Mitsubishi Electronics MSZ-GA22VA, MSZ-GA25VA, MSZ-GA35VA User Manual 2

Page 1
SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Wireless type Models
E1
E1
E1
(WH)
(WH)
(WH)
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
No. OB378
Indication of model name
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
NOTE:
This service manual describes technical data of the indoor units.
•As for outdoor units MUZ-GA25VA- , MUZ-GA35VA- , MUZ-GA25VAH­and MUZ-GA35VAH- , refer to service manual OB379.
•As for outdoor units MXZ-3A54VA- , MXZ-4A71VA- and MXZ-4A80VA- ,
refer to service manual OB377.
E1
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM················8
8. SERVICE FUNCTIONS ······································9
9. TROUBLESHOOTING······································10
10. DISASSEMBLY INSTRUCTIONS·····················24
12. OPTIONAL PARTS ···········································30
E1E1E1
E1E1E1
Page 2
1
TECHNICAL CHANGES
MSZ-A09YV - ➔ MSZ-GA22VA -
MSZ-A09YV - MSZ-GA25VA ­MSZ-A12YV - MSZ-GA35VA -
1. Indication of capacity has been changed.(BTU base kW base)
2. Control method between indoor and outdoor has been changed.
3. Power supply method has been changed (change to supply from outdoor unit).
4. Power supply cord has been removed.
5. Indoor electronic control P.C. board has been changed.
6. Position of terminal block has been changed.
7. Indoor fan motor has been changed. ( AC DC)
8. Indoor heat exchanger has been changed.
9. The horizontal vane motor unit has been changed. An external gear is added to the generalized stepping motor. The unit is structured so that the driving torque and stopping torque would increase.
Generalized stepping motor
NOTE: Do not remove the vane motor from the motor unit.
Do not disassemble the horizontal vane motor unit.
E1E1 E1E1 E1E1
10. Air cleaning filer has been removed (available as an optional part).
11. Signal of remote controller has been changed. ( It is not available for the conventional models.)
12. Symbol on terminal block has been changed (to S1/S2/S3).
2
Page 3
2
Line flow fan
Air outlet Vertical vane
Air inlet
Display section
Front panel
Panel
Heat exchanger
Horizontal vane
Operation section
(When the front panel is opened)
Remote controller
Remote control receiving section
Catechin air filter
Air cleaning filter (Optional parts,Anti­Allergy Enzyme Filter, Blue bellows type)
Emergency operation switch
Fan guard
Operation Indicator lamp
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
E1
E1
E1
3
Page 4
ACCESSORIES
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
MSZ-GA22VA -
E1
MSZ-GA25VA -
E1
1 5 1 2 2 1 1
MSZ-GA35VA -
E1
INDOOR UNIT
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
Open the front lid.
E1
E1
E1
Signal transmitting section
Operation display section
OPERATE/STOP (ON/OFF) button
Temperature buttons
Indication of remote controller model is on back
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
RESET button
(This diagram shows an overall view.)
4
OFF-TIMER button
ON-TIMER button
TIME SET buttons FORWARD button BACKWARD button
CLOCK SET button
VANE CONTROL button
Page 5
3
T3.15AL 250V
MSBPC20M16 12V DC 250" (at 25˚C)
ERZV14D471
3P
INDOOR UNIT
Item
Model
Fuse Horizontal vane motor Varistor Terminal block
MSZ-GA22VA -
E1
MSZ-GA25VA -
E1
MSZ-GA35VA -
E1
(F11)
(MV)
(NR11)
(TB)
MSZ-GA25VA -
E1
MSZ-GA22VA -
E1
MSZ-GA35VA -
E1
Indoor model
Function
Power supply
Single phase
230V,50Hz
10
0.25 33 — 57
0.25
RC0J30-CC
780O298O210
9 4
43
36W/29W/21
W
4 10 10 10
KM05B
Single phase
230V,50Hz
10
0.25 33 — 57
0.25
RC0J30-CC
780O298O210
9 4
43
36W/29W/21
W
4 10 10 10
KM05B
540
43
36W/29W/21
W
1,100
43
36W/29W/22
W
Cooling
600
480W/366W/234
W
1,200
1,000W/800W/580
W
Heating
630
504W/384W/258
W
1,250
1,040W/830W/620W
Cooling
600
480W/366W/234
W
1,200
1,000W/800W/580
W
Heating
630
504W/384W/258
W
1,250
1,040W/830W/620
W
Single phase
230V,50Hz
10
0.25 33 — 57
0.25
RC0J30-CC
780O298O210
9 4
43
36W/29W/22
W
4 10 10 10
KM05B
Cooling
600
480W/366W/246
W
1,200
1,000W/800W/600
W
Heating
630
504W/384W/270
W
1,250
1,040W/830W/640
W
