-3JA-type
32/38
2.2/2.2 w5
0.085 50 (1765) 50 (1765)
52/53
870 (34-1/4)
850 (33-7/16)
73 (161)
PC-3GJA
1
6,500
22,200
7,000
23,900
6,200
21,200
2.58/3.07
PC-2.5GJA
1
0.07
14-18
494-635
14-18
494-635
37-43 37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
PU-2.5VJA2,PU-2.5NJA1
32/-
2.0/1.7 w5
0.085 50 (1765) 50 (1765)
52/53
870 (34-1/4)
850 (33-7/16)
71 (157)
PC-2.5GJA
1
5,600
19,100
5,400
18,400
4,300
14,700
2.54/2.60
PC-2GJA
1
0.054
10-13
353-459
10-13
353-459
37-42 37-42 26 (1)
1000 (39-3/8)
680 (26-3/4)
210 (8-1/4)
27 (60)
PU-2VJA2,PU-2NJA1
32/-
2.0/1.5 w5
0.065 45 (1588) 45 (1588)
49/50
870 (34-1/4)
650 (25-5/8)
60 (132)
PC-2GJA
1
Indoor unitOutdoor unit
SPECIFICATIONS
1. STANDARD SPECIFICATIONS
Notes : w1. Rating condition (JISB8616)
Indoor : 27
Models PC-2,2.5,3 PC-4,5,6
50Hz 1ph220V / 1ph220V 1ph220V / 3ph380V 60Hz 1ph220V / 1ph220V
Outdoor : 35OC (95OF) D.B., 24OC (75OF) W.B. Refrigerant piping length (one way) : 5m (16ft)
w2. Total input based indicated voltage (In/Out)
Rating conditions (JISB8616)
w3. The capacity of crankcase heater (W)
O
C (80OF) D.B., 19OC (66OF) W.B.
1ph220V / 3ph220V
6
w4. Rating condition (SSA385, 386)
w5. Inner thermostart, HP switch, LP switch w6. Thermal switch, Reversed-phase protector, HP switch, LP
w7. Thermal switch, HP switch, LP switch, w8. Thermal switch, HP switch,Inner thermostat
w9. PU-3JA w10. PU-4JSA-type···PU-4VLJSA2, PU-4YJSA3, PU-4TJSA2
Indoor : 29OC (84OF) D.B., 19OC (66OF) W.B. Outdoor : 46OC (115OF) D.B., 24OC (75OF) W.B. Refrigerant piping lenght (one way ) : 5m (16ft)
switch Thermal relay
Inner thermostat
-type···PU-3VJA2, PU-3YJA3, PU-3NJA1,
Item
220,230,240V 380/220, 400/230, 415/240V 220V 220V
1ph. 3ph. 1ph. 3ph.
50Hz
60Hz
Power supply
Outdoor unit Service Ref.
PC-4GJSA1
PU-4VLJSA2
PU-4YJSA3
PU-4TJSA
2
PC-5GJSA1
PU-5YJSA
PU-5TJSA
PC-6GJSA
1
PU-6YJSA
PU-6TJSA
PC-3GJA
1
PU-3VJA2 PU-3YJA3 PU-3NJA1
PC-2.5GJA
1
PU-2.5VJA2
PU-2.5NJA
1
PC-2GJA
1
PU-2VJA2
PU-2NJA
1
Indoor unit Service Ref.
Cooling capacity w1
Cooling capacity w4 Total input (50/60Hz) w2
Service Ref.
External finish Fan motor output
Airflow Lo-Hi
External static pressure Operation control & Thermostat
Indoor unitOutdoor unit
Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w3 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
Service Ref.
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz 60Hz
O.D.
W
D H
50/60Hz 50/60Hz
50Hz 60Hz
50/60Hz
W
D H
W
Btu/h
W
Btu/h
W
Btu/h
K/min
CFM
K/min
CFM
Pa(mmAq)
dB(A)
dB(A) mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM) K/min(CFM)
dB(A) mm(in.) mm(in.) mm(in.) kg(lbs.)
