Mitsubishi Electric MSZ-GB35VA Operating Instructions Manual

Page 1
SPLIT-TYPE AIR CONDITIONERS
OPERATING INSTRUCTIONS
INDOOR UNIT
MSZ-GB35VA
For customers
Thank you very much for purchasing this Mitsubishi room air conditioner.
• To use this unit correctly and safely, be sure to read this operating instructions before use. Keep this manual carefully for later reference.
• Be sure to receive a guarantee card from your dealer and check that the purchased data and shop name, etc. are entered correctly.
SG79Y987H01_Cover.p65 07.4.16, 0:05 PM3
Page 2
This air conditioner is NOT intended for use by children or infirm persons without supervisions.
When the air filter is to be removed, do not touch the metal parts of the indoor unit.
• This may cause an injury.
Do not use an insecticide or flammable spray.
• This may cause a fire or deformation of the cabinet.
Do not put a pet or houseplant where it will be exposed to direct airflow.
• This could injure the pet or plant.
Do not leave the unit on an installation stand which is damaged.
• The unit may fall and this may cause an injury.
Do not step onto an unstable bench when maintaining the unit, etc.
• This may cause an injury, etc. if you fall down.
Do not pull the power supply cord.
• The core wire of the power supply cord may be disconnected and this may cause a fire.
Do not charge or disassemble the batteries and do not throw them into a fire.
• This may result in leakage, fire or an explosion.
Do not operate the unit for a long time in high humidity, e.g. leaving a door or window open.
• In the cooling mode, if the unit is operated in a room with high humidity (80% RH or more) for a long time, water condensed in the air conditioner may drop and wet or damage furniture, etc.
Do not operate the unit at low outside temperature (less than -10°C) in the cooling mode.
• In the cooling mode, if the unit is operated at low outside temperature (less than -10°C), water condensed in the air conditioner may drop and wet or damage furniture, etc.
CAUTION
Do not use intermediate connection of the power supply cord or the extension cord and do not connect many devices to one AC outlet.
• A fire or an electric shock may result from poor contact, poor insulation, exceeding the permissible current, etc.
Do not scratch or process the power supply cord, etc.
• Do not put heavy object on the power supply cord and do not scratch or process the cord. The cord may be damaged and this may cause a fire or an electric shock.
Do not turn the breaker off/on or disconnect/connect the power supply plug during operation.
• This may cause a fire due to spark, etc.
• Be sure to turn off the breaker or disconnect the power supply plug absolutely after switching the indoor unit off with the remote controller.
Do not expose your skin directly to cool air for a long time.
• This could damage your health.
The customer should not install this unit.
• If this is done incorrectly, it may cause a fire, an electric shock, or injury from the unit falling, water leaking, etc. Consult your dealer.
Do not insert your finger or a stick, etc. into the air inlet/outlet.
• Since the fan rotates at high speed, this may cause an injury.
• Young children should be supervised to ensure that they do not play with the air conditioner.
When an abnormality (burning smell, etc.) occurs, stop the air conditioner and disconnect the power supply plug or turn off the breaker.
• If the unit continues to be operated in an abnormal condition, it may cause a fire, trouble, etc. In this case, consult your dealer.
Repairs or relocation should not be done by the customer.
• If this is done incorrectly, it may cause a fire, an electric shock, or injury from the unit falling, water leaking, etc. Consult your dealer.
• If the power supply cord is damaged, it must be replaced by the manufacturer or its service agent in order to avoid a hazard.
