CITY MULTI R410A SERIES HOT WATER SUPPLY, AIR TO
WATER, and FLOW TEMP. CONTROLLER Remote Controller
PAR-W21MAA
Installation Manual
This instruction manual describes how to install the Remote Controller for CITY MULTI R410A SERIES HOT WATER SUPPLY, AIR TO WATER, and
FLOW TEMP. CONTROLLER. Please read this manual thoroughly and install the remote controller accordingly. For information on how to wire and
install CITY MULTI R410A SERIES HOT WATER SUPPLY, AIR TO WATER, and FLOW TEMP. CONTROLLER Remote Controller, refer to the
installation manual. After the installation, hand over this manual to users.
1 Safety Precautions
● Read these Safety Precautions and perform installation work accordingly.
● The following two symbols are used to dangers that may be caused by incorrect use and their degree:
WARNING
CAUTION
● After reading this installation manual, give it and units installation manual to the end user.
● The end user should keep this manual and units installation manual in a place where he or she can see it at anytime. When someone moves or
repairs the PAR-W21MAA, make sure that this manual is forwarded to the end user.
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an electric
shock or fire.
Install in a place which is strong enough to withstand the weight of the
PAR-W21MAA.
Any lack of strength may cause the PAR-W21MAA to fall down, resulting in
personal injury.
Firmly connect the wiring using the specified cables. Carefully check
that the cables do not exert any force on the terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair the PAR-W21MAA by yourself.
Any deficiency caused by your modification or repair may result in an
electric shock or fire.
Consult with your dealer about repairs.
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of PAR-W21MAA may
cause an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and sulfuric
gas may deteriorate the performance significantly or give damage to the
component parts.
When installing the remote controller in a hospital or communication
facility, take ample countermeasures against noise.
Inverters, emergency power supply generators, high-frequency medical
equipment, and wireless communication equipment can cause the remote
controller to malfunction or to fail. Radiation from the remote controller may
effect communication equipment and prevent medial operations on the
human body or interfere with image transmission and cause noise.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Completely seal the wire lead-in port with putty etc.
Any dew, moisture, insects entering the unit may cause an electric shock or
a malfunction.
Do not install in any place at a temperature of more than 40°C [104°F]
or less than 0°C [32°F] or exposed to direct sunlight.
Doing so may cause deformation or malfunction.
2 Confirming the Supplied Parts
Confirm that the box includes the following parts, in addition to this installation manual:
1. Remote controller (cover, body) ................................................................................ 1
2. Cross recessed pan head screw (M4 × 30) ............................................................... 2
3. Wood screw (4.1 × 16, used for directly hooking to the wall) .................................... 2
4. Caution label (in 16 languages) ................................................................................. 1
Use the cable specified in the Installation Manual that comes with the units for remote controllers.
This symbol denotes what could lead to serious injury or death if you misuse the PAR-W21MAA.
This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAR-W21MAA.
WARNING
Ensure that installation work is done correctly following this
installation manual.
Any deficiency caused by installation may result in an electric shock or fire.
All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation may
result in an electric shock or fire.
Do not move and re-install the PAR-W21MAA yourself.
Any deficiency caused by installation may result in an electric shock or fire.
Ask your distributor or special vendor for moving and installation.
To dispose of this product, consult your dealer.
CAUTION
Do not apply AC100V or AC200V to the remote controller. The
maximum voltage that can be applied to the remote controller is 12V.
The remote controller may be damaged or may generate heat and cause a
fire.
Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew. Doing so may
cause an electric shock or a malfunction.
Do not install in any place where acidic or alkaline solution or special
spray are often used.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not touch any control button with your wet hands.
Doing so may cause an electric shock or a malfunction.
Do not wash with water.
Doing so may cause an electric shock or a malfunction.
Do not press any control button using a sharp object.
Doing so may cause an electric shock or a malfunction.
Remote controller cover
Remote controller body
1
CAUTION Do not tighten the screws too tight. Doing so may deform or crack the lower cover.
NOTE: - Choose a flat plane for installation.
- Fasten the switch box at more than two places when installing directly on the wall.
- When reinstalling on the wall, fasten securely using anchors.
5. Connect the remote control cord to the remote controller terminal block.
To the remote controller
CAUTION
terminal block on the unit
There is no polarity.
AB
Do not use crimp terminals to connect to remote controller terminal blocks. The terminals may contact the board and cause
trouble or contact the cover and damage the cover.
To connect the remote
control cord, peel 6mm
1
[
/4 in] of coating.
