motor
Dimensions W × H × Dmm798 × 295 × 2321100 × 325 × 238
Weightkg1016
Air direction5
Airfl ow
Sound level
Special remarks
Fan speed
Fan speed regulator5
Remote controller modelKM09ASG10A
Cooling
Heating2330396258
Cooling
1
Heating0.230.310.360.530.51
Cooling
Heating0.230.310.360.530.51
Super High
+ LONG + POWERFUL
Super High
High546
Cooling
Med.402
Low288
Silent246348390588582
Super High
+ LONG + POWERFUL
Super High
High546624732
Heating
Med.396402516576804798
Low288
Silent246348390588612
Super High
+ LONG + POWERFUL
Super High
High36404445
Cooling
Med.2930353841
Low2122303337
Silent1926282930
Super High
+ LONG + POWERFUL
Super High
High36404345
Heating
Med.2930353741
Low2122303337
Silent1926282930
Super High
+ LONG + POWERFUL
Super High
High8609501,0609601,010
Cooling
Med.670
Low530680750740800
Silent470600
Super High
+ LONG + POWERFUL
Super High
High
Heating
Med.
Low530690750740800
Silent470600650660730
W
A
A
3
m
3
m
dB(A)
dB(A)
rpm
rpm
MSZ-
GE22VA
/h
/h
MSZ-
GE25VA
2229433858
0.220.290.390.350.51
0.220.290.390.350.51
6787627689061,0981,068
(552
2)
(276
6907868701,0981,068
(276 2)
42434649
42464849
1,0201,1201,1201,2801,0901,140
1,0401,1401,2401,0901,140
860 (700
670 (610
MSZ-
GE35VA
-1,2421,164
2)
402
(414
288408468678690
-1,2421,164
288420468678690
-5253
-52
-1,2801,300
670 (690 2)
-1,2801,300
2)
2)
2)
MSZ-
GE42VA
624714936924
516576804798
810890850900
950 (930 2)
810
MSZ-
GE50VA
650 (690 2)
1,080 (930 2)
890 (840 2)
MSZ-
GE60VA
936 (882 2)
960 (910 2)
MSZ-
GE71VA
660700
1,010
850900
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C
Heating: Indoor Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
1 Measured under rated operating frequency.
2 For multi system.
924
5
Specifications and rating conditions of main electric parts
Fuse(F11)
Horizontal vane motor(MV), (MV1)12 VDC
Vertical vane motor
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows. (Refer to 10-7.2.)
Set time: 1 minute → 1 second
Set time: 3 minutes → 3 seconds (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit-of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below:
the batteries and press
the OPERATE/STOP (ON/
OFF) button twice or 3
times at first.
After modification, put back
the batteries then press the
J1
J2
RESET button.
MSZ-GE60VA MSZ-GE71VA
J1J2
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
Table 1
1 unit operation2 units operation3 units operation4 units operation
No. 1 unitNo modifi cationSame as at leftSame as at leftSame as at left
No. 2 unit—Solder J1Same as at leftSame as at left
No. 3 unit——Solder J2Same as at left
No. 4 unit———Solder both J1 and J2
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote
controller for the indoor unit.
The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set.
The setting will be cancelled if the breaker is turned OFF, or the power supply is shut down.
Please conduct the above setting once again after the power has restored.
11
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed
are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation
in the same mode just before the shutoff of the main power.
Operation
If the main power has been cut, the operation settings remain.After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes
for the compressor to start running.)
How to release “AUTO RESTART FUNCTION”
Turn off the main power for the unit.Solder the jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 10-7.2.)
MSZ-GE22VA MSZ-GE25VA MSZ-GE35VA
MSZ-GE60VA MSZ-GE71VA
MSZ-GE42VA MSZ-GE50VA
JR07
Indoor electronic
control P.C. board
JR07
Indoor electronic
control P.C. board
CN 111CN112CN151CN10A
CN112
CN 111
CN152
CN151
CN10A
NOTE:
• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
• If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is can-
celled.
• If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is OFF.
• To prevent breaker OFF due to the rush of starting current, systematize other home appliance not to turn ON at the same
time.
• When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
TIME, TIMER set buttons
FORWARD button
BACKWARD button
WEEKLY TIMER
set button
RESET button
Indication of
remote controller
model is on back
CLOCK SET button
NOTE: Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receives the signal of the
remote controller with beeps.
13
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
•The following indication applies regardless of shape of the indication.
IndicationOperation stateRoom temperature
The unit is operating to
reach the set temperature
The room temperature is
approaching the set temperature
Standby mode
(Only during multi system
operation)
About 2°C or more away
from set temperature
About 1 to 2°C from set
temperature
-
Lighted
Blinking
Not lighted
9-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons [TOO WARM or TOO COOL button (MSZ-22/25/35/42/50VA)/TEMP
(MSZ-GE60/71VA)] to select the desired temperature. The setting range is 16 - 31°C.
1. Coil frost prevention
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil
from frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
or button
9-2. DRY ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
1. Coil frost prevention
Coil frost prevention is as same as COOL mode. (9-1.1.)
2. Low outside temperature operation
Low outside temperature operation is as same as COOL mode. (9-1.2.)
9-3. HEAT ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons [TOO WARM or TOO COOL button (MSZ-22/25/35/42/50VA)/TEMP
(MSZ-GE60/71VA)] to select the desired temperature. The setting range is 16 - 31°C.
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem-
perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con-
densing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor
heat exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
14
or button
9-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION
Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.
Mode selection
(1) Initial mode
When unit starts the operation with AUTO operation from OFF:
• If the room temperature is higher than the set temperature, operation starts in COOL mode.
• If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.
(2) Mode change
COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 1°C below the
set temperature.
HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 1°C above the
set temperature.
NOTE 1
If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is operating in
(AUTO), cannot change over to the other operating mode (COOL ↔ HEAT) and becomes a state of standby.
Refer to NOTE 2 “FOR MULTI SYSTEM AIR CONDITIONER”.
NOTE 2
FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT: MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
• When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and
the others for heating, the operation mode of the indoor unit that operates first is selected. Other indoor units
cannot operate, and operation indicator lamp flashes as shown in the figure below. In this case, please set all the
indoor units to the same operation mode.
OPERATION INDICATOR
Lighted
Blinking
Not lighted
• When indoor unit starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max.
10 minutes) to blow out the warm air.
• In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
9-5. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approximate 12 V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the
selected angle.
Confirming of standard position is performed in the following cases:
(a) When the operation starts or finishes (including timer operation).
(b) When the test run starts.
(c) When standby mode (only during multi system operation) starts or finishes.
(4) VANE AUTO (
In VANE AUTO mode, the microprocessor automatically determines the vane angle to make the optimum room temperature distribution.
In COOL and DRY operation
Vane angle is fixed to Horizontal position.
Horizontal
position
12345
) mode
SWING
In HEAT operation
Vane angle is fixed to Angle 5.
5
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.