Mitsubishi Electric PC-2GAKD, PC-2.5GAKD, PC-3GAKD, PC-4GAKD, PC-5GAKD Service Manual

...
SPLIT-TYPE, COOLING AIR CONDITIONERS
ON/OFF
TEMP.
TECHNICAL & SERVICE MANUAL
February 2008
No. OC382
REVISED EDITION-B
Series PC
Indoor unit [
Model names]
PC-2GAKD
PC-2.5GAKD
PC-3GAKD
PC-4GAKD
PC-5GAKD
PC-6GAKD
INDOOR UNIT
Ceiling Suspended
[Service Ref.]
PC-2GAKD PC-2.5GAKD PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
Revision:
• Combination of outdoor units (PU­3/4VAKR type) has been added in REVISED EDITION-B.
Some descriptions have been modified.
Please void OC382 REVISED EDITION-A.
Note:
• This manual does not cover the out­door units. When serving outdoor units, please refer to the service man­ual No.OC152, OC206, OC353, OCH/OCB414, OCH/OCB431 and this manual in a set.
• RoHS compliant products have <G> mark on the spec name plate.
• For servicing RoHS compliant prod­ucts, refer to the RoHS Parts List.
CONTENTS
1. PART NAMES AND FUNCTIONS········2
2. SPECIFICATIONS ·································4
3. DATA·····················································9
4. OUTLINES AND DIMENSIONS··········16
5. WIRING DIAGRAM ·····························21
REFRIGERANT SYSTEM DIAGRAM
7. TROUBLE SHOOTING ·······················27
8. FUNCTION SETTING ·························40
9. SYSTEM CONTROL···························46
10. DISASSEMBLY PROCEDURE···········60
11. PARTS LIST········································65
12. RoHS PARTS LIST·····························73
13. OPTIONAL PARTS·····························81
······22
REMOTE CONTROLLER
1
Air outlet
Intake grille
Air intake
Left/right guide vanes
Change the direction of airflow from the horizontal blower.
Long-life filter
Removes dust and foreign matter from air coming in through the grille (Recommended cleaning interval : Approx, every 2,500 operating hours).
Up/down guide vanes
Change the direction of airflow from the vertical blower.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
Temperature setting buttons
Down Up
Timer Menu button (Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button (Set Day button)
Opening the lid
ON/OFF button
Fan Speed button
Filter button (<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button (
Operation button)
To return operation number
Ventilation button (
Operation button)
To go to next operation number
PART NAMES AND FUNCTIONS
Indoor Unit
Wired remote controller
Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
2
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON OFF
Hr AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
Display Section
For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit.
Identifies the current operation
Shows the operating mode, etc. *Multilanguage display is available.
“Centrally Controlled” indicator
Indicates that operation from the remote controller has been prohib­ited by a master controller.
“Timer is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Day-of-Week
Shows the current day of the week.
Time/Timer Display
Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, the time to be switched off is shown.
“Sensor” indication
Displayed when the remote controller sensor is used.
“Locked” indicator
Indicates that remote controller but­tons have been locked.
“Clean The Filter” indicator
To be displayed on when it is time to clean the filter.
Timer indicators
The indicator comes on if the corre­sponding timer is set.
Up/Down Air Direction indica­tor
The indicator shows the direc­tion of the outcoming airflow.
“One Hour Only” indicator
Room Temperature display
Shows the room temperature. The room temperature display range is 8–39:. The display blinks if the temperature is less than 8: or 39: or more.
Louver display
Indicates the action of the swing louver. Does not appear if the louver is not running.
(Power On indicator)
Indicates that the power is on.
Fan Speed indicator
Shows the selected fan speed.
Ventilation indicator
Appears when the unit is running in Ventilation mode.
Note:
“PLEASE WAIT” message This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure. “NOT AVAILABLE” message This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have). If a single remote controller is used to simultaneously operate multiple indoor units that are different types, this message will not be displayed as far as any of the indoor units is equipped with the function.
Displayed if the airflow is set to Low or downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off in 1 hour, when the airflow direction also changes.
3
2
Service Ref.
External finish Fan motor output
Airflow Low-High
External static pressure Operation control & Thermostat
Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w3 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
W
Btu/h
W
Btu/h
W
Btu/h
K
/min
CFM
K
/min
CFM
Pa(mmAq)
dB
dB mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM) K/min(CFM)
dB mm(in.) mm(in.) mm(in.) kg(lbs.)
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz 60Hz O.D.
W D H
50/60Hz 50/60Hz
50Hz 60Hz
50/60Hz
W D H
Munsell 0.70Y 8.59/0.97
0 (Direct blow)
Remote control & Built-in
Munsell 3.0Y 7.8/1.1
Capillary tube
295+24 (11-5/8 add 1)
10,300 35,200 11,400 39,000
9,300
31,700
3.49/4.47
PC-4GAKD
0.09
20-25
706-883
20-25
706-883
40-45 40-45 26 (1)
1310 (51-9/16)
680 (26-3/4) 270 (10-5/8)
37 (82)
w10 PU-4JSA-type
32/38
2.7/2.7
w7(V)/w6(Y,T)
0.065+0.065 95 (3352) 95 (3352)
54/55
870 (34-1/4)
1258 (49-1/2)
94 (207)
Cooling capacity w1
Cooling capacity w4 Total input (50/60Hz) w2
Item
Service Ref.
PC-4GAKD
7,600
25,900
8,200
28,000
6,500
22,200
3.30/3.60
PC-3GAKD
0.07
14-18
494-635
14-18
494-635
37-43 37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
w9 PU-3J-type
32/38
2.2/2.2 w5
0.085 50 (1765) 50 (1765)
52/53
870 (34-1/4)
850 (33-7/16)
73 (161)
PC-3GAKD
6,500
22,200
7,000
23,900
6,200
21,200
2.58/3.07
PC-2.5GAKD
0.07
14-18
494-635
14-18
494-635
37-43 37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
PU-2.5VJA
1.TH/
PU-2.5NJA.TH
32/-
2.0/1.7 w5
0.085 50 (1765) 50 (1765)
52/53
870 (34-1/4)
850 (33-7/16)
71 (157)
PC-2.5GAKD
5,600
19,100
5,600
19,100
4,300
14,700
2.54/2.60
PC-2GAKD
0.054 10-13
353-459
10-13
353-459
37-42 37-42 26 (1)
1000 (39-3/8)
680 (26-3/4)
210 (8-1/4)
27 (60)
PU-2VJA
1.TH/
PU-2NJA.TH
32/-
2.0/1.5 w5
0.065 45 (1588) 45 (1588)
49/50
870 (34-1/4)
650 (25-5/8)
60 (132)
PC-2GAKD
Indoor unitOutdoor unit
SPECIFICATIONS
2-1. STANDARD SPECIFICATIONS
Notes : w1. Rating condition (JISB8616)
Models PC-2,2.5,3 PC-4,5,6
Indoor : D.B 27 Outdoor : D.B 35OC (95OF) , W.B. 24OC (75OF) Refrigerant piping length (one way) : 5m (16ft)
w2. Total input based indicated voltage (In/Out)
50Hz 1ph220V / 1ph220V 1ph220V / 3ph380V 60Hz 1ph220V / 1ph220V
w3. The capacity of crankcase heater (W) shows the
case of 220V.
O
C (80OF) , W.B. 19OC (66OF)
1ph220V / 3ph220V
w4. Rating condition (SSA385, 386)
Indoor : D.B 29OC (84OF) , W.B. 19OC (66OF) Outdoor : D.B 46OC (115OF), W.B. 24OC (75OF) Refrigerant piping length (one way ) : 5m (16ft)
w5. Inner thermostat, HP switch, LP switch w6. Thermal switch, Reversed-phase protector, HP switch,
LP switch, Thermal relay
w7. Thermal switch, HP switch, LP switch, Inner thermostat w8. Thermal switch, HP switch, Inner thermostat w9. PU-3J w10.PU-4JSA
4
-type···PU-3VJC1.TH, PU-3YJC.TH, PU-3NJA.TH
-type···PU-4VLJSA2.TH, PU-4YJSA1.TH,
PU-4TJSA.TH
Item
Cooling capacity w1
Cooling capacity w4 Total input (50/60Hz) w2
Service Ref.
External finish Fan motor output
Airflow Low-High
External static pressure Operation control & Thermostat
Indoor unitOutdoor unit
Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w3 Compressor output Protection devices Fan motor output
Airflow Noise level
Dimensions
Weight
Service Ref.
50Hz
60Hz
60Hz
50Hz
60Hz
50Hz 60Hz
O.D.
W
D H
50/60Hz 50/60Hz
50Hz 60Hz
50/60Hz
W
D H
W
Btu/h
W
Btu/h
W
Btu/h
K/min
CFM
K/min
CFM
Pa(mmAq)
dB
dB mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM) K/min(CFM)
dB mm(in.) mm(in.) mm(in.) kg(lbs.)
