RoHS compliant products have <G> mark on the spec name plate.
1
TECHNICAL CHANGES
MS-GD80VB -
1. New model
2
PART NAMES AND FUNCTIONS
MS-GD80VB
E1
Air cleaning filter (option)
(White bellows type)
Panel
Catechin air filter
Catechin air filter
Vertical vanes
Front panel
Air inlet
To breaker
Power supply cord
Remote control
receiving section
Operation section
(When the grille is opened)
ACCESSORIES
Horizontal vane
Emergency operation switch
Installation plate
Installation plate fixing screw 4 × 25 mm
Remote controller holder
Fixing screw for × 3.5 × 1.6 mm (Black)
Battery (AAA) for remote controller
Wireless remote controller
Felt tape (Used for left or left-rear piping)
Remote controller
Display section
Operation indicator lamp
Remote control
receiving section
MS-GD80VB
1
7
1
2
2
1
1
2
3
SPECIFICATION
Indoor model
Function
Power supply
Breaker capacity
Running current
datamotor
Power input
Power factor
Model
Fan motor current
FanElectrical
Dimensions W × H × D
Weight
Air direction
Air flow
(High/Med./Low)
Special
remarks
Sound level
Fan speed
(High/Med./Low)
(High/Med./Low)
Fan speed regulator
Remote controller model
A
A
W
%
A
mm
kg
/h
dB
rpm
MS-GD80VB
Cooling
Single phase
230 V, 50 Hz
10
0.34
69
88
RC4V40-AA
0.34
1,100 × 325 × 258
16
5
954/822/684
47/42/37
1,280/1,130/970
3
KM04B
NOTE: Test conditions are based on ISO 5151.
Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C
Indoor-Outdoor piping length: 5 m
4
NOISE CRITERIA CURVES
MS-GD80VB
FAN SPEED
High
Test conditions,
Cooling : Dry-bulb temperature 27˚C Wet-bulb temperature 19˚C
90
80
70
60
50
40
SPL(dB(A))LINE
47
NC-70
NC-60
NC-50
NC-40
INDOOR UNIT
WALL
1m
0.8m
MICROPHONE
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE
10
631252505001000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-30
NC-20
3
5
OUTLINES AND DIMENSIONS
MS-GD80VB
325
56
58
162
110 0
791
19
1068
253
Power supply cord
Lead to right 2.0 m
Lead to left 1.0 m
Installation plate
98
47
98173414.5414.5
Wall hole ø75
258
Air in
Air out
5
Installation plate
Indoor unit
173
Liquid line ø 9.52- 0.5 m
Gas line ø 12-0.43 m
{
Insulation øø50 O.D
Drain hose
(Connected part O.D)
Insulation ø28
ø16
Unit: mm
255.547
2.5
32 I.D
7.5
315
Wireless remote controller
6
WIRING DIAGRAM
MS-GD80VB
4
7
REFRIGERANT SYSTEM DIAGRAM
MS-GD80VB
Indoor
heat
exchanger
Room temperature
thermistor
RT11
Indoor coil
thermistor
RT12(main)
Indoor coil
thermistor
RT13(sub)
Strainer
#50
Refrigerant pipe ø15.88
(with heat insulator)
Flared connection
Flared connection
Refrigerant pipe ø9.52
(with heat insulator)
Unit: mm
Refrigerant flow in cooling
5
8
SERVICE FUNCTIONS
MS-GD80VB
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows.
Set time: 1 minute 1-second
Set time: 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below:
NOTE: For modification, take out the bat-
teries and press the OPERATE/
STOP (ON/OFF) button 2 or 3
times at first.
After modification, put back the bat-
teries then press the RESET button.
J1
J2
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
Table 1
1 unit operation
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the
remote controller for the indoor unit.
The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they are
set. The setting will be cancelled if the breaker has turned OFF, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
No modification
–
–
–
2 units operation
Same as at left
Solder J1
–
–
3 units operation
Same as at left
Same as at left
Solder J2
–
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
6
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are
memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” automatically starts operation
in the same mode just before the shutoff of the main power. However if the unit is operated in “I FEEL CONTROL” mode
before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial
room temperature.