WARNING
ENCLOSURE
AIR OUTLET
Page 3
3
CAUTION
WARNING
CAUTION
NAME OF EACH PART
Indoor unit
Air cleaning filter (Anti-Allergy Enzyme Filter, Blue bellows type)
Vertical vane
Operation section
(When the front panel is opened)
Front panel
Air inlet
Display section
Air outlet
Emergency operation switch
Remote control receiving section
Horizontal vane
Remote controller
Catechin air filter
Heat exchanger
Fan
Fan guard
Operation Indicator lamp
Outdoor unit
Air inlet (back and side)
Piping
Drainage hose
Air outlet
Drain outlet
Page 4
On-timer button
CLOCK set button
TIME set buttons Forward button Backward button
Vane control button
Off-timer button
PREPARATION BEFORE OPERATION
Auto restart function
These models are equipped with an auto restart function. If you do not want to use this function, please consult the service representative because the setting of the unit needs to be changed.
Auto restart function is ...
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature and the fan speed are stored in the memory. If a power failure occurs or the main power is turned off during operation, Auto restart function sets automatically to start operating in the same mode as the one set with the remote controller just before the shutoff of the main power. (Refer to page 6 for details.)
Outdoor unit
Insert the power supply plug into the power outlet and/or turn the breaker on.
WARNING: Remove dirt from the power supply plug and insert the plug securely. If dirt adheres to the plug or insertion is incomplete, it may cause a fire or an electric shock.
Remote controller
Use the remote controller provided with the unit only. Do not use other remote controller.
Temperature buttons
ON/OFF
TOO
COOL
CLOCK
˚C
TOO
WARM
Page 5
5
When the remote controller cannot be used (emergency operation)
When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the EMERGENCY OPERATION switch.
Handling of the remote controller
The range that the signal can reach is about 6 m when the remote controller is pointed at the front of the indoor unit.
When a button is pressed, one or two beeps will be heard from the indoor unit. If no sound is heard, operate again.
Use the remote controller carefully. If it is dropped, thrown or it gets wet, the remote controller may not operate.
When installing on a wall, etc.
Install the remote controller holder in a position where the signal reception sound (beep) can be heard from
the indoor unit when the
ON/OFF
button is pressed.
How to install/remove the remote controller
Installing :Insert the remote controller downward. Removing :Pull it up.
Dry-cell batteries
Reference for replacing batteries Replace the batteries with new AAA alkaline batteries in the following cases:
· When the indoor unit does not respond to the remote
control signal.
· When the display on the remote controller becomes
dim.
· When a button of the remote controller is pressed, all
displays appear on the screen, and then disappear immediately.
Do not use manganese batteries. The remote controller could malfunction.
The service life of an alkaline battery is about 1 year. However, a battery whose time limit is approaching may be exhausted soon. The recommended usable time limit is indicated (month/year) on the bottom of the battery.
To prevent liquid leakage, take out all batteries when the remote controller is not going to be used for a long time.
CAUTION: If liquid from the batteries gets onto your skin or clothes, wash it well with clean water. If liquid from the batteries gets into your eyes, wash them well with clean water and consult a doctor at once.
Do not use rechargeable batteries.
Replace the 2 batteries with new ones of the same
type.
Dispose of exhausted batteries in the correct manner.
button
2 To stop the emergency operation, press the
EMERGENCY OPERATION switch once (in case of EMERGENCY HEAT MODE) or twice (in case of EMERGENCY COOL MODE).
1 Press the EMERGENCY OPERATION switch.
Each time the EMERGENCY OPERATION switch is pressed, the unit will operate in order of EMERGENCY COOL MODE, EMERGENCY HEAT MODE and STOP MODE. However, when the EMERGENCY OPERATION switch is once pressed, the unit will operate in test run for 30 minutes and then the operation mode shifts to EMERGENCY MODE.
Details of EMERGENCY MODE are as shown below. However, the temperature control does not work for 30 minutes in test run and the unit is set to continuous operation. The fan speed is set to High in test run and shifts to Medium after 30 minutes.
Operation mode COOL HEAT
Set temperature 24°C24°C
Fan speed Medium Medium
Horizontal vane Auto Auto
The operation mode is indicated by the Operation Indicator lamp on the indoor unit as following figure.
