Mitsubishi MSZ-GA25VA - E2, MSZ-GA25VA - E3, MSZ-GA35VA - E1, MSZ-GA35VA - E2, MSZ-GA35VA - E3 Service Manual

...
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Wireless type Models
Revision C:
• 3.SPECIFICATION has been corrected.
Please void OB378 REVISED EDITION-B.
No. OB378
REVISED EDITION-C
MSZ-GA22VA ­MSZ-GA22VA ­MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA25VA ­MSZ-GA25VA ­MSZ-GA35VA ­MSZ-GA35VA ­MSZ-GA35VA -
E1
E2
E3
E1
E2
E3
E1
E2
E3
Outdoor unit service manual
MUZ-GA·VA Series (OB379) MXZ-A·VA Series (OB377) MXZ-8A140VA1 (OC316)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
10. DISASSEMBLY INSTRUCTIONS·····················24
11. PARTS LIST······················································27
12. RoHS PARTS LIST···········································31
13. OPTIONAL PARTS ···········································34
NOTE:
RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
Revision A:
• MSZ-GA·VA- has been added. Color of BOX and CORNER BOX has been changed to white.
E2
Revision B:
E3
model has been added.
• Failure mode recall function(9-2.) has been changed.
• RoHS PARTS LIST has been added.
Revision C:
• 3.SPECIFICATION has been corrected. Air flow of indoor units connecting to MXZ-8A140VA
1 has been corrected.
1
MSZ-A09YV - MSZ-GA22VA ­MSZ-A09YV - MSZ-GA25VA ­MSZ-A12YV - MSZ-GA35VA -
1. Indication of capacity has been changed.(BTU base kW base)
2. Control method between indoor and outdoor has been changed.
3. Power supply method has been changed (change to supply from outdoor unit).
4. Power supply cord has been removed.
5. Indoor electronic control P.C. board has been changed.
6. Position of terminal block has been changed.
7. Indoor fan motor has been changed. ( AC ➔ DC)
8. Indoor heat exchanger has been changed.
9. The horizontal vane motor unit has been changed. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
10. Air cleaning filer has been removed (available as an optional part).
11. Signal of remote controller has been changed. ( It is not available for the conventional models.)
12. Symbol on terminal block has been changed (to S1/S2/S3).
MSZ-GA22VA- MSZ-GA22VA­MSZ-GA25VA- MSZ-GA25VA­MSZ-GA35VA- MSZ-GA35VA-
1. Color of BOX and CORNER BOX has been changed to white.
TECHNICAL CHANGES
E1E1 E1E1 E1E1
NOTE:
Do not remove the vane motor from the motor unit. Do not disassemble the horizontal vane motor unit.
Generalized stepping motor
E2E1 E2E1 E2E1
MSZ-GA22VA- MSZ-GA22VA­MSZ-GA25VA- MSZ-GA25VA­MSZ-GA35VA- MSZ-GA35VA-
1. The operation of thermo-off-unit has been changed. (When 2 or more indoor units are connected with a multi type outdoor unit, and operated in heat mode.)
E2E1
< , > Indoor fan operates with very Low speed or stops.
E3
< > Indoor fan operates intermittently with very Low speed or stops.
MSZ-GA25VA- MSZ-GA25VA-
1. Indoor fan speed has been changed.
E3E2 E3E2 E3E2
E3E2
2
2
Line flow fan
Air outlet Vertical vane
Air inlet
Display section
Front panel
Panel
Heat exchanger
Horizontal vane
Operation section
(When the front panel is opened)
Remote controller
Remote control receiving section
Catechin air filter
Air cleaning filter (Optional parts,Anti­Allergy Enzyme Filter, Blue bellows type)
Emergency operation switch
Fan guard
Operation Indicator lamp
PART NAMES AND FUNCTIONS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
3
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
1 5 1 2 2 1 1
MSZ-GA22VA
ON-TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
OFF-TIMER button
(This diagram shows an overall view.)
Open the front lid.