CAUTION Prevent remote cord chips from getting into the remote controller. Electric shock or malfunction may result.
6. Wiring hole for installing directly on the wall (or open wiring)
• Cut off the shaded area from the upper cover using a knife, nippers, etc.
• Take out the remote control cord connected to the terminal block via this portion.
7. Install the cover to the remote controller.
To remove the cover, insert a minus
screwdriver into one of the open
slots, and move it in the direction of
the arrow shown in the figure.
First, hook the cover to the two upper claws and then fit it to the remote controller.
CAUTION
Press the cover until it snaps shut. If not, it may fall off.
CAUTION
Do not turn into the screwdriver in the slot. Doing so may damage the slot.
NOTE: A protection sheet is stuck to the operation section. Peel off this protection sheet before use.
4 Test Run
This setting cannot be made with FLOW TEMP. CONTROLLER.
1. Before making a test run, refer to the “Test Run” section of the unit
installation manual.
2. Press the [TEST] button twice successively within three seconds.
Test run starts.
3. Stop the test run by pressing the [ ON/OFF] button.
4. If trouble occurred during the test run, refer to the “Test Run” section
of the unit installation manual.
TEMP.
MENU
ON/OFF
BACK DAY CHECK TEST
MONITOR/SET
PAR-W21MAA
CLOCK CLEAR
˚C
INITIAL SETTING
ON/OFF
CIR.WATER
Operation mode display
“TEST RUN” and “OPERATION MODE” are
displayed alternately.
Timer stops test run after two hours.
Water Temperature
Stop test run by pressing the [ ON/OFF] button.
During test run, the RUN lamp remains on.
[TEST] button
5 Function Selection
(1) Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting
when needed.
Item 1 Item 2 Item 3 (Setting content)
1. Change Language
(“CHANGE
LANGUAGE”)
2. Function limit
(“FUNCTION
SELECTION”)
3. Mode selection
(“MODE
SELECTION”)
4. Display change
(“DISP MODE
SETTING”)
Language setting to display • Display in multiple languages is possible.
(1) Operation function limit setting (operation lock)
• Setting the range of operation limit (operation lock)
(“LOCKING FUNCTION”)
(2) Operation mode skip setting (“SELECT MODE”) • Setting the use or non-use of each operation mode
(3) Temperature range limit setting
• Setting the temperature adjustable range (maximum, minimum)
(“LIMIT TEMP FUNCTION”)
(1) Remote controller main/sub setting
(“CONTROLLER MAIN/SUB”)
• Selecting main or sub remote controller
* When two remote controllers are connected to one group, one
controller must be set to sub.
(2) Use of clock setting (“CLOCK”) • Setting the use or non-use of clock function
(3) Timer function setting (“WEEKLY TIMER”) • Setting the timer type
(4) Contact number setting for error situation (“CALL.”) • Contact number display in case of error
• Setting the telephone number
(5) Temp off set setting
• Setting the use or non-use of setback amount setting
(“TEMP OFF SET FUNCTION”)
(1) Temperature display °C/°F setting
• Setting the temperature unit (°C or °F) to display
(“TEMP MODE °C/°F”)
(2) Water temperature display setting
• Setting the use or non-use of the display of water temperature
(“WATER TEMP DISP SELECT”)
3
(3) Timer function setting
• To switch the setting, press the [ ON/OFF] button (Choose one of
the followings.).
1 WEEKLY TIMER (Initial setting value):
The weekly timer can be used.
2 AUTO OFF TIMER : The auto off timer can be used.
3 SIMPLE TIMER : The simple timer can be used.
4 TIMER MODE OFF : The timer mode cannot be used.
* When the use of clock setting is OFF, the “WEEKLY TIMER” cannot be
used.
(4) Contact number setting for error situation
• To switch the setting, press the [ ON/OFF] button.
1 CALL OFF :
The set contact numbers are not displayed in
case of error.
2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
CALL_ : The contact number can be set when the
display is as shown on the left.
• Setting the contact numbers
To set the contact numbers, follow the following procedures.
Move the flashing cursor to set numbers. Press the [ TEMP. ( ) or
( )] button to move the cursor to the right (left). Press the [ CLOCK
( ) or ( )] button to set the numbers.
6 Initial Setting
(1) Water temperature initial setting mode
1 Stop the unit by pressing the [ ON/OFF] I button.
2 To enter the water temperature initial setting, press and hold down the [INITIAL
SETTING ( )] J button for three seconds or longer. (Any of 1. to 8. will be displayed.)
