Mitsubishi MN Converter, G-50A User Manual

MITSUBISHI
Building Air Conditioning Control System
Maintenance Tools for MN converter & G-50A
- Advanced -
Operating Manual
Contents
1 Foreword
1.1 Introduction of Maintenance Tools 1
1.2 Required Operating Environment 4
1.3 Installation 5
1.4 Starting and Ending the Application
2 Terms for Each Section
2.1 Design of Screen 22
2.2 Operating Method 22
3 On-Line Monitor Operation Method
3.1 On-Line Monitor Screen Transfer 23
3.2 Function Chart 24
3.3 Address Search Method 24
3.4 Main Screen 26
3.5 Function Selection Operations 27
3.6 Connecting Information 27
3.7 Operation Monitor 29
3.8 Malfunction Log 37
3.9 Optional Setting 39
3.10
3.11
4 Off-Line Monitor Operating Method
4.1 Off-Line Monitor Screen Transfer 46
4.2 Function Chart 47
4.3 Operation Monitor 48
4.4 System Information 52
4.5 Monitoring of Pre-error Data 53
4.6 Filing Operation 54
4.7 Offline on Wide area access mode 57
Operation Control 42 Free contact of indoor unit 44
5 File Names
5.1 System Information Data 58
5.2 Operating Status Monitor Data 58
5.3 Pre-error Data 58
5.4 Text Convert Data 58
6 How to change setting of Firewall 59 7 Troubleshooting? 64
Before using Maintenance Tools, read this manual thoroughly to ensure correct operation.
WT03939X09
9
1 Foreword
1.1 Introduction of Maintenance Tools
The Maintenance Tools are comprised of the On-Line Monitor and the Off-Line Monitor. The following two connection methods are available in the Online Monitoring. (1) Monitoring by connecting the maintenance tool to MN converter (CMS-MNF) via RS-232C. (2) Monitoring through the central controller (G-50) by connecting the maintenance tool to LAN. A brief explanation of each of their function is provided here.
* To use the maintenance tool via G-50 (Network), license registration for the G-50 to be used is necessary. Purchasing the license No. for each G-50 to be used, conduct the license registration through the Web browser (http://[IP address of the G-50A]/ administrator.html). After selecting "Maintenance tool" of the optional function on the Web Browser Screen displayed, enter the purchased license No.. For the detail of the license registration, see Chapter 4 [Registering a License for Optional Functions] of Central Controller Model: G-50A Web Browser Operation Manual (For manager).
1.1.1 On-Line Monitor(via MN converter)
The On-Line Monitor is connected to the unit by a MN Converter (CMS-MNF) and can monitor such areas as system data, unit data and operating data.
(1) In case for local connection
Connecting PC installed with the maintenance tool to M-NET transmission line via MN Converter allows conducting various monitoring and setting from the maintenance tool.
Maintenance Tools PC
RS-232C
MN Converter
M-NET
(2) In case for remote connection
Using a modem and remotely connecting PC installed with the maintenance tool to MN Converter via public telephone circuit allow conducting various monitoring and setting as same in the case of local connection.
Maintenance Tools PC
*For the remote connection utilizing MN Converter, an isolator is required to be inserted between
the modem and MN Converter.
For detail, please see Installation Manual-annexing of MN Converter (CMS-MNF).
RS-232C
MODEM
Public
network
MODEM
M-NET
RS-232C
MN Converter
M-NET
1
1.1.2 On-Line Monitor(via G-50)
A
A
A
A
The On-Line Monitor is connected to the unit by the central controller(G-50A) and can monitor such areas as system data, unit data and operating data.
(1) In case for local connection
By directly connecting the PC installed with Maintenance Tools and G-50A through LAN, various monitoring/setting can be performed from the Maintenance Tools.
LAN
M-NET
Maintenance Tools PC
HUB
G-50
(2)-1 In case for remote connection (Dialup connection mode)
By connecting the PC installed with Maintenance Tools and G-50A through public network remotely, various monitoring/setting can be performed from the Maintenance Tools.
LAN
Maintenance Tool PC
MODEM etc
Public
network
Dial-up
Router
HUB
G-50A
(2)-2 In case for remote connection (E-mail connection mode)
Under E-mail connection mode, communication can be executed with G-50A through E-mail transmission via mail server. All communication with G-50A is converted into E-mail in this case.
POP
Mail server
E-mail
Maintenance
SMTP
Provider 1
ccess point
Internet
Notice
To use the E-mail connection mode, the version of G-50 should be above 2.60.