RESET button
VANE CONTROL button
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of remote controller model is on back
MSZ-GA25VA MSZ-GA35VA
ACCESSORIES
REMOTE CONTROLLER
4
3
T3.15AL 250V
MSBPC20M16 12V DC 250" (at 25˚C)
ERZV14D471
3P
INDOOR UNIT
Item Fuse Horizontal vane motor Varistor Terminal block
(F11)
(MV)
(NR11)
(TB)
MSZ-GA25VA MSZ-GA22VA MSZ-GA35VA
Indoor model
Function
Power supply
1
Single phase
230V,50Hz
630/504 384/258
10
0.25 33 57
0.25
RC0J30-CC
780O298O210
9 4
43
36/29/21
1,250/1,040
830/620
4
KM05B
Single phase
230V,50Hz
10
0.25 33 57
0.25
RC0J30-CC
780O298O210
9 4
43
36/29/21
4
KM05B
43
36/29/21
1,100
43
36/29/22
Cooling
600/480 366/234
1,200/1,000
800/580
2
486/408 336/258
1,010/880
750/620
Cooling
600/480 366/234
1,200/1,000
800/580
Heating
630/504 384/258
1,250/1,040
830/620
Single phase
230V,50Hz
10
0.25 33 57
0.25
RC0J30-CC
780O298O210
9 4
43
36/29/22
4
KM05B
Cooling
600/480 366/246
1,200/1,000
800/600
Heating
630/504 384/270
1,250/1,040
830/640
Air flow(Super High/High) Air flow(Med./Low) Power outlet Running current 1 Power input 1 Power factor 1 Fan motor current 1 Model Dimensions WOHOD Weight Air direction Sound level(Super High) Sound level(High/Med./Low)
Fan speed(Super High/High)
Fan speed(Med./Low) Fan speed regulator
Remote controller model
K /h
A
A W %
A
mm
kg
dB(A) dB(A)
rpm
Electrical
data
Fan motor
Special
remarks
Capacity
MSZ-GA25VA MSZ-GA22VA MSZ-GA35VA
Indoor model
Function
Cooling
528
432/336/234
930/760/580
Heating
540
420/366/258
900/800/620
Cooling
528
432/336/234
930/760/580
Heating
540
420/366/258
900/800/620
Cooling
582
468/354/246
1,200
1,000/800/600
Heating
618
504/390/270
1,230
1,040/850/640
Air flow(Super High) Air flow(High/Med./Low) Sound level(Super High) Sound level(High/Med./Low) Fan speed(Super High) Fan speed(High/Med./Low)
K /h K /h
dB(A) dB(A)
rpm rpm
Special
remarks
Capacity
43
36/29/21
1,100
Heating
1 :
E1 , E2 (serial number : ~ 6024700)
2 :
E2 (serial number : 6024701 ~) , E3
SPECIFICATION
When outdoor unit is MXZ-8A140VA
NOTE : Test conditions are based on ISO 5151
Specifications and rating conditions of main electric parts
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19: Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15: Refrigerant piping length (one way): 5m
1 Measured under rated operating frequency.
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24: Outdoor Dry-bulb temperature 7:Wet-bulb temperature 6:
1.
5
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
43 43
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
INDOOR UNIT
WALL
MICROPHONE
0.8m
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
43 43
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
NOISE CRITERIA CURVES
MSZ-GA22VA MSZ-GA25VA
MSZ-GA35VA
6
5
155 155
335 320
41.5 215
42.5
214
3
287.5
7055
5555 225 225
or more7
100
90
106
298
102624.5
780
210 5
53.5 19
159
58
14273.5
234
Air in
Air out
Wall hole [65
Indoor unit
Installation plate
Installation plate
11X20 Oblong hole
11X26 Oblong hole
10 or more
75 or more
66 or more
W
75 or more
W
In case of left, left back, or
left under piping (using spacer),
115 or more
Insulation [28
Drain hose [16 (Connected part O.D)
Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [35 O.D [19 I.D
{
Required space (Indoor unit)
OUTLINES AND DIMENSIONS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
Unit : mm
7
6
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12(main)
SYMBOL
DB111
F11
MF
MV
NR11
SYMBOL
RT11 RT12 RT13
T111
TB
NAME DIODE STACK FUSE (T3.15AL250V) INDOOR FAN MOTOR VANE MOTOR (HORIZONTAL) VARISTOR
NAME ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB) TRANSFORMER TERMINAL BLOCK
4 3 2 1
S2
POWER MONITOR RECEIVER P.C.BOARD
2
6
230V~
BLU
INDOOR ELECTRONIC CONTROL P.C. BOARD
SW P.C. BOARD
INTERLOCK SWITCH(FAN)
5
MV
TO OUTDOOR UNIT CONNECTING
BLK
RED
S3
TB
TAB3
DB111
NR11
F11
5
6
4
2
2
LD
105(T)
LD
101(A)
12-24V
RT13
1R1
CN
GRN
LD104
CN201
2 1
151
CN
T111
RED
WHT
111
CN
CN
112
CN211
BLU
YLW
BLK
MF
RT11
RT12
1 3 5
S1
WIRING DIAGRAM
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
7
REFRIGERANT SYSTEM DIAGRAM
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
8
Unit : mm
8
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For modification, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish modification, put back the batteries then press the RESET button.