Air flow(Super High) Air flow(HighW/Med.W/LowW) Power outlet Running current 1 Power input 1 Auxiliary heater Power factor 1 Fan motor current 1 Model Dimensions WOHOD Weight Air direction Sound level(Super High) Sound level(HighW/Med.W/LowW) Fan speed(Super High) Fan speed(HighW/Med.W/LowW) Fan speed regulator Thermistor RT11(at25:) Thermistor RT12(at25:) Thermistor RT13(at25:) Remote controller model
K /h K /h
A A
W
A(kW)
%
A
mm
kg
dB(A) dB(A)
rpm rpm
k" k" k"
Electrical
data
Fan motor
Special
remarks
Capacity
MSZ-GA25VA -
E1
MSZ-GA22VA -
E1
MSZ-GA35VA -
E1
Indoor model
Function
Cooling
438W/342W/240
W
930W/760W/580
W
Heating
420W/366W/258
W
900W/800W/620
W
Cooling
438W/342W/240
W
930W/760W/580
W
Heating
420W/366W/258
W
900W/800W/620
W
Cooling
600
480W/366W/246
W
1,200
1,000W/800W/600
W
Heating
618
504W/390W/270
W
1,230
1,040W/850W/640
W
Air flow(Super High) Air flow(HighW/Med.W/LowW) Sound level(Super High) Sound level(HighW/Med.W/LowW) Fan speed(Super High) Fan speed(HighW/Med.W/LowW)
K /h K /h
dB(A) dB(A)
rpm rpm
Special
remarks
Capacity
540
43
36W/29W/21
W
1,100
SPECIFICATION
When outdoor unit is MXZ type.
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19:
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24:
Heating : Indoor Dry-bulb temperature 20:Wet-bulb temperature 15:
Outdoor Dry-bulb temperature 7:Wet-bulb temperature 6:
Refrigerant piping length (one way): 5m w Reference value
1 Measured under rated operating frequency.
Specifications and rating conditions of main electric parts
5
Page 6
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
43 43
SPL(dB(A))
LINE
Super High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
NOISE CRITERIA CURVES
MSZ-GA22VA ­MSZ-GA25VA -
E1 E1
MSZ-GA35VA -
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15:
90
80
70
60
50
40
30
E1
FAN SPEED
Super High
FUNCTION
COOLING
HEATING
SPL(dB(A))
43 43
LINE
NC-70
NC-60
NC-50
NC-40
NC-30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
INDOORUNIT
WALL
1m
0.8m
MICROPHONE
NC-20
6
Page 7
5
OUTLINES AND DIMENSIONS
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
INDOOR UNIT
298
53.5 58
E1 E1 E1
780
19
11X26 Oblong hole
Installation plate
Indoor unit
102624.5
41.5 215
100
Air out
11X20 Oblong hole
335 320
Air in
210 5
or more7
155 155
Installation plate
90
106
Unit : mm
14273.5
5555 225 225
234
214
7055
42.5
Wall hole [65
Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [35 O.D
{
[19 I.D
Drain hose [16 (Connected part O.D)
Insulation [28
287.5
3
159
Required space (Indoor unit)
75 or more
10 or more
75 or more
W
66 or more
In case of left, left back, or
W
left under piping (using spacer),
115 or more
7
Page 8
6
SYMBOL
DB111
F11 MF
MV
NR11
SYMBOL
RT11 RT12 RT13
T111
TB
NAME DIODE STACK FUSE (T3.15AL250V) INDOOR FAN MOTOR VANE MOTOR (HORIZONTAL) VARISTOR
NAME ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB) TRANSFORMER TERMINAL BLOCK
WIRING DIAGRAM
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
E1
E1
E1
GRN
230V~
12-24V
LD104
CN
151
5
MV
MODELS WIRING DIAGRAM
TB
S1 S2 S3
CN
1R1
INTERLOCK SWITCH(FAN)
TAB3
BLK BLU
2
RED
1
CN201
2
POWER MONITOR RECEIVER P.C.BOARD
F11
NR11
101(A)
DB111
LD
6
INDOOR ELECTRONIC CONTROL P.C. BOARD
T111
LD
105(T)
2
SW P.C. BOARD
CN
112
CN211
CN
111
4 3 2 1
1 2 3 4 5 6
RED
BLK
WHT
YLW
BLU
RT13 RT12
RT11
5
MF
7
REFRIGERANT SYSTEM DIAGRAM
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
INDOOR UNIT
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
E1
E1
E1
Refrigerant pipe [9.52 (with heat insulator)
Indoor coil
Indoor heat exchanger
thermistor RT12(main)
Flared connection
Indoor coil thermistor RT13(sub)
Room temperature thermistor RT11
Unit : mm
Refrigerant flow in cooling Refrigerant flow in heating
8
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Page 9
8
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MSZ-GA22VA ­MSZ-GA25VA ­MSZ-GA35VA -
E1
E1
E1
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
Remote controller model : KM05B
NOTE : For remodelling, take out
the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at first. After finish remodelling, put back the batteries then press the RESET button.