PC-5GAKD
13,300 45,400 14,200 48,500 11,600 39,600
4.76/5.89
PC-5GAKD
0.15
27-34
953-1,200
27-34
953-1,200
41-46 41-46
26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
43(95)
PU-5YJSA
1.TH PU-5TJSA.TH
3.5
w8 w7
0.10+0.10 100(3530) 100(3530)
55
970(38-3/16)
345+24(13-9/16+1)
1,258(49-1/2)
114(251)
Munsell 0.70Y 8.59/0.97
0 (Direct blow)
Remote control & Built-in
PU-6YJSA
Munsell 3.0Y 7.8/1.1
Capillary tube
4.2 4.0
w8 w7
345+24(13-9/16+1)
PC-6GAKD
15,200 51,900 15,600 53,300 13,400 45,700
5.31/6.41
PC-6GAKD
0.15
27-34
953-1,200
27-34
953-1,200
42-48 42-48
26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
45(99)
1.TH PU-6TJSA.TH
0.10+0.10 100(3530) 100(3530)
56
970(38-3/16)
1,258(49-1/2)
117(258)
5
Service Ref.
External finish Fan motor output
Airflow Low-High External static pressure
Operation control & Thermostat Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater w3 Compressor output Protection devices Fan motor output Airflow Noise level
Dimensions
Weight
W
Btu/h
K
/min
CFM
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM)
dB mm(in.) mm(in.) mm(in.) kg(lbs.)
50Hz
50Hz
50Hz
O.D.
W
D H
50Hz 50Hz
50Hz 50Hz
W
D H
Munsell 0.70Y 8.59/0.97
0 (Direct blow)
Remote control & Built-in
Munsell 3.0Y 7.8/1.1
Capillary tube
10,300 35,200
3.61/3.54
PU-4VAKD.TH/
PU-4YAKD.TH
32
2.7/2.7
w4(V)/w5(Y)
Cooling capacity w1 Total input (50Hz) w2
Item
Service Ref.
PC-4GAKD
7,600
25,900
3.31
PU-3VAKD.TH
2.5
0.075
49 (1730)
53
840 (33-1/16)
330 (13)
850 (33-7/16)
74 (163)
7,700
26,300
3.05
PU-3VAKR.TH
35
2.5 w6
0.065+0.065 95 (3352)
54
93 (205)
9,550
32,600
3.82
PU-4VAKR.TH
35
2.7 w6
PC-3GAKD
6,500
22,200
2.33
PC-2.5GAKD
0.07
14-18
494-635
37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
PU-2.5VAKD.TH
1.7
0.06
39 (1390)
52
52 (115)
PC-2.5GAKD
5,500
18,800
1.91
PC-2GAKD
0.054 10-13
353-459
37-42 26 (1)
1000 (39-3/8)
680 (26-3/4)
210 (8-1/4)
27 (60)
PU-2VAKD.TH
1.5
0.05
38 (1340)
50
45 (99)
PC-2GAKD
Indoor unitOutdoor unit
850 (33-7/16)
290 (11-7/16)
605 (23-13/16)
Inner thermostat
PC-3GAKD
0.07
14-18
494-635
37-43 26 (1)
1310 (51-9/16)
680 (26-3/4)
210 (8-1/4)
34 (75)
0.065+0.065 95 (3352)
54
870 (34-1/4)
295+24 (11-5/8 add 1)
1258 (49-1/2)
94 (207)
PC-4GAKD
0.09
20-25
706-883
40-45 26 (1)
1310 (51-9/16)
680 (26-3/4) 270 (10-5/8)
37 (82)
870 (34-1/4)
295+24 (11-5/8 add 1)
1258 (49-1/2)
Notes : w1. Rating condition (JISB8616)
Indoor : D.B 27 Outdoor : D.B 35OC (95OF) , W.B. 24OC (75OF) Refrigerant piping length (one way) : 5m (16ft)
w2. Total input based indicated voltage (In/Out)
PU-AKD
Models PC-2,2.5,3 PC-4,5,6
50Hz 1ph220V / 1ph220V 1ph220V / 3ph380V
PU-AKR
Models PC-3 PC-4
50Hz 1ph230V / 1ph230V 1ph230V / 1ph230V
w3. The capacity of crankcase heater (W) shows the
case of 220V.(230V:VAKR)
O
C (80OF) , W.B. 19OC (66OF)
(7.5m:VAKR)
w4. Inner thermostat, HP switch w5. Thermal switch, Reversed-phase protector, HP switch,
Thermal relay
w6. Inner thermostat, HP switch, LP switch
6
Item
220,230,240V
380/220, 400/230, 415/240V
220V 220V
1
3
1 3
50Hz
60Hz
Power supply
Frequency
Phase
Outdoor unit Service Ref.
PC-4GAKD
PU-4VLJSA2.TH
PU-4VAKD.TH PU-4VAKR.TH
PU-4YJSA
1.TH
PU-4YAKD.TH
PU-4TJSA.TH
PC-5GAKD
PU-5YJSA1.TH
PU-5YAKD.TH(-T)
PU-5TJSA.TH
PC-6GAKD
PU-6YJSA1.TH
PU-6YAKD.TH(-T)
PU-6TJSA.TH
PC-3GAKD
PU-3VJC1.TH PU-3VAKD.TH PU-3VAKR.TH
PU-3YJC.TH
PU-3NJA.TH
PC-2.5GAKD
P
U-2.5VJA1.TH
PU-2.5VAKD.TH
PU-2.5NJA.TH
PC-2GAKD
PU-2VJA1.TH
PU-2VAKD.TH
PU-2NJA.TH
Indoor unit model
Cooling capacity w1 Total input (50Hz) w2
Service Ref.
External finish Fan motor output
Airflow Low-High External static pressure
Operation control & Thermostat
Indoor unitOutdoor unit
Noise level Low-High Cond. drain connector
Dimensions
Weight
Service Ref.
External finish Refrigerant (R-22) control Crankcase Heater Compressor output Protection devices Fan motor output Airflow Noise level
Dimensions
Weight
Service Ref.
50Hz
50Hz
50Hz O.D.
W
D H
50Hz 50Hz
50Hz 50Hz
W
D H
W
Btu/h
K/min
CFM
Pa(mmAq)
dB mm(in.) mm(in.) mm(in.) mm(in.) kg(lbs.)
W
kW
kW
K/min(CFM)
dB mm(in.) mm(in.) mm(in.) kg(lbs.)
PC-5GAKD
13,200 45,000
4.27
PC-5GAKD
Munsell 0.70Y 8.59/0.97
0.15
27-34
953-1,200
0 (Direct blow)
Remote control & Built-in 41-46 26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
43(95)
PU-5YAKD.TH, PU-5YAKD.TH-T
Munsell 3.0Y 7.8/1.1
Capillary tube
3.5 w6
0.10+0.10
100(3530)
55
970(38-3/16)
345+24(13-9/16+1)
1,258(49-1/2)
119 (262)
PC-6GAKD
15,200 51,900
5.26
PC-6GAKD
0.15
27-34
953-1,200
42-48
26(1)
1,620(63-3/4)
680(26-3/4) 270(10-5/8)
45(99)
PU-6YAKD.TH, PU-6YAKD.TH-T
4.2 w6
0.10+0.10
100(3530)
56
970(38-3/16)
345+24(13-9/16+1)
1,258(49-1/2)
120 (265)
w6. Thermal switch, Reversed-phase protector, HP switch,
Thermal relay, LP switch
2-2. POWER SUPPLY & MODEL NAMES
Notes : 1. Power supply key N : 1ph, 220V/60Hz T : 3ph, 220V/60Hz
V(L) : 1ph, 220, 230, 240V/50Hz Y : 3ph, 380/220, 400/230, 415/240V, 50Hz, 4wires
