• Thermiostor <Discharge/TH4> has been changed to Thermistor <Comp. Surface/TH32>.
• Electrical parts, Controller circuit board (C.B.), Power circuit board (P.B.), Noise filter circuit board (N.F.) and Active filter module (ACTM)(inclucling P.B.) have been changed.
OUTDOOR CONTROLLER BOARD (C.B) has been changed.
(Corresponding to the additional combination between PKA-RP•HAL/KAL, PCA-RP•KA and PEAD-RP•JA(L))
* In case of UL error, the compressor may be damaged if the unit is restarted by remote controller.
To avoid the damage, unit has the system that is not able to be restarted unless the power is turned OFF once.
Before obtaining access to terminal, all supply circuits must be disconnected.
Preparation before the repair service.
• Prepare the proper tools.
• Prepare the proper protectors.
• Provide adequate ventilation.
• After stopping the operation of the air conditioner, turn off the power-supply beaker.
• Discharge the condenser before the work involving the electric parts.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.
• Do not pour water into the electric parts.
• Do not touch the refrigerant.
• Do not touch the hot or cold areas in the refrigerating cycle.
• When the repair or the inspection of the circuit needs to be done without turning off the power,
exercise great caution not to touch the live parts.
3-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the followings.
· Be sure to clean the pipes and make sure that the insides
of the pipes are clean.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
Store the piping to be used indoors during
installation and both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
If large amount of mineral oil enters, that can cause deterioration of refrigerant oil etc.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition change
may occur in refrigerant and the efficiency will be lowered.
3
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.
Gauge manifold
1
Charge hose
2
Electronic scale
3
Gas leak detector· Use the detector for R134a, R407C or R410A.
4
Adaptor for reverse flow check· Attach on vacuum pump.
5
Refrigerant charge base
6
Refrigerant cylinder
7
Refrigerant recovery equipment
8
Tool name
· Only for R410A
· Use the existing fitting
· Use high-tension side pressure of 5.3 MPa·G or over.
· Only for R410A
· Use pressure performance of 5.09 MPa·G or over.
· Only for R410A · Top of cylinder (Pink)
· Cylinder with syphon
Specifications
specifications
—
—
—
. (UNF1/2)
4
Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore, as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1 Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown
below. (Never use pipes of 0.7 mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions(inch)
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
(mm)
Thickness
R410AR22
0.8
0.8
0.8
1.0
—
(mm)
0.8
0.8
0.8
1.0
1.0
2 Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2 and 5/8 inch, the dimension B changes. Use torque wrench corresponding to each
dimension.
Dimension A
Flare cutting dimensions
Nominal
dimensions(inch)
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
Dimension A
R410AR22
9.1
13.2
16.6
19.7
—
+0
( )
-0.4
9.0
13.0
16.2
19.4
23.3
(mm)
Flare nut dimensions
dimensions(inch)
Nominal
1/4
3/8
1/2
5/8
3/4
Outside
diameter
6.35
9.52
12.70
15.88
19.05
R410A
17.0
22.0
26.0
29.0
3 Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materialsUseR410A toolsCan R22 tools be used?
Gauge manifold
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
Air purge, refrigerant charge and
Operation check
Gas leak check
Refrigerant recovery
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Refrigerant charge
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Refrigerant charge
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil and alkylbenzene
oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
(Max. 30m (PUHZ-P125/P140))
The refrigerant circuit with LEV (Linear Expansion Valve) and Accumulator always control the optimal refrigerant level regardless
of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality and reliability of the work done. It also helps
to speed up the installation time.
6
5SPECIFICATIONS
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
Gas
Indoor side
Outdoor side
Height difference
Piping length
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
A
A
kW
W
kW
dB
dB
L
Cooling
4.78
)
3phase, 50Hz, 400V
13
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
TNB220FLCMT
2.9
Inverter
HP switch
Discharge thermo
—
Plate fin coil
Propeller fan % 1
0.060
60(2120)
Reverse cycle
50
54
950(37-3/8)
330+30(13+1-3/16)
943(37-1/8)
77(170)
R410A
3.0(6.6)
0.87(FV50S)
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 30m
Max. 50m
Heating
5.05
Service Ref.