J1
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J2
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
9
Housing point
JR07
CN151 CN211CN112 CN1R1
BZ
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The AUTO RESTART FUNCTION sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
1
If the main power has been cut, the operation settings remain.
2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release AUTO RESTART FUNCTION
1
Turn OFF the main power for the unit.
2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the
remote controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn ON at the
same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure,
the starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
9
TROUBLESHOOTING
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
10
3. Troubleshooting procedure
RESET button
Insert the negative pole of the batteries first. Check if the polarity of the batteries is correct.
OPERATION INDICATOR
Not lighted
Blinking
Lighted
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, all of the operation indicator lamps will blink. In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
Stopper
21
Left
In procedure stoppers until they click into place.
Lock.
Insert this end first.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
Unit wont operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
22
lock the
When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10 minutes) to blow out the warm air.
In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
11
9-2. Failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does the left lamp of OPERATION INDICATOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table(Refer to 9-2.2.). Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply. <
Preparation of the remote controller
> 1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons after all LCD except the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way. Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table (Refer to outdoor unit service manual.) Make sure to check at least two consecutive blinking cycles. W3
W1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
12
2. Indoor unit failure mode table
12-time flash
2.5-second OFF
Replace the indoor electronic control P.C. board.
Indoor control system
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
11-time flash
2.5-second OFF
Refer to 9-6.A "Check of indoor fan motor".
Indoor fan motor
The rotational frequency feedback signal is not emit during the 12-second the indoor fan operation.
2-time flash
2.5-second OFF
Refer to the characteristics of the main indoor coil thermistor, the sub indoor coil thermistor (Refer to 9-7.).
Indoor coil thermistor
The indoor coil thermistor short or open circuit is detected every 8 seconds during operation.
3-time flash
2.5-second OFF
Refer to 9-6.D "How to check mis-wiring and serial signal error".
Serial signal
The serial signal from outdoor unit is not received for a maximum of 6 minutes.
1-time flash every 0.5-second
Refer to the characteristics of the room temperature thermistor (Refer to 9-7.).
Room temperature thermistor
The room temperature thermistor short or open circuit is detected every 8 seconds during operation.
Not lighted Normal
Left lamp of OPERATION
INDICATOR lamp
Correspondence
Abnormal point (Failure mode)
Condition
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table(9-4.).
13
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates only in Test Run operation.
w
Outdoor unit doesn't operate even in Test Run operation.
w
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to 9-7. "Test point diagram and voltage".
Refer to "How to check inverter/ compressor".
Refer to 9-6.B "Check of remote controller and receiver P.C. board".
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to 9-6.C "Check of indoor electronic control P.C. board and indoor fan motor".
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to "Check of R.V. coil".
Left lamp Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit
Mis-wiring or trouble of serial signal
Left
lamp 2-time flash Cause: Indoor unit
Trouble of room temp­ erature/ indoor coil thermistor
Left
lamp 3-time flash Cause: Indoor unit
Trouble of indoor fan motor
Left lamp 5-time flash Cause: Outdoor unit
Outdoor power system abnormality
Left lamp 6-time flash Cause: Outdoor unit
Trouble of thermistor in outdoor unit
Left lamp 7-time flash Cause: Outdoor unit
Trouble of outdoor control system
Refer to 9-6. D "How to check of mis-wiring and serial signal error
".
All lamps Flash on and off at 0.5-second intervals Cause: Indoor unit
The horizontal vane is not installed correctly.
Refer to 9-6. E "Check of installation of the horizontal vane".
Check room temperature thermistor and indoor coil thermis­tor. Refer to 9-7. "Test point diagram and voltage".
Refer to 9-6. A "Check of indoor fan motor".
Refer to "How to check inverter/ compressor".
Refer to "Check of outdoor thermistors".
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
Left lamp 14-time flash Cause: Outdoor unit
Other abnormality
Check "Flow chart of the detailed outdoor unit failure mode recall function."
Left lamp 4-time flash Cause: Indoor unit
Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
Refer to outdoor unit service manual.
Indoor unit operates. Outdoor unit doesn't operate normally.
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
w
"Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.
9-3. Instruction of troubleshooting
14
9-4. Troubleshooting check table
Not lighted
Blinking
OPERATION INDICATOR
Lighted
Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
· Flashing of OPERATION INDICATOR lamp (left-hand side lamp) indicates abnormalities.
Abnormal
No.
1
2
point
Mis-Wiring or serial signal
Outdoor control system
Left lamp flashes.
0.5-second ON
0.5-second OFF
Left lamp lights up
SymptomOperation indicator lamp
Indoor unit and outdoor unit do not operate.
Outdoor unit does not operate.
The serial signal from the outdoor unit is not received for a maximum of 6 minutes.
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
Condition
Correspondence
Refer to 9-6.D "How to check mis-wiring and serial signal
error".