J1
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J2
Table 1
How to set the remote controller exclusively for particular indoor unit.
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
9
Page 10
Housing point
JR07
CN151 CN211CN112 CN1R1
BZ
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
1 If the main power has been cut, the operation settings remain. 2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release “AUTO RESTART FUNCTION”
1Turn off the main power for the unit. 2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the
remote controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn on at the
same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure,
the starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
9
TROUBLESHOOTING
MSZ-GA22VA - MSZ-GA25VA - MSZ-GA35VA -
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
10
E1E1E1
Page 11
3. Troubleshooting procedure
RESET button
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
OPERATION INDICATOR
Not lighted
Blinking
Lighted
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced. This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, all of the operation indicator lamps will blink. In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
Stopper
21
Left
In procedure
stoppers until they click into place.
Lock.
Insert this end first.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not connect indoor units beyond the outdoor unit capacity. Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units will start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
22
lock the
•When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
11
Page 12
9-2. Failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
W1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep sounds are emitted at the same timing of the blinking of the left lamp of OPERATION INDICATOR lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does the left lamp of OPERATION INDICATOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and refer to confirm the abnormal point(9-2. 2.). Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply. 1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
Deleting the abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. 2Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 3Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures. 1With the remote controller headed towards the indoor unit, press any button that is not used in this failure mode recall function (e.g. TIMER button) . OR
1Turn OFF the power supply and turn ON it again. 2Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
W1 Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed). With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 24:.
Indoor unit is normal. There is a possibility that the outdoor unit is abnormal. Confirm the presence of abnormality according to the flow chart of the detailed outdoor unit failure mode recall function.
The outdoor unit is abnormal. Check the blinking pattern, and refer to confirm the abnormal point. Make sure to check at least two consecutive blinking cycles. W3
1 While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
As for outdoor unit MUZ type, refer to service manual OB379. As for outdoor unit MXZ type, refer to service manual OB377.
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of the indoor/outdoor unit failure mode recall function
12
Page 13
2. Indoor unit failure mode table
12-time flash
2.5-second OFF
Replace the indoor electronic control P.C. board.
Indoor control system
When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
11-time flash
2.5-second OFF
Refer to 9-6.A "Check of indoor fan motor".
Indoor fan motor
When the rotational frequency feedback signal is not emitted during 12-second the indoor fan operation.
2-time flash
2.5-second OFF
Refer to the characteristic of the main indoor coil thermistor, the sub indoor coil thermistor (9-7.).
Indoor coil thermistor
When the indoor coil thermistor short or open circuit is detected every 8 seconds during operation.
3-time flash
2.5-second OFF
Refer to 9-6.D "How to check miswiring and serial signal error".
Serial signal error
When the serial signal from the outdoor unit is not received for a maximum of 6 minutes.
1-time flash every 0.5-second
Refer to the characteristics of the room temperature thermistor (9-7.).
Room temperature thermistor
When the room temperature thermistor short or open circuit is detected every 8 seconds during operation.
Not lighted Normal
Left lamp of
OPERATION
INDICATOR lamp
Check point
Abnormal point
(Failure mode)
Detection method
NOTE:Blinking patterns of this mode differs from the ones of Troubleshooting check table(9-4.).
13
Page 14
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation. w1
Outdoor unit doesn't operate even in Test Run operation. w1
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to 9-7. "Test point diagram and voltage".
Refer to "How to check inverter/ compressor".
Refer to 9-6.B "Check of remote controller and receiver P.C. board".
1. Check indoor / outdoor connecting wire. (Check if the power is supplied to the indoor unit.)
2. Refer to 9-6.C "Check of indoor electronic control P.C. board and indoor fan motor".
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to "Check of R.V. coil".