Mode
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) % No.Fan motor output
Airflow
9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity
Main switch (Breaker)
)
2
Outdoor unit power supply
.%
Indoor unit-Outdoor unit*2
ing
Indoor unit-Outdoor unit earth*2
Wir
Wire No
Remote controller-Indoor unit*3
size (mm
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
Indoor unit-Outdoor unit S1-S2*4
Indoor unit-Outdoor unit S2-S3*4
Circuit rating
Remote controller-Indoor unit*4
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker(NV).
*2. Refer to 9-3.
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always necessarily the voltage to ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
P100, 125VP140V
~/N (single), 50 Hz,~/N (single), 50 Hz,
*1
*4
230 V230 V
32 A40 A
3 % Min. 43 % Min. 6
3 % 1.5 (Polar)3 % 1.5 (Polar)
1 % Min. 1.51 % Min. 1.5
2 % 0.3 (Non-polar)2 % 0.3 (Non-polar)
AC 230 VAC 230 V
AC 230 VAC 230 V
DC 24 VDC 24 V
DC 12 VDC 12 V
P100,125,140Y
3N~ (3ph,4-wires),
50Hz, 400 V
16 A
5 % Min. 1.5
3 % 1.5 (Polar)
1 % Min. 1.5
2 % 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V
Caution: Be sure to install N-Line. Without N-Line, it could cause damage to the unit.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
Power supply
Isolator
S1
3 poles isolator
S1
A-Control
Outdoor Unit
S2
S3
S2
S3
A-Control
Indoor Unit
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line
and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is
energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
1:1 systemSynchronized twin and triple system Electrical wiring
• Synchronized twin
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
Outdoor
unit
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
Remote
controller
2
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
Outdoor
unit
L
N
Indoor/outdoor
unit connection
cable
S1
S2
S3
Indoor
unit
S1
S2
S3
1
2
• Synchronized triple
Indoor
unit
S1
S2
S3
1
2
Remote
controller
Unit
power
supply
Earth leakage breaker
wiring circuit breaker or
isolating switch
Outdoor
unit
L
N
Indoor/outdoor
connection cable
S1
S2
S3
Remote
controller
Indoor
unit
1
2
S1
S2
S3
Indoor
unit
1
2
S1
S2
S3
Indoor
unit
1
2
S1
S2
S3
23
9-2. SEPARATE INDOOR UNIT/OUTDOOR UNIT POWER SUPPLIES
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
<For models without heater>
1:1 System
* The optional indoor power supply terminal kit is required.
L
N
S1
S2
S3
L
N
S1
S2
S3
1
2
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin/triple system
<For models without heater>
* The optional indoor power supply terminal kits are required.
L
N
S1
S2
S3
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
If the indoor and outdoor units have separate power supplies, refer to the table below.
If the optional indoor power supply terminal kit is used, change the indoor unit
electrical box wiring referring to the figure in the right and the DIP switch settings of
the outdoor unit control board.
Indoor unit specifications
Indoor power supply terminal kit (option)
Indoor unit electrical box connector connection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit DIP switch settings (when
using separate indoor unit/outdoor unit
power supplies only)
Required
Required
Required
ON
OFF12
Set the SW8-3 to ON.
3
(SW8)
L
L
N
N
S1
S1
S2
S3
1
2
S2
S3
1
2
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
L
L
N
N
S1
S1
S2
S2
S3
S3
1
1
2
2
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit)
BLUE
BLUE
YELLOW
YELLOW
CND or
CN01
control board
Indoor unit
* There are three types of labels (labels A, B and C). Affix the appropriate labels to
the units according to the wiring method.
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cords
Remote controller
Indoor unit
Option
Indoor unit power supply
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cords
Remote controller
Indoor unit
Option
Indoor unit power supply
Indoor unit earth
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
Electric heater
(For models with
heater)
L
N
S1
S2
S3
Separate indoor unit/outdoor unit power
supplies
YELLOW
BLUE
BLUE
YELLOW
CN01
CND or
Connectors
Indoor unit
control board
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. % size
Remote controller-Indoor unit
Indoor unit L-N*4
Indoor unit-Outdoor unit S1-S2*4
Indoor unit-Outdoor unit S2-S3*4
rating
Circuit
Remote controller-Indoor unit*4
*1
*2
*3
RP35~140
~/N (single), 50 Hz, 230 V
16 A
2 % Min. 1.5
1 % Min. 1.5
2 % Min. 0.3
–
2 % 0.3 (Non-polar)
AC 230 V
–
DC24 V
DC12 V
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2. Max. 120 m
*3. The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4. The figures are NOT always necessarily the voltage to ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 60245 IEC 57)
3. Install an earth longer than other cables.
24
9-3. INDOOR – OUTDOOR CONNECTING CABLE
The cable shall not be lighter than design 60245 IEC or 60227 IEC.
The cable length may vary depending on the condition of installation, humidity or materials, etc.
Cross section
of cable
Round
Wire size
2
)
(mm
2.5
Number
of wires
3
PolarityL(m) *5
Clockwise : S1-S2-S3
50
*1
Flat
2.5
3
Not applicable
(Because center wire has no cover finish)
Flat
1.5
4
From left to right : S1-Open-S2-S3
Round
2.5
*1 : In case that cable with stripe of yellow and green is available.
*2 : In case that the flat cables are connected as this picture, they can be used up to 80m.
(3C Flat cable × 2)
S1 S2 S3
*3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
*4 : In case of regular polarity connection (S1-S2-S3)
*5 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or materials, etc.
4
Clockwise : S1-S2-S3-Open
Connect S1 and S3 to the opposite angle
2
.
Not
applicable
*2
45
*3
60
*4
Wire No. % Size ($)
Outdoor power supply
Max. 45m
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
+ The Max. cable length may vary depending on the condition of installation, humidity or materials, etc.
3 % 1.5 (polar)
1 % Min. 1.5
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
+ The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to
earth or a poor electrical contact at the intermediate connection point.
Max. 50m
3 % 2.5 (polar)
1 % Min. 2.5
Wire No. % Size ($)
Max. 120m
2 % Min. 0.3
Max. 80m
3 % 2.5 (polar) and S3 separated
1 % Min. 2.5
—
25
9-4. M-NET WIRING METHOD
(Points to note)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5 cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to V power supply. If it is connected, electronic
parts on M-NET P.C. board may burn out.
(3) Use 2-core × 1.25 mm² shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
Group
remote
controller
Power
supply
unit for
transmission
wire
A-control
remote
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Earth only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
Bad example (Multi spot earthing of shield wire)
Central
remote
controller
M-NET transmission wire
controller
Power
supply
appliance
Refrigerant
address 00
M-NET
address 01
M-NET type
outdoor unit
M-NET type
outdoor unit
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
M-NET type
outdoor unit
A-control
remote
controller
Refrigerant
address 00
M-NET
address 03
Good example 1 (Single spot earthing of shield wire)
Central
remote
controller
M-NET transmission wire
Good example 2 (Single spot earthing of shield wire)
Central
remote
controller
M-NET transmission wire
If there are more than 2 grounding spots on the shield wire, noise may enter into the shield wire because the earth wire
and shield wire form 1 circuit and the electric potential difference occurs due to the impedance difference among earthing
spots. In case of single spot grounding, noise does not enter into the shield wire because the earth wire and shield wire do
not form 1 circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
Power
supply
appliance
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
26
M-NET wiring
(1) Use 2-core × 1.25 mm² shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block. Connect one core of the trans-
mission wire (no-polarity) to A terminal and the other to B. Peel the shield wire,
twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
M-NET
terminal
block
ABS
Transmission
wire
Earth
wire
Shield
part
outdoor unit’s terminal, i.e. A to A, B to B and S to S. In this case, choose one of those outdoor units and drive a screw
to fix an ground wire on the plate as shown on the right figure.
9-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to CITY MULTI
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in CITY MULTI system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for 1s digit and SW12 for 10s digit), which
is located on the M-NET board of outdoor unit.
(Factory setting: all addresses are set to “0”.)
<Setting example>
M-NET Address No.
