Mitsubishi MSZ-FX12RV- E1, MUZ-FX12RV- E1 Service Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
Wireless type Models
1999
No. OB244
MSZ-FX12RV -
(WH)
MUZ-FX12RV -
CONTENTS
1. PART NAMES AND FUNCTIONS······················2
2. SPECIFICATION·················································4
4. OUTLINES AND DIMENSIONS·························7
5. WIRING DIAGRAM ············································8
6. REFRIGERANT SYSTEM DIAGRAM··············10
7. PERFORMANCE CURVES······························11
8. MICROPROCESSOR CONTROL ····················17
9. SERVICE FUNCTIONS ····································32
10. TROUBLESHOOTING ······································34
11. DISASSEMBLY INSTRUCTIONS·····················51
12. PARTS LIST······················································55
13. OPTIONAL PARTS···········································59
E1E1
1
PART NAMES AND FUNCTIONS
MSZ-FX12RV-
INDOOR UNIT
Air cleaning filter(white bellows type)
Deodorizing filter (gray sponge type)
Air filter
Front panel
Vertical vanes
Operation section
E1
Grille
Air inlet
to Breaker
Power supply cord
Remote control receiving section
Horizontal vane
Remote controller
Display section
(When the grille is open)
MUZ-FX12RV-
E1
OUTDOOR UNIT
Emergency operation switch
Operation Indicator
Receiving section
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
2
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
OPERATION SELECT button
FAN SPEED CONTROL button
ON-TIMER button
CLOCK SET button
HR. button
MIN. button
(TIME SET button)
TEMPERATURE buttons
VANE CONTROL button
OFF-TIMER button
RESET button
ON/OFF TOO
WARM
TOO
COOL
HR. MIN.
CLOCK
RESET
CLOCK
MODE
FAN
VANE
START
STOP
ECONO COOL button
ECONO COOL
I FEEL
COOL DRY HEAT
6 00
1 1 00
AM
PM
SWING
SWING button
MSZ-FX12RV-
E1
REMOTE CONTROLLER
3
2
Indoor model
Function
Power supply
Capacity Air flow(Hi) Dehumidification Power outlet Running current Power input Auxiliary heater Power factor Starting current Fan motor current Model Winding resistance(at20:) Dimensions WOHOD Weight Air direction Sound level (Hi) Fan speed (Hi) Fan speed regulator RT11(at25:) Thermistor RT12(at25:) RT13(at25:) Outdoor model Outdoor air flow Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity(R-22) Refrigerating oil (Model)
RT61(at100:)
Thermistor RT62(at0:) RT64(at70:)
kW
K /h
R/h
A A
W
A(kW)
%
A A
"
mm
kg
dB(A)
rpm
k" k" k"
K /h
A A
W
"
  
"
mm
kg
dB(A)
rpm
kg cc
k" k" k"
MSZ-FX12RV -
E1
Single phase
220-240V,50Hz
10
— 98
6.49 - 5.95
0.19
RC4V19­WHT-BLK 292 BLK-RED 325 850O278O191
10
5
3 10 10 10
MUZ-FX12RV -
E1
0.29-0.31
SHB-130FVW
1100
U-V 0.95 U-W 0.95
V-W 0.95 RA6V28-
WHT-BLK 197
BLK-RED 315 YLW-BLK 13
710(+69)o540o255
34
2
1.10
350 (MS56)
13.4
33.2
7.9
Cooling
3.5 (0.9-3.8) 588
1.6
5.47 - 5.01
1180 (150 - 1290)
39
1020
1410-1470
4.99-4.51
2.97
46
640-670
Heating
4.8 (0.9-6.7) 642
6.49 - 5.95
1400 (150 - 2150)
39
1100
1560-1620
6.01-5.45
3.43
48
680-720
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical data
Fan
motor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
Capacity
SPECIFICATION
NOTE : Test conditions.
Cooling : Indoor DB27: WB19: Heating : Indoor DB 20: WB -:
Outdoor DB35: WB24: Ondoor DB 7: WB 6:
4
1.5+ 440V
MP24GA 12V 300"
ERZV10D471
S201DH1Y
5P
JM1aN-ZTMP-DC12V
93.5:5A 250V 136:i3: 2A
250V 3.15A
500+ 450V
1.8+ 440V RR-18
250V 2A
13A 1.0mH
EM43240 50m" 5W
100" 20W
4P
PS21101-AL / PS21204-A
G4U-1-E G4U-1-E
LB6 220-240V AC
PMA10001
G4A-1A-P-PS
INDOOR UNIT
OUTDOOR UNIT
Item
Model
Model
Item
Indoor fan capacitor Vane motor Varistor (NR11) Semiconductor relay Terminal block Relay (compressor) (52C) Terminal block thermal Fuse Indoor fan motor thermal fuse Fuse (F11)
Smoothing capacitor (C61,C62) Outdoor fan capacitor (C65) Current transformer (CT61) Fuse (F801, F901) Reactor (L64) Noise filter Current detecting resistor (R61, 62, 64) Current limiting resistor (R65) Terminal block Intelligent power module Relay (X61) Relay (X62) Reversing valve coil Power factor controll module Rush current limiting relay
MSZ-FX12RV - E1
MUZ-FX12RV - E1
Specifications and rating conditions of main electric parts
5
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions.