PC-5GJSA
1
12,400 42,300 13,500 46,100 11,600 39,600
4.76/5.89
PC-5GJSA
1
Munsell 0.70Y 8.59/0.97
0.15
27-34
953-1,200
27-34
953-1,200
Remote control & Built-in 41-46 41-46
26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
43(95)
PU-5YJSA,PU-5TJSA
3.5 w8
0.10+0.10 100(3530) 100(3530)
55
970(38-3/16)
345+24(13-9/16+1)
1,258(49-1/2)
114
0 (Direct blow)
Munsell 5Y 7/1
Capillary tube
PC-6GJSA
1
14,600 49,800 15,200 51,900 13,400 45,700
5.31/6.41
PC-6GJSA
1
0.15
27-34
953-1,200
27-34
953-1,200
42-48 42-48
26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
45(99)
PU-6YJSA,PU-6TJSA
4.2/4.0 w8
0.10+0.10 100(3530) 100(3530)
56
970(38-3/16)
345+24(13-9/16+1)
1,258(49-1/2)
117
2. POWER SUPPLY & MODEL NAMES
Notes : 1. Power supply key N : 1ph, 220V/60Hz T : 3ph, 220V/60Hz
V(L) : 1ph, 220, 230, 240V/50Hz Y : 3ph, 380/220, 400/230, 415/240V, 50Hz, 4wires
2. Primary power supplies for all indoor units are single-phase.
7
3. ELECTRICAL SPECIFICATIONS
A
kW
A
V : 220V , 50Hz
PC-4GJSA1
0.68
0.14
1.36
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.51
0.12
1.17
PU-3
PC-2.5GJA1
0.51
0.12
1.17
PU-2.5
PC-2GJA
1
0.38
0.10
1.10
PU-2
PC-6GJSA1
0.96
0.20
2.00
PU-6
PC-5GJSA1
0.96
0.20
2.00
PU-5
A
kW
A
V : 230V , 50Hz
PC-4GJSA1
0.69
0.15
1.42
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.53
0.13
1.22
PU-3
PC-2.5GJA1
0.53
0.13
1.22
PU-2.5
PC-2GJA
1
0.41
0.12
1.15
PU-2
PC-6GJSA1
1.01
0.22
2.10
PU-6
PC-5GJSA1
1.01
0.22
2.10
PU-5
A
kW
A
V : 240V , 50Hz
PC-4GJSA1
0.70
0.16
1.48
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.55
0.15
1.27
PU-3
PC-2.5GJA1
0.55
0.15
1.27
PU-2.5
PC-2GJA
1
0.43
0.14
1.20
PU-2
PC-6GJSA1
1.06
0.25
2.20
PU-6
PC-5GJSA1
1.06
0.25
2.20
PU-5
A
kW
A
N : 220V , 60Hz
PC-4GJSA1
0.95
0.20
1.27
PU-4
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.70
0.16
1.11
PU-3
PC-2.5GJA1
0.70
0.16
1.11
PU-2.5
PC-2GJA
1
0.61
0.15
1.03
PU-2
PC-6GJSA1
1.20
0.26
1.91
PU-6
PC-5GJSA1
1.20
0.26
1.91
PU-5
A
kW
A
N : 220V , 60Hz
PC-4GJSA1
0.95
0.20
1.27
PU-4
PC-5GJSA1
1.20
0.26
1.91
PU-5
PC-6GJSA1
1.20
0.26
1.91
PU-6
Power supply (1 Phase)
Service Ref.
Current Input Starting current Outdoor unit to be connected
PC-3GJA
1
0.70
0.16
1.11
PU-3
PC-2.5GJA1
0.70
0.16
1.11
PU-2.5
PC-2GJA
1
0.61
0.15
1.03
PU-2
Rating conditions — JIS B8616 Indoor : 27°C (80°F) D.B., 19°C (66°F) W.B.
Outdoor : 35°C (95°F) D.B., 24°C(75°F) W.B.
Serises PC Indoor unit (Single phase)
Rating conditions — SSA385, 386
8
Indoor : 29°C (84°F) D.B., 19°C (66°F) W.B. Outdoor : 46°C (115°F) D.B., 24°C(75°F) W.B.
4
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F. (T.I.)
Service Ref.
