The rated capacity should be determined by observing the below. The unit’s quantities are limited in 1 to 8 units. For
the next step, make sure that the selected total indoor unit capacity is in a range of 63 ~ 163.
The total indoor unit capacity should be within the outdoor units. (=125 is preferred).
Combination of excessive indoor units and an outdoor unit may reduce the cooling capacity of each indoor unit.
The rated indoor capacity is as blow table.
• Use tie beams (single storied houses) or second floor
beams (two story houses) as reinforcing members.
• Wooden beams for suspending air conditioners must be
sturdy and their sides must be at least 6 cm long if the
beams are separated by not more than 90 cm. The size of
the suspension bolts should be M10 (W3/8). (The bolts are
not supplied with the unit.)
A Ceiling
B Rafter
C Beam
D Roof beam
B* Suspension bolt pitch
Ferro-concrete structures
Secure the suspension bolts using the method shown, or use
steel or wooden hangers, etc. to install the suspension bolts.
E Use inserts rated at 100-150 kg each (procure locally)
F Suspension bolts M10 (W3/8) (procure locally)
G Steel reinforcing rod
(2) Install the R-Converter unit.
Installing the unit on a wall
(1) Install the anchor bolts.
(2) Install the R-Converter unit.
Do not install the refrigerant pipes on top of the unit when
installing the unit on a wall, otherwise condensation can
enter the electrical devices, which can cause an electric
shock or a fire.
4
1-5-2. Installing Refrigerant Piping (mm)
Copper piping
O.D. (mm)
{6.35
{9.52
Flare dimensions
{A dimenson (mm)
8.6-9.0
12.6-13.0
Torque
N-m (kgf
•cm)
14-18 (140-180)
34-42 (340-420)
In order to prevent gas leaks, tighten the flared nut to the
specified torque even when not connecting the indoor unit
refrigerant piping.
Check the R-Converter unit accessories and parts
1 Pipe cover o 2 2 Band (long) o 4 3 Thermistor holder—[6.35 (liquid) o 1 4 Thermistor holder—[9.52 (liquid or gas) o 1
5 Thermistor holder—[12.7 (gas) o 1 6 Thermistor holder—[15.88 (gas) o 1 7 Thermistor insulation (3o150o60) o 2
8 Band (short) o 2
Connect R-Converter unit to the liquid pipe
• For identification purposes, list the indoor unit model names in the nameplate on the control box of the R-Converter
unit.
• To prevent water from dripping from the refrigerant piping, wrap both the liquid and gas piping with commercially available
thermal insulation that is at least 12 mm thick and which is able to withstand temperatures in excess of 100 °C.
• See the indoor and outdoor unit installation manual when creating a vacuum and opening or closing valves.
• Install the piping so that vibrations from the piping do not transmit to the unit.
Installing piping to the unit
(1) Remove the flared nuts and caps from the R-Converter unit.
(2) Flare the ends of the liquid and gas piping, and apply refrigeration oil (procure locally) to the flared seat.
(3) Connect the refrigerant piping immediately. Always tighten the flared nuts to the specified torque using a torque wrench and
double spanner.
(4) Press the pipe covers 1 on the liquid piping against the unit and wrap it to hold it in place.
(5) Fasten the supplied bands 2 10-20 mm from each end of the pipe covers 1 .
. Caution :
• Tighten the flare nut with a torque wrench in the specified method.
• Do not use the existing refrigerant piping, when use R407C refrigerant.
• Take precautions so that the Freon gas is not leaked during a fire.
Section of connection
Match the refrigerant piping size to
the indoor unit. If using a liquid pipe
that is [[9.52 mm, use joint pipe PAC493PI or a locally procured tandem
joint.
• Refrigerant charge :
See the outdoor unit installation manual.
Use only R407C or R22 refrigerant.
• Use the following procedures for connecting parts to
the indoor unit.
a) Tighten the flared nuts to prevent refrigerant leaks.
b) Fasten the pipe covers 1 to the pipes with the
bands 2 to prevent condensation.
5
1-5-3. Installing the thermistors (mm)
Indoor unit capacitypipe size (mm)
BTU
07, 09
12, 13
18
24, 30
HP
1
1.6
2
2.5
Liquid
{6.35
{6.35
{6.35
{9.52
Gas
{9.52
{12.7
{15.88
{15.88
Be sure to install the thermistors (gas and liquid) supplied with the unit as shown in the illustration.
• If the thermistors are not installed, the unit will not operate. If the thermistors are installed incorrectly, the unit will not operate
properly.
Take precaution so that condensation does contact the thermistor leads or enters the electrical devices.
Before installing thermal insulation to the frame connecting points of the indoor unit, be sure to install the thermistors
according to the procedures given on this page.
Thermistor installation order
(1) Securely fasten the thermistors (liquid and gas) supplied with the unit using the thermistor holders (3, 4, 5, 6) at the
fastening points of indoor unit refrigerant pipes.
• Set thermistor-L (liquid) in thermistor holders 3 or 4 and thermistor-G (gas) in thermistor holders 4, 5 or 6, and then
fasten the refrigerant pipes.
Select thermistor holders that match the size of the
refrigerant piping.
Liquid
Gas
. Caution :
• To prevent condensation from dripping on the thermistor fasteners, wrap them with sufficient thermal insulation.
• Install the thermistors so that the piping is on top (as shown in above illustration).
• Take out the thermistor lead from above the piping.
• Install the thermistors indoors.
• Route the following lead, line, and cable pairs so that they do not come into contact with each other.
-Thermistor lead and indoor unit-R-Converter transmission line
-Thermistor lead and power supply cable
-Transmission line and power supply cable
6
(2) Insulate the thermistors with the supplied thermal insulation 7.
(3) Cut a 100 mm slit on the top portion of the extension piping pipe covers, and then cover the thermistors with the pipe
covers.
(4) Wrap the thermal insulation covering the thermistor with tape.
. Caution :
Be sure to take out the thermistor lead from above.
(5) Cover the flare and thermistor with the thermal insulation (for protecting the flare) supplied with the indoor unit.
Bundle up the excess thermistor lead.
. Caution :
• Do not make the thermistor lead taut.
• Do not add extensions to the thermistor lead.
• Do not cut the excess thermistor lead.
• Make sure that the bundled thermistor lead does not interfere with any other wiring.
7
2SPECIFICATIONS
mm
mm
mm
mm
kg
mm(in.)
mm(in.)
Model name
Connectable number of indoor units
Total capacity index of indoor units to be connected
Power supply
External finish
Drain hose size (on site)
Dimensions
Weight
Piping connection (Flare)
Wiring
Width
Depth
Height
Liquid
Gas
To indoor unit
To outdoor unit
PAC-SF29LB
1
Type 20-63
Single phase, 220/230/240V, 50Hz, Single phase, 220V, 60Hz
Hot-dip Zinc - coated steel (No external finish)
—
280
220
126
2.8
6.35 (1/4)W
—
2-core cable
2-core shield cable (Non-polarized)
Model Name (series)
Connectable indoor units
Connectable outdoor units
Wall mounted MS series*
Cassette Ceiling SL series*
PUMY series *
* See page 2 for detail model name.
R-Converter Unit : PAC-SF29LB
W If using on indoor unit with [9.52 piping connection and using a [9.52 refrigerant pipe, use joint pipe “PAC-493PI” (optional
parts) or a locally procured tandem joint ([6.35
➝[9.52)
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.