Check the blinking pattern of the LED on the inverter P.C. board or the outdoor electronic control P.C. board.
Indoor coil thermistor
3
Room tempera­ture thermistor
Indoor fan
4
motor
Indoor control
5
system
Outdoor power
6
system
Outdoor
7
thermistors
Outdoor control
8
system
Other
9
abnormality
Left lamp flashes. 2-time flash
2.5-second OFF
Left lamp flashes. 3-time flash
2.5-second OFF
Left lamp flashes. 4-time flash
Left lamp flashes. 5-time flash
2.5-second OFF Left lamp flashes.
6-time flash
2.5-second OFF
Left lamp flashes. 7-time flash
Left lamp flashes. 14-time flash
2.5-second OFF
2.5-second OFF
2.5-second OFF
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
The indoor coil or the room temperature thermistor is short or open circuit.
The rotational frequency feedback signal is not emitted during the indoor fan operation.
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
It consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection within 1 minute after start-up.
The outdoor thermistors short or open circuit during the compressor operation.
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
An abnormality other than above mentioned is detected.
Refer to 9-7.the characteristics of indoor coil thermistor, and the room temperature thermistor.
Refer to 9-6.A "Check of indoor fan motor".
Replace the indoor electronic control P.C. board.
Refer to "How to check of
inverter/compressor". Refer to outdoor unit service manual.
Check the stop valve.
Refer to "Check of outdoor
thermistor". Refer to outdoor unit service manual.
Replace the inverter P.C.
board or the outdoor electronic control P.C. board. Refer to outdoor unit service manual.
Confirm the abnormality in
detail using the failure mode recall function for outdoor unit.
15
OPERATION INDICATOR
Not lighted
Blinking
Lighted
OPERATION INDICATOR
Not lighted
Blinking
Lighted
No.
1
SymptomOperation indicator lamp
Condition
Correspondence
Abnormal
point
0.5-second ON
0.5-second OFF
The electricity is not conducted to the interlock switch (Fan) of the horizontal vane.
Refer to 9-6.E "Check of installation of the horizontal vane".
Indoor unit and outdoor unit do not operate.
Attachment of the horizontal vane
All lamps flash at the same time.
No.
SymptomOperation indicator lamp
Condition
Correspondence
Abnormal
point
1
MXZ type
Operation mode setting
Outdoor unit operates but indoor unit does not operate.
The operation mode of the each indoor unit is differently set to COOL(includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at first has the priority.
Unify the operation mode. Refer to outdoor unit service manual.
2.5-second OFF
Right lamp flash
9-5. Trouble criterion of main parts
Part name FigureCheck method and criterion
Indoor fan motor(MF)
Measure the resistance with a tester. Refer to 9-7."Test point diagram and voltage",
"Indoor electronic control P.C. board", the chart of thermistor.
Room temperature thermistor(RT11)
Indoor coil thermistor (RT12(MAIN), RT13(SUB))
Horizontal vane motor(MV)
Normal
BRN-other one
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
235 " ~ 255 "
Color of the lead wire
Check 9-6. A.
RED
YLW BRN
ORN
GRN
ROTOR
· Flashing of OPERATION INDICATOR lamp (all lamps) indicates abnormality.
· Flashing of OPERATION INDICATOR lamp (right-hand side lamp) indicates
abnormality.
· OPERATION INDICATOR lamp (left-hand side lamp) is lighted.
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
16
w If more than 12 seconds or more passes after EMERGENCY OPERATION
switch is pressed, the voltage mentioned above 2 goes 0V DC although the indoor electric control P.C. board is normal.
Indoor electronic control P.C. board
Pay careful attention to the high voltage on the fan motor connector CN211.
Yes
No
No
No (Changed)
Yes (Unchanged)
Is there any foreign matter that interferes the rotation of the line flow fan?
Turn OFF the power supply.
Remove the foreign matter and adjust the line flow fan.
Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch. Measure the supply voltage as follows within 12 seconds after EMERGENCY OPERATION switch is pressed. If more than 12 seconds passes by, turn OFF the power supply and turn ON it again, then measure the voltage. w
1.Measure the voltage between CN211 1(+) and 3(-).
2.Measure the voltage between CN211 5(+) and 3(-).
Is there 325V DC between CN211 1 (+) and 3 (-), and does the voltage between CN211 5(+) and 3(-) rise to the range of 3 to 6V DC within 12 seconds after EMERGENCY OPERATION switch is pressed?
Yes
Replace the indoor fan motor.
CN211
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211 6(+) and 3(-) while the fan motor is rotating.
Is it unchanged holding 0V DC or 15V DC?