Operation Indicator lamp
EMERGENCY COOL
EMERGENCY HEAT
STOP
Remote controller holder
➝ ➝
Page 6
ON/OFF
button.
ON/OFF
button.
ON/OFF
button.
Description of AUTO RESTART FUNCTION
These units are equipped with an auto restart function. When the main power is turned on, the air conditioner will start operation automatically in the same mode as the one set with the remote controller before the shutoff of the main power.
If the unit was set to off with the remote controller before the shutoff of the main power, it will remain stopped even after the main power is turned on.
If the unit is operated in
AUTO” mode before power failure, the operation mode (COOL, DRY or HEAT) is not stored in the memory. When the main power is turned on, the unit decides the operation mode by the initial room temperature at restart and starts operation again.
Information for multi system air conditioner
Multi system air conditioner can connect two or more indoor units with one outdoor unit. According to the capacity, two or more units can operate simultaneously.
When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units that will start the operation later cannot operate, indicating an operation state. (Refer to the table of Operation Indicator lamp below.) In this case, please set all the indoor units to the same operation mode.
When indoor unit starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10 minutes) to blow out the warm air.
In the heating operation, the indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard. This is not a malfunction since the refrigerant continuously flows into the indoor unit that does not operate.
Details of display on the indoor unit
The operation indicator at the right side of the indoor unit indicates the operation state.
Operation Indicator
Lighted Blinking Not lighted
Operation indicator lamp
Indication
Difference between target
temperature and room temperature
Operation state
This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained.
This shows that the room temperature is approaching the target temperature.
This shows a state of standby for operation. Please refer to Information for multi system air conditioner above.
About 2°C or more
About 2°C or less
MODE
Page 7
7
Change the fan speed.
Fan speed: Med. or upper
ON/OFF
ON/OFF
ON/OFF
AIR FLOW VELOCITY AND DIRECTION ADJUSTMENT
To change the AIR FLOW velocity, press the button.
Each time the button is pressed, the fan speed is changed in sequence:
(Low) (Med.) (High) (Super High) (AUTO)
Use the
(Super High) notch to cool/heat the room more efficiently.
If the operating sound of the air conditioner disturbs your sleep, use the (Low) notch.
To change the AIR FLOW blowing direction vertically, press the
button.
Each time the button is pressed, the angle of the horizontal vane is changed in sequence:
(1) (2) (3) (4) (SWING) (AUTO)
SWING OPERATION
Use the swing operation for the air flow to reach all corners of the room.
Recommended horizontal vane range for more efficient air-conditioning
Use the (AUTO) position usually. Use position (1) in the COOL or DRY mode and use positions (2) to (4) in the HEAT mode when
adjusting to your requirements.
FAN
VANE
1
2
3
4
HEAT
COOL
DRY
MODE
AIR FLOW velocity and direction can be selected as required.
Page 8
Immediately after the air conditioner starts operating, the vane stays at horizontal position. Once the air from the indoor unit becomes sufficiently warm, the vane moves to position (4).
Once the air conditioner starts operating, the fan speed increases gradually as the air from the indoor unit gets warmer, and continues until the set speed is finally reached.
At the start of heating operation
Horizontal position
When air becomes warm
Position (4)
Very small air flow
Immediately after the air conditioner starts operating, the vane stays at horizontal position. Once the air from the indoor unit becomes sufficiently warm, the vane moves to the position corresponding to the set direction of air flow.
Once the air conditioner starts operating, the fan speed increases gradually as the air from the indoor unit gets warmer, and continues until the set speed is finally reached.
The vane moves intermittently between positions (2) and (4). The vane stops for a brief period at positions (2) and (4).
At the start of heating operation
Horizontal position
Very small air flow
When air becomes warm
Set position
Adjust the vane before operation starts. Since the horizontal vane moves automatically, your fingers may be caught.
To change the air flow direction not to blow directly onto your body.