Operation
If the main power has been cut, the operation settings remain.
After the power is restored, the unit restarts automatically
according to the memory. (However, it takes at least 3 minutes
for the compressor to start running.)
CN201
C11
CN211
How to release “AUTO RESTART FUNCTION”
Turn OFF the main power for the unit.
Solder jumper wire to JR07 on the indoor electronic control P.C.
board. (Refer to 10-6.)
TAB12
CN112
CN111
CN121
RA102
IC101
IC152
CN151
SW1
JR07
NOTE: •The operation settings are memorized when 10 seconds have passed after the remote controller was operated with
the remote controller.
•If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
•If the unit has been OFF with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is OFF.
•To prevent breaker OFF due to the rush of starting current, systematize other home appliances not to turn ON at the
same time.
•When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting cur-
rent by adding to the system that allows the units to start one by one.
7
9
MICROPROCESSOR CONTROL
MS-GD80VB
WIRELESS REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE/STOP
(ON/OFF) button
VANE button
(Horizontal vane button)
OPERATION SELECT button
ECONO COOL button
WIDE VANE button
(Vertical vane button)
RESET button
ON/OFF
WARM
ON/OFF
WARM
FAN
I FEEL
COOL
VAN E
DRY
FAN
MODE
WIDE VANE
ECONO COOL
LONG
RESET CLOCK
TOO
TOO
PM
AM
TOO
COOL
AM
TOO
COOL
STOP
START
HR.
MIN.
TEMPERATURE buttons
FAN SPEED CONTROL button
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
LONG button
NOTE: • The last setting will be stored after the unit is turned OFF with the remote controller.
• Indoor unit receives the signal of the remote controller with beeps.
INDOOR UNIT DISPLAY SECTION
OPERATION INDICATOR lamp
The OPERATION INDICATOR at the right side of the indoor
unit indicates the operation state.
The following indication applies regardless of
shape of the indicator.
Lighted
Not lighted
Indication
8
Operation state
This shows that the
air conditioner is
operating to reach
the target temperature.
Please wait until the
target temperature is
obtained.
This shows that the
room temperature is
approaching the
target temperature.
Difference
between target
temperature
and room
temperature
Approximate
2 or more
Approximate
2 or less
9-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons.
(TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31˚C
Indoor fan continues to operate regardless of thermostat's OFF-ON at set speed.
1. Coil frost prevention
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of
indoor heat exchanger rises.
2. Discharge temperature protection
The compressor is controlled by the temperature of discharge temperature thermistor RT62 for excess rise protection
of compressor discharge pressure.
9-2. DRY ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
(4) DRY operation will not function when the room temperature is 13˚C or below.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2˚C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection (Coil frost prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, it's speed becomes Low.
9-3. FAN ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select FAN mode with OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates. Outdoor unit dose not operate.
9-4. "I FEEL CONTROL" ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote controller. OPERATION INDICATOR lamp of the indoor unit
turns ON with a beep tone.
(2) Select "I FEEL CONTROL" mode with OPERATION SELECT button.
(3) The operation mode is determined by the room temperature at start-up of the operation.
Initial room temperature
25°C or more
more than 13
less than 25
°C
°C
,
"I FEEL CONTROL"
"I FEEL CONTROL"
Mode
COOL mode of
DRY mode of
• Once the mode is fixed, the mode dose not change by room temperature afterwards.
• Under the ON-TIMER (
When the system is stopped on the remote controller, and restarted within 2 hours in " I FEEL CONTROL" ( ) mode,
the system operates in previous mode automatically regardless of the room temperature.
) operation, mode is determined as follows.
9
(4) The initial set temperature is decided by the initial room temperature.
ModelInitial room temperatureInitial set temperature
COOL mode of
" I FEEL CONTROL"
DRY mode of
" I FEEL CONTROL"
1 When the system is restarted with the remote controller, the system operates with the previous set temperature
regardless of room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In " I FEEL CONTROL " (
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too
warm.
Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
• Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user's preference to
heat or cool. So this is called "Fuzzy control", and works only in "I FEEL CONTROL" mode.
In DRY mode of "I FEEL CONTROL", the set temperature doesn't change.
more than 13˚C, less than 25˚CInitial room temperature minus 2˚C
) mode, set temperature is decided by the microprocessor based on the room temperature.
26˚C or more24˚C
25˚C to 26˚CInitial room temperature minus 2˚C
1
…
To raise the set temperature 1~2˚C
…
To lower the set temperature 1~2˚C
9-5. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approximate 12 V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing the VANE button.
10
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the desired
angle.
Confirming of standard position is performed in the following case:
(a) When the power supply turns ON.
(b) When the operation starts or finishes (including timer operation).
(c) When the test run starts.
(d) When the vane control is changed AUTO to MANUAL (except SWING).
(d) When the SWING is finished (including ECONO COOL).
(4) VANE AUTO (
In VANE AUTO mode, the microprocessor automatically determines the horizontal vane angle and operation to make the
optimum room-temperature distribution.
(5) STOP (operation OFF) and ON-TIMER standby
When the following cases occur, the horizontal vane returns to the closed position.
(a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When ON-TIMER is on standby.
(6) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the compressor cumulative operation time of compressor
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(7) SWING ( ) mode
By selecting SWING mode with VANE button, the horizontal vane swings vertically. The remote controller displays " ".
SWING mode is cancelled when VANE button is pressed once again.
) mode
(8) ECONO COOL (
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2 °C higher.
Also the horizontal vane swings in various cycle.
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the air
conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE button or LONG
button is pressed or changed to other operation mode.
(9) LONG ( ) mode
By pressing LONG button indoor fan speed becomes faster than setting fan speed on the remote controller, and the
horizontal vane moves to the position for LONG mode. The remote controller displays "". LONG mode is cancelled
when LONG button is pressed once again or VANE button is pressed or ECONO COOL button is pressed in COOL
mode.
• In the following example, the vertical vane is set to (front.).
) operation (ECONOmical operation)
11
2. Vertical vane
(1) Vane motor drive
These models are equipped with a stepping motor for the vertical vane. The rotating direction, speed, and angle of the
motor are controlled by pulse signals (approximate 12 V) transmitted from microprocessor.
(2) The vertical vane angle and mode change as follows by pressing WIDE VANE button.
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the desired
angle.
Confirming of standard position is performed in the following case:
(a) When OPERATE/STOP (ON/OFF) button is pressed (POWER ON/OFF).
(b) When SWING is started or finished.
(c) When the power supply turns ON.
(4) SWING (
By selecting SWING mode with WIDE VANE button, the vertical vane swings horizontally. The remote controller displays "
(5) WIDE (
By selecting WIDE mode with WIDE VANE button, indoor fan speed becomes faster than setting fan speed on the
remote controller ( ). The remote controller displays " ".
Indoor fan speed becomes faster than setting fan speed on the remote controller even when or is selected.
) mode
".The vane moves right and left in the width of Angle 4 repeatedly.
) mode
9-6. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE: Timer operation will not work without setting the current time. Initially "AM0:00" blinks at the current time display
of TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press ON/OFF TIMER buttons to select the operation.
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when " " or "
These marks disappear in 1 minute.
After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1: Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2: Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
• A power failure occurs.
• The circuit breaker functions.
" mark is flashing.
2. Cancel
TIMER setting can be cancelled with ON/OFF TIMER buttons.
To cancel ON timer, press "ON-TIMER" button.
To cancel OFF timer, press "OFF-TIMER" button.
TIMER is cancelled and the display of set time disappears.
12
PROGRAM TIMER
• OFF timer and ON timer can be used in combination.
• " " and " " display shows the order of OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns OFF at 11:00 PM, and ON at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns ON at 5:00 PM, and OFF at 9:00 PM.
NOTE: TIMER setting will be cancelled by failure or breaker functioning.