Temperature
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
PC-2GJA1
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.5
5.9
6.0
6.1
6.2
6.6
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.1
5.4
5.6
5.7
5.8
6.2
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
4.8
5.2
5.3
5.4
5.5
5.9
4.6
4.9
5.1
5.1
5.2
5.6
4.3
4.6
4.7
4.8
4.9
5.3
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.3
5.6
5.8
5.9
6.0
6.4
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
(125.5°F)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
16°C (60.8°F
)
18°C (64.4°F
)
19°C (66.2°F
)
19.4°C (67°F
)
20°C (68°F
)
22°C (71.6°F
)
5.6
6.0
6.2
6.2
6.4
6.7
5.2
5.5
5.7
5.8
5.9
6.3
4.9
5.2
5.4
5.4
5.5
5.9
4.6
4.9
5.1
5.2
5.3
5.7
4.4
4.7
4.9
4.9
5.0
5.4
Indoor W.B.Outdoor D.B.
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F.
(T.I.)
PC-2.5GJA
1
6.4
6.8
7.0
7.1
7.2
7.7
5.9
6.3
6.5
6.6
6.7
7.2
5.6
6.0
6.2
6.3
6.4
6.8
5.3
5.7
5.9
6.0
6.1
6.5
4.9
5.3
5.5
5.6
5.7
6.1
6.1
6.6
6.8
6.9
7.0
7.4
6.5
6.9
7.2
7.3
7.4
7.8
6.0
6.4
6.6
6.7
6.9
7.3
5.6
6.0
6.2
6.3
6.4
6.9
5.4
5.7
5.9
6.0
6.1
6.6
5.1
5.4
5.6
5.7
5.8
6.3
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F.
(T.I.)
PC-3GJA
1
7.1
7.5
7.8
7.9
8.0
8.5
6.5
7.0
7.2
7.3
7.4
7.9
6.2
6.6
6.9
6.9
7.1
7.6
5.9
6.3
6.5
6.6
6.7
7.2
5.5
5.9
6.1
6.2
6.3
6.8
6.8
7.3
7.5
7.6
7.7
8.2
7.2
7.7
7.9
8.0
8.2
8.7
6.7
7.1
7.4
7.5
7.6
8.1
6.2
6.7
6.9
7.0
7.1
7.6
5.9
6.4
6.6
6.7
6.8
7.3
5.6
6.0
6.2
6.3
6.5
6.9
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F. (T.I.)
PC-4GJSA
1 PC-5GJSA1 PC-6GJSA1
9.6
10.2
10.6
10.7
10.9
11.6
8.9
9.5
9.8
9.9
10.1
10.8
8.4
9.0
9.3
9.5
9.6
10.3
8.0
8.6
8.9
9.0
9.2
9.8
7.4
8.0
8.3
8.4
8.6
9.2
9.3
9.9
10.2
10.3
10.5
11.2
9.8
10.5
10.8
10.9
11.1
11.8
9.1
9.7
10.0
10.2
10.3
11.0
8.5
9.1
9.4
9.5
9.7
10.3
8.1
8.6
8.9
9.1
9.3
9.9
7.6
8.2
8.5
8.6
8.8
9.4
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F. (T.I.)
12.2
13.0
13.4
13.6
13.8
14.7
11.2
12.0
12.4
12.6
12.8
13.6
10.7
11.4
11.8
12.0
12.2
13.0
10.1
10.8
11.2
11.3
11.5
12.4
8.1
8.7
9.0
9.1
9.3
9.7
11.7
12.5
12.9
13.1
13.3
14.2
12.4
13.3
13.7
13.8
14.1
14.9
11.5
12.3
12.7
12.8
13.1
13.9
10.7
11.5
11.9
12.0
12.3
13.1
10.2
10.9
11.3
11.5
11.7
12.5
9.1
9.8
10.2
10.3
10.5
10.9
T.C.
0.84
0.85
0.86
0.86
0.87
0.89
0.96
0.99
1.00
1.00
1.01
1.04
1.04
1.06
1.08
1.08
1.09
1.12
1.11
1.14
1.15
1.16
1.17
1.21
1.19
1.22
1.24
1.25
1.26
1.31
0.90
0.92
0.93
0.93
0.94
0.96
0.81
0.82
0.83
0.83
0.84
0.86
0.93
0.95
0.96
0.97
0.97
0.99
1.03
1.06
1.07
1.08
1.08
1.11
1.10
1.12
1.14
1.15
1.16
1.20
1.16
1.19
1.21
1.22
1.23
1.28
C.F.
(T.I.)