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
9-6. Troubleshooting flow
When OPERATION INDICATOR lamp flashes 3-time. Indoor fan does not operate.
A
Check of indoor fan motor
17
Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check of remote controller and receiver P.C. board
B
wCheck if the remote controller is exclusive for this air conditioner.
Press OPERATE/STOP(ON/OFF) button on the remote controller.
Is LCD display on the the remote controller visible?
Yes
Remove the batteries, then set them back and press RESET button. (Refer to 9-1.4.) Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
No (not clear)
No
Replace the batteries. (Refer to 9-1.4.)
Turn ON a radio to AM and press OPERATE/STOP(ON/OFF) button on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
No
Replace the indoor electronic control P.C. board.
No
Yes
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
18
The unit does not operate with the remote controller. Also, OPERATION INDICATOR lamp does not light up by pressing EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board and indoor fan motor
C
Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
Yes
Does the unit operate with the remote controller? Does OPERATION INDICATOR lamp light up by pressing EMERGENCY
Turn OFF the power supply. Check both parts side and pattern side of the indoor electronic control P.C. board visually.
OPERATION switch?
No
Measure the resistance between CN211 3 and 4 of the indoor fan motor connector.
Measure the resistance of the horizontal vane motor coil. Refer to 9-5.
Replace the varistor(NR11) and fuse(F11).
Yes
Are the varistor(NR11) burnt and the fuse(F11) blown?
Be sure to check both the fuse and the varistor in any case.
Is the fuse(F11) blown only?
Yes
Measure the resistance between 1(+) and 3(-) of the indoor fan motor connector. w1,w2
Is the resistance 1M' or more?
Yes
Replace the fuse (F11).
No
No
No
Short/open circuit: Replace the indoor fan motor.
Short/open circuit: Replace the horizontal vane motor and the indoor electronic control P.C. board.
w1. The fan motor connector's 1 lead wire is red, whereas 3 is black. w2. Connect "+" of the tester to fan motor connector's 1 lead
wire, and "-" to 3 lead wire, otherwise the resistance cannot be measured properly.
Replace the fuse (F11) and the indoor fan motor.
Measure the resistance of cement resistor R111 on the indoor electronic control P.C. board.
Indoor electronic control P.C.Board
Varistor(NR11) Fuse(F11) CN211
Is the resistance approx. 4'?
Yes
Replace the indoor electronic control P.C. board.
No
Replace the indoor electronic control P.C. board and the indoor fan motor.
19
When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.
When OPERATION INDICATOR lamp flashes ON and OFF every 0.5-second. Outdoor unit does not operate.
D
How to check mis-wiring and serial signal error
Turn OFF the power supply.
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
Is serial signal error indicated 6 minutes later?
A
· Reinstall either the unit or the light each other away.
No
· Attach a filter on remote control receiving
Yes
B
section of the indoor unit.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Yes
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Is serial signal error indicated 6 minutes later?
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
B
Short-circuit outdoor terminal block S2 and S3. W1
Turn ON the power supply.
Does the LED on the inverter P.C. board or the outdoor electronic contorol P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.
Refer to outdoor unit service manual.
Yes
Yes
A
W3
Yes
Yes
Yes
No
No
No
Check the power supply.
Check the wiring.
No
Is there any mis-wiring, poor contact, or wire
No
disconnection of the indoor/outdoor connecting wire?
No
W1. Mis-wiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. W3.Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes. (Except for outdoor unit of multi system type)
Replace the inverter P.C. board or
No
(Lighted or not lighted)
No
the outdoor electronic control P.C.board.
W2
W2 Be careful to the residual
voltage of smoothing capacitor.
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Yes
Yes
Yes
Correct them.
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
20
Replace the indoor electronic control P.C. board.
Replace the interlock switch(Fan).
Is the stopper of the horizontal vane locked to the indoor unit correctly?
Yes
No
Is there resistance 0 "?
Relock the stopper of the horizontal vane to the indoor unit. (Refer to 9-1.5.)
Yes
Are all lamps flashing?
Yes
No()
No
OK
Turn ON the power supply.
To check the continuity of the interlock switch (Fan), measure the resistance of connector 1 - 2 connected to CN1R1 on the indoor electronic control P.C. board.
Turn OFF the power supply.
Turn OFF the power supply.
When all lamps flash ON and OFF every 0.5-second. Indoor unit and outdoor unit do not operate.
Check of installation of the horizontal vane
E
21
Electromagnetic noise enters into TV sets or radios
Replace or repair the antenna. Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
After checking the above, consult the service representative.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
F
22
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT11)
Temperature (:)
Resistance (k")
9-7. Test point diagram and voltage
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
Indoor electronic control P.C. board
Varistor (NR11)
Release of Auto restart function Solder the Jumper wire to JR07 (Refer to 8-3.)