Cooling : DB27: WB19: Heating : DB20: WB -:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
MSZ-FX12RV- E1
COOLING
HEATING
NOTCH
39
SPL(dB(A)) LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
MUZ-FX12RV- E1
HEATING
NOTCH
46
COOLING
48
SPL(dB(A)) LINE
Test conditions.
Cooling :DB35: WB24: Heating :DB 7: WB 6:
3
NOISE CRITERIA CURVES
6
116.581.5
818
278
850
16562956
or more
100
41
2.5
42
271 4.5
231.5
82
169
326 326
5
189
56
160
17.5
Air in
Air out
Insulation [28
Drain hose [16 (Connected part O.D)
Installation plate
Wall hole [65
Indoor unit
Installation plate
Power supply cord Lead to right 1.0m Lead to left 0.3m
Wireless remote controller
Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [37 O.D
[21 I.D
78
67
7
{
OUTLINES AND DIMENSIONS4
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
Service port
Bolt pitch for installation
Handle
Air out
Air in
Drainage holes [28
4 holes 10o21
18
500 710
265
105
69
138
20
40
If both sides or back side is vacant. only to be free 50 cm in front of a unit
Air in
265
REQUIRED SPACE
If a front side or both sides is vacant. an upper side of a unit has only to be vacant 10cm.
Drainage holes [28
127
32.4
92
367
Drainage holes [28
33
32.5
255
285
320
155
90
43-
35-
540
270
10
35cm or more
50cm or more
10cm or more
10cm or more
10cm
or m
ore
MSZ-FX12RV-
INDOOR UNIT
E1
Unit: mm
MUZ-FX12RV-
OUTDOOR UNIT
E1
7
5 WIRING DIAGRAM
MSZ-FX12RV- MODEL WIRING DIAGRAM
E1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
220-240V~
POWER SUPPLY CORD ~/N 220-240V 50Hz
PE
CIRCUIT BREAKER
TB
L
BRN
BRN
3
2
WHT
N
BLU
BLU
GRN/YLW
RED
F12
GRN/YLW
GREEN SIGN MONITOR P.C.BOARD
11
BLU BLU
1 2
BLU
CN
CN
151
1J1
CN201
3 2 1
LD101T
10
MV1
MV2
3
52C
4
ELECTRONIC CONTROL P.C. BOARD
5
POWER MONITOR, RECEIVER P.C.BOARD
HIC1
TRANS
F11
NR11
C11
SR141
REMOTE CONTROLLER
4 3 2
1
CN112
CN
121
1 2 3
CN211
CN 111
RT13 RT12
BLK
3
GRY YLW BRN WHT RED
1 2 3
MF
4 5 6
RT11
SYMBOL C11 F11 F12 HIC1 MF MV1 MV2
NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE (3.15A) THERMAL FUSE (93:) DC/DC CONVERTER INDOOR FAN MOTOR VANE MOTOR (HORIZONTAL) VANE MOTOR (VERTICAL)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
NAME
SYMBOL NR11
RT11
RT12
RT13
NAME VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
SYMBOL SR141 TB 52C
NAME SOLID STATE RELAY TERMINAL BLOCK CONTACTOR
8
MUZ-FX12RV- MODEL WIRING DIAGRAM
E1
OUTDOOR UNIT
220-240V ~
SYMBOL CT61 C61,C62 C65 DSA61 F801 F901 IC950 IPM LEV L61
NOISE FILTER P.C BOARD
R65
X64
LDNF2
CT61
LD-E
GRN
DSA61
NR61
TB1
3
12V
FROM INDOOR UNIT CONNECTING
RED WHT
2
BLU
N
TAB61
L61
TAB62
BLU
GRN/YLW
NAME CURRENT TRANSFORMER SMOOTHING CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE (2A) FUSE (2A) DC/DC CONVERTER
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL CMC COIL
BLU
CN913
TAB72
SSR61
12
21S4
L63
LDNF1
WHT
RELAY
TAB71
P.C BOARD
F901
C65
ORN
WHT
SYMBOL L63 L64 MC MF61 NR61 PFC RT61 RT62 RT64 R61,62
TAB68
TAB69
CN912
CN
X61
X62
WHT
BLU
CN914
3 2
911
1
654321
LD62 LD61
4
CN779CN778
4
3 2
CN726
1
CN771
ELECTRONIC
R61
R62
C61
C62
IC950
TRANS
+ +
F801
CONTROL
BLK
RED
YLW
5
MF61
COIL REACTOR COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) VARISTOR POWER FACTOR CONTROL MODULE DISCHARGE TEMPERATURE THERMIST OR DEFROST THERMISTOR FIN TEMPERATURE THERMIST OR CURRENT-DETECTING RESISTOR
P.C BOARD
CN601
231
CN641
NAME
PFC
R64
6 5 4 3 2 1
-
1 2
CN642