14.3
15.3
15.8
16.0
16.3
17.3
13.2
14.1
14.6
14.8
15.1
16.1
12.6
13.4
13.9
14.1
14.4
15.3
11.9
12.7
13.1
13.3
13.5
14.6
9.5
10.2
10.6
10.7
11.0
11.4
13.8
14.7
15.2
15.4
15.7
16.7
14.7
15.6
16.1
16.3
16.6
17.6
13.6
14.5
14.9
15.1
15.4
16.4
12.6
13.5
14.0
14.2
14.4
15.4
12.0
12.9
13.3
13.5
13.8
14.7
10.7
11.5
12.0
12.1
12.4
12.8
T.C.
DATA
1. PERFORMANCE DATA Cooling capacity
Cooling Capacity Correction Factors
Service Ref.
PC-2GJA PC-2.5GJA PC-3GJA PC-4GJSA PC-5GJSA
PC-6GJSA
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft)
1
1
1.0 0.985 0.975 0.964 0.954 0.944
1.0
1
1.0 0.978 0.962 0.948 0.934 0.921
1.0 0.984 0.974 0.964 0.954 0.944
1
1.0
1
1.0
1
50Hz
0.983 0.972 0.961 0.951 0.940
0.978
0.970
0.962
0.950
50Hz
Refrigerant piping length (one way)
0.948
0.931
0.934
0.912
0.921
0.896
35m(115ft)
— —
0.935 0.926
0.908
0.880
40m(131ft)
0.896
0.864
45m(148ft)
0.884
0.850
— —
— —
50m(164ft)
— — — —
0.875
0.840
9
Cooling capacity
Service Ref.
Temperature
Indoor W.B.Outdoor D.B.
16°C (60.8°F
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
(125.5°F)
Notes:1.T.C. : Total capacity (xkW)
C.F. (T.I.) : Correction factors of Total input + Outdoor unit input)
2.(oF)=32+9/5(oC)
3.Guaranteed operating range (cooling):
18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F 16°C (60.8°F 18°C (64.4°F
19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F
22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F
18°C (64.4°F
19°C (66.2°F
19.4°C (67°F
20°C (68°F
22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F
18°C (64.4°F
19°C (66.2°F
19.4°C (67°F
20°C (68°F
22°C (71.6°F 16°C (60.8°F 18°C (64.4°F 19°C (66.2°F
19.4°C (67°F 20°C (68°F 22°C (71.6°F
16°C (60.8°F
18°C (64.4°F
19°C (66.2°F
19.4°C (67°F
20°C (68°F
22°C (71.6°F
60Hz
PC-2GJA1
T.C.
)
5.4
)
5.8
)
6.0
)
6.0
)
6.1
)
6.5
)
5.3
)
5.6
)
5.8
)
5.9
)
6.0
)
6.4
)
5.1
)
5.4
)
5.6
)
5.7
)
5.8
)
6.2
)
5.0
)
5.3
)
5.5
)
5.6
)
5.7
)
6.1
)
4.9
)
5.2
)
5.4
)
5.5
)
5.6
)
5.9
)
4.7
)
5.0
)
5.2
)
5.2
)
5.3
)
5.7
)
4.7
)
5.0
)
5.1
)
5.2
)
5.3
)
5.7
)
4.4
)
4.8
)
4.9
)
5.0
)
5.1
)
5.5
)
4.4
)
4.7
)
4.9
)
4.9
)
5.0
)
5.4
)
4.2
)
4.5
)
4.7
)
4.7
)
4.8
)
5.2
)
4.1
)
4.4
)
4.6
)
4.6
)
4.7
)
5.1
...
Btu/h=(W)x0.86
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
Lower limit
{ }
Upper limit
PC-2.5GJA
T.C.
7.0
7.5
7.7
7.8
7.9
8.4
6.9
7.3
7.6
7.7
7.8
8.3
6.6
7.1
7.3
7.4
7.5
8.0
6.5
6.9
7.2
7.3
7.4
7.9
6.3
6.8
7.0
7.1
7.2
7.7
6.1
6.5
6.7
6.8
6.9
7.4
6.0
6.4
6.7
6.8
6.9
7.4
5.8
6.2
6.4
6.5
6.6
7.1
5.7
6.1
6.3
6.4
6.5
7.0
5.5
5.9
6.1
6.2
6.3
6.7
5.3
5.7
5.9
6.0
6.1
6.6
...