9-7. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor
unit. Emergency operation is available when the remote controller is missing, has failed or batteries of remote controller
run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at
High speed and the system is in continuous operation. (The thermostat is ON.)
After 30 minutes of test run operation, the system shifts to EMERGENCY COOL MODE with a set temperature of 24˚C.
The fan speed shifts to Med. speed.
The coil frost prevention works even in emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO (
Emergency operation continues until EMERGENCY OPERATION switch is pressed again or the unit receives any signal
from the remote controller. In case of latter, normal operation will start.
) mode.
NOTE: Do not press EMERGENCY OPERATION switch during normal operation.
• The following indication applies regardless of shape of the indicator.
9-8. 3-MINUTE TIME DELAY OPERATION
When the system turns OFF, compressor will not restart for 3 minutes as 3-minute time delay function operates to protect
compressor form overload.
13
10
TROUBLESHOOTING
MS-GD80VB
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
(1) Check the power supply voltage.
(2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
(1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
(2) Be sure to turn OFF the power supply before removing the panel, the cabinet, the top panel, and the electronic control P.C.
board.
(3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the com-
ponents.
(4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
Housing point
3. Troubleshooting procedure
(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing ON and OFF before starting serv-
ice work.
(2) Before servicing check, that the connector and terminal are connected properly.
(3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
(4) When troubleshooting, refer to 10-2. and 10-3.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
Remove the front lid and insert batteries.
Then reattach the front lid.
FAN
Insert the negative pole
of the batteries first.
Check if the polarity of
the batteries is correct.
Press the RESET button with tip end of ball point
pen or the like, and then use the remote controller.
FAN
RESET button
NOTE: If the RESET button is not pressed, the remote controller may not operate correctly.
14
10-2. INSTRUCTION OF TROUBLESHOOTING
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Outdoor unit
operates only
in “Test run
operation”.
Check room
temperature
thermistor.
Refer to 10-6.
"Test point
diagram and
voltage".
Outdoor unit
doesn't
operate
even in
“Test run
operation”.
Refer to
"Check of
outdoor unit".
Indoor unit
operates.
Outdoor unit
doesn't operate
normally.
Outdoor unit
doesn't
stop even
if indoor unit
stops.
Refer to
"Check of
outdoor unit".
Indoor unit
doesn't receive
the signal from
remote controller.
Indoor unit
operates when
the EMERGENCY
OPERATION
switch is pressed.
Refer to 10-5.
"Check of
remote controller
and receiver
P.C. board".
OPERATION INDICATOR
lamp on the indoor unit is
flashing ON and OFF.
Indoor unit
doesn't operate
when the
EMERGENCY
OPERATION
switch is pressed.
1. Check indoor /
outdoor
connecting wire.
2. Refer to 10-5.
"Check of indoor
electronic control
P.C. board".
Flash ON and
OFF at 0.5second
intervals
Cause:
Indoor/
outdoor unit
• Mis-wiring
Refer to 10-5.
"How to
check
mis-wiring
(When
outdoor unit
doesn't
work)".
Refer to outdoor unit service manual.
"Test run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.
2-time flash
Cause:
Indoor unit
• Trouble of
room temp erature/
indoor coil
thermistor
Check room
temperature
thermistor
and indoor
coil thermistor.
Refer to 10-6.
"Test point
diagram and
voltage".
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
Refer to 10-5.
"Check of
indoor fan
motor".
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
6-time flash
Cause:
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
Refer to
"Check of
outdoor
thermistor".
15
7-time flash
Cause:
Outdoor unit
• Trouble of
outdoor
control
system
Replace the
deicer
P.C. board.
10-time flash
Cause:
Outdoor unit
• Trouble of
low discharge
temperature
protection
Refer to
"Check of
LEV".
10-3. TROUBLESHOOTING CHECK TABLE
• Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and the following detection method has detected an abnormality
(the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor
with the OPERATION INDICATOR lamp flashing.
Abnormal
No.