* Wait a while because the water temperature initial setting takes approximately 30
seconds to display after the [INITIAL SETTING ( )] J button is pressed.
* Depending on the model of the unit to connect, the water temperature initial setting may
F
I
J
K
DE
1. Water temperature initial setting
Water Temp Heating
1 Water temperature display
8. Water temperature initial setting
Temp Offset Cooling
0 Offset amount display
7. Water temperature initial setting
Temp Offset Heating
9 Offset amount display
* The available settings differ depending on the model of the unit to connect.
not be possible. In such case, the screen transitions to the unit stop screen after the
display of the error.
3 To select a water temperature initial setting from 1. to 8., press the [Mode (Back)] E
button.
2. Water temperature initial setting
Water Temp Heating ECO No.1
2 Water
temperature
display
6. Water temperature initial setting
Water Temp Cooling
8 Water temperature display
(5) Temp off set setting
• To switch the following settings, press the [ ON/OFF] button.
1 ON : The setback amount setting is displayed under the water
temperature initial setting mode.
7 Self Check
Retrieve the error history of each unit using the remote controller.
2 OFF : The setback amount setting is not displayed under the water
temperature initial setting mode.
[4] -4. Display change setting
(1) Temperature display °C/°F setting
• To switch the setting, press the [ ON/OFF] button.
1 °C: The temperature unit °C is used.
2 °F: The temperature unit °F is used.
(2) Water temperature display setting
• To switch the setting, press the [ ON/OFF] button.
1 ON : The water temperature is displayed.
2 OFF : The water temperature is not displayed.
1 Switch to the self check mode.
When the [CHECK] H button is pressed twice successively within
three seconds, the display shown below appears.
The initial operation mode can be set. Change the setting when needed.
Self check address or self check refrigerant address
3 Self check result display <Error history> (For the contents of the error code, refer to the units installation manual or service handbook.)
3. Water temperature initial setting
Water Temp Heating ECO No.2
4 Error history reset
The error history is displayed in 3 Self check results display.
3 Outside air
temperature
display
Outside air
temperature
setting of Heati ng
ECO No.2 must be
higher than that of
() ()
Heating ECO No.1.
4 Water
temperature
display
5 Outside air
temperature
display
Outside air
temperature
setting of Heating
ECO No.2 must be
higher than that of
Heating ECO No.1.
When the [ ON/OFF] D button is pressed twice successively
within three seconds, the self check address or refrigerant address
flashes.
4. Water temperature initial setting
Water Temp Hot Water
5 Self check reset
There are the following two ways of resetting self check.
Press the [CHECK] H button twice successively within three seconds → Resets self check and returns to the state before self check.
6 Water temperature display
Press the [ ON/OFF] I button → Self check resets and units stop.
5. Water temperature initial setting
Water Temp Anti-freeze
7 Water temperature display
5
ERROR CODE
TEMP.
MENU
ON/OFF
BACK DAY CHECK TEST
MONITOR/SET
PAR-W21MAA
CLOCK CLEAR
INITIAL SETTING
ON/OFF
CIR.WATER
2 Set the address or refrigerant address No. you want to self check.
When the [ TEMP. ( ) or ( )] F buttons are pressed, the
address decreases and increases between 001 and 127 or 00 and
15. Set it to the address No. or refrigerant address No. you want to
self check.
Approximately three seconds after the change operation, the self
check refrigerant address changes from flashing to a steady light and
self check begins.
ERROR CODEERROR CODE
Address 3 digits or unit address No. 2 digits Error code 4 digits or error code 2 digits
<When there is no error history> <When opposite side does not exist>
ERROR CODE ERROR CODE
ERROR CODE
When the error history was reset, the display shown below appears.
When error history reset failed, the error contents are displayed
again.
ERROR CODE
(When operation is prohibited, this operation is ineffective.)
7
3 How To Install
1. Choose a place in which to install the remote controller (switch box).
Be sure to observe the following steps:
(1) When installing on either the switch box or the wall, allow extra space around the remote controller as
shown in the figure at the right.
(2) Parts which must be supplied on site.
External size
of remote
controller
• Switch box for two units
]
16
1
]
8
7
5
[2-
73
15 [19/32] or less
]
32
±
]
16
32
1
[4-
[3-
102
83.5±0.4
[1]
25
[1]
25
9
[
]
7
32
13
[
]
10
φ6
13
[
44
32
20
]
16
10
3
[1-
]
4
Switch box two units
13
[
]
32
(Unit: mm [in])
30 [1-3/16] 30 [1-3/16]
120 [4-
• Thin-copper wiring pipe
• Lock nut and bushing
• Surface raceways
]
16
13
[
20
]
16
φ6
13
[
3
3
30[1-
30[1-
]
20
16
13
46[1-
]
16
1
102[4-
]
32
2. Seal the remote controller cord with putty in order to prevent the possible entry of dew, water droplets, cockroaches, other insects, etc.