When using E-mail connection mode, the local G-50A is required to be initially set with Maintenance Tool and
the mail address by the G-50A initial setting tool.
- For each mail address, it is required to obtain and set an exclusive one. To transmit mail via an internet provider, obtain the mail address from the provider. When a mail server is existing on the LAN, obtain the mail address from the LAN administrator.
- Set the [Pop receive interval] within 3 minutes. However to monitor operating status [Operation Monitor], set it within 1 minute.
- Setting of initial information to G-50A can not be executed from Maintenance Tool. Make sure to set it from the G-50A initial setting tool locally. If dialup connection environment is available, it can be set from a remote position. (For detail, please refer to 6-1 Mail Basic Setting in the instruction manual of the G-50A initial setting tool.)
The communication speed under E-mail connection mode largely depends on the transfer rate of each mail server. Under the circumstance, the action of Maintenance Tool may take a lot of time under some internet environments or routing mail servers.
Provider1 Mail server
Provider 2
ccess point
Provider2 Mail server
E-mail
LAN
SMTP
Mail server
POP
M-NET
G-50
2
1.1.3 Off-Line Monitor
A
A
A
q
The Off-Line Monitor can display, print information obtained by the On-Line Monitor. In the case of connection monitoring utilizing G-50, the operation monitor data collected by G-50A will be transmitted to remote mail servers periodically if the [Operation monitor - mail communication mode] of online mode is adapted. Using this function allows to collect and monitor the operation monitor data without continually connecting the maintenance tool. *For the setting of the [Operation monitor - mail communication mode], refer to 3.7.1 and 4.3.3 description.
*Image of the [Operation monitor - mail communication mode]
Maintenance
Operation monitor mail data ac
MODEM etc
uisition
Provider 1
ccess point
Internet
Provider1 Mail server
Provider 2
ccess point
Provider2 Mail server
Operation monitor data automatic mail transmit
Public
network
Dial-up
Router
LAN
Collecting the operation monitoring data of air conditioners
G-50
Notice
This differs from the E-mail connection mode of (2)-2 in 1.1.2 On-Line Monitor (via G-50).
1.1.4 Wide area access mode
The “Wide area access mode" has been located starting from Ver4.06(D). Under the "Wide area access mode," the access method for remote connection can be registered to the database of each customer enabling easy online connection with the air conditioning system of the customer desired to be accessed.
[Remote access method]
- LAN : Accessing by directly connecting Maintenance Tool PC and G-50A with LAN (WAN).
- Dialup : Accessing by dialup connection to G-50A via public network.
- E-mail : Accessing by E-mail communication to G-50A via mail server.
- Modem (MN Converter) : Accessing by connecting Modem to MN Converter via public telephone
circuit.
After the online connection performed by any of the above methods, you may use the similar function as that obtainable in the normal online connection. While under the offline mode, customer information will be provided to the monitored data enabling only to select a specified customer for display.
3
A
1.2 Required Operating Environment
This manual refers to Windows® 2000 as Windows 2000, and Windows® XP as Windows XP.
Trademarks
MS, Microsoft, Microsoft logo, and Windows are registered trademarks and trade names of Microsoft Corporation. Each company may use as registered trademarks and trade names the product names used in this manual.
1.2.1 Hardware Requirements
The computer must be IBM compatible on DOS/V and capable of satisfying the following requirements.
- OS .................... Windows2000 or WindowsXP (Recommended English version *1)
- CPU .................... PentiumIII 500 MHz (Recommended 1GHz or more)
- RAM .................... Minimum 128 MB (Recommended 256MB or more)
- HDD .................... Available space 5 GB or more *2
- LCD .................... Display resolution:XGA(1024x768) or more
Unit should be equipped with a pointing device, such as a mouse pointer or track ball.
*1 About OS
1.2.2 Required Materials
Fundamentally, it corresponds to OS of each country. However, separators of time and date differ in each language. This separator may affect a maintenance tool. It recommends using it by English OS and Regional options setup, changing into English area form. Or it recommends using it, changing date separator into [/] and time separator into [:].
*2 About Hard Disk Space
The hard disk space recommended above is only the amount required for installing the maintenance application. Additional space will be required if the operating data is also to be stored on the hard disk.
ccordingly, there may not be enough memory to store operating data if the maintenance system is
installed in a computer with limited hard disk memory.
* NOTE
TG-2000A and Maintenance Tool cannot operate with the same personal computer.