1
Mis-Wiring
Indoor coil
thermistor
2
Room
temperature
thermistor
3
Indoor
4
control
system
5
point
Indoor fan
motor
Outdoor
thermistor
Lighted
Not lighted
0.5-second ON
0.5-second OFF
2-time flash
2.5-second OFF
3-time flash
2.5-second OFF
4-time flash
2.5-second OFF
6-time flash
2.5-second OFF
· Flashing of the OPERATION INDICATOR lamp (the left-hand side lamp)
indicates possible abnormalities.
Indoor fan repeats
12 seconds ON
and 3 minutes OFF.
When the indoor
fan breaks, the
fan keeps stopping.
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
3 minutes after power supply turns ON,
serial signal is not received.
Indoor coil/room temperature thermistor
detects short or open circuit every 8 seconds
during operation.
The rotational frequency feedback signal is
not sent out for 12 seconds after indoor fan
motor is operated.
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
<Thermistor short>
Thermistors are abnormal when they short
after compressor start-up.
<Thermistor open>
Thermistors are abnormal when they open
after compressor start-up.
However, discharge temperature thermistor is
abnormal when open circuit is detected more
than 10 minutes after compressor start-up.
• Refer to 10-5. "How to
check mis-wiring ".
• Refer to the characteristics of
indoor coil thermistor, and
room temperature thermistor
on 10-6.
• Refer to 10-5. "Check of
indoor fan motor".
• Check the indoor electronic
control P.C. board.
• Check the deicer P.C.
board.
• Reconnect the connector.
Refer to "Check of outdoor
thermistor". Refer to outdoor
service manual.
Outdoor
6
control
system
Low
discharge
7
temperature
protection
7-time flash
2.5-second OFF
10-time flash
2.5-second OFF
Outdoor unit
does not
operate.
Outdoor unit
does not
operate.
It cannot properly read data in the nonvolatile
memory of the deicer P.C. board, outdoor unit
stops.
Discharge temperature has been 50°C or less
on cool operation.
16
• Check the deicer P.C. board.
Refer to outdoor service
manual.
• Refer to "Check of LEV".
• Check refrigerant circuit and
refrigerant amount.
Refer to outdoor service
manual.
10-4. TROUBLE CRITERION OF MAIN PARTS
MS-GD80VB
Part name
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12 (main), RT13 (sub))
Indoor fan motor (MF)
INNER
PROTECTOR
135± 5 °C OPEN
Horizontal vane
motor (MV1)
Vertical vane
motor (MV2)
Check method and criterion
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Refer to 10-6."Test point diagram and voltage",
"Indoor electronic control P.C. board", the chart of thermistor.
Measure the resistance between the terminals with a tester.
(Part temperature 10°C ~ 30°C)
Color of lead wire
Motor part
WHT – BLK
BLK – RED
Normal
132 Ω ~ 144 Ω
152 Ω ~ 166 Ω
Measure the voltage power ON.
Color of lead wire
BRN – YLW
Normal
4.5 ~ 5.5 V
(When fan revolved one time)
YLW – GRY
Sensor part
0 V → 5 V → 0 V
(Approx.)
Measure the resistance between the terminal with a tester.
°C
(Part temperature 10
~ 30°C)
Normal
282 Ω ~ 306 Ω
Figure
MAIN
AUX.
P
BLK
YLW
BRN
GRY
RED
YLW
BRN
ROTOR
P
:INNER PROTECTOR
RED
WHT
GRNORN
10-5. TROUBLESHOOTING FLOW
When OPERATION INDICATOR lamp flashes 3-time.
Indoor fan motor doesn’t operate.
A
Check of indoor fan motor
No
Reconnect the lead wires.
Are lead wires connected?
Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board.
Measure resistance between lead wires No.1 and No.4 and then No.3 and No.4.
Is resistance 0 (short circuit) or (open circuit)?
Repair or replace the indoor fan motor.
Turn OFF the power supply.
Check connector CN211 visually.
Yes
Yes ( 0 or )
Is soldered point of the connector
correctly soldered?
Yes
Turn ON the power supply. Stop it if the unit operate.
Insert screwdriver into air outlet to rotate indoor fan
motor slowly for 1 revolution or over, and measure
No
(others)
voltage between No.2(+) and No.3(-) on CN121.
