Mitsubishi Electric MSZ-GC22VA, MSZ-GC25VA, MSZ-GC35VA, MSZ-GC22VA - E1, MSZ-GC25VA -E1 Service Manual

...
Page 1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. SPECIFICATION·················································3
4. NOISE CRITERIA CURVES ·······························4
5. OUTLINES AND DIMENSIONS ·························5
6. WIRING DIAGRAM ············································6
8. SERVICE FUNCTIONS ······································7
9. MICROPROCESSOR CONTROL ······················9
10. TROUBLESHOOTING······································14
11. DISASSEMBLY INSTRUCTIONS·····················26
MSZ-GC22VA ­MSZ-GC22VA ­MSZ-GC25VA ­MSZ-GC25VA ­MSZ-GC35VA ­MSZ-GC35VA -
E2
E1
E2
E1
E2
E1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Outdoor unit service manual MUZ-GC·VA Series (OBH469) MXZ-A·VA Series (OB377) MXZ-8A140A (OC316)
SERVICE MANUAL
Wireless type Models
No. OBH468
REVISED EDITION-B
INDOOR UNIT
PARTS CATALOG (OBB468)
Revision B:
has been added.
E2
Please void OBH468 REVISED EDITION-A.
Page 2
2
1
TECHNICAL CHANGES
MSZ-GA22VA -
MSZ-GC22VA ­MSZ-GA25VA - MSZ-GC25VA ­MSZ-GA35VA - MSZ-GC35VA -
E1
E1
E1E1
E1E1
1. Indoor model has been changed.
PART NAMES AND FUNCTIONS
2
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
Air outlet
Vertical vane
Air inlet
Operation Indicator lamp
Front panel
Catechin air filter
Horizontal vane
Remote controller
Remote control receiving section
Emergency operation switch (E.O. SW)
Air cleaning filter (Anti-allergy enzyme filter, option)
Line flow fan
Revision A:
• 10.TROUBLESHOOTING has been corrected.
• Color of lead wire (indoor fan motor : sensor part) of 10-5.”Trouble criterion of main parts” has been corrected.
• 10-6.”ACheck of indoor fan motor” has been corrected.
Revision B:
has been added.
E2
MSZ-GC22VA - MSZ-GC22VA ­MSZ-GC25VA - MSZ-GC25VA ­MSZ-GC35VA - MSZ-GC35VA -
E2
E1
E2E1
E2E1
1. Panel has been changed.
Page 3
3
SPECIFICATION
3
Fuse
Horizontal vane motor
Varistor
Terminal block
(F11)
(MV)
(NR11)
(TB)
T3.15AL 250V
12V DC
S10K320E3K1(ERZV14D471)
3P
Specifications and rating conditions of main electric parts
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor Dry-bulb temperature 27
:Wet-bulb temperature 19:
Outdoor Dry-bulb temperature 35:
Heating : Indoor Dry-bulb temperature 20:
Outdoor Dry-bulb temperature 7:Wet-bulb temperature 6:
Refrigerant piping length (one way): 5m 1 Measured under rated operating frequency.