Indoor 21oC(70oF) D.B.,15.5oC(60oF) W.B., Outodoor 21oC(70oF) D.B.
...
Indoor 35oC(95oF) D.B.,22.5oC(72.5oF) W.B.,Outodoor 52oC(125.5oF) D.B.
Cooling Capacity Correction Factors
Service Ref.
PC-2GJA PC-2.5GJA PC-3GJA PC-4GJSA PC-5GJSA PC-6GJSA
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft) 35m(115ft) 40m(131ft)
1
1
1.0 0.985 0.975 0.964 0.954 0.944
1.0 0.978 0.963 0.948 0.934 0.921
1
1.0 0.971 0.950 0.931 0.913 0.896
1.0 0.980 0.966 0.952 0.939 0.826 0.914 0.902
1
1.0
1
1.0
1
0.971
0.960
0.950
0.933
0.931
0.908
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
1
PC-3GJA
T.C.
7.8
8.3
8.6
8.7
8.9
9.4
7.7
8.2
8.4
8.5
8.7
9.2
7.4
7.9
8.1
8.2
8.4
8.9
7.2
7.7
8.0
8.1
8.2
8.8
7.1
7.5
7.8
7.9
8.1
8.6
6.8
7.2
7.5
7.6
7.7
8.2
6.7
7.2
7.4
7.5
7.7
8.2
6.4
6.9
7.1
7.2
7.4
7.9
6.4
6.8
7.1
7.1
7.3
7.8
6.1
6.5
6.8
6.9
7.0
7.5
5.9
6.4
6.6
6.7
6.9
7.3
1
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
PC-4GJSA
T.C.
10.8
11.5
11.9
12.0
12.3
13.0
10.6
11.3
11.7
11.8
12.0
12.8
10.2
10.9
11.2
11.4
11.6
12.3
10.0
10.7
11.0
11.2
11.4
12.1
9.8
10.5
10.8
10.9
11.1
11.9
9.4
10.0
10.3
10.5
10.7
11.4
9.3
9.9
10.3
10.4
10.6
11.3
8.9
9.5
9.9
10.0
10.2
10.9
8.8
9.4
9.8
9.9
10.1
10.8
8.4
9.0
9.4
9.5
9.7
10.4
8.2
8.8
9.2
9.3
9.5
10.2
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
60Hz
Refrigerant piping length (one way)
0.913
0.885
0.896
0.864
0.880
0.845
1 PC-5GJSA1 PC-6GJSA1
T.C.
13.6
14.4
14.9
15.1
15.3
16.2
13.2
14.1
14.6
14.8
15.0
16.0
12.8
13.6
14.0
14.2
14.5
15.4
12.5
13.4
13.8
14.0
14.3
15.2
12.2
13.1
13.5
13.7
13.9
14.9
11.7
12.5
12.9
13.1
13.4
14.3
11.6
12.4
12.9
13.0
13.3
14.2
11.1
11.9
12.3
12.5
12.7
13.6
11.0
11.8
12.1
12.3
12.5
13.5
10.7
11.1
11.2
11.4
11.8
10.1
10.5
9.9
8.8
9.4
9.8
9.9
C.F. (T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
T.C.
15.3
16.2
16.8
17.0
17.3
18.3
14.9
15.9
16.4
16.6
16.9
18.0
14.4
15.3
15.8
16.0
16.3
17.4
14.1
15.1
15.5
15.7
16.0
17.1
13.8
14.7
15.2
15.4
15.7
16.7
13.2
14.1
14.6
14.7
15.0
16.0
13.1
14.0
14.5
14.7
15.0
16.0
12.5
13.4
13.9
14.1
14.4
15.3
12.4
13.3
13.7
13.8
14.1
15.2
11.2
12.0
12.4
12.6
12.9
13.3
9.9
10.6
11.0
11.2
11.4
11.8
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
45m(148ft) 50m(164ft)
— — —
— — —
0.864
0.828
0.850 0.840
0.812 0.800
C.F.
1.11
1.11
10
2. STANDARD OPERATION DATA
Capacity Input Indoor unit Service Ref. phase, Hz Volts Amperes
Outdoor unit Service Ref.
phase, Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V A
V A
MPa.G
(kgf/F•G)
MPa.G
(kgf/F•G)
°C °C °C
m
D.B.°C
W.B.°C
D.B.°C D.B.°C
W.B.°C
Service Ref.