2. Primary power supplies for all indoor units are single-phase.
7
2-3. ELECTRICAL SPECIFICATIONS
A
kW
A
V : 220V , 50Hz
PC-4GAKD
0.68
0.14
1.36
PU-4
Power supply (1 Phase)
Model
Current Input Starting current Outdoor unit to be connected
PC-3GAKD
0.51
0.12
1.17
PU-3
PC-2.5GAKD
0.51
0.12
1.17
PU-2.5
PC-2GAKD
0.38
0.10
1.10
PU-2
PC-6GAKD
0.96
0.20
2.00
PU-6
PC-5GAKD
0.96
0.20
2.00
PU-5
A
kW
A
V : 230V , 50Hz
PC-4GAKD
0.69
0.15
1.42
PU-4
Power supply (1 Phase)
Model
Current Input Starting current Outdoor unit to be connected
PC-3GAKD
0.53
0.13
1.22
PU-3
PC-2.5GAKD
0.53
0.13
1.22
PU-2.5
PC-2GAKD
0.41
0.12
1.15
PU-2
PC-6GAKD
1.01
0.22
2.10
PU-6
PC-5GAKD
1.01
0.22
2.10
PU-5
A
kW
A
V : 240V , 50Hz
PC-4GAKD
0.70
0.16
1.48
PU-4
Power supply (1 Phase)
Model
Current Input Starting current Outdoor unit to be connected
PC-3GAKD
0.55
0.15
1.27
PU-3
PC-2.5GAKD
0.55
0.15
1.27
PU-2.5
PC-2GAKD
0.43
0.14
1.20
PU-2
PC-6GAKD
1.06
0.25
2.20
PU-6
PC-5GAKD
1.06
0.25
2.20
PU-5
A
kW
A
N : 220V , 60Hz
PC-4GAKD
0.95
0.20
1.27
PU-4
Power supply (1 Phase)
Model
Current Input Starting current Outdoor unit to be connected
PC-3GAKD
0.70
0.16
1.11
PU-3
PC-2.5GAKD
0.70
0.16
1.11
PU-2.5
PC-2GAKD
0.61
0.15
1.03
PU-2
PC-6GAKD
1.20
0.26
1.91
PU-6
PC-5GAKD
1.20
0.26
1.91
PU-5
A
kW
A
N : 220V , 60Hz
PC-4GAKD
0.95
0.20
1.27
PU-4
PC-5GAKD
1.20
0.26
1.91
PU-5
PC-6GAKD
1.20
0.26
1.91
PU-6
Power supply (1 Phase)
Model
Current Input Starting current Outdoor unit to be connected
PC-3GAKD
0.70
0.16
1.11
PU-3
PC-2.5GAKD
0.70
0.16
1.11
PU-2.5
PC-2GAKD
0.61
0.15
1.03
PU-2
Rating conditions — SSA385, 386
Indoor : D.B. 29°C (84°F) , W.B. 19°C (66°F) Outdoor : D.B. 46°C (115°F) , W.B. 24°C (75°F)
Rating conditions — JIS B8616 Indoor : D.B. 27°C (80°F) , W.B. 19°C (66°F)
Outdoor : D.B. 35°C (95°F) , W.B. 24°C (75°F)
Series PC Indoor unit (Single phase)
8
3
DATA
3-1. PERFORMANCE DATA Cooling capacity
Model
Outdoor D.B.
(125.5°F)
Notes : 1. T.C. : Total capacity (kW) ... (kcal/h) = (kW) 860, (Btu/h) = 4 (kW) 860
Temperature
Indoor W.B.
16°C
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
Evaporator air flow (m3/min) Bypass factors S.H.F. at rating conditions
18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
C.F. (T.I.): Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3.
Guaranteed operating range (cooling)
50Hz
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
(Outdoor unit : PU-J type)
PC-2GAKD
T.C. C.F.
5.6
6.0
6.2
6.2
6.4
6.7
5.5
5.9
6.0
6.1
6.2
6.6
5.3
5.6
5.8
5.9
6.0
6.4
5.2
5.5
5.7
5.8
5.9
6.3
5.1
5.4
5.6
5.7
5.8
6.2
4.8
5.2
5.4
5.4
5.5
5.9
4.8
5.2
5.3
5.4
5.5
5.9
4.6
4.9
5.1
5.2
5.3
5.7
4.6
4.9
5.1
5.1
5.2
5.6
4.4
4.7
4.9
4.9
5.0
5.4
4.3
4.6
4.7
4.8
4.9
5.3 13
0.07
0.72
{
PC-2.5GAKD
C.F.
(T.I.)
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
Lower limit ···················Indoor : D.B. 21°C (70°F) , W.B. 15.5°C (60°F) , Outdoor : D.B. 21°C (70°F)
Upper limit····················Indoor : D.B. 35°C (95°F) , W.B. 22.5°C (72.5°F) , Outdoor : D.B.52°C (125.5°F)
T.C. C.F.
(T.I.)
6.5
0.81
6.9
0.82
7.2
0.83
7.3
0.83
7.4
0.84
7.8
0.86
6.4
0.84
6.8
0.85
7.0
0.86
7.1
0.86
7.2
0.87
7.7
0.89
6.1
0.90
6.6
0.92
6.8
0.93
6.9
0.93
7.0
0.94
7.4
0.96
6.0
0.93
6.4
0.95
6.6
0.96
6.7
0.97
6.9
0.97
7.3
0.99
5.9
0.96
6.3
0.99
6.5
1.00
6.6
1.00
6.7
1.01
7.2
1.04
5.6
1.03
6.0
1.06
6.2
1.07
6.3
1.08
6.4
1.08
6.9
1.11
5.6
1.04
6.0
1.06
6.2
1.08
6.3
1.08
6.4
1.09
6.8
1.12
5.4
1.10
5.7
1.12
5.9
1.14
6.0
1.15
6.1
1.16
6.6
1.20
5.3
1.11
5.7
1.14
5.9
1.15
6.0
1.16
6.1
1.17
6.5
1.21
5.1
1.16
5.4
1.19
5.6
1.21
5.7
1.22
5.8
1.23
6.3
1.28
4.9
1.19
5.3
1.22
5.5
1.24
5.6
1.25
5.7
1.26
6.1
1.31
18
0.08
0.78
PC-3GAKD
T.C. C.F.
(T.I.)
7.6
0.81
8.1
0.82
8.4
0.83
8.5
0.83
8.6
0.84
9.1
0.86
7.5
0.84
7.9
0.85
8.2
0.86
8.3
0.86
8.5
0.87
9.0
0.89
7.2
0.90
7.7
0.92
7.9
0.93
8.0
0.93
8.2
0.94
8.7
0.96
7.1
0.93
7.5
0.95
7.8
0.96
7.9
0.97
8.0
0.97
8.5
0.99
6.9
0.96
7.4
0.99
7.6
1.00
7.7
1.00
7.8
1.01
8.4
1.04
6.6
1.03
7.0
1.06
7.3
1.07
7.4
1.08
7.5
1.08
8.0
1.11
6.5
1.04
7.0
1.06
7.2
1.08
7.3
1.08
7.5
1.09
8.0
1.12
6.3
1.10
6.7
1.12
6.9
1.14
7.0
1.15
7.2
1.16
7.7
1.20
6.2
1.11
6.6
1.14
6.9
1.15
7.0
1.16
7.1
1.17
7.6
1.21
5.9
1.16
6.4
1.19
6.6
1.21
6.7
1.22
6.8
1.23
7.3
1.28
5.8
1.19
6.2
1.22
6.4
1.24
6.5
1.25
6.7
1.26
7.2
1.31
18
0.08
0.73
PC-4GAKD PC-5GAKD
T.C. C.F.
(T.I.)
0.81
10.4
0.82
11.0
0.83
11.3
0.83
11.5
0.84
11.7
0.86
12.4
0.84
10.1
0.85
10.8
0.86
11.1
0.86
11.3
0.87
11.5
0.89
12.2
0.90
9.7
0.92
10.4
0.93
10.7
0.93
10.9
0.94
11.1
0.96
11.8
0.93
9.6
0.95
10.1
0.96
10.5
0.97
10.7
0.97
10.9
0.99
11.5
0.96
9.3
0.99
10.0
1.00
10.3
1.00
10.5
10.6
1.01
11.3
1.04
8.9
1.03
9.5
1.06
9.9
1.07
10.0
1.08
10.2
1.08
10.9
1.11
8.9
1.04
9.5
1.06
9.8
1.08
9.9
1.08
10.1
1.09
10.8
1.12
8.5
1.10
9.1
1.12
9.4
1.14
9.5
1.15
9.7
1.16
10.4
1.20
8.4
1.11
9.0
1.14
9.4
1.15
9.4
1.16
9.6
1.17
10.3
1.21
8.0
1.16
8.6
1.19
8.9
1.21
9.1
1.22
9.2
1.23
9.9
1.28
7.8
1.19
8.4
1.22
8.7
1.24
8.9
1.25
9.1
1.26
9.7
1.31
25
0.08
0.73
T.C. C.F.
(T.I.)
13.4
0.81
14.2
0.82
14.6
0.83
14.8
0.83
15.1
0.84
16.0
0.86
13.0
0.84
13.9
0.85
14.4
0.86
14.6
0.86
14.8
0.87
15.7
0.89
12.6
0.90
13.4
0.92
13.8
0.93
14.1
0.93
14.3
0.94
15.2
0.96
12.4
0.93
13.1
0.95
13.6
0.96
13.8
0.97
14.0
0.97
14.9
0.99
12.1
0.96
12.9
0.99
13.3
1.00
13.5
1.00
13.7
1.01
14.6
1.04
11.5
1.03
12.3
1.06
12.7
1.07
12.9
1.08
13.2
1.08
14.0
1.11
11.4
1.04
12.2
1.06
12.6
1.08
12.8
1.08
13.1
1.09
14.0
1.12
11.0
1.10
11.7
1.12
12.1
1.14
12.3
1.15
12.6
1.16
13.4
1.20
10.8
1.11
11.6
1.14
12.1
1.15
12.2
1.16
12.4
1.17
13.3
1.21
10.3
1.16
11.1
1.19
11.5
1.21
11.7
1.22
11.8
1.23
12.8
1.28
10.1
1.19
10.9
1.22
11.2
1.24
11.5
1.25
11.7
1.26
12.6
1.31
34
0.08
0.75
wPU-4VLJSA : D.B. 46°C (115°F)
PC-6GAKD
T.C.
(T.I.)