SYMBOL R64 R65 SSR61 TB1, TB2 X61, X62 X64
21S4
6
LEV
+
U V
W
RT64
CN724
TAB75
TAB76
LD65
LD66
LD67
V
GRY
TB2
BLK
GRY
1 2
BLK
WHT
RED
3
RED
~
~
P N
IPM
RT61
RT62
MC
NAME CURRENT-DETECTING RESISTOR CURRENT-LIMITING RESISTOR SOLID STATE RELAY TERMINAL BLOCK RELAY RELAY REVERSING VALVE COIL (COOLING TURN ON)
L64
BLK
21
BLK
WHT
W
U
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
9
6
Refrigerant Piping Max. length A
Height difference should be within 8m regardless of which unit, indoor or outdoor position is high.
w Max. Height
difference 8m
Indoor unit
Outdoor unit
Indoor heat exchanger
Outdoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13(sub)
Defrost thermistor RT62
Discharge thermistor RT61
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
Capillary tube (2 pcs)
Refrigerant flow in cooling
Compressor
Accumulator
Maffler
Muffler
Reversing valve
Refrigerant flow in heating
Refrigerant pipe [12.7 (Option)
Refrigerant pipe [6.35 (Option)
Indoor coil thermistor RT12(main)
Expansion valve
[3.0o[2.0o200
[3.0o[2.0o300
REFRIGERANT SYSTEM DIAGRAM
MSZ-FX12RV -
Unit : mm
E1
MUZ-FX12RV -
E1
INDOOR UNIT
MAX. REFRIGERANT PIPING LENGTH
Additional piping
Model
Max. length :mm
A
OUTDOOR UNIT
Piping size O.D : mm
Gas Liquid Indoor unit Outdoor unit
Length of connecting pipe : m
MSZ-FX12RV-
E1
12
12.7 6.35 0.43 0
MAX. HEIGHT DIFFERENCE
Model
E1
Outdoor unit precharged
1100
ADDITIONAL REFRIGERANT CHARGE (R-22:g)
MSZ-FX12RV-
5m
0
6m
30
Refrigerant piping length (one way)
7m
60
90
Calculation : Xg=30g /m(A-5)m
9m8m
120
11m10m
180150
12m
210
10
PERFORMANCE CURVES7
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198 ~ 242V ),50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature ::WB (2) Indoor discharge air wet-bulb temperature ::WB (3) Outdoor intake air dry-bulb temperature ::DB (4) Total input :W (5) Indoor intake air dry-bulb temperature ::DB (6) Outdoor intake air wet-bulb temperature ::WB (7) Total input :W
Indoor air wet-bulb temperature difference on the left side of the chart on next page shows the difference between the indoor intake air wet-bulb temperature and the indoor discharge air wet-bulb temperature for your reference at service.
E1
Cooling
}
Heating
}
How to measure the indoor air wet-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
11
29.3
27.1
24.8
22.6
20.3
18.1
15.8
13.5
MSZ-FX12RV- E1
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
11.2
10.2
9.3
8.4
7.5
6.7
MSZ-FX12RV- E1
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Cooling capacity
MUZ-FX12RV -
E1
Heating capacity
NOTE:The above curves are for the heating operation without any frost.
MUZ-FX12RV -
E1
Correction of total input
2.0
1.5
1.0
0.5
Capacity correction factors
0 50 100 150(Hz)
The operational frequency of compressor
MUZ-FX12RV -
E1
MUZ-FX12RV -
E1
Correction of total input
1.5
1.0
0.5
Capacity correction factors
0 50 100 150(Hz)
The operational frequency of compressor
12
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
(MPa • G)
(kgf/F • G)
(reference)
18 32
15 20
50
25 60
30 70(%)
35(:)
0.2
0.3
0.4
0.5
0.6
0.7
82Hz
2
3
4
5
6
7
8
0.8
220V
240V
15 20
50
25 60
30
70(%)
35(:)
3
4
5
6
7
82Hz
32
18
6.0
5.5
5.0
4.5
4.0
3.5
3.0 2
5 10152025
240V
220V
58Hz
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit , and select either the COOLmode or the HEAT mode before starting to operate the air conditioner.