Left lamp Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring or trouble of serial signal
Left
lamp 2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
Left
lamp 3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Left lamp 5-time flash Cause: Outdoor unit
• Outdoor power system abnormality
Left lamp 6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Left lamp 7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Refer to 9-6. D "How to check of mis-wiring and serial signal error (when outdoor unit doesn't work)".
All lamps Flash on and off at 0.5-second intervals Cause: Indoor unit
• The horizontal vane is not installed correctly.
Refer to 9-6. E "Check of installation of the horizontal vane".
Check room temperature thermistor and indoor coil thermis­tor. Refer to 9-7. "Test point diagram and voltage".
Refer to 9-6. A "Check of indoor fan motor".
Refer to "How to check inverter/ compressor".
Refer to "Check of outdoor thermistors".
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
Left lamp 14-time flash Cause: Outdoor unit
• Other abnormality
Check "Flow chart of the detailed outdoor unit failure mode recall function."
Left lamp 4-time flash Cause: Indoor unit
• Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
As for outdoor unit MUZ type,
refer to service manual OB379. As for outdoor unit MXZ type, refer to service manual OB377.
Indoor unit operates. Outdoor unit doesn't operate normally.
If blinking of OPERATION INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
w1 "Test Run operation" means the operation within 30 minutes after EMERGNCY OPERATION switch is pressed.
9-3. Instruction of troubleshooting
14
Page 15
No.
1
3
6
7
SymptomOperation indicator lamp Detection method
Check point
Left lamp flashes.
0.5-second ON
0.5-second OFF
Mis-Wiring or serial signal
Outdoor power system
Outdoor thermistors
Outdoor control system
Indoor coil thermistor
When the serial signal from the outdoor unit is not received for a maximum of 6 minutes.
When it consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection within 1 minute after start-up.
When the outdoor thermistors short or open circuit during the compressor operation.
When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Refer to "Check of outdoor thermistor".
Refer to service manual OB379 or OB377.
• Refer to "Check of inverter/ compressor".
Refer to service manual OB379 or OB377. Check the stop valve.
• Replace the inverter P.C.
board or the outdoor
electronic control P.C. board.
Refer to service manual
OB379 or OB377.
• Refer to 9-6.D "How to check
mis-wiring and serial signal
error".
4
Indoor fan motor
8
Abnormal
point
Room tempera­ture thermistor
Left lamp flashes. 2-time flash
2.5-second OFF
When the indoor coil or the room temperature thermistor is shorts or opens circuit.
• Refer to 9-7.the
characteristics of indoor coil thermistor, and the room temperature thermistor.
Left lamp flashes. 3-time flash
2.5-second OFF
When the rotational frequency feedback signal is not emitted during the indoor fan operation.
• Refer to 9-6.A "Check of indoor fan motor".
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Left lamp flashes. 5-time flash
2.5-second OFF Left lamp flashes.
6-time flash
2.5-second OFF
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
Other abnormality
An abnormality other than above mentioned is detected.
• Confirm the abnormality in detail using the failure mode recall function.
Indoor unit and outdoor unit do not operate.
Indoor unit and outdoor unit do not operate.
9
5
Left lamp flashes. 4-time flash
2.5-second OFF
Indoor control system
When it cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
Indoor unit and outdoor unit do not operate.
• Replace the indoor electronic control P.C. board.
Outdoor control system
When it cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
• Check the blinking pattern of the LED on the inverter P.C. board or the outdoor electronic control P.C. board.
2
Outdoor unit does not operate.
Left lamp lights up
Left lamp flashes. 7-time flash
2.5-second OFF
Left lamp flashes. 14-time flash
2.5-second OFF
9-4. Troubleshooting check table
Not lighted
Blinking
OPERATION INDICATOR
Lighted
· Flashing of OPERATION INDICATOR lamp (left-hand side lamp) indicates abnormalities.
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
15
Page 16
OPERATION INDICATOR
Not lighted
Blinking
Lighted
OPERATION INDICATOR
Not lighted
Blinking
Lighted
No.
1
SymptomOperation indicator lamp Detection method
Check point
Abnormal
point
0.5-second ON
0.5-second OFF
When the electricity is not conducted to the interlock switch (Fan) of the horizontal vane.
• Refer to 9-6.E "Check of installation of the horizontal vane".
Indoor unit and outdoor unit do not operate.
Attachment of the horizontal vane
All lamps flash at the same time.
No.
SymptomOperation indicator lamp Detection method
Check point
Abnormal
point
1
MXZ type
Operation mode setting
Outdoor unit operates but indoor unit does not operate.
When the operation mode of the each indoor unit is differently set to COOL(includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at first has the priority.