15.3
0.81
16.2
0.82
16.7
0.83
17.0
0.83
17.3
0.84
18.2
0.86
14.9
0.84
15.9
0.85
16.4
0.86
16.7
0.86
16.9
0.87
18.0
0.89
14.4
0.90
15.3
0.92
15.8
0.93
16.1
0.93
16.3
0.94
17.4
0.96
14.1
0.93
15.0
0.95
15.5
0.96
15.7
0.97
16.0
0.97
17.0
0.99
13.8
0.96
14.7
0.99
15.2
1.00
15.4
1.00
15.7
1.01
16.7
1.04
13.2
1.03
14.1
1.06
14.6
1.07
14.8
1.08
15.0
1.08
16.1
1.11
13.1
1.04
14.0
1.06
14.4
1.08
14.7
1.08
15.0
1.09
16.0
1.12
12.5
1.10
13.4
1.12
13.9
1.14
14.1
1.15
14.3
1.16
15.4
1.20
12.4
1.11
13.2
1.14
13.8
1.15
13.9
1.16
14.2
1.17
15.2
1.21
11.8
1.16
12.7
1.19
13.2
1.21
13.4
1.22
13.5
1.23
14.7
1.28
11.6
1.19
12.5
1.22
12.8
1.24
13.1
1.25
13.4
1.26
14.4
1.31
34
0.03
0.72
9
Cooling capacity
Evaporator air flow (m3/min) Bypass factors S.H.F. at rating conditions
5.6
6.0
6.2
6.2
6.4
6.7
5.5
5.9
6.0
6.1
6.2
6.6
5.3
5.6
5.8
5.9
6.0
6.4
5.2
5.5
5.7
5.8
5.9
6.3
5.1
5.4
5.6
5.7
5.8
6.2
4.8
5.2
5.4
5.4
5.5
5.9
4.8
5.2
5.3
5.4
5.5
5.9
4.6
4.9
5.1
5.2
5.3
5.7
4.6
4.9
5.1
5.1
5.2
5.6
4.4
4.7
4.9
4.9
5.0
5.4
4.3
4.6
4.7
4.8
4.9
5.3
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
7.0
7.5
7.7
7.8
7.9
8.4
6.9
7.3
7.6
7.7
7.8
8.3
6.6
7.1
7.3
7.4
7.5
8.0
6.5
6.9
7.1
7.2
7.4
7.8
6.3
6.8
7.0
7.1
7.2
7.7
6.1
6.5
6.7
6.8
6.9
7.4
6.0
6.4
6.7
6.8
6.9
7.4
5.8
6.2
6.4
6.5
6.6
7.1
5.7
6.1
6.4
6.4
6.5
7.0
5.4
5.9
6.1
6.2
6.2
6.8
5.3
5.7
5.9
6.0
6.2
6.6
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
8.2
8.7
9.0
9.1
9.3
9.8
8.0
8.6
8.9
9.0
9.1
9.7
7.7
8.3
8.5
8.7
8.8
9.4
7.6
8.1
8.4
8.5
8.7
9.2
7.4
7.9
8.2
8.3
8.5
9.0
7.1
7.6
7.9
8.0
8.1
8.7
7.1
7.5
7.8
7.9
8.1
8.6
6.8
7.2
7.5
7.6
7.7
8.3
6.7
7.1
7.5
7.5
7.7
8.2
6.4
6.9
7.1
7.2
7.3
7.9
6.2
6.7
6.9
7.1
7.2
7.7
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
11.5
12.1
12.5
12.7
12.9
13.7
11.2
11.9
12.3
12.5
12.7
13.5
10.8
11.5
11.9
12.1
12.2
13.0
10.6
11.2
11.6
11.8
12.0
12.8
10.3
11.0
11.4
11.6
11.8
12.5
9.9
10.6
10.9
11.1
11.3
12.0
9.8
10.5
10.8
11.0
11.2
12.0
9.4
10.1
10.4
10.5
10.8
11.5
9.3
9.9
10.4
10.5
10.7
11.4
8.9
9.5
9.9
10.0
10.1
11.0
8.7
9.3
9.6
9.8
10.0
10.8
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
14.3
15.1
15.6
15.8
16.1
17.0
13.9
14.9
15.3
15.6
15.8
16.8
13.4
14.3
14.8
15.0
15.3
16.2
13.2
14.0
14.5
14.7
15.0
15.9
12.9
13.7
14.2
14.4
14.7
15.6
12.3
13.1
13.6
13.8
14.0
15.0
12.2
13.1
13.5
13.7
14.0
14.9
11.7
12.5
13.0
13.1
13.4
14.3
11.6
12.4
12.9
13.0
13.3
14.2
11.0
11.9
12.3
12.5
12.6
13.7
10.8
11.6
12.0
12.2
12.5
13.4
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
15.7
16.6
17.2
17.4
17.7
18.7
15.3
16.3
16.8
17.1
17.4
18.5
14.7
15.7
16.2
16.5
16.8
17.8
14.5
15.4
15.9
16.1
16.5
17.5
14.1
15.1
15.6
15.8
16.1
17.2
13.5
14.4
14.9
15.2
15.4
16.5
13.4
14.4
14.8
15.1
15.4
16.4
12.9
13.8
14.2
14.4
14.7
15.8
12.7
13.6
14.2
14.3
14.6
15.6
12.1
13.1
13.5
13.7
13.9
15.1
11.9
12.8
13.2
13.4
13.7
14.7
0.81
0.82
0.83
0.83
0.84
0.86
0.84
0.85
0.86
0.86
0.87
0.89
0.90
0.92
0.93
0.93
0.94
0.96
0.93
0.95
0.96
0.97
0.97
0.99
0.96
0.99
1.00
1.00
1.01
1.04
1.03
1.06
1.07
1.08
1.08
1.11
1.04
1.06
1.08
1.08
1.09
1.12
1.10
1.12
1.14
1.15
1.16
1.20
1.11
1.14
1.15
1.16
1.17
1.21
1.16
1.19
1.21
1.22
1.23
1.28
1.19
1.22
1.24
1.25
1.26
1.31
C.F. (T.I.)
Model
Temperature
PC-2GAKD
Indoor W.B.
Outdoor D.B.
T.C. C.F.
(T.I.)
PC-2.5GAKD
T.C. C.F.
(T.I.)
PC-3GAKD
T.C. C.F.
(T.I.)
PC-4GAKD PC-5GAKD
PC-6GAKD
T.C. C.F.
(T.I.)
T.C. C.F.
(T.I.)
T.C.
13
0.07
0.72
18
0.08
0.75
18
0.08
0.70
25
0.08
0.70
34
0.08
0.73
34
0.03
0.72
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
(125.5°F)
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
60Hz
Notes:1.T.C. : Total capacity (x kW)···Btu/h=(W)x0.86
C.F. (T.I.) : Correction factors of Total input + Outdoor unit input)
2.(°C)=32+9/5(°C)
3.Guaranteed operating range (cooling):
Lower limit···Indoor D.B. 21°C(70°F) , W.B. 15.5°C(60°F) , Outdoor D.B. 21°C(70°F)
{
Upper limit···Indoor D.B. 35
°C
(95°F) , W.B. 22.5°C(72.5°F) , Outdoor D.B. 52°C(125.5°F)
10
Cooling capacity (Outdoor unit : PU-AKD type)
Evaporator air flow (m3/min) Bypass factors S.H.F. at rating conditions
C.F.
(T.I.)
Model
Temperature
PC-2GAKD
Indoor W.B.
Outdoor D.B.
T.C. C.F.
(T.I.)
PC-2.5GAKD
T.C. C.F.
(T.I.)
PC-3GAKD
T.C. C.F.
(T.I.)
PC-4GAKD PC-5GAKD PC-6GAKD
T.C. C.F.
(T.I.)
T.C. C.F.
(T.I.)
T.C.