When using the switch box
• When installing on the switch box, seal the
connections between the switch box and
wiring pipe with putty.
When installing directly on the wall
• When opening a hole using a drill for the remote controller cord (or when taking the cord
out of the back of the remote controller), seal the hole with putty.
• When routing the cord via the portion cut off from the upper cover, similarly seal that
portion with putty.
• When taking the remote controller cord from back of the controller, use surface raceways.
Remote control cord
Seal around here
with putty.
For taking cord
out from back of
remote
controller
For taking cord out of top of
remote controller
Bushing
Wall
Remote control
cord
Wiring pipe
Lock nut
Switch box
Seal around here
with putty.
3. Remove the remote controller cover.
• Insert a minus screwdriver into one of the open slots and move the screwdriver in the arrow direction.
CAUTION Do not turn the screwdriver in the slot. Doing so may damage the slot.
4. Install the lower case on the switch box or directly on the wall.
When using the switch box When installing directly on the wall
Switch box for two units
Seal the remote control cord
lead-in hole with putty.
(See 2 above)
Remote control cord
(See 5 in the next
page)
Cross recessed pan
head screw
Remote control cord
(See 5 in the next page)
Extra space
around remote
controller
30 [1-
3
/4]
Use surface
raceways
Wood screw
3
/16]
30 [1-
3
2
/16]
[Function selection flowchart]
[1] Stop the unit to start remote controller function selection mode. → [2] Select from item1. → [3] Select from item2. →
[4] Make the setting. (Details are specified in item3) → [5] Setting completed. → [6] Change the display to the normal one. (End)
Normal display (Display when the
air condition is not running)
(Hold down the E button and press the D button for two
seconds.)
* The display cannot be changed during the unit function
selection, the test run and the self diagnosis.
Item 1 Remote Controller Function
Press the
E button.
Press the
G button.
Press the
E button.
Press the
G button.
Press the
E button.
Press the
G button.
Press the G button.
Operation function limit setting (“LOCKING FUNCTION”)
Operation mode skip setting (“SELECT MODE”)
Temperature range limit setting (“LIMIT TEMP FUNCTION”)
Remote controller main/sub setting (“CONTROLLER MAIN/SUB”)
Use of clock setting (“CLOCK”)
Timer function setting (“WEEKLY TIMER”)
Contact number setting for error situation (“CALL.”)
Temp off set setting (“TEMP OFF SET FUNCTION”)
Temperature display °C/°F setting (“TEMP MODE °C/°F”)
Water temperature display setting (“WATER TEMP DISP SELECT”)
Change Language
(“CHANGE
LANGUAGE”)
Function limit
(“FUNCTION
SELECTION”)
Press the
E button.
Mode selection
(“MODE
SELECTION”)
Display change
(“DISP MODE
SETTING”)
Selection Mode
Item 2
[Detailed setting]
[4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [ MENU] button to change the language.
1 English (GB), 2 German (D), 3 Spanish (E), 4 Russian
(RU), 5 Italian (I), 6 French (F), 7 Swedish
[4] -2. Function limit
(1) Operation function limit setting (operation lock)
• To switch the setting, press the [ ON/OFF] button.
1 no1 : Operation lock setting is made on all buttons other than
the [ ON/OFF] button.
2 no2 : Operation lock setting is made on all buttons.
3 OFF (Initial setting value) : Operation lock setting is not made.
* To make the operation lock setting valid on the normal screen, it
is necessary to press buttons (Press and hold down the
[CIR.WATER] and [ ON/OFF] buttons at the same time for
two seconds.) on the normal screen after the above setting is
made.
(Hold down the E button and press
the D button for two seconds.)
* The remote controller records the
setting that is made in this way.
See [4]-1
Item 3
(Setting content)
Press the G button.
Press the G button.
Press the G button.
Press the
D button.
Press the
D button.
Press the
D button.
See [4]-2. (1)
See [4]-2. (2)
See [4]-2. (3)
See [4]-3. (1)
See [4]-3. (2)
See [4]-3. (3)
See [4]-3. (4)
See [4]-3. (5)
See [4]-4. (1)
See [4]-4. (2)
(3) Temperature range limit setting
After this setting is made, the temperature can be changed within the set range.