No
Does voltage repeat 0 V DC and 5 V DC?
Replace the indoor electronic control P.C. board.
No
Resolder it.
Yes
17
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesn’t operate with the remote controller.
Check of remote controller and receiver P.C. board
B
Check if the remote controller is exclusive for this air conditioner.
Press OPERATE/STOP (ON/OFF)
button on the remote controller.
Is LCD display on the remote controller visible?
Yes
Remove the batteries, then set them back
and press the RESET button. Check if the
unit operates with the remote controller.
Does the unit operate with the
remote controller?
Yes
OK
No
(not clear)
No
Replace the batteries. (Refer to 10-1.4.)
Turn ON a radio to AM and press
OPERATE/STOP (ON/OFF) button on the
remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1 m?
No
Measure the voltage between receiver P.C. board connector CN301 No.2(+) and No.1(-) when the remote
controller button is pressed.
Is the voltage approx. 4 V DC?
No (5 V or 0 V DC)
No
Yes
Yes
Replace the remote controller.
Reinstall the unit away from lights.
Attach a filter on receiving part.
Replace the indoor electronic control P.C.
board.
Replace the receiver P.C. board.
18
The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board
C
Check the both “parts side” and “pattern
side” of indoor electronic control P.C.
board visually.
Turn OFF the power supply.
Remove indoor fan motor connector CN211 and
vane motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.
Does the unit operate with the remote controller?
Does the OPERATION INDICATOR lamp light up
by pressing the EMERGENCY OPERATION switch?
Yes
Turn OFF the
power supply.
Replace the vane
motor.
Yes
Is winding
resistance of
vane motor 0 Ω?
No
Is winding
resistance of
fan motor 0 Ω?
Yes
Replace the fan
motor.
Turn OFF the
power supply.
No
No
Replace the fuse.
Yes
Is fuse (F11) blown?
No
Is varistor (NR11) burnt?
Yes
Replace the varistor.
Fuse (F11)
Indoor electronic
control P.C. board
No
Varistor (NR11)
Replace the indoor
electronic control
P.C. board.
19
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit doesn’t operate.
How to check mis-wiring
D
Short circuit of JPG and JPS on the indoor electronic control
P.C. board enables self -check to be displayed in 3 seconds.
Start
• Turn ON the power supply. (indoor/outdoor unit)
• Press EMERGENCY OPERATION switch once.
After 3 minutes, mis-wiring is indicated
(0.5-second ON, 0.5-second OFF)
on OPERATION INDICATOR
lamp on indoor unit.
Correct them.
Yes
1. Turn OFF the power supply (indoor/outdoor unit) and disconnect indoor and outdoor
connecting wire at the terminal block
2. Short-circuit terminal block
3. Turn ON the power supply (indoor unit) and press EMERGENCY OPERATION switch once.
Is this mis-wiring, poor contact,
or wire disconnection?
No
3
□
N
□
-□
Is there 20 V DC between both ends of
R132 on the indoor electronic control P.C.
board ?
( By tester, the stylus is between 0 ~ 20 V. )
• Turn OFF the power supply.
• Disconnect the lead wire that terminal
block
short-circuited.
• Connect indoor/outdoor connecting
wire.
Turn ON the power supply. (outdoor unit)
Is there 230 V AC between
on the outdoor terminal block?
Is there 5 V DC between J101 + -J401
on the deicer P.C. board?
During EMERGENCY OPERATION, is there
10 V DC between both ends of R601 on the
deicer P.C. board?
(By tester, the stylus is between 5 ~10 V.)
Replace the deicer P.C. board.
of the indoor unit.
3
of indoor unit by lead wire.
Yes
(indoor unit)
N
3
□
-□
of the indoor unit is
L
□
Yes
Yes
Yes
-□
N
-
No
Replace the indoor electronic
control P.C. board.
No
Check the outdoor power supply
and connection of wiring.
No
Replace the deicer P.C. board.
Make the wiring between CN730
No
on the deicer P.C. board and
outdoor terminal block correct.