• Unify the operation mode. Refer to service manual OB377.
2.5-second OFF
Right lamp flash
· Flashing of OPERATION INDICATOR lamp (all lamps) indicates abnormality.
Part name FigureCheck method and criterion
Indoor fan motor(MF)
Measure the resistance with a tester. (Part temperature 10˚C ~ 30˚C)
Normal
8 k" ~ 20 k"
Abnormal
Open or short-circuit
Room temperature thermistor(RT11)
Indoor coil thermistor (RT12(MAIN), RT13(SUB))
Horizontal vane motor(MV)
Normal
BRN-other one
Abnormal
Open or short-circuit
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
235 " ~ 255 "
Color of the lead wire
Check 9-6. A.
RED
YLW BRN
ORN
GRN
ROTOR
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
· Flashing of OPERATION INDICATOR lamp (right-hand side lamp) indicates abnormality.
· OPERATION INDICATOR lamp (left-hand side lamp) is lighted.
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
9-5. Trouble criterion of main parts
MSZ-GA22VA - MSZ-GA25VA - MSZ-GA35VA -
E1E1E1
16
Page 17
wIf 12 seconds or more passes after EMERGENCY OPERATION switch is pressed, the voltage mentioned above 2 goes 0V DC although the indoor electric control P.C. board is normal.
Indoor electronic control P.C. board
Pay careful attention to the high voltage on the fan motor connector CN211.
Yes
No
No
Changed
Unchanged
Is there any foreign matter that interferes the rotation of the line flow fan?
Turn OFF the power supply. Insert a stick such as a screw driver into the air outlet, and check if there is any catch in the rotation of the line flow fan.
Adjust the line flow fan and remove the foreign matter.
w
Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch. Measure the supply voltage as follows within 12 seconds after EMERGENCY OPERATION switch is pressed. If more than 12 seconds passes by, turn OFF the power supply and turn ON it again, then measure the voltage.
1.Measure the voltage between CN211 1(+) and 3(-).
2.Measure the voltage between CN211 5(+) and 3(-).
Is there 311V DC between CN211 1 (+) and 3 (-), and does the voltage between CN211 5(+) and 3(-) rise to the range of 3 to 6V DC within 12 seconds after EMERGENCY OPERATION switch is pressed?
Yes
Replace the indoor fan motor.
CN211
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3times, and then stops.
Measure the voltage between CN211 6(+) and 3(-) while the fan motor is rotating.
Is it unchanged holding 0V DC or 15V DC?
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
9-6. Troubleshooting flow
When OPERATION INDICATOR lamp flashes 3-time. Indoor fan does not operate.
A
Check of indoor fan motor
17
Page 18
Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check of remote controller and receiver P.C. board
B
wCheck if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the the remote controller visible?
Yes
Remove the batteries, then set them back and press RESET button. (Refer to 9-1.4.) Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
No (not clear)
No
Replace the batteries. (Refer to 9-1.4.)
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
Replace the indoor electronic control P.C. board.
No
Yes
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
18
Page 19
The unit does not operate with the remote controller. Also, OPERATION INDICATOR lamp does not light up by pressing EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board and indoor fan motor
C
Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
Yes
Does the unit operate with the remote controller? Does OPERATION INDICATOR lamp light up by
pressing EMERGENCY
Turn OFF the power supply. Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.
OPERATION switch?
No
w3. Short circuit: The indoor fan motor is abnormal.
Measure the resistance between CN211 3 and 4 of the indoor fan motor connector. Normal value is approx. 30k' to 50k'.
Measure the resistance of the horizontal vane motor coil. Normal value is approx. 300' to 250'.
Replace the varistor(NR11) and fuse(F11).
Yes
Are the varistor(NR11) burnt and the fuse(F11) blown?
Be sure to check both the fuse and the varistor in any case.
Is the fuse(F11) blown only?
w1,2
Yes
Measure the resistance between 1(+) and 3(-) of the indoor fan motor connector (to CN211 on the indoor electronic control P.C. board) .
w3
Is the resistance 1M' or more?
Yes
Replace the fuse (F11).
No
No
w1. The fan motor connector's 1 lead wire is red, whereas 3 is black. w2. Connect "+" of the tester to fan motor connector's 1 lead
wire, and "-" to 3 lead wire, otherwise the resistance cannot be measured properly.
No
Short circuit: Replace the indoor fan motor.
Short circuit: Replace the horizontal vane motor and the indoor electronic control P.C. board.
Replace the fuse (F11) and the indoor fan motor.