SW11
Switch
setting
1s
digit
SW12
10s
digit
12
3
3
4
4
2
2
5
1
0
9
2
1
0
9
5
1
6
6
0
7
7
9
8
8
3
3
4
4
2
5
5
1
6
6
0
7
7
9
8
8
50
3
4
2
5
1
6
0
7
9
8
~
3
4
2
5
1
6
0
7
9
8
9-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Initial setting: all
switches are OFF. (All refrigerant addresses are “00”.)]
Refrigerant
address
ON
OFF
1
ON
OFF
1
The black square (
ON
OFF
1
3
4
5
2
6
0
ON
OFF
1
3
4
5
2
6
8
ON
OFF
1
3
4
5
2
6
1
ON
OFF
1
3
4
5
2
6
9
■
) indicates a switch position.
ON
OFF
1
3
4
5
2
6
2
ON
OFF
1
3
4
5
2
6
10
ON
OFF
1
3
4
5
2
6
3
ON
OFF
1
3
4
5
2
6
11
ON
OFF
1
3
4
5
2
6
4
ON
OFF
1
3
4
5
2
6
12
ON
OFF
1
3
4
5
2
6
5
ON
OFF
1
3
4
5
2
6
13
ON
OFF
1
3
4
2
6
3
4
2
14
3
5
5
4
5
2
6
OFF
6
6
7
ON
1
3
4
5
2
6
15
9-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
Group AGroup BGroup C
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
A-control
remote
controller
Refrigerant
address 01
M-NET
address 03
TB5
Refrigerant
address 00
M-NET
address 04
A-control
remote
controller
w Refrigerant addresses can be overlapped if they are in the different group.
Group AGroup B
System
controller
Power
supply
unit for
transmission
wire
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
Refrigerant
address 01
M-NET
address 02
Refrigerant
address 00
M-NET
address 04
TB5
A-control
remote
controller
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in the
group for the outdoor unit whose refrigerant address is “00”.
Perform the following procedures to recover the refrigerant when moving the indoor unit or the outdoor unit.
1 Turn on the power supply (circuit breaker).
w When power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If
“CENTRALLY CONTROLLED” is displayed, the refrigerant recovering (pump down) cannot be completed normally.
2 After the liquid stop valve is closed, set the SWP switch on the control board of the outdoor unit to ON. The compressor
(outdoor unit) and ventilators (indoor and outdoor units) start operating and refrigerant recovery operation begins. LED1 and
LED2 on the control board of the outdoor unit are lit.
w Set the SWP switch (push-button type) to ON in order to perform refrigerant recovery operation only when the unit is
stopped. However, refrigerant recovery operation cannot be performed until compressor stops even if the unit is stopped.
Wait 3 minutes until compressor stops and set the SWP switch to ON again.
3 Because the unit automatically stops in about 2 to 3 minutes after the refrigerant recovering operation (LED1 is not lit and
LED2 is lit), be sure to quickly close the gas stop valve.
w In case the outdoor unit is stopped when LED1 is lit and LED2 is not lit, open the liquid stop valve completely, and then
repeat step 2 3 minutes later.
w If the refrigerant recovering operation has been completed normally (LED1 is not lit and LED2 is lit), the unit will remain
stopped until the power supply is turned off.
4 Turn off the power supply (circuit breaker.)
2. Start and finish of test run
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit
By using the DIP switch SW4 on the control board of outdoor unit, test run can be started and finished, and its operation
mode (cooling/heating) can be set up.
1Set the operation mode (cooling/heating) using SW4-2.
2Turn on SW4-1 to start test run with the operation mode set by SW4-2.
3Turn off SW4-1 to finish the test run.
• There may be a faint knocking sound around the machine room after power is supplied, but this is
no problem with product because the linear expansion pipe is just moving to adjust opening pulse.
• There may be a knocking sound around the machine room for several seconds after compressor
starts operating. But this is not a problem with product because the check valve itself generates the
sound due to small pressure difference in the refrigerant circuit.
Stop Operation
Cooling Heating
<SW4>
ON
OFF
12
Note:
The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1,
change the operation mode and restart the test run by SW4-1.)
30
Loading...
+ 84 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.