MSZ-GC25VA MSZ-GC35VA
Single phase
230V,50Hz
0.22 40
0.22
788O295O234
9 4
43
4
KM05B
36/29/22
Cooling
576
462/354/246
1,070
890/720/550
Heating
600
480/378/276
1,100
920/760/600
MSZ-GC22VA
Indoor model
Function
Power supply
36/29/21
Cooling
576
462/354/246
1,070
890/720/550
Heating
600
480/378/276
1,100
920/760/600
RC4V18-BA or CA
Cooling
552
444/330/234
1,110
930/740/580
Heating
570
462/354/246
1,140
960/780/600
Air flow(Super High) Air flow(High/Med./Low) Running current 1 Power input 1 Fan motor current 1 Model Dimensions WOHOD Weight Air direction Sound level (Super High) Sound level (High/Med./Low) Fan speed (Super High) Fan speed (High/Med./Low) Fan speed regulator
Remote controller model
K /h K /h
A
W
A
mm
kg
dB(A) dB(A)
rpm rpm
Electrical
data
Fan motor
Special
remarks
Capacity
ACCESSORIES
1 2 3 4 5 6 7
Installation plate
Installation plate fixing screw 4 o 25 mm
Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black)
Battery (AAA) for remote controller
Wireless remote controller
Felt tape (Used for left or left-rear piping)
1
5
1
2
2
1
1
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
Page 4
4
4
NOISE CRITERIA CURVES
MSZ-GC22VA MSZ-GC25VA
INDOOR UNIT
WALL
MICROPHONE
0.8m
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Test conditions Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20:
43
43
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
MSZ-GC35VA
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
43
43
Page 5
5
OUTLINES AND DIMENSIONS
5
Unit : mm
7459
41.5
214
235
253.5
18.5
320335
155 155
21540.5
254.5
5959 225 225
2
295
53 607 128
8
100
137
119
Piping
Insulation
[35 O.D
Liquid line
[6.35 - 0.5 m (Flared connection [6.35)
Gas line
[9.52 - 0.43 m (Flared connection [9.52)
Drain hose
Insulation [28 O.D Connected part [16 O.D
11 X 26 Oblong hole
11
X 20 Oblong hole
Installation plate
Indoor unit
Wall hole
[65
Air in
Air out
Installation plate
Piping
Drain hose
19
159
58
234
5
788
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
Page 6
6
6
WIRING DIAGRAM
REFRIGERANT SYSTEM DIAGRAM
7
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
Refrigerant flow in cooling Refrigerant flow in heating
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Flared connection
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12 (main)
Indoor coil thermistor RT13 (sub)
Unit : mm
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
Page 7
7
SERVICE FUNCTIONS
8
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. The time will be shortened as follows. (Refer to 10-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
2 units operation
Same as at left
Solder J1
3 units operation
Same as at left
Same as at left
Solder J2
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker is turned OFF, or the power supply is shut down. Please conduct the above setting once again after the power has restored.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
NOTE : For modification, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After modification, put back the batteries then press the RESET button.
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
J2
J1
Page 8
8
NOTE :
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the
remote controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker OFF due to the rush of starting current, systematize other home appliance not to turn ON at the
same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure,
the starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
JR07
Indoor electronic control P.C. board
CN10A CN111CN151 CN112
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in the same mode just before the shutoff of the main power.
Operation
1
If the main power has been cut, the operation settings remain.
2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release “AUTO RESTART FUNCTION”
1
Turn off the main power for the unit.
2Solder the jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 10-7.)
Page 9
9
MICROPROCESSOR CONTROL
9
Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
WIRELESS REMOTE CONTROLLER
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
INDOOR UNIT DISPLAY SECTION
About 2 : or more away from set temperature
Room temperature
About 1 to 2 : from set temperature
The unit is operating to reach the set temperature
The room temperature is approaching the set temperature
Standby mode (only during multi system operation)
Operation state
Indication
Lighted
Not lighted
•The following indication applies regardless of shape of the indicator.
Blinking
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
ON TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
OFF TIMER button
Open the front lid.
RESET button
VANE CONTROL button
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of remote controller model is on back
Page 10
10
1. Coil frost prevention
Coil frost prevention is as same as COOL mode. (9-1.1.)
2. Low outside temperature operation
Low outside temperature operation is as same as COOL mode. (9-1.2.)
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem­perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
9-2. DRY ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select DRY mode with OPERATION SELECT button. (3) The set temperature is determined from the initial room temperature.
9-3. HEAT ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select HEAT mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Coil frost prevention
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil
from frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
9-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con­densing pressure from increasing excessively. When the temperature of indoor heat exchanger becomes too high, the high pressure protection works. The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor heat exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low. The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts. This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
9-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION
Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.
Mode selection
(1) Initial mode
When unit starts the operation with AUTO operation from off;
• If the room temperature is higher than the set temperature, operation starts in COOL mode.
• If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.
(2) Mode change
COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 2 degrees below the set temperature. HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 2 degrees above the set temperature.
NOTE 1
If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is operating in (AUTO), cannot change over to the other operating mode (COOL HEAT) and becomes a state of standby. Refer to NOTE 2 “FOR MULTI SYSTEM AIR CONDITIONER”.
Page 11
11
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the selected angle. Confirming of standard position is performed in the following cases: (a) When the operation starts or finishes (including timer operation). (b) When the test run starts. (c) When standby mode (only during multi system operation) starts or finishes.