Electrical circuit TotalRefrigerant circuit
Indoor side
Outdoor
side
MODE
PC-4GJSA1 PC-5GJSA1 PC-6GJSA1
PC-4GJSA1 PC-5GJSA1 PC-6GJSA1PC-3GJA1PC-2.5GJA1PC-2GJA1
Cooling
9,300
5.17
1,60
220
0.95
PU-
4TJSA2
3,60
220
14.0
2.40
(24.4)
0.51 (5.2)
88.4
54.5
6.0 5
29 19
11.7 46 24
Cooling
12,400
4.76
1,50
220
0.96
PU-
5YJSA
3,50
380
8.15
1.83
(18.7)
0.46
(4.7)
72.9
48.8
3.1 5
27 19
13.7 35 24
Cooling
11,600
6.94
1,60
220
1.20
PU-
5TJSA
3,60
220
19.61
2.41
(24.6)
0.43
(4.4)
94.8
60.1
1.7 5
29 19
14.9 46 24
Cooling
14,600
5.31
1,50
220
0.96
PU-
6YJSA
3,50
380
8.63
1.96
(20.0)
0.41
(4.2)
75.4
51.1
2.3 5
27 19
12.2 35 24
Cooling
13,400
7.54
1,60
220
1.20
PU-
6TJSA
3,60
220
21.45
2.41
(24.6)
0.42 (4.3)
94.8
60.3
1.6 5
29 19
12.6 46 24
Cooling
9,800
3.43
1,50
220
0.68
PU-
4YJSA3
3,50
380
5.7
1.80
(18.3)
0.51 (5.2)
67.5
48.3
7.3 5
27 19
10.5 35 24
Cooling 6,500
4.25
1,60
220
0.70
PU-
3NJA
1
1,60
220
20.9
2.54
(25.9)
0.44
(4.5)
82.0
61.6
3.6 5
29 19
12.8 46 24
PC-3GJA
1
Cooling
7,200
3.30
1,50
220
0.51
PU-
3VJA
2
1,50
220
15.1
1.96
(20.0)
0.44
(4.5)
63.9
52.3
3.7 5
27 19
10.7 35 24
Cooling
6,200
3.60
1,60
220
0.70
PU-
2.5NJA1
1,60
220
15.8
2.68
(27.3)
0.52
(5.3)
94.3
57.6
10.2 5
29 19
15.3
46 24
PC-2.5GJA
1
Cooling 6,500
2.58
1,50
220
0.51
PU-
2.5VJA2
1,50
220
11.4
1.96
(20.0)
0.5
(5.1)
72.3
52.4
8.6 5
27 19
12.0 35 24
Cooling
4,300
3.12
1,60
220
0.61
PU-
2NJA
1
1,60
220
13.6
2.49
(25.4)
0.53
(5.4)
77.7
60.5
8.3 5
29 19
13.8 46 24
PC-2GJA
1
Cooling
5,600
2.54
1,50
220
0.38
PU-
2VJA
2
1,50
220
11.3
1.93
(19.7)
0.44
(4.5)
68.6
51.6
3.3 5
27 19
9.7
35 24
Airflow Air speed Coverage range Airflow Air speed Coverage range
m
3
/min
m/sec.
m
ft
m
3
/min
m/sec.
m
ft
Configuration
50Hz
Frequency
60Hz
Service Ref.
PC-4GJSA
1
25
4.1
12.6
41.6 25
4.1
12.6
41.6
PC-5GJSA
1
34
4.38
15.2
50.0 34
4.38
15.2
50.0
PC-6GJSA
1
34
4.38
15.2
50.0 34
4.38
15.2
50.0
PC-3GJA
1
18
3.8
10.4
34.5 18
3.8
10.4
34.5
PC-2.5GJA
1
18
3.8
10.4
34.5 18
3.8
10.4
34.5
Ceiling suspended
PC-2GJA
1
13
3.7
8.8 29 13
3.7
8.8 29
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International Organization for Standardization).
The conversion factor is : 1(MPa•G)=10.2(kgf / FF•G)
3. OUTLET AIR SPEED AND COVERAGE RANGE
The air coverage range is the value up to the position where the air speed is 0.25 m/sec. when air is blown out horizontally from the unit at Hi notch position. The coverage range should be used as a general guide­line since it varies according to the size of the room and furniture inside the room.