Indoor electronic control P.C.Board
Measure the cement resistance R111 on the indoor electronic control P.C. board.
Varistor(NR11) Fuse(F11) CN211
Is the resistance approx. 4'?
Yes
Replace the indoor electronic control P.C. board.
No
Replace the indoor electronic control P.C. board and the indoor fan motor.
19
Page 20
When POWER lamp flashes ON and OFF in every 0.5-second.
Is there rated voltage of 230V AC in the power supply?
In 3 minutes after turning ON the power supply of the outdoor unit, does the LED on the inverter P.C. board repeat quick blinking "3.6-second-OFF and 0.8-second-ON"? Be sure to check above in 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. When the inverter P.C. board is normal, LED also blinks 6 times after 3 minutes.
Is there any mis-wiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
W1. Mis-wiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts.
(Lighting)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
No
W2 Be careful to the residual voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
No
No
Yes
No
Yes
Serial signal error display
Yes
Yes
No
Yes
As for outdoor unit MUZ type,refer to service manual OB379. As for outdoor unit MXZ type,refer to service manual OB377.
Inverter P.C.board (Parts side)
LED
Blinking
Turn OFF the power supply.
Turn ON the power supply.
Is there 230V AC between outdoor terminal block S1 and S2?
Does the lefl lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch.
Check the power supply.
Is the self-check of the indoor unit displayed 6 minutes after?
The left lamp of OPERATION INDICATOR lamp blinks quickly.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and S3. W1
B
Turn ON the power supply of the outdoor unit.
Check the wiring.
Make them sure.
Remove the short-circuit between outdoor terminal block S2 and S3. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there 230V AC between outdoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board. W2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Replace the indoor/outdoor connecting.
Replace the indoor/outdoor connecting.
Is serial signal error indicated 6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
B
· Reinstall either the unit or the light each other away.
· Attach a filter on receiving section of the indoor unit.
A
Outdoor unit does not operate.
D
How to check mis-wiring and serial signal error
20
Page 21
Start
Replace the indoor electronic control P.C. board.
Replace the interlock switch(Fan).
Is the stopper of the horizontal vane locked to the indoor unit correctly?
Yes
No
Is there resistance 0 "?
Relock the stopper of the horizontal vane to the indoor unit. Refer to 9-1.5.
Yes
Are all lamp flashing?
Yes
No()
No
OK
Turn ON the power supply.
To check the continuity of the interlock switch (Fan), measure the resistance of connector 1 - 2 connected to CN1R1 on the indoor electronic control P.C. board.
Turn OFF the power supply.
Turn OFF the power supply.
When All lamps flash ON and OFF every 0.5-second. Indoor unit and outdoor unit do not operate.
Check of installation of the horizontal vane
E
21
Page 22
Electromagnetic noise enters into TV sets or radios
Replace the antennas. Replace the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Is there any antennas damage by rust or something , coaxial cable damage, or poor contact such as loosing of the connectors or wire disconnection of wiring of the antennas?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas in close?
Even if all of the above conditions is fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power-on, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power off, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation check for the electromagnetic noise.
After checking the above, consult the service representative.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, or the antennas and the outdoor unit.
Extend the distance between the TV sets or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
F
22
Page 23
9-7. Test point diagram and voltage
MSZ-GA22VA - MSZ-GA25VA - MSZ-GA35VA -
Indoor electronic control P.C. board
Power supply input
Varistor (NR11)
Release of Auto restart function Solder the Jumper wire to JR07. (Refer to 8-3.)
230V AC Fuse(F11)
E1E1E1
}
Indoor fan motor (CN211)
1311V DC 3(-) Fiducial terminal of
cathode side on measur­ing high-voltage DC
415
V DC
5(+)3-6V DC 6(+)0V DC or 15V DC
Interlock switch(Fan) (CN1R1)
Power monitor receiver P.C. board.
Emergency operation switch
SW P.C. board
12V DC
5V DC
Indoor coil thermistor RT12(MAIN) 12 RT13(SUB) 34
(CN112) Horizontal vane
motor(CN151) Room temperature
thermistor(RT11)
Timer short mode point JPG, JPS
}
(Refer to 8-1.)
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT11)
23
Resistance (k")
Temperature (:)
Page 24
10
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
MSZ-GA22VA - MSZ-GA25VA - MSZ-GA35VA ­INDOOR UNIT
OPERATING PROCEDURE
1. Removing the panel
(1) Remove the horizontal vane. (2) Remove the screw caps of the panel.
Remove the screws. (See Photo 1.)
(3) Hold the lower part of both ends on the panel and pull it
slightly toward you, and then remove the panel by pushing it upward.
Photo 1
Horizontal vane
E1E1E1
PHOTOS
Screws of the panel
24
Page 25
OPERATING PROCEDURE PHOTOS
2. Removing the electronic control P.C. board, the power monitor receiver P.C. board, SW P.C. board and the terminal block
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the screw of V.A. clamp, and then the
indoor/outdoor connecting wire. (See Photo 2.)
(3) Remove the switch holder from the electrical cover.
(See Photo 3.)
(4) Remove the screw of the electrical cover, and then the
electrical cover. (See Photo 3.)
(5) Remove the ground wire connected to the indoor
electronic control P.C. board from the electrical box.
(See Photo 4.)
(6) Unhook the power monitor receiver P.C. board holder from
the catch. (See Photo 4.)
(7) Open the rear cover of the power monitor receiver P.C.
board holder and pull out the power monitor receiver P.C.
board. (8) Open the switch holder and pull out SW P.C. board. (9) Pull the electronic control P.C. board slightly toward you
from the electrical box, and disconnect TAB3 and all the
connectors on the electronic control P.C. board.
(LD101 and LD105 are direct-mounted to the electronic
control P.C. board.)
(10)
Pull out the electronic control P.C. board from the electrical
box. (11)
Remove the ground wire connected to the heat exchanger
from the electrical box. (See Photo 4.)
(12)
Unhook the catches of the electrical box, and pull out the
electrical box.
(13)
Remove the screws of the terminal block cover, and then the terminal block cover and the terminal block holder. (See Photo 2.)
(14)
Remove the terminal block by sliding it.
Photo 2
Screws of the terminal block cover
Drain hose
Photo 3
Screw of V.A. clamp
Switch holder
Screw of the electrical cover.
3. Removing the electrical box
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2) Remove the screw of V.A. clamp, and then the indoor/
outdoor connecting wire. (See Photo 2.)
(3) Remove the switch holder and the electrical cover.
(See Photo 3.)
(4) Remove the ground wire connected to the heat exchanger
from the electrical box. (See Photo 4.)
(5) Disconnect the following connectors on the electronic
control P.C. board; the fan motor connector <CN211>, the indoor coil thermistor connector <CN112>, the vane motor connector <CN151>, the connector of the interlock switch (Fan) of the horizontal vane <CN1R1>.
(6) Unhook the catches of the electrical box, and pull out the
electrical box.
Photo 4
Ground wires
Fan motor connector (CN211)
Connector of the interlock switch(Fan) (CN1R1)
Indoor coil thermistor connector (CN112)
Vane motor connector (CN151)
Power monitor receiver P.C. board holder
25
Page 26
OPERATING PROCEDURE PHOTOS
4. Removing the horizontal vane motor unit
(1) Remove the horizontal vane and the panel. (Refer to 1.) (2) Remove the screws of the horizontal vane motor unit,
and pull out the horizontal vane motor unit. (See Photo 5.)
(3) Disconnect the connector from the horizontal vane motor
unit.
5. Removing the indoor fan motor and the line flow fan
(1) Remove the horizontal vane, the panel (Refer to 1.) and
the corner box.
(2)
Remove the switch holder and the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly, and
remove the nozzle assembly. (4) Remove the screws fixing the motor bed. (5) Loosen the screw fixing the line flow fan. (6) Remove the motor bed together with fan motor and motor
band. (7) Release the hooks of the motor band, and remove the
motor band then pull out the indoor fan motor. (8) Remove the screws fixing the left side of the heat
exchanger. (9) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.
(See Photo 8.)
(See Photo 6.)
(See Photo 7.)
Photo 5
Photo 6
Screws of the motor bed
Photo 7
Screws of the horizontal vane motor unit
Motor band
26
Screw of the line flow fan
Photo 8
Screws of the left side of the heat exchanger
Page 27
PARTS LIST11
MSZ-GA22VA - (WH) MSZ-GA25VA - (WH) MSZ-GA35VA - (WH)
E1
E1
E1
11-1. INDOOR UNIT STRUCTURAL PARTS
1
2
3
4
9
8
7 (See 12.)
11-2. ACCESSORY AND REMOTE
CONTROLLER
10
11
5 6
11-1. INDOOR UNIT STRUCTURAL PARTS
Symbol
No.
E02 897 234
1
E02 915 000
2
E02 913 067
3
E02 915 010
4
E02 915 100
5
E02 916 100
6
7
E02 913 975
8
E02 913 970
9
Part No.