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
(125.5°F)
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
5.5 0.81 6.5 0.81 7.6 0.81 10.3 0.81 13.3 0.81 15.3 0.81
5.9 0.82 6.9 0.82 8.1 0.82 11.0 0.82 14.1 0.82 16.2 0.82
6.1 0.83 7.2 0.83 8.4 0.83 11.4 0.83 14.5 0.83 16.8 0.83
6.1 0.83 7.3 0.83 8.5 0.83 11.5 0.83 14.7 0.83 17.0 0.83
6.2 0.84 7.4 0.84 8.6 0.84 11.7 0.84 15.0 0.84 17.3 0.84
6.6 0.86 7.8 0.86 9.1 0.86 12.4 0.86 15.9 0.86 18.3 0.86
5.4 0.84 6.4 0.84 7.5 0.84 10.1 0.84 13.0 0.84 14.9 0.84
5.8 0.85 6.8 0.85 7.9 0.85 10.8 0.85 13.8 0.85 15.9 0.85
5.9 0.86 7.0 0.86 8.2 0.86 11.1 0.86 14.3 0.86 16.4 0.86
6.0 0.86 7.1 0.86 8.3 0.86 11.3 0.86 14.4 0.86 16.6 0.86
6.1 0.87 7.2 0.87 8.5 0.87 11.5 0.87 14.7 0.87 16.9 0.87
6.5 0.89 7.7 0.89 9.0 0.89 12.2 0.89 15.6 0.89 18.0 0.89
5.2 0.90 6.1 0.90 7.2 0.90 9.7 0.90 12.5 0.90 14.4 0.90
5.5 0.92 6.6 0.92 7.7 0.92 10.4 0.92 13.3 0.92 15.3 0.92
5.7 0.93 6.8 0.93 7.9 0.93 10.7 0.93 13.7 0.93 15.8 0.93
5.8 0.93 6.9 0.93 8.0 0.93 10.9 0.93 13.9 0.93 16.0 0.93
5.9 0.94 7.0 0.94 8.2 0.94 11.1 0.94 14.2 0.94 16.3 0.94
6.3 0.96 7.4 0.96 8.7 0.96 11.8 0.96 15.1 0.96 17.4 0.96
5.1 0.93 6.0 0.93 7.1 0.93 9.6 0.93 12.3 0.93 14.1 0.93
5.4 0.95 6.4 0.95 7.5 0.95 10.2 0.95 13.1 0.95 15.1 0.95
5.6 0.96 6.6 0.96 7.8 0.96 10.5 0.96 13.5 0.96 15.5 0.96
5.7 0.97 6.7 0.97 7.9 0.97 10.7 0.97 13.7 0.97 15.7 0.97
5.8 0.97 6.9 0.97 8.0 0.97 10.9 0.97 13.9 0.97 16.0 0.97
6.2 0.99 7.3 0.99 8.5 0.99 11.6 0.99 14.8 0.99 17.1 0.99
5.0 0.96 5.9 0.96 6.9 0.96 9.3 0.96 12.0 0.96 13.8 0.96
5.3 0.99 6.3 0.99 7.4 0.99 10.0 0.99 12.8 0.99 14.7 0.99
5.5 1.00 6.5 1.00 7.6 1.00 10.3 1.00 13.2 1.00 15.2 1.00
5.6 1.00 6.6 1.00 7.7 1.00 10.4 1.00 13.4 1.00 15.4 1.00
5.7 1.01 6.7 1.01 7.8 1.01 10.6 1.01 13.6 1.01 15.7 1.01
6.1 1.04 7.2 1.04 8.4 1.04 11.3 1.04 14.5 1.04 16.7 1.04
4.8 1.03 5.6 1.03 6.6 1.03 8.9 1.03 11.4 1.03 13.2 1.03
5.1 1.06 6.0 1.06 7.0 1.06 9.5 1.06 12.2 1.06 14.1 1.06
5.3 1.07 6.2 1.07 7.3 1.07 9.9 1.07 12.6 1.07 14.6 1.07
5.3 1.08 6.3 1.08 7.4 1.08 10.0 1.08 12.8 1.08 14.7 1.08
5.4 1.08 6.4 1.08 7.5 1.08 10.2 1.08 13.1 1.08 15.0 1.08
5.8 1.11 6.9 1.11 8.0 1.11 10.9 1.11 13.9 1.11 16.0 1.11
4.7 1.04 5.6 1.04 6.5 1.04 8.9 1.04 11.4 1.04 13.1 1.04
5.1 1.06 6.0 1.06 7.0 1.06 9.5 1.06 12.2 1.06 14.0 1.06
5.2 1.08 6.2 1.08 7.2 1.08 9.8 1.08 12.6 1.08 14.5 1.08
5.3 1.08 6.3 1.08 7.3 1.08 9.9 1.08 12.7 1.08 14.7 1.08
5.4 1.09 6.4 1.09 7.5 1.09 10.1 1.09 13.0 1.09 15.0 1.09
5.8 1.12 6.8 1.12 8.0 1.12 10.8 1.12 13.9 1.12 16.0 1.12
4.5 1.10 5.4 1.10 6.3 1.10 8.5 1.10 10.9 1.10 12.5 1.10
4.9 1.12 5.7 1.12 6.7 1.12 9.1 1.12 11.6 1.12 13.4 1.12
5.0 1.14 5.9 1.14 6.9 1.14 9.4 1.14 12.1 1.14 13.9 1.14
5.1 1.15 6.0 1.15 7.0 1.15 9.5 1.15 12.2 1.15 14.1 1.15
5.2 1.16 6.1 1.16 7.2 1.16 9.7 1.16 12.5 1.16 14.4 1.16
5.6 1.20 6.6 1.20 7.7 1.20 10.4 1.20 13.3 1.20 15.3 1.20
4.5 1.11 5.3 1.11 6.2 1.11 8.4 1.11 10.8 1.11 12.4 1.11
4.8 1.14 5.7 1.14 6.6 1.14 9.0 1.14 11.5 1.14 13.3 1.14
5.0 1.15 5.9 1.15 6.9 1.15 9.3 1.15 11.9 1.15 13.7 1.15
5.0 1.16 6.0 1.16 7.0 1.16 9.4 1.16 12.1 1.16 13.9 1.16
5.1 1.17 6.1 1.17 7.1 1.17 9.6 1.17 12.3 1.17 14.2 1.17
5.5 1.21 6.5 1.21 7.6 1.21 10.3 1.21 13.2 1.21 15.2 1.21
5.9 1.16
6.4 1.19
6.6 1.21
6.7 1.22
6.8 1.23
7.3 1.28
5.8 1.19
6.2 1.22
6.4 1.24
6.5 1.25
6.7 1.26
7.2 1.31
13 18 18 25 34 34
0.10 0.10 0.11 0.09 0.09 0.07
0.72 0.77 0.71 0.73 0.75 0.71
50Hz
Notes : 1. T.C. : Total capacity (kW) ... (kcal/h) = (kW) 860, (Btu/h) = 4 (kW) 860
2. (°F) = 32 + 9 / 5 (°C)
3.
C.F. (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
Guaranteed operating range (cooling){Upper limit···Indoor : D.B. 35°C (95°F) , W.B. 22.5°C (72.5°F) , Outdoor : D.B.46°C (115°F)
Lower limit···Indoor : D.B. 21°C (70°F) , W.B. 15.5°C (60°F) , Outdoor : D.B. 21°C (70°F)
wPU-3VAKD : D.B. 52°C (125.5°F)
11
Cooling capacity (Outdoor unit : PU-AKR type)
Evaporator air flow (m3/min) Bypass factors S.H.F. at rating conditions
C.F.
(T.I.)
Model
Temperature
PC-3GAKD
Indoor W.B.
Outdoor D.B.
T.C. C.F.
(T.I.)
PC-4GAKD
T.C.
21°C
(69.8°F)
25°C
(77°F)
30°C
(86°F)
32.2°C (90°F)
35°C
(95°F)
40°C
(104°F)
40.6°C
(105°F)
45°C
(113°F)
46°C
(115°F)
50°C
(69.8°F)
52°C
(125.5°F)
(60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F) (60.8°F) (64.4°F) (66.2°F)
(67°F)
(68°F) (71.6°F)
16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C 16°C 18°C 19°C
19.4° 20°C 22°C 16°C 18°C 19°C
19.4°C 20°C 22°C
18 25
0.08 0.09
0.72 0.75
7.7 0.81 9.6 0.81
8.2 0.82 10.2 0.82
8.5 0.83 10.5 0.83
8.6 0.83 10.7 0.83
8.7 0.84 10.8 0.84
9.3 0.86 11.5 0.86
7.6 0.84 9.4 0.84
8.1 0.85 10.0 0.85
8.3 0.86 10.3 0.86
8.4 0.86 10.4 0.86
8.6 0.87 10.6 0.87
9.1 0.89 11.3 0.89
7.3 0.90 9.0 0.90
7.8 0.92 9.6 0.92
8.0 0.93 9.9 0.93
8.1 0.93 10.1 0.93
8.3 0.94 10.3 0.94
8.8 0.96 10.9 0.96
7.2 0.93 8.9 0.93
7.6 0.95 9.5 0.95
7.9 0.96 9.8 0.96
8.0 0.97 9.9 0.97
8.1 0.97 10.1 0.97
8.7 0.99 10.7 0.99
7.0 0.96 8.7 0.96
7.5 0.99 9.2 0.99
7.7 1.00 9.6 1.00
7.8 1.00 9.7 1.00
7.9 1.01 9.9 1.01
8.5 1.04 10.5 1.04
6.7 1.03 8.3 1.03
7.1 1.06 8.8 1.06
7.4 1.07 9.1 1.07
7.5 1.08 9.3 1.08
7.6 1.08 9.4 1.08
8.1 1.11 10.1 1.11
6.6 1.04 8.2 1.04
7.1 1.06 8.8 1.06
7.3 1.08 9.1 1.08
7.4 1.08 9.2 1.08
7.6 1.09 9.4 1.09
8.1 1.12 10.0 1.12
6.3 1.10 7.9 1.10
6.8 1.12 8.4 1.12
7.0 1.14 8.7 1.14
7.1 1.15 8.8 1.15
7.3 1.16 9.0 1.16
7.8 1.20 9.6 1.20
6.3 1.11 7.8 1.11
6.7 1.14 8.3 1.14
7.0 1.15 8.6 1.15
7.1 1.16 8.8 1.16
7.2 1.17 8.9 1.17
7.7 1.21 9.6 1.21
50Hz
Notes : 1. T.C. : Total capacity (kW) ... (kcal/h) = (kW) 860, (Btu/h) = 4 (kW) 860
C.F. (T.I.) : Correction factors of Total input (Indoor unit input + Outdoor unit input)
2. (°F) = 32 + 9 / 5 (°C)
3.