The following materials are needed for operating the Maintenance Tools :
(1) In case of routing via MN converter
MN Converter (CMS-MNF), Personal Computer, RS-232 (cross), and modem in the case of remote connection, are required. RS-232 C is to be straight cable in this case. For detail, please see Installation Manual-annexing of MN Converter (CMS-MNF).
(2) In case of routing via G-50
G-50, personal computer, LAN cable (Straight) and HUB. A dial-up router is required for remote communication. For the dial-up router to be used, employ that allowing data communication by receiving external telephone transmission.
4
1.3 Installation
A
r
There are two Maintenance Tool setup methods:
Method 1) New setup.(See Section 1.3.1) Method 2) Upgrading with existing setup.(See Section 1.3.2)
Caution
Please refer to also 1.3.4 RE: Change of computer name on PC.
1.3.1 Setting Up the Maintenance Tools (New setup)
To set up Maintenance Tools, follow the 3 steps below.
Step 1) Setting up of MSDE Step 2) Setting up of database Step 3) Setting up of
Request
For setting up, be sure to practice 3 steps in order.
Before setting up, be sure to log in with the log-in name authorized as administrator.
Maintenance Tools
Step 1) Setting up the MSDE
Notice
Before Setting up the MSDE, restart your computer and Ending software for application program
and Anti-Virus.
Execute “SETUP.exe” located in SetUp ¥1_MSDE4VS folder of CD-ROM.
Double clicking on “SETUP.exe” with the explorer displays the
MSDE setup screen as shown right. PC is reset automatically after completing installation of MSDE. After closing other application software, click [OK] and start installation. * To stop setting up, click on [Cancel] button.
The setting up processing requires for about 2-3minutes
If processing progresses to 100%, the screen in the right will be displayed. Clicking on [OK] resets PC automatically. Please carry out STEP2 after PC's starting.
Notice
fter setting up MSDE, PC is designed to automatically reset. However, if this setting up is executed without finishing other application software, PC may not be reset automatically. In this case, reset PC manually. Afte restarting, go to Step 2. Without restarting PC, Maintenance Tool can not be set up unless replacing OS itself.
Step 2) Setting up the database
Execute “Setup.bat” located in the folder of SetUp ¥2_DB_SETUP Double clicking on “Setup.bat” with the explorer displays the command prompt screen. The setting up processing ends within about 10 seconds
- 3 minutes
After ending of the setting up, “Press any key to continue …” is displayed. Pressing any key closes the command prompt screen.
.
” of CD-ROM.
: After finishing Step 1, PC restarts automatically.
(Restarting PC is essential before going to Step 2.)
Otherwise, Maintenance Tools will not operate normally.
in the
.
5
Notice
r
During database setting, the process may be observed as stopped for a while. However, it is still unde operation internally. Wait for some time until "Press any key to continue - - - -" appears without doing anything. *Do not stop the set up procedure by pressing
Step 3) Setting up the Maintenance Tools
Set up the application of this to proceed the setting up.
Maintenance Tools. Please read the guide shown on the screen carefully
at the upper right of the screen.
(1) Starting the setup program
1) Start setup.exe. Execute “setup.exe” located in SetUp ¥3_MNTTOOL Double clicking on “setup.exe” with the explorer displays “Welcome” screen. Please confirm the caution shown on the screen before setting up.
2) Confirm the display contents, and select [Next] button.
If no problem was found on the content, click [Next] button. * To stop setting up, click on [Cancel] button.
(2) Confirming the Installation folder
1) Confirm the installation folder and select [Next] button. Confirm the folder on which this program should be installed. To change the installation folder (C drive only), Use [Previous] button. After confirming the installation folder, click on [Next] button. * Clicking on [Cancel] button stops installation procedure.
(3) Confirming the installation start
1) Confirm the starting and select [Next] button. Clicking on [Next] button starts installation. * Clicking on [Cancel] button stops installation.
(4) Confirming the completion of Maintenance Tools setup
1) Select [Close] button. Click on [Close] button on the Installation Complete screen.
After completing installation, restart your computer. Keep the CD-ROM used with you carefully.
folder of CD-ROM.
Request
After installing Maintenance Tools, be sure to restart your computer.
6
r
1.3.2 Running Maintenance Tool Upgrade
The following describes how to upgrade the Maintenance Tool.
Step 1) Ending the Maintenance Tool Step 2) Uninstalling the Maintenance Tool :Restart your computer after completing the STEP 2. Step 3) Upgrade the Database Step 4) Upgrade the Maintenance Tool :Restart your computer after completing the STEP 4.
Request
For setting up, be sure to practice 4 steps in order.
Otherwise, Maintenance Tools will not operate normally.
Step 1) Ending the Maintenance Tool
End the Maintenance Tool program. *Refer to 1.4.5 Ending the Maintenance Tool
Step 2) Uninstalling the Maintenance Tool
Uninstall the Maintenance Tool program. * Refer to 1.3.3 Uninstalling the Maintenance Tool
Request
After uninstalling Maintenance Tool program, be sure to restart your computer.
Step 3) Upgrade the Database
Execute "Setup.bat" located in VerUp ¥1_DB_UPDATE Double clicking on "Setup.bat" with the explorer displays the command prompt screen. The setting up processing ends within about 10 seconds When the set up processing is completed, [Press any key to continue …] will be displayed at the bottom of the screen. Please wait for this display. About 10 seconds - 3 minutes are required to complete the set up processing. The screen will be closed by pressing any button after completing the processing with the display of [Press any key to continue …].
Notice
During database setting, the process may be observed as stopped for a while. However, it is still unde operation internally. Wait for some time until "Press any key to continue - - - -" appears without doing anything. *Do not stop the set up procedure by pressing
Step 4) Upgrade the Maintenance Tool
Execute "setup.exe" located in VerUp ¥2_MNTTOOL_UPDATE Double clicking on "setup.exe". *The Maintenance Tool program version upgrading procedure is the same as new setup. Refer to 1.3.1 Step 3) Setting up the Maintenance Tool.
Request
folder of CD-ROM.
and the screen closes.
at the upper right of the screen.
folder of CD-ROM.
After installing Maintenance Tool program, be sure to restart your computer.
7
1.3.3 Uninstalling the Maintenance Tools
The method to uninstall the application of the [Maintenance Tools] once installed is given below.
(1) Uninstalling the Maintenance Tools
1) Confirm the ending of Maintenance Tools. Confirm that Maintenance Tools program has been ended. If not, end the program. *For the ending method, refer to Chapter 1.4.5.
2) Start [Add/Remove Programs]. Click on [Add/Remove Programs] from [Control panel] to start.
3) Select [Maintenance Tool for windows 2000 and XP]
and press [Change & Remove] button. Select [Maintenance Tool for windows 2000 and XP] from the application, and click on [Remove] button. The deletion of Maintenance Tools application starts.
Notice
Recommend not to delete the common components.
There are folders and files that can not be deleted with this uninstalling.
(Example:C:¥Program files¥Mnttool32)
4) Ending the [Add/Remove Programs]. After ending the deletion of application, end [Add/Remove Programs].
1.3.4 RE: Change of computer name on PC
Do not change the computer name after the Maintenance tool has been setup. Maintenance tool will not run properly if changed, and may require the OS to be installed again.
8
1.4 Starting and Ending the Application
1.4.1 Starting the Maintenance Tool
(1) Connect the computer and G-50A(MN Converter) and
air conditioner.
(2) Click on “Start
(3) Click on “Maintenance Tool for Windows2000 & XP
the “Maintenance Tool
(4) The Title Screen will soon appear.
In addition, the message of [This unit can be changed into °F and pounds/inch displayed, and the temperature is set into °F if is clicked on, while into °C if is clicked on.
*After upgrade, if a maintenance tool is started for the first time, conversion processing of a database may be performed. In this case, "Now, Converting database! " and a progress state are displayed.
*The capacity to store the data obtained by the maintenance tool counts for 2G-bite maximum. When the remaining storage capacity is insufficient at starting, Warning Screen will appear. In this case, move to OFF- Line Screen to delete unnecessary data.
(5) Thereafter, the selection screen of Monitor mode is
displayed. Selecting the mode to be adapted.
Normal mode
a) ON LINE MODE
- MN CONVERTER
When on-line monitoring is adapted to air conditioning system by connecting MN Converter [Refer to 1.4.2.1.] Further select Remote connection to conduct remote connection. [Refer to 1.4.2.2.]
- G50(LAN)
When on-line monitoring is adapted to air conditioning system via G-50 by connecting the maintenance tool to LAN. [Refer to 1.4.3.1.] For remote connection, select either “Dialup connection mode” or “E-mail connection mode”. [Refer to 1.4.3.2., 1.4.3.3.]
b) OFF LINE MODE
- Offline analysis When offline analysis is adapted to the data collected under ON-LINE MODE [Refer to 1.4.4.]
Wide area access mode The detail is described in the item 1.4.5.