2. The compressor starts up. The operational frequency of the compressor is 82Hz in the COOL mode and 58Hz in the HEAT mode.
3. The fan speed of the indoor unit is Hi.
4. This operation continues for 30minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch again, press any button on the remote
controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa • G) =10.2(kgf/ff• G)
COOL operation
1 Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20 25 30
2 Air flow should be set at Hi. 3 Operational frequency : 82Hz
Relative humidity(%)
50 60 70
MUZ-FX12RV -
Outdoor low pressure
Ambient temperature(:)
HEAT operation
Condition Indoor : Dry bulb temperature 20.0:
Wet bulb temperature 14.5:
E1
Outdoor : Dry bulb temperature 2 7 15 20.0:
MUZ-FX12RV -
Outdoor unit current (A)
Ambient temperature(:)
MUZ-FX12RV -
Outdoor unit current (A)
Ambient temperature(:)
Wet bulb temperature 1 6 12 14.5:
E1
13
E1
PERFORMANCE DATA COOL operation
MSZ-FX12RV - MUZ-FX12RV -
CAPACITY : 3.5 kW INPUT : 1180 W SHF : 0.67
INDOOR INDOOR
DB(:) WB(:)
21 18 4.11 2.02 0.49 944 3.94 1.93 0.49 991 3.78 1.85 0.49 1038 3.64 1.78 0.49 1086 21 20 4.29 1.59 0.37 991 4.11 1.52 0.37 1050 3.99 1.48 0.37 1074 3.85 1.42 0.37 1121 22 18 4.11 2.18 0.53 944 3.94 2.09 0.53 991 3.78 2.00 0.53 1038 3.64 1.93 0.53 1086 22 20 4.29 1.76 0.41 991 4.11 1.69 0.41 1050 3.99 1.64 0.41 1074 3.85 1.58 0.41 1121 22 22 4.46 1.29 0.29 1027 4.31 1.25 0.29 1092 4.20 1.22 0.29 1121 4.03 1.17 0.29 1168 23 18 4.11 2.34 0.57 944 3.94 2.24 0.57 991 3.78 2.15 0.57 1038 3.64 2.07 0.57 1086 23 20 4.29 1.93 0.45 991 4.11 1.85 0.45 1050 3.99 1.80 0.45 1074 3.85 1.73 0.45 1121 23 22 4.46 1.47 0.33 1027 4.31 1.42 0.33 1092 4.20 1.39 0.33 1121 4.03 1.33 0.33 1168 24 18 4.11 2.51 0.61 944 3.94 2.40 0.61 991 3.78 2.31 0.61 1038 3.64 2.22 0.61 1086 24 20 4.29 2.10 0.49 991 4.11 2.02 0.49 1050 3.99 1.96 0.49 1074 3.85 1.89 0.49 1121 24 22 4.46 1.65 0.37 1027 4.31 1.59 0.37 1092 4.20 1.55 0.37 1121 4.03 1.49 0.37 1168 24 24 4.69 1.17 0.25 1074 4.52 1.13 0.25 1133 4.41 1.10 0.25 1168 4.27 1.07 0.25 1227 25 18 4.11 2.67 0.65 944 3.94 2.56 0.65 991 3.78 2.46 0.65 1038 3.64 2.37 0.65 1086 25 20 4.29 2.27 0.53 991 4.11 2.18 0.53 1050 3.99 2.11 0.53 1074 3.85 2.04 0.53 1121 25 22 4.46 1.83 0.41 1027 4.31 1.77 0.41 1092 4.20 1.72 0.41 1121 4.03 1.65 0.41 1168 25 24 4.69 1.36 0.29 1074 4.52 1.31 0.29 1133 4.41 1.28 0.29 1168 4.27 1.24 0.29 1227 26 18 4.11 2.84 0.69 944 3.94 2.72 0.69 991 3.78 2.61 0.69 1038 3.64 2.51 0.69 1086 26 20 4.29 2.44 0.57 991 4.11 2.34 0.57 1050 3.99 2.27 0.57 1074 3.85 2.19 0.57 1121 26 22 4.46 2.01 0.45 1027 4.31 1.94 0.45 1092 4.20 1.89 0.45 1121 4.03 1.81 0.45 1168 26 24 4.69 1.55 0.33 1074 4.52 1.49 0.33 1133 4.41 1.46 0.33 1168 4.27 1.41 0.33 1227 26 26 4.83 1.01 0.21 1133 4.69 0.98 0.21 1192 4.62 0.97 0.21 1227 4.48 0.94 0.21 1263 27 18 4.11 3.00 0.73 944 3.94 2.87 0.73 991 3.78 2.76 0.73 1038 3.64 2.66 0.73 1086 27 20 4.29 2.62 0.61 991 4.11 2.51 0.61 1050 3.99 2.43 0.61 1074 3.85 2.35 0.61 1121 27 22 4.46 2.19 0.49 1027 4.31 2.11 0.49 1092 4.20 2.06 0.49 1121 4.03 1.97 0.49 1168 27 24 4.69 1.74 0.37 1074 4.52 1.67 0.37 1133 4.41 1.63 0.37 1168 4.27 1.58 0.37 1227 27 26 4.83 1.21 0.25 1133 4.69 1.17 0.25 1192 4.62 1.16 0.25 1227 4.48 1.12 0.25 1263 28 18 4.11 3.17 0.77 944 3.94 3.03 0.77 991 3.78 2.91 0.77 1038 3.64 2.80 0.77 1086 28 20 4.29 2.79 0.65 991 4.11 2.67 0.65 1050 3.99 2.59 0.65 1074 3.85 2.50 0.65 1121 28 22 4.46 2.37 0.53 1027 4.31 2.28 0.53 1092 4.20 2.23 0.53 1121 4.03 2.13 0.53 1168 28 24 4.69 1.92 0.41 1074 4.52 1.85 0.41 1133 4.41 1.81 0.41 1168 4.27 1.75 0.41 1227 28 26 4.83 1.40 0.29 1133 4.69 1.36 0.29 1192 4.62 1.34 0.29 1227 4.48 1.30 0.29 1263 29 18 4.11 3.33 0.81 944 3.94 3.19 0.81 991 3.78 3.06 0.81 1038 3.64 2.95 0.81 1086 29 20 4.29 2.96 0.69 991 4.11 2.84 0.69 1050 3.99 2.75 0.69 1074 3.85 2.66 0.69 1121 29 22 4.46 2.54 0.57 1027 4.31 2.45 0.57 1092 4.20 2.39 0.57 1121 4.03 2.29 0.57 1168 29 24 4.69 2.11 0.45 1074 4.52 2.03 0.45 1133 4.41 1.98 0.45 1168 4.27 1.92 0.45 1227 29 26 4.83 1.59 0.33 1133 4.69 1.55 0.33 1192 4.62 1.52 0.33 1227 4.48 1.48 0.33 1263 30 18 4.11 3.50 0.85 944 3.94 3.35 0.85 991 3.78 3.21 0.85 1038 3.64 3.09 0.85 1086 30 20 4.29 3.13 0.73 991 4.11 3.00 0.73 1050 3.99 2.91 0.73 1074 3.85 2.81 0.73 1121 30 22 4.46 2.72 0.61 1027 4.31 2.63 0.61 1092 4.20 2.56 0.61 1121 4.03 2.46 0.61 1168 30 24 4.69 2.30 0.49 1074 4.52 2.21 0.49 1133 4.41 2.16 0.49 1168 4.27 2.09 0.49 1227 30 26 4.83 1.79 0.37 1133 4.69 1.74 0.37 1192 4.62 1.71 0.37 1227 4.48 1.66 0.37 1263 31 18 4.11 3.66 0.89 944 3.94 3.50 0.89 991 3.78 3.36 0.89 1038 3.64 3.24 0.89 1086 31 20 4.29 3.30 0.77 991 4.11 3.17 0.77 1050 3.99 3.07 0.77 1074 3.85 2.96 0.77 1121 31 22 4.46 2.90 0.65 1027 4.31 2.80 0.65 1092 4.20 2.73 0.65 1121 4.03 2.62 0.65 1168 31 24 4.69 2.49 0.53 1074 4.52 2.39 0.53 1133 4.41 2.34 0.53 1168 4.27 2.26 0.53 1227 31 26 4.83 1.98 0.41 1133 4.69 1.92 0.41 1192 4.62 1.89 0.41 1227 4.48 1.84 0.41 1263 32 18 4.11 3.82 0.93 944 3.94 3.66 0.93 991 3.78 3.52 0.93 1038 3.64 3.39 0.93 1086 32 20 4.29 3.47 0.81 991 4.11 3.33 0.81 1050 3.99 3.23 0.81 1074 3.85 3.12 0.81 1121 32 22 4.46 3.08 0.69 1027 4.31 2.97 0.69 1092 4.20 2.90 0.69 1121 4.03 2.78 0.69 1168 32 24 4.69 2.67 0.57 1074 4.52 2.57 0.57 1133 4.41 2.51 0.57 1168 4.27 2.43 0.57 1227 32 26 4.83 2.17 0.45 1133 4.69 2.11 0.45 1192 4.62 2.08 0.45 1227 4.48 2.02 0.45 1263
NOTE Q :Total capacity (kW) SHF :Sensible heat factor
SHC :Sensible heat capacity (kW) INPUT :Total power input (W)
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 25 27 30
E1E1
OUTDOOR DB(:)
14
OUTDOOR DB(:)
INDOOR INDOOR
35 40 43 46
DB(:) WB(:)
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 3.43 1.68 0.49 1156 3.15 1.54 0.49 1227 3.03 1.48 0.49 1251 2.91 1.42 0.49 1274 21 20 3.61 1.33 0.37 1204 3.36 1.24 0.37 1263 3.24 1.20 0.37 1298 3.12 1.15 0.37 1333 22 18 3.43 1.82 0.53 1156 3.15 1.67 0.53 1227 3.03 1.60 0.53 1251 2.91 1.54 0.53 1274 22 20 3.61 1.48 0.41 1204 3.36 1.38 0.41 1263 3.24 1.33 0.41 1298 3.12 1.28 0.41 1333 22 22 3.82 1.11 0.29 1251 3.57 1.04 0.29 1322 3.45 1.00 0.29 1345 3.33 0.96 0.29 1369 23 18 3.43 1.96 0.57 1156 3.15 1.80 0.57 1227 3.03 1.73 0.57 1251 2.91 1.66 0.57 1274 23 20 3.61 1.62 0.45 1204 3.36 1.51 0.45 1263 3.24 1.46 0.45 1298 3.12 1.40 0.45 1333 23 22 3.82 1.26 0.33 1251 3.57 1.18 0.33 1322
3.45 1.14 0.33 1345
3.33 1.10 0.33 1369 24 18 3.43 2.09 0.61 1156 3.15 1.92 0.61 1227 3.03 1.85 0.61 1251 2.91 1.77 0.61 1274 24 20 3.61 1.77 0.49 1204 3.36 1.65 0.49 1263 3.24 1.59 0.49 1298 3.12 1.53 0.49 1333 24 22 3.82 1.41 0.37 1251 3.57 1.32 0.37 1322 3.45 1.28 0.37 1345 3.33 1.23 0.37 1369 24 24 4.03 1.01 0.25 1298 3.78 0.95 0.25 1357 3.68 0.92 0.25 1387 3.57 0.89 0.25 1416 25 18 3.43 2.23 0.65 1156 3.15 2.05 0.65 1227 3.03 1.97 0.65 1251 2.91 1.89 0.65 1274 25 20 3.61 1.91 0.53 1204 3.36 1.78 0.53 1263 3.24 1.72 0.53 1298 3.12 1.65 0.53 1333 25 22 3.82 1.56 0.41 1251 3.57 1.46 0.41 1322 3.45 1.41 0.41 1345 3.33 1.36 0.41 1369 25 24 4.03 1.17 0.29 1298 3.78 1.10 0.29 1357 3.68 1.07 0.29 1387 3.57 1.04 0.29 1416 26 18 3.43 2.37 0.69 1156 3.15 2.17 0.69 1227 3.03 2.09 0.69 1251 2.91 2.00 0.69 1274 26 20 3.61 2.05 0.57 1204 3.36 1.92 0.57 1263 3.24 1.85 0.57 1298 3.12 1.78 0.57 1333 26 22 3.82 1.72 0.45 1251 3.57 1.61 0.45 1322 3.45 1.55 0.45 1345 3.33 1.50 0.45 1369 26 24 4.03 1.33 0.33 1298 3.78 1.25 0.33 1357 3.68 1.21 0.33 1387 3.57 1.18 0.33 1416 26 26 4.24 0.89 0.21 1345 3.99 0.84 0.21 1404 3.87 0.81 0.21 1434 3.75 0.79 0.21 1463 27 18 3.43 2.50 0.73 1156 3.15 2.30 0.73 1227 3.03 2.21 0.73 1251 2.91 2.12 0.73 1274 27 20 3.61 2.20 0.61 1204 3.36 2.05 0.61 1263 3.24 1.97 0.61 1298 3.12 1.90 0.61 1333 27 22 3.82 1.87 0.49 1251 3.57 1.75 0.49 1322 3.45 1.69 0.49 1345 3.33 1.63 0.49 1369 27 24 4.03 1.49 0.37 1298 3.78 1.40 0.37 1357 3.68 1.36 0.37 1387 3.57 1.32 0.37 1416 27 26 4.24 1.06 0.25 1345 3.99 1.00 0.25 1404 3.87 0.97 0.25 1434 3.75 0.94 0.25 1463 28 18 3.43 2.64 0.77 1156 3.15 2.43 0.77 1227 3.03 2.33 0.77 1251 2.91 2.24 0.77 1274 28 20 3.61 2.34 0.65 1204 3.36 2.18 0.65 1263 3.24 2.10 0.65 1298 3.12 2.02 0.65 1333 28 22 3.82 2.02 0.53 1251 3.57 1.89 0.53 1322 3.45 1.83 0.53 1345 3.33 1.76 0.53 1369 28 24 4.03 1.65 0.41 1298 3.78 1.55 0.41 1357 3.68 1.51 0.41 1387 3.57 1.46 0.41 1416 28 26 4.24 1.23 0.29 1345 3.99 1.16 0.29 1404 3.87 1.12 0.29 1434 3.75 1.09 0.29 1463 29 18 3.43 2.78 0.81 1156 3.15 2.55 0.81 1227 3.03 2.45 0.81 1251 2.91 2.35 0.81 1274 29 20 3.61 2.49 0.69 1204 3.36 2.32 0.69 1263 3.24 2.23 0.69 1298 3.12 2.15 0.69 1333 29 22 3.82 2.17 0.57 1251 3.57 2.03 0.57 1322 3.45 1.97 0.57 1345 3.33 1.90 0.57 1369 29 24 4.03 1.81 0.45 1298 3.78 1.70 0.45 1357 3.68 1.65 0.45 1387 3.57 1.61 0.45 1416 29 26 4.24 1.40 0.33 1345 3.99 1.32 0.33 1404 3.87 1.28 0.33 1434 3.75 1.24 0.33 1463 30 18 3.43 2.92 0.85 1156 3.15 2.68 0.85 1227 3.03 2.57 0.85 1251 2.91 2.47 0.85 1274 30 20 3.61 2.63 0.73 1204 3.36 2.45 0.73 1263 3.24 2.36 0.73 1298 3.12 2.27 0.73 1333 30 22 3.82 2.33 0.61 1251 3.57 2.18 0.61 1322 3.45 2.10 0.61 1345 3.33 2.03 0.61 1369 30 24 4.03 1.97 0.49 1298 3.78 1.85 0.49 1357 3.68 1.80 0.49 1387 3.57 1.75 0.49 1416 30 26 4.24 1.57 0.37 1345 3.99 1.48 0.37 1404 3.87 1.43 0.37 1434 3.75 1.39 0.37 1463 31 18 3.43 3.05 0.89 1156 3.15 2.80 0.89 1227 3.03 2.69 0.89 1251 2.91 2.59 0.89 1274 31 20 3.61 2.78 0.77 1204 3.36 2.59 0.77 1263 3.24 2.49 0.77 1298 3.12 2.40 0.77 1333 31 22 3.82 2.48 0.65 1251 3.57 2.32 0.65 1322 3.45 2.24 0.65 1345 3.33 2.16 0.65 1369 31 24 4.03 2.13 0.53 1298 3.78 2.00 0.53 1357 3.68 1.95 0.53 1387 3.57 1.89 0.53 1416 31 26 4.24 1.74 0.41 1345 3.99 1.64 0.41 1404 3.87 1.59 0.41 1434 3.75 1.54 0.41 1463 32 18 3.43 3.19 0.93 1156 3.15 2.93 0.93 1227 3.03 2.82 0.93 1251 2.91 2.70 0.93 1274 32 20 3.61 2.92 0.81 1204 3.36 2.72 0.81 1263 3.24 2.62 0.81 1298 3.12 2.52 0.81 1333 32 22 3.82 2.63 0.69 1251 3.57 2.46 0.69 1322 3.45 2.38 0.69 1345 3.33 2.29 0.69 1369 32 24 4.03 2.29 0.57 1298 3.78 2.15 0.57 1357 3.68 2.09 0.57 1387 3.57 2.03 0.57 1416 32 26 4.24 1.91 0.45 1345 3.99 1.80 0.45 1404 3.87 1.74 0.45 1434 3.75 1.69 0.45 1463
CAPACITY : 3.5 kW INPUT : 1180 W SHF : 0.67
PERFORMANCE DATA COOL operation
MSZ-FX12RV - MUZ-FX12RV -
NOTE Q :Total capacity (kW) SHF :Sensible heat factor
SHC :Sensible heat capacity (kW) INPUT :Total power input (W)
E1E1
15
OUTDOOR DB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 3.02 910 3.65 1092 4.27 1232 4.90 1330 5.52 1414 6.10 1456 6.72 1484 21 2.88 980 3.46 1162 4.08 1288 4.66 1386 5.28 1456 5.86 1498 6.46 1554 26 2.59 1050 3.22 1232 3.79 1358 4.42 1456 5.04 1526 5.62 1568 6.24 1610
CAPACITY : 4.8 kW INPUT : 1400 W
PERFORMANCE DATA HEAT operation
MSZ-FX12RV - MUZ-FX12RV -
NOTE Q :Total capacity (kW) INPUT :Total power input (W)
E1E1
16
MICROPROCESSOR CONTROL8
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
OPERATION SELECT button
FAN SPEED CONTROL button
ON-TIMER button
CLOCK SET button
HR. button
MIN. button
(TIME SET button)
TEMPERATURE buttons
VANE CONTROL button
OFF-TIMER button
RESET button
ON/OFF TOO
WARM
TOO
COOL
HR. MIN.
CLOCK
RESET
CLOCK
MODE
FAN
VANE
START
STOP
ECONO COOL button
ECONO COOL
I FEEL
COOL DRYHEAT
6 00
1
1 00
AM
PM
SWING
SWING button
GREEN SIGN
21 22 23 24 25 26 27 28 29 30
Blinking lamp shows the room temperature
Lighting lamp shows the set temperature
GREEN SIGN
21 22 23 24 25 26 27 28 29 30
Blinking lamp shows the room temperature
Lighting lamp shows the set temperature
MSZ-FX12RV-
E1
Once the controls are set, the same operation mode can be repeated by simply turning the OPERATE/STOP button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for
3 minutes.
WIRELESS REMOTE CONTROLLER
INDOOR UNIT DISPLAY SECTION
GREEN SIGN
GREEN SIGN shows the current room temperature and set temperature. The room temperature indicated on the temperature monitor lamp may not be exactly the same as the actual room temperature.
Available the set temperature range is 16:~31:, however, indication range of temperature monitor lamp is 21:~30:.
The set temperature (lighting) and room temperature (blinking) are displayed.
1.
When the room temperature or set temperature is out of the indication range
If the set temperature is lower than 21:, indicating lamp at 21: is lighting. And if the room temperature is lower than 21:, indicating lamp at 21: is blinking.
If the set temperature is higher than 30:, indicating lamp at 30: is lighting. And if the room temperature is higher than 30:, indicating lamp at 30: is blinking.
(Example) When the set temperature is 28:, indicating lamp at 28:
2.When the room temperature or set temperature is within the indication range
(Example) When the set temperature is 26:, indicating lamp at 26:
w When the set temperature and room temperature are the same, corresponding indicating lamp is lighting.
NOTE: When the unit is not operating : Both POWER MONITOR lamp and green sign lamps are off. When ON- Timer is set : POWER MONITOR lamp is on. All green sign lamps are off. When OFF- Timer is set : The lamp indication is as same as ordinary operation.
is lighting. When the room temperature is 30: or higher, indicating lamp at 30: is blinking.
is lighting.
When the room temperature is 27.5: or higher and lower
than 28.5:, indicating lamp at 28: is blinking.
17
Model
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature Initial set temperature
26:
26: or more
26: or less
23: or less
23: to 25:
24:
Initial room temperatureminus 2:
Initial room temperatureminus 2:
1
8-1. “I FEEL CONTROL” ( ) OPERATION
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
more than 25:
23: to 25:
less than 23:
1. Press OPERATE/STOP button on the remote controller. OPERATION INDICATOR lamp of the indoor unit will turn on with a beep tone.
2. Press OPERATION SELECT button to set “I FEEL CONTROL”( ) Then a beep tone is heard.
3. The operation mode is determined by the initial room temperature at start-up of the operation.
Once the mode is fixed, the mode will not change by room temperature afterwards.
Under the ON-TIMER ( ) operation, mode is determined according to the room temperature as the operation
starts.
When the system is stopped with the OPERATE/STOP button on the remote controller, and restarted within 2 hours in “I
FEEL CONTROL” ( ) mode, the system operates in previous mode automatically regardless of the room temperature.
Example
Previous operation COOL mode of “I FEEL CONTROL”
Restart
COOL mode of “I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours, the operation mode is determined by the initial room temperature at start-up
of the operation.
Example
Previous operation COOL mode of “I FEEL CONTROL” or COOL mode
Restart
COOL or DRY or HEAT mode of “I FEEL CONTROL” that determined by initial room temperature start-up of the operation.
4. The initial set temperature is decided by the initial room temperature.
1 After the system restarts by the remote controller, the system operates with the previous set temperature regardless
of the initial set temperature The set temperature is calculated by the previous set temperature.
18