Guaranteed operating range (cooling){Upper limit···Indoor : D.B. 35°C (95°F) , W.B. 22.5°C (72.5°F) , Outdoor : D.B.46°C (115°F)
Lower limit···Indoor : D.B. 21°C (70°F) , W.B. 15.5°C (60°F) , Outdoor : D.B. 21°C (70°F)
12
Cooling Capacity Correction Factors (Outdoor unit:PU-J type)
Model
PC-2GAKD PC-2.5GAKD PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft)
1.0
1.0
1.0
1.0
1.0
1.0
0.985
0.983
0.978
0.978
0.978
0.970
0.975
0.972
0.962
0.974
0.962
0.950
50Hz
Refrigerant piping length (one way)
0.964
0.961
0.948
0.964
0.948
0.931
0.954
0.951
0.934
0.954
0.934
0.912
0.944
0.940
0.921
0.944
0.921
0.896
35m(115ft)
— — —
0.935
0.908
0.880
40m(131ft)
— — —
0.926
0.896
0.864
45m(148ft)
— — — —
0.884
0.850
50m(164ft)
— — — —
0.875
0.840
Cooling Capacity Correction Factors
Model
PC-2GAKD PC-2.5GAKD PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft) 35m(115ft) 40m(131ft)
1.0 0.985 0.975 0.964 0.954 0.944
1.0 0.978 0.963 0.948 0.934 0.921
1.0 0.971 0.950 0.931 0.913 0.896
1.0 0.980 0.966 0.952 0.939 0.826 0.914 0.902
1.0
1.0
0.971
0.960
0.950
0.933
Cooling Capacity Correction Factors (Outdoor unit:PU-AKD type)
Model
PC-2GAKD PC-2.5GAKD PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft)
1.0
1.0
1.0
1.0
1.0
1.0
0.985
0.983
0.978
0.984
0.978
0.970
0.975
0.972
0.962
0.974
0.962
0.950
60Hz
Refrigerant piping length (one way)
0.931
0.908
0.913
0.885
0.896
0.864
50Hz
Refrigerant piping length (one way)
0.964
0.961
0.948
0.964
0.948
0.931
0.954
0.951
0.934
0.954
0.934
0.912
0.944
0.940
0.921
0.944
0.921
0.896
0.880
0.845
35m(115ft)
— — —
0.935
0.908
0.880
0.864
0.828
40m(131ft)
— — —
0.926
0.896
0.864
45m(148ft) 50m(164ft)
— — — ——
0.850 0.840
0.812 0.800
45m(148ft)
— — — —
0.884
0.850
— — —
50m(164ft)
— — — —
0.875
0.840
Cooling Capacity Correction Factors (Outdoor unit:PU-AKR type)
Model
PC-3GAKD PC-4GAKD
5m(16ft) 10m(33ft) 15m(49ft) 20m(66ft) 25m(82ft) 30m(98ft)
1.0
1.0
0.978
0.984
0.962
0.974
50Hz
Refrigerant piping length (one way)
0.948
0.964
0.934
0.954
0.921
0.944
13
35m(115ft)
0.935
40m(131ft)
0.926
45m(148ft)
— —
50m(164ft)
— —
3-2. STANDARD OPERATION DATA
Capacity Input Indoor unit Model Phase, Hz Voltage Current
Outdoor unit Model
Phase, Hz Voltage Current Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V A
V A
°C °C °C
m
°C °C °C °C °C
D.B.
W.B.
D.B. D.B.
W.B.
Models
Electrical circuit TotalRefrigerant circuit
Indoor side
Outdoor
side
MODE
PC-4GAKD PC-5GAKD PC-6GAKD
PC-4GAKD PC-5GAKD PC-6GAKDPC-3AKD
PC-2.5GAKD
PC-2GAKD
9,300
5.17
1, 60
220
0.95
PU-
4TJSA
3, 60
220
14.0
2.40
(24.4)
0.51 (5.2)
88.4
54.5
6.0 5
29 19
11.7 46 24
13,300
4.76
1, 50
220
0.96
PU-
5YJSA
3, 50
380
8.15
1.83
(18.7)
0.46 (4.7)
72.9
48.8
3.1 5
27 19
12.8 35 24
11,600
6.94
1, 60
220
1.20
PU-
5TJSA
3, 60
220
19.61
2.41
(24.6)
0.43
(4.4)
94.8
60.1
1.7 5
29 19
14.9 46 24
14,600
5.31
1, 50
220
0.96
PU-
6YJSA
3, 50
380
8.63
1.96
(20.0)
0.41
(4.2)
75.4
51.1
2.3 5
27 19
11.4 35 24
13,400
7.54
1, 60
220
1.20
PU-
6TJSA
3, 60
220
21.45
2.41
(24.6)
0.42 (4.3)
94.8
60.3
1.6 5
29 19
12.6 46 24
10,300
3.43
1, 50
220
0.68
PU-
4YJSA
3, 50
380
5.7
1.80
(18.3)
0.51
(5.2)
67.5
48.3
7.3 5
27 19
10.5 35 24
6,500
4.25
1, 60
220
0.70
PU-
3NJA
1, 60
220
20.9
2.54
(25.9)
0.44
(4.5)
82.0
61.6
3.6 5
29 19
12.8 46 24
PC-3GAKD
7,600
3.30
1, 50
220
0.51
PU-
3VJC
1, 50
220
15.1
1.96
(20.0)
0.44 (4.5)
87.9
52.3
3.7 5
27 19
12.2 35 24
6,200
3.60
1, 60
220
0.70
PU-
2.5NJA
1, 60
220
15.8
2.68
(27.3)
0.52 (5.3)
94.3
57.6
10.2 5
29 19
15.3
46 24
PC-2.5GAKD
6,500
2.58
1, 50
220
0.51
PU-
2.5VJA
1, 50
220
11.4
1.96
(20.0)
0.5
(5.1)
72.3
52.4
8.6 5
27 19
12.0 35 24
4,300
3.12
1, 60
220
0.61
PU-
2NJA
1, 60
220
13.6
2.49
(25.4)
0.53 (5.4)
77.7
60.5
8.3 5
29 19
13.8 46 24
PC-2GAKD
5,600
2.54
1, 50
220
0.38
PU-
2VJA
1, 50
220
11.3
1.93
(19.7)
0.44
(4.5)
68.6
51.6
3.3 5
27 19
9.7
35 24
MPa
(kgf/F)
MPa
(kgf/F)
Cooling
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International Organization for Standardization).
The conversion factor is : 1(MPa)=10.2(kgf / FF)
14
Airflow Air speed
Coverage range
Airflow Air speed
Coverage range
m3/min
m/sec.
m
ft
m
3
/min
m/sec.
m
ft
Configuration
50Hz
Frequency
60Hz
Model
PC-4GAKD
25
4.1
12.6
41.6 25
4.1
12.6
41.6
PC-5GAKD
34
4.38
15.2
50.0 34
4.38
15.2
50.0
PC-6GAKD
34
4.38
15.2
50.0 34
4.38
15.2
50.0
PC-3GAKD
18
3.8
10.4
34.5 18
3.8
10.4
34.5
PC-2.5GAKD
18
3.8
10.4
34.5 18
3.8
10.4
34.5
Ceiling suspended
PC-2GAKD
13
3.7
8.8 29 13
3.7
8.8 29
The unit of pressure has been changed to MPa based on SI(International System of unit) in accordance with I.S.O.(International
Capacity Input Indoor unit Model Phase, Hz Voltage Current
Outdoor unit Model
Phase, Hz Voltage Current Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
W
kW
V A
V A
°C °C °C
m
°C °C °C °C °C
D.B. W.B. D.B. D.B. W.B.
Model
Electrical circuit TotalRefrigerant circuit
Indoor side
Outdoor
side
MODE
MPa
(kgf/F)
MPa
(kgf/F)
PC-2GAKD
PC-2.5GAKD
PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
Cooing
5500 6500 7600 10300 13200 15200
1.91 2.33 3.31 3.61 / 3.54 4.27 5.26
PC-2GAKD PC-2.5GAKD PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
1, 50 1, 50 1, 50 1, 50 1, 50 1, 50
220 220 220 220 220 220
0.38 0.51 0.51 0.68 0.96 0.96
PU-2VAKD PU-2.5VAKD PU-3VAKD
PU-4VAKD/
PU-4YAKD
PU-5YAKD PU-6YAKD
1, 50 1, 50 1, 50 1 / 3 , 50 3, 50 3, 50
220 220 220 220 / 380 380 380
8.4 10.3 15.1 17.5 / 5.9 7.2 9.0
1.90
(19.4)
2.07
(21.1)
2.13
(21.8)
1.96
(20.0)
1.90
(19.4)
2.06
(21.0)
0.49
(5.0)
0.53
(5.4)
0.47 (4.8)
0.51 (5.2)
0.44 (4.5)
0.41 (4.2)
78.5 80 83.7 77.1 76 81.6
47.7 54.4 55.5 51.2 47.5 52.8
3.7 6.9 3.2 6.9 3.5 2 555555
27 27 27 27 27 27 19 19 19 19 19 19
12.4 13.5 12.4 12.5 13.0 11.6 35 35 35 35 35 35 24 24 24
7700
3.05
PC-3GAKD
1, 50
230
0.53
PU-3VAKR
1, 50
230
12.6
1.64
(16.7)
0.43
(4.4)
79.8
44.7
1.8
7.5 27 19
12.1 35 24 24
9550
3.82
PC-4GAKD
1, 50
230
0.69
PU-4VAKR
1, 50
230
16.6
1.92
(19.6)
0.51 (5.2)
75.8
48.2
6.4
7.5 27 19
13.1 35 24 24 24
Organization for Standardization).