• To switch the setting, press the [ ON/OFF] button.
1 LIMIT TEMP HEATING MODE:
The temperature range can be changed on heating mode.
This mode cannot be used with FLOW TEMP. CONTROLLER.
2 LIMIT TEMP HOT WATER MODE:
The temperature range can be changed on hot water mode.
Heating mode can be used with FLOW TEMP. CONTROLLER.
3 LIMIT TEMP ANTI-FREEZE MODE:
The temperature range can be changed on anti-freeze mode.
4 LIMIT TEMP COOLING MODE:
The temperature range can be changed on cooling mode.
5 OFF (Initial setting):
The temperature range limit is not active.
* When the setting, other than OFF, is made, the temperature range limit
setting on hot water, anti-freeze and cooling mode is made at the same
time. However, the range cannot be limited when the set temperature range
has not changed.
NOTE
Timer operation stops when the display
for remote controller function selection is
changed to the normal one.
Dot display
The language that is selected in
CHANGE LANGUAGE mode
appears on this display. English
is set in this manual.
MENU
BACK DAY CHECK TEST
MONITOR/SET
PAR-W21MAA
• To increase or decrease the temperature, press the [ TEMP. ( ) or
(2) Operation mode skip setting
After setting is changed, the operation mode can be changed
within the changed range.
• To switch the following settings, press the [ ON/OFF]
button.
1 Heating mode : Sets the use or non-use of the
Heating mode.
2 Heating ECO mode : Sets the use or non-use of the
Heating ECO mode.
3 Hot Water mode : Sets the use or non-use of the Hot
Water mode.
4 Anti-freeze mode : Sets the use or non-use of the
Anti-freeze mode.
5 Cooling mode : Sets the use or non-use of the
Cooling mode.
6 OFF (Initial setting value) : Operation mode skip is not
executed.
* When the setting, other than OFF, is made, the skip settings of
the Heating, Heating ECO, Hot Water, Anti-freeze, and Cooling
modes are executed at the same time.
* A mode that is not available on the unit to connect cannot be
( )] button.
• To switch the upper limit setting and the lower limit setting, press the
[INITIAL SETTING ( )] button. The selected setting will flash and the
temperature can be set.
• Settable range
Heating/Hot Water mode : Lower limit: 20 ~ 90 °C (68 ~ 194°F)
Upper limit: 90 ~ 20 °C (194 ~ 68°F)
Anti-freeze mode : Lower limit: 5 ~ 45 °C (41 ~ 113°F)
Upper limit: 45 ~ 5 °C (113 ~ 41°F)
Cooling mode : Lower limit: 5 ~ 30 °C (41 ~ 87°F)
Upper limit: 30 ~ 5 °C (87 ~ 41°F)
* The settable range varies depending on the unit to connect.
[4] -3. Mode selection setting
(1) Remote controller main/sub setting
• To switch the setting, press the [ ON/OFF] button.
1 Main : The controller will be the main controller.
2 Sub : The controller will be the sub controller.
(2) Use of clock setting
• To switch the setting, press the [ ON/OFF] button.
1 ON : The clock function can be used.
2 OFF : The clock function cannot be used.
used even if the setting is “AVAILABLE”.
TEMP.
ON/OFF
CLOCK CLEAR
INITIAL SETTING
ON/OFF
CIR.WATER
4
1.
Water Temp Heating : Sets the water temperature to 1°C when starting operation in Heating mode.
2.
Water Temp Heating ECO No.1 : Sets the water temperature to 2°C for an outside air temperature of 3°C when operating in Heating ECO mode.
3.
Water Temp Heating ECO No.2 : Sets the water temperature to 4°C for an outside air temperature of 5°C when operating in Heating ECO mode.
4.
Water Temp Hot Water : Sets the water temperature to 6°C when starting operation in Hot Water mode.
5.
Water
Temp Anti-freeze : Sets the water temperature to 7°C when starting operation in Anti-freeze mode.
6. Water Temp Cooling : Sets the water temperature to 8°C when starting operation in Cooling mode.
7. Temp Offset Heating : Sets the offset amount of the Heating system to 9°C.
8. Temp Offset Cooling : Sets the offset amount of the Cooling system to 0°C.
4 Switch the outside air temperature or water temperature setting by pressing the [ ON/OFF] D button.
5 To set the water temperature, outside air temperature, or offset amount, press the [ TEMP. ( ) or ( )] F (setting temperature) button.