Power supply input 230V AC Fuse(F11)
}
(T3.15AL250V)
R111
Indoor fan motor (CN211)
1311V DC 3(-) Fiducial terminal of
cathode side on measur­ing high-voltage DC
415
V DC
5(+)3-6V DC 6(+)0V DC or 15V DC
Interlock switch(Fan) (CN1R1)
5V DC
Power monitor receiver P.C. board
Emergency operation switch
SW P.C. board
12V DC
Indoor coil thermistor RT12(MAIN) 12 RT13(SUB) 34
(CN112) Horizontal vane
motor(CN151) Room temperature
thermistor(RT11)
Timer short mode point JPG, JPS
}
(Refer to 8-1.)
23
10
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the locking mechanism.
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA INDOOR UNIT
OPERATING PROCEDURE
1. Removing the panel
(1) Remove the horizontal vane. (2) Remove the screw caps of the panel.
Remove the screws. (See Photo 1.)
(3) Hold the lower part of both ends on the panel and pull it
slightly toward you, and then remove the panel by pushing it upward.
PHOTOS
Photo 1
Screws of the panel
Horizontal vane
24
OPERATING PROCEDURE PHOTOS
2. Removing the electronic control P.C. board, the power monitor receiver P.C. board, SW P.C. board and the terminal block
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the screw of V.A. clamp, and then the
indoor/outdoor connecting wire. (See Photo 2.)
(3) Remove the switch holder from the electrical cover.
(See Photo 3.)
(4) Remove the screw of the electrical cover, and then the
electrical cover. (See Photo 3.)
(5) Remove the earth wire connected to the indoor
electronic control P.C. board from the electrical box.
(See Photo 4.)
(6) Unhook the power monitor receiver P.C. board holder from
the catch. (See Photo 4.)
(7) Open the rear cover of the power monitor receiver P.C.
board holder and pull out the power monitor receiver P.C.
board. (8) Open the switch holder and pull out SW P.C. board. (9) Pull the electronic control P.C. board slightly toward you
from the electrical box, and disconnect TAB3 and all the
connectors on the electronic control P.C. board.
(LD101 and LD105 are direct-mounted to the electronic
control P.C. board.)
(10)
Pull out the electronic control P.C. board from the electrical
box. (11)
Remove the earth wire connected to the heat exchanger
from the electrical box. (See Photo 4.)
(12)
Unhook the catches of the electrical box, and pull out the
electrical box.
(13)
Remove the screws of the terminal block cover, and then
the terminal block cover and the terminal block holder.
(See Photo 2.)
(14)
Remove the terminal block by sliding it.
Photo 2
Screws of the terminal block cover
Drain hose
Photo 3
Screw of V.A. clamp
Switch holder
Screw of the electrical cover.
3. Removing the electrical box
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the screw of V.A. clamp, and then the indoor/
outdoor connecting wire. (See Photo 2.)
(3) Remove the switch holder and the electrical cover.
(See Photo 3.)
(4) Remove the earth wire connected to the heat exchanger
from the electrical box. (See Photo 4.)
(5) Disconnect the following connectors on the electronic
control P.C. board; the fan motor connector <CN211>, the indoor coil thermistor connector <CN112>, the vane motor connector <CN151>, the connector of the interlock switch (Fan) of the horizontal vane <CN1R1>.
(6) Unhook the catches of the electrical box, and pull out the
electrical box.
Photo 4
Earth wire
Fan motor connector (CN211)
Connector of the interlock switch(Fan) (CN1R1)
Indoor coil thermistor connector (CN112)
Vane motor connector (CN151)
Power monitor receiver P.C. board holder
25
OPERATING PROCEDURE PHOTOS
4. Removing the horizontal vane motor unit
(1) Remove the horizontal vane and the panel. (Refer to 1.) (2) Remove the screws of the horizontal vane motor unit,
and pull out the horizontal vane motor unit. (See Photo 5.)
(3) Disconnect the connector from the horizontal vane motor
unit.
5. Removing the indoor fan motor and the line flow fan
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2)
Remove the switch holder and the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly. (4) Remove the screws fixing the motor bed. (5) Loosen the screw fixing the line flow fan. (6) Remove the motor bed together with fan motor and motor
band. (7) Release the hooks of the motor band, and remove the
motor band then pull out the indoor fan motor. (8) Remove the screws fixing the left side of the heat
exchanger. (9) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
(See Photo 8.)
(See Photo 6.)
(See Photo 7.)
Photo 5
Photo 6
Screws of the motor bed
Photo 7
Screws of the horizontal vane motor unit
Motor band
Screw of the line flow fan
Photo 8
Screws of the left side of the heat exchanger
26
PARTS LIST (non-RoHS compliant)11
No.
Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2
3 4 5 6 7
8 9
10 11
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
KM05B
BOX BOX PANEL ASSEMBLY SCREW CAP FRONT PANEL CATECHIN AIR FILTER (LEFT) CATECHIN AIR FILTER (RIGHT) AIR CLEANING FILTER CORNER BOX (RIGHT) CORNER BOX (RIGHT) INSTALLATION PLATE
Including No.3,4 2PCS/SET
MAC-415FT-E
MSZ-GA22VA-
E1 E2 E1 E2 E1 E2
MSZ-GA25VA- MSZ-GA35VA-
1
1 2 1 1 1 1 1
1
1 1 2 1 1 1 1
1 1
1
1 2 1 1 1 1 1
1
E02 897 234 E02 A32 234 E02 915 000 E02 913 067 E02 915 010 E02 915 100 E02 916 100
E02 913 975 E02 A32 975 E02 913 970
1 1
E02 915 426 E02 527 083
1
1 2 1 1 1 1 1
1
1 1 2 1 1 1 1
1 1
1 1 2 1 1 1 1
1 1
1 1
11111
1
1 1
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA 11-1. INDOOR UNIT STRUCTURAL PARTS
11-2. ACCESSORY AND REMOTE
CONTROLLER
1
2
3
4
5
11-1. INDOOR UNIT STRUCTURAL PARTS
9
10
11
8
7 (See 13.)
6
11-2. ACCESSORY AND REMOTE CONTROLLER
27
PARTS LIST (non-RoHS compliant)
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
11-3. INDOOR UNIT ELECTRICAL PARTS
AND FUNCTIONAL PARTS
19
21
1
2
3 4
5
6
7
15
20
14 13
12
11
18
15
17
11-4. INDOOR UNIT HEAT EXCHANGER
23
24
22
28
10
9
8
15
16
BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBL Y VANE MOTOR UNIT (HORIZONTAL) INTERLOCK SWITCH(FAN) HORIZONTAL VANE FUSE FUSE VARISTOR POWER MONITOR RECEIVER P.C. BOARD HOLDER V.A. CLAMP TERMINAL BLOCK COVER TERMINAL BLOCK HOLDER TERMINAL BLOCK ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR SWITCH HOLDER INDOOR FAN MOTOR W2 MOTOR BAND LINE FLOW FAN
UP & DOWN
T3.15AL250V T3.15AL250V
AUTO RESTART AUTO RESTART AUTO RESTART
RC0J30-
MV
F11 F11
NR11
TB
RT11
RT12, RT13
MF
No. Part No.
Part name
Remarks
Symbol in Wiring Diagram
Q'ty/unit
1 2 3 4 5 6 7
8
9 10 11 12 13 14
15
16 17 18 19 20 21
22 23 24
INDOOR HEAT EXCHANGER UNION (GAS) UNION (LIQUID)
{9.52 {6.35
E02 751 509 E02 001 504 E02 897 702 E02 915 235 E02 897 303 E02 897 316 E02 913 040 E02 127 382 E02 A49 382 E02 661 385 E02 915 095 E02 897 784 E02 897 780 E02 897 779 E02 913 375 E02 915 452 E02 916 452 E02 917 452 E02 897 308 E02 913 307 E02 915 782 E02 915 300 E02 897 333 E02 897 302
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
E02 913 620 E02 815 666 E02 151 667
1 1 1
W1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD W2 Including FAN MOTOR RUBBER MOUNT (2 PCS/SET)
1 1 1 1 1 1 1 1
1 1 1 1 1 1
1
1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1
1 1 1 1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
MSZ-GA22VA- MSZ-GA25VA- MSZ-GA35VA-
E1 E1 E1E2 E2 E2
PARTS LIST (non-RoHS compliant)
11-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
11-4. INDOOR UNIT HEAT EXCHANGER
29
30
RoHS PARTS LIST (RoHS compliant)12
No.
Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2 3 4 5 6 7 8 9
G G G G G G G G G
1011G
G
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
KM05B
BOX PANEL ASSEMBLY SCREW CAP FRONT PANEL CATECHIN AIR FILTER (LEFT) CATECHIN AIR FILTER (
RIGHT
) AIR CLEANING FILTER CORNER BOX (RIGHT) INSTALLATION PLATE
Including No.3,4 2PCS/SET
MAC-415FT-E
MSZ-GA22VA-
E2 E3 E2 E3 E2 E3
MSZ-GA25VA- MSZ-GA35VA-
1 1 2 1 1 1 1 1 1
1 1 2 1 1 1 1 1 1
1 1 2 1 1 1 1 1 1
E12 A32 234 E12 915 000 E12 913 067 E12 915 010 E12 915 100 E12 916 100
E12 A32 975 E12 913 970
1 1
E12 915 426 E12 527 083
1 1 2 1 1 1 1 1 1
1 1 2 1 1 1 1 1 1
1 1 2 1 1 1 1 1 1
1 1
111
1
1 1
1 1
RoHS
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA 12-1. INDOOR UNIT STRUCTURAL PARTS
12-2. ACCESSORY AND REMOTE
CONTROLLER
1
2
3
4
5
12-1. INDOOR UNIT STRUCTURAL PARTS
9
10
11
8
7 (See 13.)