The conversion factor is : 1(MPa)=10.2(kgf / FF)
3-3 . OUTLET AIR SPEED AND COVERAGE RANGE
w The air coverage range is the distance to which the 0.25 m/sec. air can reach when air is blown out horizontally from the unit
at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the fur­niture inside the room.
15
4
180
210
157
15
85
182 (3/8) liquid 201 (5/8) gas 241 (Drainage)
Air intake
918
254
680
Electrical box
226
70
525
928
352
263
171
138
86
46
175 1
131
38
38 79
161
32
179
42
6-7
Celling
Electrical box
When electrical box is pulled down
3
2
8
5
1
4
6
2
1
17
150
140
70
320
80
933 (suspension bolt pitch)
983
1000
Air outlet
81
904
76
Gap to ceiling
OUTLINES AND DIMENSIONS
4-1. INDOOR UNIT PC-2GAKD
1 Drainage pipe connection (Unit side: 26mm I.D.) 5 2 Drainage pipe connection (for the left arrangement) 6 Knockout hole for upper pipe arrangement 3 Knockout hole for left drain-piping arrangement 7 Knockout hole for left drain pipe arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knockout hole for wiring arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When installing the drain-up machine (option parts), please be sure that refrigerant pipe will be only upper pipe arrangement.
Refrigerant-pipe connection (liquid pipe side/flared connection)
[FRONT VIEW]
Unit : mm(inch)
16
PC-2.5GAKD
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
1290
1214
210
180
81 76
1310
Air outlet
1228
680
254
Air intake
85
182 201 241
15
157
(3/8 liquid) (5/8 gas) (Drainage)
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
Celling
32
179
161
38
38 79
42
6~7
525
1235
416
263
171
138
86
131
175 1
46
1
2
Electrical box
70
226
Gap to ceiling
PC-3GAKD
1 Drainage pipe connection (Unit side : 26mm I.D.) 5 2 Drainage pipe connection (for the left arrangement) 6 Knockout hole for upper pipe arrangement 3 Knockout hole for left drain-piping arrangement 7 Knockout hole for left drain pipe arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knockout hole for wiring arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When installing the drain-up machine (option parts), please be sure that refrigerant pipe will be only upper pipe arrangement.
Refrigerant-pipe connection (liquid pipe side/flared connection)
[FRONT VIEW]
Unit : mm(inch)
17
1228
680
254
Air intake
1214
270
207
81 96
1310
Air outlet
1240 (suspension bolt pitch)
140
150
320 80
17
70
6
87
182 198 245
16
217
(3/8 liquid) (3/4 gas) (Drainage)
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
Celling
93
160
38
38 140
42 239
6~7
525
1235
687
263
171
138
86
192
236
1
45
1
2
Electrical box
70
229
Gap to ceiling
PC-4GAKD
1 Drainage pipe connection (Unit side : 26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 6 Knockout hole for upper pipe arrangement 3 Knockout hole for left drain-piping arrangement 7 Knockout hole for left drain pipe arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knockout hole for wiring arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When installing the drain-up machine (option parts), please be sure that refrigerant pipe will be only upper pipe arrangement.
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
[FRONT VIEW]
Unit : mm(inch)
18
PC-5GAKD
1535
680
254
Air intake
1524
270
207
81 96
1620
Air outlet
1547(suspension bolt pitch)
140
150
320 80
18
70
6
87
182 198 245
16
217
(3/8 liquid) (3/4 gas) (Drainage)
3
2
8
5
1
4
Electrical box
When electrical box is pulled down
Celling
93
160
38
38 140
42 239
6~7
525
1545
687
263
171
138
86
192
236
1
45
1
2
Electrical box
70
229
Gap to ceiling
PC-6GAKD
1 Drainage pipe connection (Unit side : 26mm I.D.) 2 Drainage pipe connection (for the left arrangement) 6 Knockout hole for upper pipe arrangement 3 Knockout hole for left drain-piping arrangement 7 Knockout hole for left pipe arrangement 4 Refrigerant-pipe connection (gas pipe side/flared connection) 8 Knockout hole for wiring arrangement
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When installing the drain-up machine (option parts), please be sure that refrigerant pipe will be only upper pipe arrangement.
5 Refrigerant-pipe connection (liquid pipe side/flared connection)
[FRONT VIEW]
Unit : mm(inch)
19
4-2. REMOTE CONTROLLER
130
120
19
43.5
Unit : mm(inch)
20
5
Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual
SW6
SWE
ON OFF
ON OFF
1 2
SW2 SW5SW1
Refer to tables 1, 2, 3 .
WHT
(
D.SENSOR
)
CN31
WHT
(
D.SENSOR
)
CN31
DS
WHT
(
WIRELESS
)
CN90
1 2 1 23
RED
(INTAKE)
CN20
1 2
WHT (PIPE) CN21
BLU
(
REMOCON
)
CN22
BLK
(
INDOOR/OUTDOOR
COMUNICATION
)
CN30
1 2 1 2
TH1 TH2
6
R.B
CN41 CN2L
CN51 CN32
W.B (OPTION)
CNB
RECEIVER
RU
LED1
LED1
LED2
LED2 SW2 SW1
X4 X1
I.B
P.B
CNSK (RED)
DC13.1V
CN2S (WHT)
TO OUTDOOR UNIT
POWER SUPPLY ~(1 PHASE) 220-240V 50Hz 220V 60Hz
TB4
TB2
1 2 3
L N
GRN/YLW
Table 2
SW2
1 2 3 4 5
ON OFF
MODELS
PC-2GAKD
1 2 3 4 5
ON OFF
PC-2.5GAKD
1 2 3 4 5
ON OFF
MODELS
1 2 3 4 5
ON OFF
1 2 3 4 5
ON OFF
PC-3GAKD
PC-4GAKD
PC-5GAKD
PC-6GAKD
1 2 3 4 5
ON OFF
ZNR
WHT
(FAN)
FAN
RED
(PUMP)
CN27
GRN
(VANE)
CN6V
BLU
(D.U.M)
CNP
X1
FUSE
RED
(D.HEATER)
CNC
(OPTION)
ORN
(POWER)
CND
RED
(POWER
BOARD)
CNDK
WHT
(POWER
BOARD)
CN2D
1 3 1 3 1 3 1 3 1 3
1 2
1 2
3
1 2
5
1 3 5
BLK
WHT WHT
RED
RED
YLW
ORN
BLU
BLU
RED
BLK WHT
WHT
BLU
MF
MV
DP
BCR
X4
9
1 2 3
1 2 3
2
1
TB5
TRANSMISSION WIRES DC12V
TB6
12
BZ
w
When installing optional
drain-up machine, disconnect the CN31 jumper connector and replace it with the drain sensor (DS).
When installing drain-up machine (Optional part)
SW1
Table 1
1 2 3 4 5
ON OFF
SW5
Table 3
1 2 3 4 5 6 7 8
ON OFF
SW2
[Servicing] Fasten terminal of the terminal board "TB4" that equips lock system. To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward.
Check code
Symptom
Fb
Abnormality of indoor controller board
FFFF
No corresponding unit
No trouble generated in the past
P4
Abnormality of drain sensor(DS)
P5
Malfunction of drain-up machine
P6
Freezing / overheating protection is working.
P8
Abnormality in outdoor unit Refer to outdoor unit wiring diagram.
P2
Abnormality of pipe temperature thermistor / Liquid(TH2)
P1
Abnormality of room temperature thermistor(TH1)
E0–E5
Abnormality of the signal transmission between remote controller and indoor unit
P.B
INDOOR POWER BOARD
SYMBOL NAME
[LEGEND]
I.B
INDOOR CONTROLLER BOARD FUSE FUSE (T6.3AL250V) ZNR VARISTOR CN2L CONNECTOR<LOSSNAY> CN32 CONNECTOR<REMOTE SWITCH> CN41 CONNECTOR<HA TERMINAL-A> CN51 CONNECTOR<CENTRALLY CONTROL> SW1 SWITCH <MODEL SELECTION>wSee Table 1. SW2 SWITCH <CAPACITY CODE>wSee Table 2.
SW6 SWE
SWITCH<EMERGENCY OPERATION>
SW5 SWITCH<SYSTEM SELECTION>wSee Table 3.