The adjustment range is as shown below.
Water Temp Hot Water (Heating, Heating ECO) : 20°C~ 90°C (68°F ~ 194°F) *1
°
Water Temp Anti-freeze : 5
Water Temp Cooling : 5
Outside air temperature : –20
Temp Offset Heating (Cooling) : –15
C~ 45°C (41°F~113°F) *1
°
C~ 30°C (41°F~ 87°F) *1
°
C~ 40°C (–4°F ~ 104°F)
°
C~ 15°C ( 5°F~ 59°F)
*1 The adjustment range differs depending on the model of the unit to connect.
6 To cancel the water temperature initial setting, press the [INITIAL SETTING ( )] J button for three seconds or longer.
Alternatively, press the [ ON/OFF] I button.
(2) Interface (I/F) Option Setting mode
The upper and lower limit values for the “water temperature switching by analog input (4-20 mA/0-10 V)”
used by the interface (I/F) can be set. Change the setting when needed.
1 Stop the unit by pressing the [ ON/OFF] I button.
2 To enter the interface (I/F) option setting, press the [INITIAL SETTING ( )] K button for three seconds or longer. (1. or 2. will be displayed.)
* Depending on the model of the unit to connect, the “Interface (I/F) Option Setting mode” may not be available. In such case, the screen transitions
to the unit stop screen after the display of the error.
3 To select an interface (I/F) option setting 1. or 2., press the [Mode (Back)] E button.
1. Interface (I/F) option setting
Heating system
1 Lower limit
value
display
2 Upper limit
value
display
2. Interface (I/F) option setting
Cooling system
3 Lower limit
value
display
4 Upper limit
value
display
* The available settings differ depending on the model of the unit to connect.
Lower limit value setting: Defines the “4 mA/0 V” input as the “water temperature 1°C” of the Heating, Hot Water, and Anti-
A Heating system
Upper limit value setting: Defines the “20 mA/10 V” input as the “water temperature 2°C” of the Heating, Hot Water, and
freeze modes.
Anti-freeze modes.
B Cooling system
Lower limit value setting: Defines the “4 mA/0 V” input as the “water temperature 3°C” of the of the Cooling mode.
Upper limit value setting: Defines the “20 mA/10 V” input as the “water temperature 4°C” of the Cooling mode.
4 To switch the upper/lower limit value display, press the [ ON/OFF] D button.
5 To set the upper/lower limit value, press the [ TEMP. ( ) or ( )] F (setting temperature) button.
• The adjustment range for both the upper and lower limit values is -20°C (-4°F) to 90°C (194°F).
6 To cancel the interface (I/F) option setting, press the [INITIAL SETTING ( )] K button for three seconds or longer.
Alternatively, press the [ ON/OFF] I button.
6
8 Remote Controller Check
BACK DAY CHECK TEST
MONITOR/SET
PAR-W21MAA
MENU
When the unit cannot be controlled from the remote controller, use this
function to check the remote controller.
TEMP.
ON/OFF
CLOCK CLEAR
INITIAL SETTING
ON/OFF
CIR.WATER
A
H
1 First check the power mark.
When normal voltage (DC12V) is not applied to the remote controller, the
power mark goes off.
When the power mark is off, check the remote controller wiring and the
unit.
2 Switch to the remote controller check mode.
When the [CHECK] H button is held down for five seconds or
longer, the display shown below appears.
When the [CIR.WATER] A button is pressed, remote controller check
begins.
3 Remote controller check result
When remote controller is normal
When remote controller is faulty
(Error display 1) “NG” flashes → Remote controller send/receive circuit
abnormal
Since there is no problem at the remote controller, check for other
Remote controller switching is necessary.
causes.
When the problem is other than the checked remote controller
(Error code 2) “E3” “6833” “6832” flash → Cannot send (Error display 3) “ERC” and data error count are displayed → Data error
generation
ERROR CODE
There is noise on the transmission line, or the unit or another remote
controller is faulty. Check the transmission line and the other remote
controllers.
“Data error count” is the difference between the number of bits of remote
controller send data and the number of bits actually sent to the
transmission line. In this case, the send data was disturbed by the
noise, etc. Check the transmission line.
When data error count is 02
Remote controller send data
Send data on transmission line
4 Remote controller check reset
When the [CHECK] H button is held down for five seconds or longer, remote controller check resets and the “PLEASE WAIT” and RUN lamp
flash. Approximately 30 seconds later, the remote controller returns to the state before remote controller check.