To change the air
flow direction
Pressing and holding
the
VANE
button for 2
seconds or more causes the horizontal vane to reverse and move to horizontal position.
Horizontal position
When to use this function?
Use this function if you don’t want the air from the indoor unit to blow directly onto your body.
Depending on the shape of the room, the air may blow directly onto your body.
Press the
VANE
button again
to return the vane to the previously-set position.
COOL/DRY
The air conditioner starts the cooling or drying operation approx. 3 minutes after the vane has moved to the horizontal position.
When the
VANE
button is
pressed again, the vane returns to the previouslyset position and the air conditioner starts the cooling or drying operation in approx. 3 minutes.
HEAT
The air conditioner starts heat­ing operation approx. 3 min­utes after the vane has moved to the horizontal position.
Sometimes the area around your feet may not warm. To warn the area around the feet, set the horizontal vane to (AUTO) or the downwardblowing position.
When the
VANE
button is
pressed again, the vane returns to the previously-set position and the air condi­tioner starts heating opera­tion in approx. 3 minutes.
To change the horizontal direction of the air flow, move the vertical vane manually.
NOTE:
If you make the air flow not to blow directly onto your body by pressing
VANE
button, the compressor stops for 3 minutes
even during the operation of the air conditioner.
The air conditioner operates with decreased air flow until the compressor turns on again.
(2)
(4)
Page 9
9
WHEN THE AIR CONDITIONER IS NOT GOING TO BE USED FOR A LONG TIME
When it is not going to be used for a long time:
1 Perform the FAN operation for 3 or 4 hours
to dry the inside of the air conditioner.
To perform FAN operation, set the remote controller to the highest temperature in the MANUAL COOL mode. (Refer to page 7.)
2 Turn off the breaker and/or disconnect the
power supply plug.
CAUTION: Turn off the breaker or disconnect the power supply plug when the air conditioner is not going to be used for a long time. Dirt may collect and this may cause a fire.
3 Remove the batteries from the remote con-
troller.
CAUTION: To prevent liquid leakage, take out all batteries when the remote controller is not going to be used for a long time.
When the air conditioner is to be used again:
1 Clean the air filter and install it in the indoor
unit.
(Refer to page 10 for cleaning instructions.)
2 Check that the air inlet and outlet of the in-
door/outdoor units are not blocked with any obstacles.
3 Check that the earth is connected correctly.
CAUTION: Earth the unit. Do not connect the earth to a gas pipe, water pipe, lightning rod or the earth of a telephone. If the earthing is incorrect, it may cause an electric shock.
FAN
button, the
TOO
WARM
or
TOO
COOL
button and ON/OFF timer (explained below)
How to set the OFF timer
1 Press the button during operation.
Each time the button is pressed, the OFF timer mode alternates between ON and OFF.
2 Set the time of the timer using the TIME but-
tons (Forward) and (Backward).
Each time the button is pressed, the set time in­creases by 10 minutes; each time the
button is
pressed, the set time decreases by 10 minutes.
To release the OFF timer:
Press the button.
MAINTENANCE
Before starting maintenance
Turn off the breaker and/or disconnect the power supply plug.
CAUTION: When the unit is to be cleaned, switch it off and disconnect the power supply plug or turn off the breaker. Since the fan rotates at high speed during operation, it may cause an injury.
Cleaning the indoor unit
Clean the unit using a soft dry cloth.
If the dirt is noticeable, wipe the unit with a cloth soaked in a solution of mild detergent diluted in lukewarm water.
Do not use gasoline, thinner, benzine, polishing powder, or insecticide. The unit may be damaged.
The front panel may come off if it is lifted up past its level position. If the front panel comes off, refer to step 3 in CLEANING THE FRONT PANEL.
ECONO COOL
ECONO COOL
VANE
STOP
STOP
Page 10
Heat exchanger
Remove the catechin air filter before cleaning
the heat exchanger.