Part name
BOX PANEL ASSEMBLY (WH) SCREW CAP FRONT PANEL (WH) CATECHIN AIR FILTER (LEFT) CATECHIN AIR FILTER (RIGHT) AIR CLEANING FILTER CORNER BOX (RIGHT) INSTALLATION PLATE
in Wiring
Diagram
11-2. ACCESSORY AND REMOTE CONTROLLER
E02 915 426
10
E02 527 083
11
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
Q'ty/unit
MSZ-GA22VA -
E1
MSZ-GA25VA -
(WH) (WH)
1 1 2 1 1 1 1 1 1
1 1
E1
(WH)
1 1 2 1 1 1 1 1 1
1 1
MSZ-GA35VA -
E1
1 1 2 1 1 1 1 1 1
1 1
Including No.3,4 2PCS/SET
MAC-415FT-E
KM05B
Remarks
27
Page 28
MSZ-GA22VA - (WH) MSZ-GA25VA - (WH) MSZ-GA35VA - (WH)
E1
E1
E1
11-3. INDOOR UNIT ELECTRICAL PARTS
AND FUNCTIONAL PARTS
1
2
3 4
5
INTERLOCK SWITCH (FAN)
6
7
POWER MONITOR RECEIVER P.C. BOARD
15
21
20
19
18
14 13
12
11
SW P.C. BOARD
15
17
11-4. INDOOR UNIT HEAT EXCHANGER
23
24
22
28
10
9
VARISTOR
8
FUSE
15
ROOM TEMPERATURE THERMISTOR
16
Page 29
11-3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
Symbol
No. Part No.
E02 751 509
1
E02 001 504
2
E02 897 702
3
E02 915 235
4
E02 897 303
5
E02 897 316
6
E02 913 040
7
E02 127 382
8
E02 661 385
9
E02 915 095
10
E02 897 784
11
E02 897 780
12
E02 897 779
13
E02 913 375
14
E02 915 452 E02 916 452
15
E02 917 452 E02 897 308
16
E02 913 307
17
E02 915 782
18
E02 915 300
19
E02 897 333
20
E02 897 302
21
W1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD W2 Including FAN MOTOR RUBBER MOUNT (2 PCS/SET)
BEARING MOUNT SLEEVE BEARING DRAIN HOSE NOZZLE ASSEMBLY VANE MOTOR UNIT (HORIZONTAL) INTERLOCK SWITCH(FAN) HORIZONTAL VANE FUSE VARISTOR POWER MONITOR RECEIVER P.C. BOARD HOLDER V.A. CLAMP TERMINAL BLOCK COVER TERMINAL BLOCK HOLDER TERMINAL BLOCK ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ELECTRONIC CONTROL P.C. BOARD W1 ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR SWITCH HOLDER INDOOR FAN MOTOR W2 MOTOR BAND LINE FLOW FAN
Part name
in Wiring
Diagram
NR11
RT11
RT12, RT13
MSZ-GA22VA - E1MSZ-GA25VA - E1MSZ-GA35VA -
MV
F11
TB
MF
(WH)
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1
Q'ty/unit
(WH)
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1
1 1 1 1 1 1
11-4. INDOOR UNIT HEAT EXCHANGER
E02 913 620
22 23
E02 815 666
24
E02 151 667
INDOOR HEAT EXCHANGER UNION (GAS) UNION (LIQUID)
1 1 1
1 1 1
(WH)
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1
E1
Remarks
UP & DOWN
3.15A
AUTO RESTART AUTO RESTART AUTO RESTART
RC0J30-
{9.52 {6.35
29
Page 30
12
Model
Part No.
E1 E1
MAC-415FT-E
MSZ-GA22VA­MSZ-GA25VA­MSZ-GA35VA-
E1
Air cleaning filter (Blue bellows type)
OPTIONAL PARTS
AIR CLEANING FILTER (ANTI-ALLERGY ENZYME FILTER)
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 1 year.
If AIR CLEANING FILTER is to be washed, soak AIR CLEANING FILTER in water (when showing dirt, in lukewarm
water) and rinse it delicately, without removing the filter from the frame about once every 3 months.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
Do not remove or attach AIR CLEANING FILTER during unit operation.
Replacement of the air cleaning filter
(1) Remove the catechin air filter(left one)
The air cleaning filter is not attached to the right side catechin air filter
(2) Remove the air cleaning filter(Blue
bellows type) from the catechin air filter.
30
Page 31
31
Page 32
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Jan. 2005. No. OB378 6 Made in Japan
New publication, effective Jan. 2005 Specifications subject to change without notice.
Loading...