”, and then click on ”Programs”.
” folder.
2
. Do you change them?] is
” in
9
1.4.2 Starting the On-Line Monitor(MN Converter connection)
1.4.2.1 In case for local connection
This will be used when online monitoring is adapted to air conditioning system by connecting the maintenance tool and MN Converter locally. The maintenance tool, MN Converter and air conditioning system should be connected beforehand.
(1) Clicking "MN CONVERTER" on the selection screen of
Monitor mode selects "Local connection" simultaneously. Select the model name of the connected MN Converter and the COM port No. of the connected RS-232C. Last click .
1.4.2.2 In case for remote connection
This will be used when online monitoring is adapted to air conditioning system by using a modem, and connecting the maintenance tool and MN Converter with public telephone circuit remotely. The setting up of the modem for Windows (modem at the remote site side) and the initial setting up (modem connecting MN Converter at the local side. For detail, refer to (3).) are previously required. The connection of the modem, public telephone circuit and local MN Converter is necessary.
* For a description of the on-site air conditioner system connection method, refer to the MN Converter Operation Manual. * If communication does not have for 10 minutes in remote connection, "Timeout occurred!" will be
displayed, if O.K. is pushed, a telephone circuit will be cut automatically and the Maintenance tool will be ended.
(1) After clicking "MN CONVERTER" on the selection screen
of Monitor mode, and click "REMOTE CONNECTION." For MN Converter, "CMS-MNF-B" will automatically be selected. Then select COM port No. of RS-232C connected with equipment (like a modem) for connection to public telephone line.Last click .
*MN Converter to be locally installed should be "CMS-MNF-B." Remote connection can not be performed with "CMS-MNF."
(2) Next the screen to set remote connection will appear. In
order to conduct the initial setting (AT command setting) of the modem to be used, click , and to initiate remote connection, click .
*Insert an isolator between the local MN Converter and modem for insulation. Inserting the isolator reduces the number of lines used by the internal wiring of RS-323C. For this reason, it is required to select before the remote connection to change the setting information on the modem to be installed at the local side. For detail, see Installation Manual-annexing of MN Converter (CMS-MNF).
10
(3) Initial setting of modem
For the modem to be installed at the local side (MN Converter side), initial setting should be applied before connecting remotely. To apply the initial setting of the modem, click on the remote setting screen. The Connection Modem Initial Setting Screen will appear. A modem that is already initialized does not have to be re-initialized. The explanation of the operation only is described here. For the detail of the setting content, see Installation Manual-annexing of MN Converter (CMS-MNF).
(a) Explanation of screen
-Select a registered modem setup file at the Select Initial Settings File Box. The contents of the selected file will be listed below the selection box.
-Click on and the modem will be set up according to the contents selected at the selection box. (AT commands are sent to the modem.) Check if transfer with the modem is normal at the Transfer with Modem Status Screen.
- Click on to initialize another modem. Send the initialize command and register the transfer contents for the modem at the AT Command Transmit Screen. [Refer to (b)]
- Click on to delete the selected modem settings from the registered settings. When the number of registrations limit is exceeded, delete the unwanted contents. [Refer to (b)]
- Click on to return to the Connection Setting Screen.
(b) Perform new modem setup.
- Enter the command (you want to set) you want to send
to the modem at the AT command input text. Then click on to send the entered AT command to the modem. The response from the modem will appear below the entered AT command. Check the contents.
- After transmission to the modem is complete, click
on . The contents sent to the modem will be registered as an initialize file. (Registered in the setup file list of the Connection Modem Initial Setting Screen.) At this time, do not forget to enter the registration name. Up to ten items can be registered. If ten items are already registered, new items cannot be registered. Delete unwanted items using the Connection Modem Initial Setting Screen.
- Click on to return to the Connection Modem Initial Setting Screen.
11
(4) Initiating the remote connection To initiate the remote connection, click
on the remote setting screen. The Customer Selection Screen will appear. This screen connects to the on-site remote modem.
(a) When the addressee has already been registered, select
the customer name to be connected in "Select customer
name box" and then click to initiate
connection.
In the case of initial connection or to change to a new addressee, click . Then the Customer Information Registration Screen will appear.
(b) Enter Customer name of the field addressee, enter the type of the telephone circuit to be used and the
telephone number of the addressee, and click . The set content will be registered.
* The contents transmitted to the modem vary in the chosen Line type. Pay attention to the following. When PB is chosen, "ATDT" is added before the telephone number. For example, when a telephone number is 0123456789, "ATDT0123456789" is transmitted to the modem. It becomes the following when "DP", "NONE" are chosen in the same way.