You can sweep the surface of heat exchanger if you install the brush of QUICK CLEAN KIT to your vacuum cleaner. Please refer to the instructions described in QUICK CLEAN KIT for details.
WARNING:
Do not touch the heat exchanger directly with your hands. Otherwise you may get injured. (It’s recommended to protect your hands with a pair of gloves.)
CAUTION:
Do not step onto an unstable bench when cleaning. Otherwise you may fall down and get injured.
Use only the brush of QUICK CLEAN KIT. Do not use other stuffs. Otherwise the heat exchanger of the indoor unit may get damaged.
Optional product
Name of parts Quick Clean Kit
Parts number MAC-093SS-E
Optional product is available from your local dealer.
NOTE: The QUICK CLEAN KIT can only be fitted to a vacuum cleaner with a hose/tube diameter (inside diameter) of 32 to 39 mm. Refer to the instructions of the QUICK CLEAN KIT.
Fan
Refer to page 12 for cleaning the fan.
Heat exchanger
CLEANING THE CATECHIN AIR FILTER
Cleaning the catechin air filter (about once every 2 weeks)
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
What is Catechin air filter”?
The air filter is dyed with a natural material, catechin, that is contained in tea. The catechin air filter deodorizes odor and noxious gases such as formaldehyde, ammonia, and acetaldehyde. Moreover, it restraints the activity of the viruses adhering to the filter.
1 Remove the catechin air filter.
CAUTION: When the catechin air filter is to be removed, do not touch the metal parts of the indoor unit. This may cause an injury.
2 Remove dirt from the catechin air filter us-
ing a vacuum cleaner or by washing the fil­ter with water.
Do not wash with scrubbing brush or hard surface of sponge. Otherwise, the filter may deform.
If the dirt is noticeable, wash the filter with a solution of mild detergent diluted in lukewarm water.
If hot water (50 °C or more) is used, the filter may be deformed.
3 After washing with water/lukewarm water, dry
the catechin air filter well in the shade.
Do not expose the catechin air filter to direct sunlight or heat from a fire when drying it.
4 Install the catechin air filter.
(Securely install its tabs.)
Install.
Open the front panel, then remove/replace the filter.
Remove.
Catechin air filter
Page 11
11
3 Soak the filter together with its frame in luke-
warm water and wash it.
If the dirt is noticeable, use a solution of mild detergent diluted in lukewarm water.
If hot water (50°C or more) is used, the filter may be deformed.
Do not use a scrubbing brush or sponge. This may damage the surface of the filter.
Do not use a chlorine detergent.
4 After rinsing with water/lukewarm water,
shake off the excess water and dry the filter well in the shade.
Do not expose the filter to direct sunlight or heat from a fire when drying it.
REPLACEMENT OF THE AIR CLEANING FILTER
When the capacity is lowered because of dirt, etc., it is necessary to replace the air cleaning filter.
Air cleaning filter replacement (about once every year)
1 Remove the catechin air filter (left one).
The air cleaning filter is not attached to the right side catechin air filter.
2 Pull up the tabs on both sides of the air clean-
ing filter with your finger and remove the air cleaning filter (blue bellows type) from the catechin air filter.
3 Attach a new air cleaning filter to the catechin
air filter so that all 8 tabs on the catechin air filter are securely installed.
4 Install the catechin air filter. (Securely install
its tabs.)
5 Securely close the front panel.
Catechin air filter
Catechin air filter (Back side)
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Air cleaning filter
If the air cleaning filter is clogged, it may lower the units capacity or cause condensation at the air outlet.
The air cleaning filter is disposable. The standard usable term is about 1 year.
Optional parts Optional parts are available from your local dealer.
Name of parts
Parts number MAC-415FT-E
This optional part is for the replacement of the left side filter only. No optional part is available for the right side filter.
AIR CLEANING FILTER
(Anti-Allergy Enzyme Filter)
Page 12
Upward.
12
Stopper
Unlock.
2 Hold the tab of each vertical vane and move the
vertical vanes in the directions of the arrows. The vanes cannot be removed.
Swing to the left.
Swing to the right.
Cannot be removed.
4 Clean the air outlet and fan of the indoor unit. (Make sure the fan has stopped.)
Be careful not to injure your hands.
If the air outlet or fan is dirty, moldy, or dusty, clean with a wet or dry soft cloth or with the brush of QUICK
CLEAN KIT which is installed to a vacuum cleaner. If the dirt is noticeable around the air outlet, clean with a cloth soaked in a solution of mild detergent diluted in lukewarm water.
Please refer to the instructions described in QUICK CLEAN KIT for the details of the way to clean with the brush of QUICK CLEAN KIT.
Do not use gasoline, benzine and polishing powder.
Do not use excessive force to the fan. Otherwise, it may be cracked.
Groove
1
2
Stopper
Insert this end first.
Left
Lock.
5 Put the vertical vanes back to their original positions one by one.
2
Push each vertical vane until it clicks into place.
1
Hold the tab of each vertical vane and insert the vertical vanes into their respective grooves.
Be sure to hold the tabs to install the vertical vanes, otherwise the vanes can be damaged.
Do not use excessive force to the fan guard during this procedure. The fan guard may be deformed and
the vanes may not work properly.
Put the vertical vanes back correctly to their original positions. Otherwise, condensed water may drip down from the indoor unit or the horizontal vane could malfunction.
6 Install the horizontal vanes. (Reverse the removal procedures.)
Insert the power supply plug into the power outlet and/or turn on the breaker. Check that all LED lamps are not blinking. If they are blinking, the horizontal vane is not installed correctly. In this case, disconnect the power supply plug and/or turn off the breaker, and then reinstall the horizontal vane by following the procedures in step 6.
If you operate the air conditioner after cleaning the air outlet and fan, do not get close to the air outlet as any remaining dirt may be discharged.
After Cleaning
In procedure 2 lock the stoppers until they click into place.
Page 13
13
Question
The air conditioner cannot be operated for about 3 minutes when restarted.
Cracking sound is heard.
The air from the indoor unit smells strange.
The fan of the outdoor unit does not rotate even though the compressor is running. Even if the fan starts to rotate, it stops soon.
The sound of water flowing is heard.
The sound as burbling is heard.
The room cannot be cooled sufficiently.
Mist is discharged from the air outlet of the indoor unit.
Mechanical sound is heard from the indoor unit.
The swing operation of the HORIZONTAL VANE is suspended for about 15 seconds, then restarted.
Answer (not a malfunction)
This protects the air conditioner according to instructions from the microprocessor. Please wait.
This sound is generated by the expansion/ contraction of the front panel, etc. due to change in temperature.
The air conditioner may suck in an odor adhering to the wall, carpet, furniture, cloth, etc. and blow it out with the air.
When the outside temperature is low, the fan may not operate to maintain sufficient cooling capacity.
This is the sound of refrigerant flowing inside the air conditioner.
This is the sound of condensed water flowing in the heat exchanger.
This is the sound of the heat exchanger defrosting.
This sound is heard when the outside air is absorbed from the drain hose in turning on the range hood or the ventilation fan and that makes water flowing in the drain hose spout out. This sound is also heard when the outside air blows into the drain hose in case the outside wind is strong.
When a ventilation fan or a gas cooker is used in a room, the cooling load increases, resulting in an insufficient cooling effect.
When the outside air temperature is high, the cooling effect may not be sufficient.
The cool air from the air conditioner rapidly cools moisture in the air inside the room, and it turns into mist.
This is the switching sound in turning on/off the fan or the compressor.
This is for the swing operation of the HORIZONTAL VANE to be performed normally.
WHEN YOU THINK THAT TROUBLE HAS OCCURRED
Question
The air flow direction changes during operation. The direction of the horizontal vane cannot be adjusted with the remote controller.
Water leaks from the outdoor unit.
White smoke is discharged from the outdoor unit.
Air does not blow out soon in the heating operation.
The operation is stopped for about 10 minutes in the heating operation.
Hissing sound is sometimes heard.
The room cannot be heated sufficiently.
In a multi-unit system, the indoor unit which is not operating becomes warm and a sound, similar to water flowing, is heard from the unit.
The air conditioner starts the operation only with the main power turned on, though you do not operate the unit with the remote controller.
Answer (not a malfunction)
When the air conditioner is operated in COOL or DRY mode, if the operation continues with air blowing down for 1 hour, the direction of the air flow is automatically set to position (1) to prevent condensed water from dropping.
In the heating operation, if the air flow temperature is too low or when defrosting is being done, the horizontal vane position is automatically set to horizontal.
During COOL and DRY operations, pipe or pipe connecting sections are cooled and this causes water to condense.
In the heating operation, the defrosting operation makes water frozen on the outdoor unit melt and drip down.
In the heating operation, water condensed on the heat exchanger drips down.
In the heating operation, vapor generated by the defrosting operation looks like white smoke.
Please wait as the air conditioner is preparing to blow out warm air.
Defrosting of the outdoor unit is being done (Defrosting operation). Since this is completed in 10 minutes, please wait. (When the external temperature is too low and humidity is too high, frost is formed.)
This is the sound when the flow of refrigerant inside the air conditioner is switched.
When the outside air temperature is low, the heating effect may not be sufficient.
A small amount of refrigerant continues to flow into the indoor unit even though it is not operating.
These models are equipped with an auto restart function. When the main power is turned off without stopping the air conditioner with the remote controller and is turned on again, the air conditioner will start operation automatically in the same mode as the one set with the remote controller just before the shutoff of the main power.
Page 14
CAUTION:
Earth the unit. Do not connect the earth to a gas pipe, water pipe, lightning rod or the earth of a telephone. If the earthing is incorrect, it may cause an electric shock.
Install an earth leakage breaker depending on the place where the air conditioner is to be installed (humid places, etc.). If the earth leakage breaker is not installed, it may cause an electric shock.
Inspection and maintenance
When the air conditioner is used for several seasons, the capacity may be lowered due to dirt inside the unit.
Depending on the condition, an odor may be generated or dehumidified water may not drain out smoothly due to dirt,
dust, etc.
It is recommended that the unit be inspected and maintained (charged) by specialist in addition to normal maintenance. Consult your dealer.
Operating sound considerations
Do not put an object around the air outlet of the outdoor unit. This may lower the capacity or increase the volume of the operating sound.
If an abnormal sound is heard during operation, consult your dealer.
Relocation
When the air conditioner is to be removed or re-installed because of rebuilding, moving, etc., special techniques and work are required.
WARNING: Repairs or relocation should not be done by the customer. If this is done incorrectly, it may cause a fire, an electric shock, or an injury from the unit falling, water leaking, etc. Consult your dealer.
Disposal
To dispose of this product, consult your dealer.
If you have any questions, consult your dealer.
To prevent the effects of a fluorescent lamp, keep as far apart as possible.
wall, etc.
Inverter-type fluorescent lamp
Keep a space to prevent the picture distortion or the noise.
1 m or more
Radio
100 mm or more
Well­ventilated dry place
200 mm or more
TV
Cordless phone or Portable phone
3 m or more
1 m or more
The installation location of the outdoor unit should be at least 3 m away from the antennas for TV sets, radios, etc. In areas where the reception is weak, pro­vide greater space between the outdoor unit and the antenna of the affected device if operation of the air conditioner interferes with radio or TV reception.
Page 15
Page 16
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODAKU, TOKYO 100-8310, JAPAN
SG79Y987H01
SG79Y987H01_Cover.p65 07.4.16, 0:05 PM2
Loading...