6
12-2. ACCESSORY AND REMOTE CONTROLLER
31
RoHS PARTS LIST (RoHS compliant)
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
12-3. INDOOR UNIT ELECTRICAL PARTS
AND FUNCTIONAL PARTS
19
21
1
2
3 4
5
6
7
15
20
14 13
12
11
18
15
17
12-4. INDOOR UNIT HEAT EXCHANGER
23
24
22
32
10
9
8
15
16
BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBL Y VANE MOTOR UNIT (HORIZONTAL) INTERLOCK SWITCH(FAN) HORIZONTAL VANE FUSE VARISTOR POWER MONITOR RECEIVER P.C. BOARD HOLDER V.A. CLAMP TERMINAL BLOCK COVER TERMINAL BLOCK HOLDER TERMINAL BLOCK ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR SWITCH HOLDER INDOOR FAN MOTOR W2 MOTOR BAND LINE FLOW FAN
UP & DOWN
T3.15AL250V
AUTO RESTART AUTO RESTART AUTO RESTART AUTO RESTART
RC0J30-
MV
F11
NR11
TB
RT11
RT12, RT13
MF
No. Part No.
Part name
Remarks
Symbol
in Wiring
Diagram
Q'ty/unit
1 2 3 4 5 6 7 8
9 10 11 12 13 14
15
16 17 18 19 20 21
G G G G G G G G G G G G G G G G G G G G G G G G
22 23 24
G G G
INDOOR HEAT EXCHANGER UNION (GAS) UNION (LIQUID)
{9.52 {6.35
E12 751 509 E12 001 504 E12 897 702 E12 915 235 E12 897 303 E12 897 316 E12 913 040 E12 A49 382 E12 661 385 E12 915 095 E12 897 784 E12 897 780 E12 897 779 E12 913 375 E12 916 452 E12 B39 452 E12 B40 452 E12 B41 452 E12 897 308 E12 913 307 E12 915 782 E12 915 300 E12 897 333 E12 897 302
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
E12 913 620 E12 815 666 E12 151 667
1 1 1
W1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD W2 Including FAN MOTOR RUBBER MOUNT (2 PCS/SET) W3 Serial number : ~6024700 W4 Serial number : 6024701~
Refer to 3.SPECIFICATION as for difference between W3 and W4.
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
W3
1
W4
1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
1 1 1 1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
MSZ-GA22VA- MSZ-GA25VA- MSZ-GA35VA-
E2 E2 E2E3 E3 E3
RoHS
RoHS PARTS LIST (RoHS compliant)
12-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
12-4. INDOOR UNIT HEAT EXCHANGER
33
MAC-093SS-E
Model Part No.
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
Heat exchanger
13
Model
Part No.
MAC-415FT-E
MSZ-GA22VA MSZ-GA25VA MSZ-GA35VA
Air cleaning filter (Blue bellows type)
OPTIONAL PARTS
13-1. AIR CLEANING FILTER (ANTI-ALLERGY ENZYME FILTER)
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 1 year.
If AIR CLEANING FILTER is to be washed, soak AIR CLEANING FILTER in water (when showing dirt, in lukewarm
water) and rinse it delicately, without removing the filter from the frame about once every 3 months.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
Do not remove or attach AIR CLEANING FILTER during unit operation.
Replacement of the air cleaning filter
(1) Remove the catechin air filter(left one)
The air cleaning filter is not attached to the right side catechin air filter
(2) Remove the air cleaning filter(Blue
bellows type) from the catechin air filter.
13-2. QUICK CLEAN KIT
You can sweep the surface of heat exchanger if you install the special-made brush to your vacuum cleaner.
34
35
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Apr. 2007. No. OB378 REVISED EDITION-C 6 Distributed in Jan. 2007. No. OB378 REVISED EDITION-B 6 Distributed in Jan. 2006. No. OB378 REVISED EDITION-A 6 Distributed in Jan. 2005. No. OB378 6 Made in Japan
New publication, effective Apr. 2007 Specifications subject to change without notice.
Loading...