11
5
180
210
157
15
85
182 (3/8F) liquid
201 (5/8F) gas
241 (Drainage)
Air intake
918
254
680
Electrical box
226
70
525
928
352
263
171
138
86
46 175 1
131
38
3879
161
32
179
42
6-7
Celling
Electrical box
[FRONT VIEW]
When electrical
box is pulled
down
3
2
8
5
1
4
6
2
1
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
Gap to ceiling
OUTLINES AND DIMENSIONS
1. INDOOR UNIT PC-2GJA1
NOTES:
refrigerant pipe will be only upper drain pipe arrangement.
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
12
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210 180
81 76
1310
Air outlet
1228
680
254
Air intake
85
182
201
241
15
157
(3/8F liquid)
(5/8F gas)
(Drainage)
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ FRONT VIEW ]
Celling
32
179
161
38
3879
42
6~7
525
1235
416
263
171
138
86
131
175 1
46
1
2
Electrical box
70
226
Gap to ceiling
PC-2.5GJA1 PC-3GJA1
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
refrigerant pipe will be only upper drain pipe arrangement.
2. Please be sure when installing the drain-up machine (option parts).
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
13
1228
680
254
Air intake
1214
270
207
81 96
1310
Air outlet
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
87
182
198
245
16
217
(3/8F liquid)
(5/8F gas)
(Drainage)
3
2
8
5
1
4
Electrical box
When electrical
box is pulled
down
[ FRONT VIEW ]
Celling
93
160
38
38 140
42 239
6~7
525
1235
687
263
171
138
86
192
236
1
45
1
2
Electrical box
70
229
Gap to ceiling
PC-4GJSA1
refrigerant pipe will be only upper drain pipe arrangement.
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. Please be sure when installing the drain-up machine (option parts).
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
14
PC-5GJSA1 PC-6GJSA1
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
87
6
16
320 80
70
140
150
18
217
270
refrigerant pipe will be only upper drain pipe arrangement.
2. Please be sure when installing the drain-up machine (option parts).
207
81 96
(3/8F liquid)
(3/4F gas)
182
198
245
(Drainage)
680
254
Gap to ceiling
1
4
1
5
8
Celling
[ FRONT VIEW ]
93
Electrical box
236
192
38 140
160
1535
1620
1524
1547(suspension bolt pitch)
45
86
138
171
687
263
38
Air outlet
Air intake
2
229
1
6~7
525
1545
70
Electrical box
2
1 Drainage pipe connection (26mm I.D.) 5 Refrigerant-pipe connection (liquid pipe side/flared connection)
2 Drainage pipe connection (for the left arrangement) 6 Knock out hole for upper drain pipe arrangement
3 Knock out hole for left drain-piping arrangement 7 Knock out hole for left drain pipe arrangement
4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knock out hole for wiring arrangement
3
42 239
When electrical
box is pulled
down
15
2.REMOTE CONTROLLER
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON AUTO
STOP START
75
69
108(4-1/4)
117(4-5/8)
108(4-1/4)
96.5
12(15/32)
90.5
11.6
3.6
33
117(4-5/8)
33
Rear side wiring arrangememt opening
Upper side wiring arrangement opening
Fixing hole
83.5(3-9/32)
12(15/32)
8 6
4.6
46
9.2
MITSUBISHI ELECTRIC
12 11 10
9 8 7 6 5 4 3 2 1
29 28 27 26 25 24 23 22 21 20 19 18
TIMER TEMP
TIMER/TEMP.
UP
DOWN
POWER
COOL
ON/OFF
LOUVER
MODE
SELECT
FAN
SPEED
TIMER MODE
DRY FAN
HIGH LOW
ON
AUTO
STOP START
Exposed remote controller cable
Cable connection is only from the top. (right, left and bottom not possible)
Note:The cable for the remote controller is 5m (16ft)and 12-core with connection O.D. 5.8.
Remote controller cable installation
For exposed remote controller cable installation ●For recessed remote controller cable installation
Remote controller cable
Conduit tube (local arrangement)
Switch box (local arrangement)
Set screw (match with switch box), local arrangement.
16
Loading...
+ 36 hidden pages