X4 RELAY<FAN MOTOR>
X1 RELAY<DRAIN PUMP> BCR
POWER SUPPLY<R.B>
CONNECTOR<EMERGENCY OPERATION>
LED1 POWER SUPPLY<I.B> LED2
FAN CONTROL ELEMENT
C CAPACITOR<FAN MOTOR>
FAN MOTOR VANE MOTOR
MF MV
DRAIN-UP MACHINE (OPTIONAL)
DP
DRAIN SENSOR(OPTIONAL)
DS
SYMBOL NAME
TB4
TERMINAL BLOCK<INDOOR/OUTDOOR
TB2
TERMINAL BLOCK (POWER SUPPLY) CONNECTING LINE>
TERMINAL BLOCK<REMOTE CONTROLLER TRANSMISSION LINE >
TERMINAL BLOCK<REMOTE CONTROLLER
TRANSMISSION LINE > ROOM TEMP.THERMISTOR <0:/15k", 25:/5.4k" DETECT> PIPE TEMP.THERMISTOR/LIQUID <0:/15k", 25:/5.4k" DETECT>
TB5 TH1 TH2
W.B
R.B
WIRELESS REMOTE CONTROLLER BOARD<OPTION>
RECEIVING UNIT
BUZZER
LED<RUN INDICATOR >
LED<HOT ADJUST>
SWITCH<HEATING ON/OFF>
SWITCH<COOLING ON/OFF>
WIRED REMOTE CONTROLLER BOARD
RU BZ LED1 LED2 SW1 SW2
TB6
NAMESYMBOL
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (1, 2, 3) for correct wirings.
3. SymboIs used in wiring diagram above are, : Connector, : Terminal (block).
[Self-diagnosis]
1. For details on how to operate self-diagnosis with the wireless
remote control, refer to the technical manuals etc.
2. For the wired remote control : When you quickly press twice the
CHECK switch on the remote control, the unit begins self-diagnosis, and Check Codes generated in the past appear on the display. For Check Codes and Symptoms refer to the table.
[Emergency operation procedure]
1.When the indoor unit microcomputer has failed, but all other components work properly, if you set the switch(SWE,SW6) on the indoor control board, the indoor unit will begin Emergency Operation.
2.When you activate emergency operation of the cooling, you have to set the switch(SWE) and switch(SW6) on indoor controller.
SWE:ON ·Indoor fan is running at high speed.
·Drain-up machine(optional) is working.
SW6-1:ON ·Emergency operation of cooling mode
3.Before you activate emergency operation, check the following points: (1) Emergency operation cannot be activated when:
· The outdoor unit malfunctions. · The indoor fan malfunctions. (2) Emergency operation becomes continuous only by switching the power source on / off. ON / OFF on the remote control or temperature control etc. does not function. (3) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (4) After emergency operation has been deactivated, set the switches etc. to their original positions. (5) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the appropriate position.
––––
WIRING DIAGRAM
PC-2GAKD PC-2.5GAKD PC-3GAKD PC-4GAKD PC-5GAKD PC-6GAKD
21
REFRIGERANT SYSTEM DIAGRAM6
INDOOR UNIT OUTDOOR UNIT
Refrigerant flow
Outdoor heat exchanger
Ball valve (with service port)
Flared connection
Flexible tube
Compressor
Capillary tube size
Capillary tube
Capillary tube for injection
Flared connection
Low pressure switch
High pressure switch
Thermal switch (Only PU-4VLJSA)
Refrigerant pipe
15.88 (5/8)
(With insulator) option
Refrigerant pipe
9.52 (3/8)
Strainer
PC-2.5/3GAKD
PC-4GAKD
Refrigerant pipe
19.05 (3/4)
Ball valve
Check plug
Charge plug
Accumulator
Only PU-2.5 PU-3NJA PU-4YJSA, 4TJSA
PU-2.5 (O.D.3.2 o I.D.1.6 –R760) o 2pcs PU-3NJA (O.D.3.2 o I.D.1.8 –R800) o 2pcs PU-4YJSA, 4VLJSA, 4TJSA PU-3VAKR, PU-4VAKR
}
w
w
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
(O.D.3.2 o I.D.2.0 –R840) o 2pcs
Refrigerant flow
INDOOR UNIT
OUTDOOR UNIT
Outdoor heat exchanger
(With insulator) option
Ball valve (with service port)
Flared connection
Flexible tube
Compressor
Capillary tube for injection
Flared connection
Low pressure switch
High pressure switch
Refrigerant pipe
15.88 (5/8)
(With insulator) option
Refrigerant pipe
9.52 (3/8)
Strainer
Ball valve
Check plug
Charge plug
Accumulator
O.D.4 I.D.2 –R430
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
PC-2GAKD / PU-2NJA.TH, PU-2VJA
1.TH Unit : mm(inch)
PC-2.5GAKD, PC-3GAKD, PC-4GAKD / PU-2.5NJA.TH, PU-2.5VJA1.TH, PU-3NJA.TH, PU-3VAKR.TH PU-4TJSA.TH, PU-4YJSA1.TH, PU-4VLJSA2.TH , PU-4VAKR.TH
22
PC-2GAKD / PU-2VAKD.TH Unit : mm(inch)
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
Flared connection
Flared connection
Stop valve
Stop valve (with service port)
(#100) Strainer
Capillary tube (
[3.0 o [1.8 o L450
)
Refrigerant flow
Compressor
Refrigerant pipe [15.88(5/8) (Option) (with heat insulator)
Refrigerant pipe (Option) [9.52 (with heat insulator)
INDOOR UNIT OUTDOOR UNIT
Outdoor heat exchanger
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
Flared connection
Flared connection
Stop valve
Stop valve (with service port)
(#100) Strainer
Capillary tube ([3.0 o [2.0 o L700)
Refrigerant flow
Compressor
Accumulator
Refrigerant pipe [15.88(5/8) (Option) (with heat insulator)
Refrigerant pipe (Option) [9.52 (with heat insulator)
INDOOR UNIT
OUTDOOR UNIT
Outdoor heat exchanger
PC-2.5GAKD / PU-2.5VAKD.TH
23
PC-3GAKD / PU-3VJC1.TH, PU-3YJC.TH
Refrigerant flow
Refrigerant flow
INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT OUTDOOR UNIT
PC-3GAKD PU-3VJC
PU-3YJC
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
strainer
Refrigerant pipe [ 9.52(3/8) (with heat insulator) option
Ball valve (with service port)
D.P.R. (Discharge pressure regulator)
Capillary tube
Compressor
Accumulator
(O.D.3.2 oI.D.1.8 o800mm) o2pcs
Ball valve
Low pressure switch
Charge pIug
Check pIug
High pressure switch
Outdoor heat exchanger
strainer
strainer
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [15.88(5/8) (with insulator) option
Indoor heat exchanger
Distributor with strainer
Pipe temperature thermistor TH2
strainer
Refrigerant pipe [ 9.52(3/8) (with heat insulator) option
Flexible tube
Flared connection
Flared connection
Refrigerant pipe [15.88(5/8) (with insulator) option
Charge plug
Ball valve
Accumulator
Compressor
Strainer
Outdoor heat exchanger
Stop valve (With service port)
Capillary tube
( [3.2 o[1.8 -L700)
o 2pcs
Strainer
Discharge pressure regulator
(#50)
(#50)
Unit : mm(inch)
PC-3GAKD / PU-3VAKD.TH
24
PC-4GAKD / PU-4VAKD.TH, PU-4YAKD.TH Unit : mm(inch)
Charge plug
Accumulator
Compressor
Ball valve (With service port)
Outdoor heat exchanger
Check plug
High pressure switch
Refrigerant flow
Capillary tube (
[3.2o[2.0-L840)
o2pcs
Strainer #50
Strainer
#50
Strainer #50
INDOOR UNIT OUTDOOR UNIT
Refrigerant pipe [15.88(5/8) (with insulator) option
Indoor heat exchanger
Distributor with strainer
Pipe temperature thermistor TH2
strainer
Refrigerant pipe [ 9.52(3/8) (with heat insulator) option
Flexible tube
Flared connection
Flared connection
Refrigerant flow
Thermal switch
INDOOR UNIT OUTDOOR UNIT
Flared connection
Flexible tube
Compressor
Flared connection
High pressure switch
(With insulator) option
Refrigerant pipe
9.52 (3/8)
(With insulator) option
Refrigerant pipe
19.05 (3/4)
Ball valve
Check plug
Outdoor heat exchanger
Charge plug
Accumulator
Indoor heat exchanger
Distributor with strainer
Indoor coil thermistor TH2
Capillary tube PU-5YJSA (O.D. 4.0 oI.D. 2.4 –R400) PU-6YJSA (O.D. 4.0 oI.D. 2.4 –R200)
Capillary tube PU-5YJSA (O.D. 4.0 oI.D. 2.4 –R840)o2pcs PU-6YJSA (O.D. 4.0 oI.D. 2.4 –R1200)o2pcs
Strainer
Ball valve (with service port)
DPR
PC-5GAKD / PU-5YJSA1.TH PC-6GAKD / PU-6YJSA1.TH
25
Loading...
+ 57 hidden pages