9-5. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
(4) VANE AUTO ( ) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle to make the optimum room temper­ature distribution.
Horizontal
position
In COOL and DRY operation
In HEAT operation
Vane angle is fixed to Horizontal position.
Vane angle is fixed to Angle 4.
(6) Dew prevention
During COOL or DRY operation with the vane angle at Angle 2 ~ 4 when the compressor cumulative operation time
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(5) STOP (operation OFF) and ON TIMER standby
In the following cases, the horizontal vane returns to the closed position. (a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF). (b) When the operation is stopped by the emergency operation. (c) When ON TIMER is ON standby.
NOTE 2 FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the others for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
•When indoor unit starts the operation while the defrosting of outdoor unit is being done, it takes a few
minutes(max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant
flowng may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
OPERATION INDICATOR
Not lighted
Blinking
Lighted
Page 12
12
To change the air
flow direction
When to use this function?
Use this function if you don’t want the air from the indoor unit to blow directly onto your body.
• Depending on the shape of the room, the air may blow directly onto your body.
• Pr es s VANE CONTROL bu tt on again to return the
vane to the previously-set position.
Pressing and holding VANE CONTROL button for 2 s ec on ds or m or e cau se s the horizontal vane to reverse and move to horizontal position.
The air conditioner starts the cooling or dr ying operat ion appr ox. 3 minutes after the vane has moved to the hori­zontal position.
• When VANE CONTROL button is pressed again, the vane returns to the previously-set position and the air conditioner starts the cool or dry operation in approx. 3 minutes.
The air conditioner starts heat­ing operation approx. 3 minutes after the vane has moved to the horizontal position.
• Sometimes the area around your feet may not warm. To warm the area around the feet, set the horizontal vane to (AUTO) or the downward­ blowing position.
• When VANE CONTROL button is pressed again, the vane returns to the previously-set position and the air conditioner starts the heat operation in approx. 3 minutes.
COOL/DRY
HEAT
NOTE :
• If you make the air flow not to blow directly onto your body by pressing VANE CONTROL button, the compressor stops for 3 minutes even during the operation of the air conditioner.
• The air conditioner operates with Very Low speed until the compressor turns on again.
(9) To change the air flow direction not to blow directly onto your body.
Horizontal
position
(10) ECONO COOL ( ) operation (ECONOmical operation)
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher. Also the horizontal vane swings in various cycle. SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the air conditioner can keep comfort. As a result, energy can be saved. ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is pressed or change to other operation mode.
9-6. TIMER OPERATION
1. How to set the time
(1) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIME MONITOR, so set the current time correctly with CLOCK SET button.
How to set the current time
(a) Press the CLOCK set button.
(b) Press the TIME SET buttons ( and ) to set the current time.
• Each time FORWARD button ( ) is pressed, the set time increases by 1minute, and each time BACK WARD button ( ) is pressed, the set time decreases by 1minute.
• Pressing those buttons longer, the set time increases / decreases by 10 minutes.
(c) Press the CLOCK set button. (2) Press OPERATE/STOP (ON/OFF) button to start the air conditioner. (3) Set the time of timer.
ON timer setting
(a) Press ON TIMER button( ) during operation.
(b) Set the time of the timer using TIME SET buttons ( and ) .
w
OFF timer setting
(a) Press OFF TIMER button ( ) during operation.
(b) Set the time of the timer using TIME SET buttons ( and ).
w
w Each time FORWARD button ( ) is pressed, the set time increases by 10 minutes; each time BACKWARD but-
ton ( ) is pressed, the set time decreases by 10 minutes.
START
STOP
NOTE : When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat
off, this control doesn’t work in the indoor unit.
(8) Cold air prevention in HEAT operation
The horizontal vane position is set to Upward.
(7) SWING ( ) mode
By selecting SWING mode with VANE CONTROL button, the horizontal vane swings vertically.
Page 13
13
EMERGENCY OPERATION switch (E.O. SW)
Operation mode COOL HEAT
Set temperature
24:
24:
Fan speed Medium Medium
Horizontal vane Auto Auto
The operation mode is indicated by the Operation Indicator lamp on the indoor unit as following
Not lighted
Lighted
Operation Indicator lamp
EMERGENCY HEAT
EMERGENCY COOL
STOP
9-7. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the right side of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote controller run down. The unit will start and OPERATION INDICATOR lamp will light. The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan runs at High speed and the system is in continuous operation (The thermostat does not work). After 30 minutes of test run operation, the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of 24°C. The fan speed shifts to Med..
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode. Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any signal from the remote controller. In case of latter, normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.
2. To release the timer
To release ON timer, press ON TIMER button ( ). To release OFF timer, press OFF TIMER button( ). TIMER is cancelled and the display of set time disappears.
START
STOP
PROGRAM TIMER
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
• OFF timer and ON timer can be used in combination. The timer of the set time that is reached first will operate first.
• “ ” and “ ” display shows the order of OFF timer and ON timer operation.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : If the main power is turned off or a power failure occurs while ON/OFF timer is active, the timer setting
is cancelled. As these models are equipped with an auto restart function, the air conditioner starts operating with
timer cancelled when power is restored.
Page 14
14
10
TROUBLESHOOTING
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) If the P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for
bursting and discoloration.
4) When troubleshooting, refer to 10-2., 10-3. and 10-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by
the battery replacement.
10-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the P.C. board.
3) When removing the P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Housing point
Lead wiring
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
RESET button
Insert the negative pole of the batteries first. Check if the polarity of the batteries is correct.
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
1
Lock
2
If horizontal vane is not installed correctly, all of the operation indicator lamps will blink. In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE : Before installation of the horizontal vane, turn OFF the power supply.
5. How to install the horizontal vane
In procedure
2
lock the stoppers until they click into place.
Page 15
15
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
10-2. Failure mode recall function
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
NOTE: 1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
Does upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of upper lamp of OPERATION INDICATOR lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does upper lamp of OPERATION INDICATOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table(10-2.2.). Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply. <
Preparation of the remote controller
>
1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way. Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to outdoor unit service manual.) Make sure to check at least two consecutive blinking cycles. W3
W1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Page 16
16
2. Indoor unit failure mode table
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-4.).
12-time flash
2.5-second OFF
Replace the indoor electronic control P.C. board.
Indoor control system
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
11-time flash
2.5-second OFF
Refer to 10-6.A "Check of indoor fan motor".
Indoor fan motor
The rotational frequency feedback signal is not sent out for 12-seconds after indoor fan motor is opeated.
2-time flash
2.5-second OFF
Refer to the characteristics of the main indoor coil thermistor, the sub indoor coil thermistor (10-7.).
Indoor coil thermistor
The indoor coil thermistor short or open circuit is detected every 8 seconds during operation.
3-time flash
2.5-second OFF
Refer to 10-6.D "How to check mis-wiring and serial signal error".
Serial signal
The serial signal from outdoor unit is not received for 6 minutes.
1-time flash every 0.5-second
Refer to the characteristics of the room temperature thermistor (10-7.).
Room temperature thermistor
The room temperature thermistor short or open circuit is detected every 8 seconds during operation.
Not lighted Normal
Upper lamp of OPERATION
INDICATOR lamp
Correspondence
Abnormal point
(Failure mode)
Condition
Page 17
17
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates only in Test Run operation.
w
Outdoor unit doesn't operate even in Test Run operation.
w
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to 10-7. "Test point diagram and voltage".
Refer to "How to check inverter/ compressor".
Refer to 10-6.B "Check of remote controller and indoor electronic control P.C. board".
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to 10-6.C "Check of indoor P.C. board and indoor fan motor".
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to "Check of R.V. coil".
Refer to outdoor unit service manual.
Indoor unit operates. Outdoor unit doesn't operate normally.
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
w
"Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.
Upper lamp Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring or trouble of serial signal
Upper
lamp 2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
Upper
lamp 3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Upper
lamp 5-time flash Cause: Outdoor unit
• Outdoor power system abnormality
Upper
lamp 6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Upper
lamp 7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Refer to 10-6. D "How to check of mis-wiring and serial signal error
".
All lamps Flash on and off at 0.5-second intervals Cause: Indoor unit
• The horizontal vane is not installed correctly.
Refer to 10-6. E "Check of installation of the horizontal vane".
Check room temperature thermistor and indoor coil thermis­tor. Refer to 10-7. "Test point diagram and voltage".
Refer to 10-6. A "Check of indoor fan motor".
Refer to "How to check inverter/ compressor".
Refer to "Check of outdoor thermistors".
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
Upper
lamp 14-time flash Cause: Outdoor unit
• Other abnormality
Check "Flow chart of the detailed outdoor unit failure mode recall function."
Upper
lamp 4-time flash Cause: Indoor unit
• Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
10-3. Instruction of troubleshooting
Page 18
18
No.
1
2
5
6
SymptomOperation indicator lamp
Condition
Correspondence
Upper lamp flashes.
0.5-second ON
0.5-second OFF
Mis-Wiring or serial signal
Outdoor power system
Outdoor thermistors
Outdoor control system
Indoor coil thermistor
The serial signal from the outdoor unit is not received for 6 minutes.
It consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection within 1 minute after start-up.
The outdoor thermistors short or open circuit during the compressor operation.
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Refer to "Check of outdoor thermistor".
Refer to outdoor unit service manual.
• Refer to "How to check of
inverter/compressor".
Refer to outdoor unit service manual.
• Check the stop valve.
• Replace the inverter P.C.
board or the outdoor electronic control P.C. board. Refer to outdoor unit service manual.
• Refer to 10-6.D "How to check
mis-wiring and serial signal
error".
3
Indoor fan motor
7
Abnormal
point
Room temperature thermistor
Upper lamp flashes. 2-time flash
2.5-second OFF
The indoor coil or the room temperature thermistor is short or open circuit.
• Refer to 10-7.the
characteristics of indoor coil thermistor, and the room temperature thermistor.
Upper lamp flashes. 3-time flash
2.5-second OFF
The rotational frequency feedback signal is not emitted during the indoor fan operation.
• Refer to 10-6.A "Check of
indoor fan motor".
Indoor unit and outdoor unit do not operate.
Upper lamp flashes. 5-time flash
2.5-second OFF
Upper lamp flashes. 6-time flash
2.5-second OFF
Other abnormality
An abnormality other than above mentioned is detected.
• Check the stop valve.
• Confirm the abnormality in
detail using the failure mode recall function for outdoor unit.
8
4
Upper lamp flashes. 4-time flash
2.5-second OFF
Indoor control system
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
• Replace the indoor electronic
control P.C. board.
Outdoor control system
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Check the blinking pattern of the LED on the inverter P.C. board or the outdoor electronic control P.C. board.
9
Outdoor unit does not operate.
Upper lamp lights up
Upper lamp flashes. 7-time flash
2.5-second OFF
Upper lamp flashes. 14-time flash
2.5-second OFF
10-4. Troubleshooting check table
Not lighted
Blinking
OPERATION INDICATOR
Lighted
Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
Page 19
19
10-5. Trouble criterion of main parts
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
Measure the voltage power ON.
Figure
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
BLK
BLK RED
BLK
BLK
ROTOR
BLK
RED
WHT
GRY
YLW
BRN
MAIN
AUX.
FUSE
Motor part
Sensor part
Measure the resistance between the terminals with a tester. (Part temperature 10˚C ~ 30˚C)
BRN – YLW
BRN – GRY
Normal
4.5 ~ 5.5V
(When fan revolved one time)
0V5V0V
(Approx.)
Color of lead wire
Part name Check method and criterion
Indoor fan motor (MF) INNER FUSE BA : 135i3: CUT OFF CA : 140i2: CUT OFF
Measure the resistance with a tester.
Refer to 10-7."Test point diagram and voltage", "2.Indoor electronic control P.C. board", the chart of thermistor.
Room temperature thermistor (RT11)
Indoor coil thermistor (RT12, RT13)
Vane motor (MV)
Normal
RED-BLK
235 " ~ 255 "
Color of the lead wire
WHT – BLK
BLK – RED
Normal
RC4V18-BA
273 " ~ 296 " 295 " ~ 320 "
Color of lead wire
RC4V18-CA
308 " ~ 334 " 295 " ~ 320 "
OPERATION INDICATOR
OPERATION INDICATOR
No.
1
SymptomOperation indicator lamp
Condition
Correspondence
Abnormal
point
0.5-second ON
0.5-second OFF
The electricity is not conducted to the interlock switch (Fan) of the horizontal vane.
• Refer to 10-6.E "Check of installation of the horizontal vane".
Indoor unit and outdoor unit do not operate.
Attachment of the horizontal vane
All lamps flash at the same time.
No.
SymptomOperation indicator lamp
Condition
Correspondence
Abnormal
point
1
MXZ type
Operation mode setting
Outdoor unit operates but indoor unit does not operate.
The operation mode of the each indoor unit is differently set to COOL(includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at first has the priority.
• Unify the operation mode. Refer to outdoor unit service manual.
2.5-second OFF
Upper lamp lights and lower lamp flashes.
Page 20
20
Check of remote controller and indoor electronic control P.C. board
B
Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.
wCheck if the remote controller is exclusive for this air conditioner.
Yes
Replace the batteries. (Refer to 10-1.4.)
Is noise heard from radio?
Are there any fluorescent lights of
inverter or rapid-start type within the range of 1m?
Replace the indoor electronic control P.C. board. (including the receiver)
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
Press OPERATE/STOP(ON/OFF) button on the remote controller.
Is LCD display on the the remote controller visible?
Remove the batteries, then set them back and press RESET button. (Refer to 10-
1.4.) Check if the unit operates with the remote controller.
Yes
Does the unit operate with the remote controller?
Yes
OK
No
(not clear)
Yes
No
No
No
Check of indoor fan motor
A
When OPERATION INDICATOR lamp flashes 3-time. Indoor fan does not operate.
10-6. Troubleshooting flow
CN211
Indoor power P.C.board
Fuse (F11)
Indoor terminal P.C.board
Varistor (NR11)
CN121
Is the resistance 0 (short circuit) or (open circuit)?
Yes ( 0 or )
No
Yes
No
Turn OFF the power supply. Check connector CN211 visually.
Disconnect the lead wires from connector CN211 on indoor power P.C. board. Measure the resistance between lead wires No.1 and No.4 and then No.4 and No.7.
Turn ON the power supply. Rotate indoor fan slowly for 1 revo­lution or over with a screwdriver etc. from air outlet, and mea­sure the voltage No.2(+) and No.1(-) on CN121.
No
(others)
Replace the indoor power / terminal P.C. board and the indoor electronic control P.C. board.
Does the voltage repeat 0V DC and 5V DC?
Yes
No
Are lead wires connected?
Reconnect the lead wires.
Resolder it.
Replace the indoor fan motor.
Are soldered points of the
connector correctly soldered to
indoor power P.C. board?
Yes
Turn ON a radio to AM and press OPERATE/STOP(ON/OFF) button on the remote controller.
Page 21
21
The unit does not operate with the remote controller. Also, OPERATION INDICATOR lamp does not light up by pressing EMERGENCY OPERATION switch.
Check of indoor P.C. board and indoor fan motor
C
Yes
No
w. Please replace the fuse after removing the indoor terminal P.C. board from the electrical box.
Yes
No
Does the unit operate with the remote controller? Does OPERATION INDICATOR lamp light up by pressing EMERGENCY
OPERATION switch?
Turn OFF the power supply. Remove indoor fan motor connector CN211 from indoor power P.C. board and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
Measure the resistance of the vane motor coil. Refer to 10-5.
Measure the resistance Refer to 10-5 of indoor fan motor.
Short circuit: Replace the indoor fan motor.
Short circuit: Replace the vane motor and the indoor electronic control P.C. board.
Turn OFF the power supply. Check both “parts side” and “pattern side” of the indoor terminal P.C. board visually.
Replace the varistor(NR11) and fuse(F11). w
Are the varistor (NR11) burnt and the fuse (F11) blown?
Be sure to check both the fuse and the varistor in any case.
No
Yes
No
Is the fuse (F11) blown only?
Yes
No
Is the resistance normal?
Is the approx. 5VDC between 5V (+) and JPG(GND) (–) of the indoor electronic control P.C.board? Is there approx. 9V to 13VDC between 12V (+) and JPG (GND) (–) of the indoor electronic control P.C. board.
Measure the resistance of indoor fan motor. Refer to 10-5.
Replace the fuse (F11). w
Replace the fuse (F11) and the indoor fan motor. w
Is the resistance approx. 4'?
Measure the resistance of cement resistor R111 on the indoor power P.C. board.
Replace the indoor fan motor.
Yes
Connect the connector or repair disconnection.
Yes
No
Are connector CN10A on the indoor electronic control P.C. board or lead wires disconnected?
No
Replace the indoor power / terminal P.C. board.
Replace the indoor power / terminal P.C. board and the indoor fan motor.
Yes
JPG (GND)
12VDC
5VDC
CN10A
CN211
Indoor power P.C.board
Indoor electronic control P.C.board
Fuse (F11)
Indoor terminal P.C.board
Varistor (NR11)
R111
Page 22
22
How to check mis-wiring and serial signal error
D
Is there rated voltage in the power supply?
Is there any mis-wiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
W1. Mis-wiring may damage indoor P.C. board during the
operation. Be sure to confirm the wiring is correct before the operation starts.
W3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes. (Except for outdoor unit of multi system type)
(Lighted or not lighted)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
W2 Be careful to the residual voltage of smoothing capacitor.
No
No
Yes
No
Yes
Yes
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Does the upper lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power supply.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and S3. W1
B
Turn ON the power supply.
Check the wiring.
Correct them.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between indoor terminal block S2 and S3? <Confirmation of serial signal> Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
No
No
No
Yes
Yes
Yes
Replace the inverter P.C. board or the outdoor electronic control P.C.board. W2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Replace the indoor/outdoor connecting wire.
Is serial signal error indicated 6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
B
· Reinstall either the unit or the light each other away.
· Attach a filter on remote control receiving section of the indoor unit.
A
Is serial signal error indicated 6 minutes later?
Is there 2V DC or less between CN10A3(+) and JPG(GND)(–) on the indoor electronic control P.C. board?
Is there 2V DC or less between CN10A4(+) and JPG(GND)(–) on the indoor electronic control P.C. board?
Be sure to release the failure-mode recall function after checking.
Is there 2V DC or less between CN10A4(+) and JPG(GND)(–) on the indoor electronic control P.C. board?
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? W3
Replace the indoor power / terminal P.C. board.
Replace the indoor electronic control P.C. board.
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.
• When OPERATION INDICATOR lamp flashes ON and OFF every 0.5-seconds. Outdoor unit does not operate.
Page 23
23
Check of installation of the horizontal vane
E
Replace the indoor electronic control P.C. board.
Replace the interlock switch(Fan).
Is the stopper of the horizontal vane locked to the indoor unit correctly?
Yes
No
Is there resistance 0 "?
Relock the stopper of the horizontal vane to the indoor unit. (Refer to 10-1.5.)
Yes
Are all lamps flashing?
Yes
No()
No
OK
Turn ON the power supply.
To check the continuity of the interlock switch (Fan), measure the resistance of connector 1 - 2 connected to CN1R1 on the indoor electronic control P.C. board.
Turn OFF the power supply.
Turn OFF the power supply.
When All lamps flash ON and OFF every 0.5-second. Indoor unit and outdoor unit do not operate.
Page 24
24
Electromagnetic noise enters into TV sets or radios
F
Replace or repair the antenna. Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
After checking the above, consult the service representative.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
Page 25
25
Room temperature thermistor (RT11) Indoor coil thermistor (RT12, RT13)
Temperature (:)
Resistance (k")
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
1. Indoor power P.C. board, Indoor terminal P.C. board
10-7. Test point diagram and voltage
Timer short mode point JPG JPS (Refer to 8-1.)
Room temperature thermistor RT11 (CN111)
Indoor coil thermistor RT12, RT13(CN112)
Vane motor (CN151)
Connector to Indoor power P.C. board (CN10A)
12V DC
5V DC
Release of Auto restart function Solder the Jumper wire to JR07 (Refer to 8-3.)
Emergency operation switch (E.O.SW) (SW1)
2. Indoor electronic control P.C. board
Indoor terminal P.C. board Indoor power P.C. board
w Please replace the fuse after removing the indoor terminal P.C. board from the electrical box.
Fuse (F11)(w)
Varistor (NR11)
Terminal block
Connector to indoor electronic control P.C. board (CN20A)
5VDC
12VDC GND
Indoor fan motor (CN211) 230V AC
R111
}
CN121
GND
Interlock switch (FAN)(CN1R1)
Page 26
26
11
DISASSEMBLY INSTRUCTIONS
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the locking mechanism.
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
MSZ-GC22VA MSZ-GC25VA MSZ-GC35VA
OPERATING PROCEDURE
PHOTOS
Photo 1
1. Removing the panel
(1) Remove the screw caps of the panel. Remove the screws. (2) Hold the lower ends part of the panel and pull it slightly
toward you, and then remove the panel by pushing it upward.
Screws of the panel
Page 27
27
3. Remove the indoor power P.C. board, the indoor ter­minal P.C. board, and the electrical box
(1) Turn the breaker OFF. (2) Remove the panel (Refer to 1) and the corner box. (3) Remove the screw of V.A. clamp, and then the indoor/out-
door connecting wire.
(4) Remove the earth wire connected to the indoor heat
exchanger from the electrical box.
(5) Unhook first the lower, then the upper catches of the elec-
trical box, and pull out the electrical box.
(6) Remove the screw of the electrical cover and remove the
electrical cover.
(7) Disconnect all the connectors on the indoor power P.C.
board and unhook all lead wires.
(8) Remove the screw of terminal block on the indoor terminal
P.C. board.
(9) Remove the indoor power P.C. board and the indoor termi-
nal P.C. board.
OPERATING PROCEDURE PHOTOS
Lower catch
Indoor terminal P.C. board
Photo 3
2. Removing the indoor electronic control P.C. board
and the room temperature thermistor
(1) Turn the breaker OFF. (2) Remove the panel (Refer to 1) and the corner box. (3) Open the indoor electronic control P.C. board holder (to
right side), and disconnect connectors of the indoor coil thermistor (CN112), vane motor (CN151), interlock switch (CN1R1) and connector (CN10A) to the indoor power P.C. board on the indoor electronic control P.C. board.
(4) Unhook the catches of the indoor electronic control P.C.
board holder from the nozzle and the electrical box (right side).
(5) Remove the room temperature thermistor from the hook of
the indoor electronic control P.C. board holder.
(6) Open the back side of the indoor electronic control P.C.
board holder, and remove the indoor electronic control P.C. board.
(7) Remove the room temperature thermistor from the indoor
electronic control P.C. board.
Photo 2
V.A. clamp
Indoor electronic control P.C. board holder
Screw of the electrical cover
Terminal block
Indoor power P.C. board
Catch of indoor electronic control P.C. board holder
Catch of indoor electronic control P.C. board holder
Upper catch
Electrical box
Page 28
OPERATING PROCEDURE PHOTOS
4. Removing the vane motor
(1) Turn the breaker OFF. (2) Remove the panel (Refer to 1) and the corner box. (3) Remove the indoor electronic control P.C. board
holder(Refer to 2).
(4) Remove the screws of vane motor and remove the vane
motor.
(5) Disconnect the connector from vane motor.
5. Removing the indoor fan motor, the indoor coil ther­mistor, and the line flow fan
(1) Remove the panel (Refer to 1) and the corner box. (2)
Remove the indoor electronic control P.C. board holder (Refer to
2) and the electrical box (Refer to 3) .
(3)
Remove
the drain hose from the nozzle assembly, and
remove the nozzle assembly. (4) Loosen the screw fixing the line flow fan. (5) Remove the screws fixing the motor bed. Lift the right side
of motor bed a little, and pull right to remove the fan motor
together with motor band/bed. (6) Remove the indoor coil thermistor from the heat exchanger (w) Install the indoor coil thermistor in its former position when
assembling it.
(Refer to Photo 7)
(7) Remove the screws fixing the left side of the heat exchang-
er. (8) Lift the left side of the heat exchanger, and pull out the line
flow fan to the lower-left.
Photo 6
Photo 4
Screws of the vane motor
Screws of the motor bed
Photo 5
Screws of the line flow fan
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
C
Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Aug. 2007. No. OBH468 REVISED EDITION-B 6 Distributed in Feb. 2007. No. OBH468 REVISED EDITION-A 6 Distributed in Dec. 2006. No. OBH468 6 Made in Japan
New publication, effective Aug. 2007 Specifications subject to change without notice.
Photo 7
Indoor coil thermistor(sub) RT13
Indoor coil thermistor(main) RT12
Loading...