Refer to outdoor unit service manual.
20
10-6. TEST POINT DIAGRAM AND VOLTAGE
MS-GD80VB
Indoor electronic control P.C. board
Fuse (F11)
T3.15AL250V
R132
Fan motor power supply
Power supply input
}
230 V AC
5 V DC
}
+
Room temperature
thermistor (RT11)
Indoor coil
thermistor (RT12 (main))
Receiver P.C. board
Release of “Auto restart function”
Solder jumper wire to JR07.
(Refer to 8-3.)
Indoor coil
thermistor (RT13 (sub))
Emergency operation
switch
Timer short mode point
(JPS, JPG)
(Refer to 8-1.)
+
}
12 V DC
Indoor coil thermistor (RT12(main), RT13 (sub))
Room temperature thermistor (RT11)
21
Resistance(kΩ)
11
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
1
Slide the sleeve.
○
2
Pull the terminal while
○
Locking lever
pushing the locking
lever.
MS-GD80VB
OPERATING PROCEDUREPHOTOS
1. Removing the panel
(1) Remove the screw caps of the panel.
Remove the screws of the panel.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
(3) Remove the screw of the corner box.
Remove the corner box.
(2) The terminal with this connector has the locking
mechanism.
1
Hold the sleeve, and
○
pull out the terminal
slowly.
Connector
Photo 1
2. Removing the electronic control P.C. board, the receiver
P.C. board and the display P.C. board
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the screw of the electrical cover.
Remove the electrical cover.
(3) Remove the screws of the V.A. clamp.
Remove the V.A. clamp.
(4) Remove the screw of the terminal block.
(5) Remove the screws of the earth wire.
(6) Disconnect all the connectors and all the lead wires on the
electronic control P.C. board.
(7) Remove the R.L holder.
(8) Remove the electronic control P.C. board.
(9) Open the R.L holder, remove the receiver P.C. board and
the display P.C. board.
Photo 2
R.L
holder
Screws of the panel
Screws of the earth wire
Screw of
the terminal
block
Receiver
P.C.
board
Screw of the
corner box
Fan motor
connectors
Vane motor
connector
Indoor
electronic
control
P.C. board
Screw of
the electrical
cover
Screw of the
V.A. clamp
22
OPERATING PROCEDURE
PHOTOS
3. Removing the electrical box
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the electrical cover. (Refer to 2.)
(3) Disconnect the connector of the indoor coil thermistor.
(4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic
control P.C. board.
(5) Remove the screws of earth wire.
(6) Remove the fan motor lead wire and indoor coil thermistor
from the electrical box.
(7) Remove the lead wire of vane motor from the bottom of
electrical box.
(8) Remove the screw of the electrical box and remove the
electrical box.
4. Removing the vane motor
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the electrical cover. (Refer to 2.)
(3) Remove the lead wire of vane motor. (Refer to 3.)
(4) Remove the R.L. holder.
(5) Pull out the drain hose from the nozzle assembly and
remove the nozzle assembly.
(6) Remove the screws of the vane motor and disconnect the
connector.
(7) Remove the vane motor.
Photo 5
Screws of the
vane motor
Photo 3
Photo 4
Screws of the earth wire
Vane motors
Screw of the
electrical cover
Screw of the
electrical box
Screws
of the
vane
motor
Vane motor
5. Removing the line flow fan and the indoor fan motor
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly and
remove the nozzle assembly.
(4) Remove the water cut.
(5) Slide the hole cover and remove the hole cover.
(6) Remove the hexagon socket set screw from the line flow
fan.
(7) Remove the screws of the fan motor and remove the fan
motor. (Be careful not to drop the fan motor because it is
heavy.)
(8) Remove the screws of the left side of the heat exchanger.
(9) Lift the left side of the heat exchanger.
10
) Remove the line flow fan.
(
Photo 8
Hole
cover
Photo 6
Screws of
the left side
of the heat
exchanger
Photo 7
Indoor
coil
thermistor
Water cut
23
Screws of the fan motor
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN