Mitsubishi MSZ-FS18NA, MUZ-FS18NAH Submittal

MSZ-FS18NA & MUZ-FS18NAH
18,000 BTU/H DELUXE WALL MOUNT
18,000 BTU/H HYPER-HEATING OUTDOOR UNIT W/BASE PAN HEATER
Job Name:
System Reference: Date:
Indoor Unit MSZ-FS18NA
Outdoor Unit MUZ-FS18NAH
INDOOR UNIT FEATURES
• Slim wall-mounted indoor units provide zone comfort control
• Dual Barrier Coating applied to the heat exchanger, vanes and fan to prevent hydrophilic and hydrophobic dirt build-up
• 3D i-see Sensor ○ Indirect or Direct Airow for personalized comfort ○ Absence Detection for energy-saving mode ○ Double Vane features: ○ Separates airow to deliver air across a large area ○ Simultaneously deliver to air separate sections of a room ○ Generates more comfortable natural airow pattern
• Multiple control options available: ○ Back-lit screen handheld remote controller (provided with unit) ○ kumo cloud ○ Third-party interface options ○ Wired or wireless controllers
• Triple-action Filtration: Nano Platinum Filter, Deodorizing Filter, & Electrostatic Anti-Allergy Enzyme Filter
• Hot-Start Technology: no cold air rush at equipment startup or when restarting after Defrost Cycle
• Quiet operation
OUTDOOR UNIT FEATURES
• INVERTER-driven compressor and LEV provide high efciency and comfort while using only the energy needed to maintain maximum performance
• H2i plus
• Blue Fin anti-corrosion treatment applied to the outdoor unit heat exchanger for increased coil protection and longer life
• Built-in base pan heater
®
enables advance features:
®
smart device app for remote access
TM
performance offers 100% heating capacity at -5° and 70% to 81% heating capacity at -13° F
Specications are subject to change without notice. © 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: MSZ-FS18NA & MUZ-FS18NAH
test
Maximum Capacity BTU/H 21,000
Rated Capacity BTU/H 17,200
Minimum Capacity BTU/H 6,450
Cooling at 95°F
1
Maximum Power Input W 2,220
Rated Power Input W 1,375
Moisture Removal Pints/h 4.8
Sensible Heat Factor 0.69
Power Factor % 98.0/98.0
Maximum Capacity BTU/H 30,000
Rated Capacity BTU/H 19,000
Heating at 47°F
2
Minimum Capacity BTU/H 5,150
Maximum Power Input W 4,000
Rated Power Input W 1,610
Power Factor % 98.0/98.0
Maximum Capacity BTU/H 27,000
Heating at 17°F
3
Rated Capacity BTU/H 12,800
Maximum Power Input W 3,820
Rated Power Input W 1,280
Heating at 5°F
Heating at -5°F
Heating at -13°F
Efciency
4
6
7
Maximum Capacity BTU/H 23,000
Maximum Power Input W 3,250
Maximum Capacity BTU/H 19,000
Maximum Capacity BTU/H 17,100
SEER 21.0
1
EER
HSPF [IV] 12.0
COP at 47°F
COP at 17°F at Maximum Capacity
COP at 5°F at Maximum Capacity
COP at -5°F at Maximum Capacity
COP at -13°F at Maximum Capacity
2
3
4
6
7
ENERGY STAR® Certied Yes
Voltage, Phase, Frequency 208/230, 1, 60
Guaranteed Voltage Range V AC 187 - 253
Voltage: Indoor - Outdoor, S1-S2 V AC 208/230
Electrical
Voltage: Indoor - Outdoor, S2-S3 V DC 24
Short-circuit Current Rating [SCCR] kA 5
Recommended Fuse/Breaker Size (Oudoor) A 20
Recommended Wire Size [Indoor - Outdoor] AWG 14
MCA A 1.0
Fan Motor Full Load Amperage A 0.65
Fan Motor Output W 40
Airow Rate at Cooling, Dry CFM 225–262–304–355–437
Airow Rate at Cooling, Wet CFM 194–225–261–305–376
Airow Rate at Heating, Dry CFM 201–272–350–410–514
Sound Pressure Level [Cooling] dB[A] 27–31–35–39–44
Indoor Unit
Sound Pressure Level [Heating] dB[A] 25–31–37–40–46
Drain Pipe Size In. [mm] 5/8 [15.88]
Coating on Heat Exchanger Dual Barrier Coating
External Finish Color Munsell 1.0Y 9.2/0.2
Unit Dimensions W x D x H: In. [mm] 36-7/16 x 9-3/16 x 12 (+11/16) [925 x 234 x 305 (+17)]
Package Dimensions W x D x H: In. [mm] 39 x 12-1/4 x 15-1/2 [990 x 310 x 400]
Unit Weight Lbs. [kg] 29 [13.5]
Package Weight Lbs. [kg] 34 [15.4]
Indoor Unit Operating Temperature
Range
NOTES: AHRI Rated Conditions (Rated data is determined at a xed compressor speed)
Conditions
*Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
• For P-Series only: » Wind bafes required to operate below 23°F DB in cooling mode. » Cooling-only system with wind bafe: -40°F - 115°F. » Heat pump system with wind bafe: 0°F - 115°F. » Refer to wind bafe documentation for further information.
**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
SEACOAST PROTECTION (ONLY APPLIES TO P-SERIES -BS MODELS)
• External Outer Panel: Phosphate coating + Acrylic-Enamel coating
• Fan Motor Support: Epoxy resin coating (at edge face)
• Separator Assembly Valve Bed: Epoxy resin coating (at edge face)
• Blue Fin treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants.
Cooling Intake Air Temp [Maximum / Minimum]* °F 90 DB, 73 WB / 67 DB, 57 WB
Heating Intake Air Temp [Maximum / Minimum] °F 80 DB / 70 DB
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB
5
Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
6
Heating at -5°F (Indoor // Outdoor) °F 70 DB, 60 WB // -5 DB, -6 WB
7
Heating at -13°F (Indoor // Outdoor) °F 70 DB, 60 WB // -13 DB, -14 WB
12.5
3.46
2.07
1.91
1.91
1.91
Specications are subject to change without notice. © 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
SPECIFICATIONS: MSZ-FS18NA & MUZ-FS18NAH
test
MCA A 18.0
MOCP A 20
Fan Motor Full Load Amperage A 0.93
Fan Motor Output W 50
Airow Rate CFM 1801/1949
Refrigerant Control LEV
Defrost Method Reverse Cycle
Outdoor Unit
Coating on Heat Exchanger Blue Fin Coating
Sound Pressure Level, Cooling
Sound Pressure Level, Heating
Compressor Type Twin Rotary
1
2
dB(A) 52
dB(A) 55
Compressor Model SNB172FQKMT
Compressor Rated Load Amps A 17.0
Compressor Locked Rotor Amps A 13.6
Compressor Oil Type // Charge oz. FV50S // 0.40
External Finish Color Munsell 3Y 7.8/1/1
Base Pan Heater Built-in
Unit Dimensions W x D x H: In. [mm] 33-1/16 x 13 x 34-5/8 [840 x 330 x 880]
Package Dimensions W x D x H: In. [mm] 38-3/4 x 16-3/4 x 39 [980 x 420 x 990]
Unit Weight Lbs. [kg] 118 [53.5]
Package Weight Lbs. [kg] 135 [61]
Cooling Air Temp [Maximum / Minimum]* °F 115 DB / 14 DB
Outdoor Unit Operating Temperature
Range
Cooling Thermal Lock-out / Re-start Temperatures** °F -4 / 0
Heating Air Temp [Maximum / Minimum] °F 75 DB, 65 WB / -13 DB, -14 WB
Heating Thermal Lock-out / Re-start Temperatures** °F -18 / -14
Type R410A
Refrigerant
Charge Lbs, oz 3, 7
Chargeless Piping Length Ft. [m] 25 [7.5]
Additional Refrigerant Charge Per Additional Piping Length oz./Ft. [g/m] 0.216 [20]
Gas Pipe Size O.D. [Flared] In.[mm] 1/2 [12.7]
Liquid Pipe Size O.D. [Flared] In.[mm] 1/4 [6.35]
Piping
Maximum Piping Length Ft. [m] 100 [30]
Maximum Height Difference Ft. [m] 50 [15]
Maximum Number of Bends 10
NOTES: AHRI Rated Conditions (Rated data is determined at a xed compressor speed)
Conditions
*Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)):
• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
• For P-Series only: » Wind bafes required to operate below 23°F DB in cooling mode. » Cooling-only system with wind bafe: -40°F - 115°F. » Heat pump system with wind bafe: 0°F - 115°F. » Refer to wind bafe documentation for further information.
**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
SEACOAST PROTECTION (ONLY APPLIES TO P-SERIES -BS MODELS)
• External Outer Panel: Phosphate coating + Acrylic-Enamel coating
• Fan Motor Support: Epoxy resin coating (at edge face)
• Separator Assembly Valve Bed: Epoxy resin coating (at edge face)
• Blue Fin treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants.
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB
5
Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
6
Heating at -5°F (Indoor // Outdoor) °F 70 DB, 60 WB // -5 DB, -6 WB
7
Heating at -13°F (Indoor // Outdoor) °F 70 DB, 60 WB // -13 DB, -14 WB
Specications are subject to change without notice. © 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
INDOOR UNIT ACCESSORIES: MSZ-FS18NA
□□□
□□□
□□□
□□□
□□□
□□□
□□□
®
and Modbus Interface
BACnet
CN24 Relay Kit
IT Extender
kumo station
Control Interface
Remote Sensor
Wired Remote Controller
Wireless Remote Controller kumo touch
Condensate
Disconnect Switch
Filter
Lineset
NOTES:
Requires MAC-334IF-E
• M-Series EZ FIT
Allows indoor units to connect to an MA Controller:
Deluxe MA Remote Controller Simple MA Controller Touch MA Controller
PAC-SF40RM-E (Unable to use with wireless remote controller)
• M-Series Ceiling Cassette, Ceiling Suspended, Horizontal-ducted and Multi-position Air Handler
• P-Series Ceiling Cassette, Ceiling Suspended, Horizontal-ducted and Multi-position Air Handler
®
Recessed Ceiling Cassette, Floor-mount and Wall-mount
Lockdown bracket for remote controller
System Control Interface
Thermostat Interface
USNAP Adapter
Wireless Interface for kumo cloud
Wired Remote Sensor
Wireless temperature and humitity sensor for kumo cloud
Deluxe Wired MA Remote Controller
Simple MA Remote Controller
Touch MA Controller
Blue Diamond (MicroBlue) Mini Condensate Pump (110/208/230V) up to 18,000 BTU/H
Blue Diamond Alarm Extension Cable — 6.5 Ft.
Blue Diamond MultiTank — collection tank for use with multiple pumps
Blue Diamond Sensor Extension Cable — 15 Ft.
Drain Pan Level Sensor/Control
Fascia Kit for MicroBlue Pump, mounts the MicroBlue and sensor directly beneath indoor unit
Sauermann Condensate Pump
(30A/600V/UL) [ts 2” X 4” utility box] - Black
(30A/600V/UL) [ts 2” X 4” utility box] - White
Electro Static Anti-allergy Enzyme Filter
Platinum Deodorizing Filter
15’ x 1/4” x 15’ / 1/2” Lineset (Twin-Tube Insulation)
30’ x 1/4” x 30’ / 1/2” Lineset (Twin-Tube Insulation)
50’ x 1/4” x 50’ / 1/2” Lineset (Twin-Tube Insulation)
65’ x 1/4” x 65’ / 1/2” Lineset (Twin-Tube Insulation)
®
for kumo cloud
RedLINK™ Wireless Controller
®
®
PAC-UKPRC001-CN-1
CN24RELAY-KIT-CM3
PAC-WHS01IE-E
PAC-WHS01HC-E
RCMKP1CB
MAC-334IF-E
PAC-US444CN-1
PAC-WHS01UP-E
PAC-USWHS002-WF-2
®
M21EAA307
PAC-USWHS003-TH-1
PAR-40MAAU
PAC-YT53CRAU-J
PAR-CT01MAU-SB
MHK2
X85-003
C13-192
C21-014
C13-103
SS610E
T18-016
SI30-230
TAZ-MS303
TAZ-MS303W
MAC-2330FT-E
MAC-3000FT-E
MLS141212T-15
MLS141212T-30
MLS141212T-50
MLS141212T-65
Specications are subject to change without notice. © 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT ACCESSORIES: MUZ-FS18NAH
□□□
□□□
□□□
Condensate Drain Socket
Hail Guards Hail Guard
14 Gauge, 4 wire MiniSplit Cable—250 ft. roll
Mini-Split Wire
Mounting Pad
Stand
14 Gauge, 4 wire MiniSplit Cable—50 ft. roll
16 Gauge, 4 wire MiniSplit Cable—250 ft. roll
16 Gauge, 4 wire MiniSplit Cable—50 ft. roll
Condensing Unit Mounting Pad: 16” x 36” x 3”
Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic
18” Single Fan Stand
24” Single Fan Stand
Condenser Wall Bracket
Condenser Wall Bracket -Stainless Steel Finish
Outdoor Unit Stand — 12” High
MAC-871DS
HG-A7
S144-250
S144-50
S164-250
S164-50
ULTRILITE1
DSD-400P
QSMS1801M
QSMS2401M
QSWB2000M-1
QSWBSS
QSMS1201M
Specications are subject to change without notice. © 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Unit: inch
INDOOR UNIT DIMENSIONS: MSZ-FS18NA
(06/09/12 KBTU/H)
(15/18 KBTU/H)
Specications are subject to change without notice. © 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Unit: inch
OUTDOOR UNIT DIMENSIONS: MUZ-FS18NAH
REQUIRED SPACE
BASICALLY OPEN
20 in OR MORE WITHOUT
ANY OBSTRUCTION
IN FRONT AND BOTH
SIDES OF THE UNIT.
4 in OR MORE.
16-7/16
AIR IN
2
DRAIN HOLE ø1-21/32
14 in OR MORE.
HANDLE
13
AIR IN
OVAL HOLES 2× 3/8 ×13/16
34-5/8
17-25/32
5/16
6-7/8 19-11/16
AIR OUT
13
33-1/16 3-3/16
1-9/16
14-5/8
13-3/4
BOLT PITCH FOR
INSTALLATION
11/16
SERVICE PANEL
VALVE COVER
6-1/2
SERVICE PORT
15-3/8
3-29/32
19/32
7-11/16
20 in OR MORE. OPEN TWO SIDES OF RIGHT OR REAR SIDE.
LIQUID REFRIGERANT PIPE JOINT
35
43
GAS REFRIGERANT PIPE JOINT
4 in OR MORE.
FLARED ø6.35 (1/4”) FLARED ø12.7 (1/2”)
1340 Satellite Boulevard Suwanee, GA 30024
Toll Free: 800-433-4822 www.mehvac.com
FORM# MSZ-FS18NA-U1 & MUZ-FS18NAH-U1 - 202101
Specications are subject to change without notice. © 2021 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.