DP --- ATDP0123456789
NONE --- ATD0123456789 When a circuit connection is impossible in the case of above three which as well, "ELSE" is used. When "ELSE" is chosen, nothing is added to before the telephone number. Input a command for the circuit connection from the beginning. For example, "ATD0,0123456789" is transmitted to the modem when "ATD0,0123456789" is inputted in the telephone number column. When the one except for the "ELSE” is chosen, only a number can be inputted in the telephone number column.
The information for up to 100 customers can be registered. When the information for 100 customers has been registered, new customer information cannot be registered. Delete the unwanted customer information using the customer selection screen.
(c) Check the contents, then click on .
The Connection Status Indication Screen will appear. Connect the line. When you want to disconnect the line, click on . The line will be disconnected.
12
1.4.3 Starting the On-Line Monitor(G-50 connection)
* To use the maintenance tool via G-50 (Network), license registration for the G-50 to be used is necessary. Purchasing the license No. for each G-50 to be used, conduct the license registration through the Web browser (http://[IP address of the G-50A]/ administrator.html). After selecting "Maintenance tool" of the optional function on the Web Browser Screen displayed, enter the purchased license No.. For the detail of the license registration, see Chapter 4 [Registering a License for Optional Functions] of Central Controller Model: G-50A Web Browser Operation Manual (For manager).
* To use the maintenance tool via G-50 (Only for LAN mode and Dialup connection mode), please check a setup of Internet Connection Firewall of PC. If the FIREWALL function is used, communication will be normally impossible with G-50A, and normal data will not be displayed. For detail, please refer to [6. How to change setting of Firewall] on Page 57.
In the case of permanently installing an anti-virus software and always started under this environment, the fire wall function of this software may be activated sometimes. In such case, The normal communication with G-50 will be hindered not displaying data normally. When operating Maintenance Tool, finish the anti-virus software once or remove the fire wall function.
1.4.3.1 In case for local connection
In the case when on line monitoring is applied to air conditioning system via G-50 by connecting the maintenance tool to LAN locally.
(1) Clicking "G-50(Network)" on the selection screen of
Monitor mode selects "Local connection" simultaneously. Last click " ."
(2) Next IP address input screen is displayed. Here,input IP
address of G-50A connected to the air conditioning system of which operating information is desired to monitor, and click on .
Request
It is required to set to the IP address in the same system with G-50 to be connected to Maintenance Tool PC from [Control Panel].
13
1.4.3.2 In case for remote connection (Dialup)
In the case when on line monitoring is applied to local air conditioning system (with G-50 installed) from the maintenance tool in the remote place via public telephone circuit.
* When utilizing Remote connection (Dialup),please prepare MODEM and DIAL-UP ROUTER (of a type
allowing data communication by receiving external telephone transmission) for the connection with the public circuit in addition to the components used by Local connection (LAN). For the system composition, please refer to the system diagram of (2)-1 in 1.1.2. To use Remote connection (Dialup), it is previously required to register MODEM onto Windows and set the information on the receiver (the dial-up router at G-50A in the field) of the telephone transmission
onto the dial-up connection screen. * If communication does not have for 10 minutes in remote connection, "Timeout occurred!" will be displayed, if O.K. is pushed, a telephone circuit will be cut automatically and the Maintenance tool will be ended.
(1) After clicking "G-50(Network)" on the selection screen of
Monitor mode, and click "REMOTE CONNECTION(Dialup)."
Last click " ."
(2) Next Remote Monitor screen is displayed.
Here select the connection name of the dial-up router at G-50A in the field desired to be remotely connected. It is being set previously on the dial-up connection screen. Then input Dial-up user name and Dial-up password to connect with the dial-up router,and click on .
After connecting to the telephone circuit, on-line monitoring can be performed as same as the case when connected with LAN.
14
A
A
1.4.3.3 In case for remote connection (E-mail)
In the case when on line monitoring is applied to local air conditioning system (with G-50 installed) from the maintenance tool in the remote place via mail server.
ll communication to G-50 is converted in E-mail in this case.
Notice
To use the E-mail connection mode, the version of G-50 should be above 2.60.
When using E-mail connection mode, the local G-50A is required to be initially set with Maintenance Tool and
the mail address by the G-50A initial setting tool.
- For each mail address, it is required to obtain and set an exclusive one. To transmit mail via an internet provider, obtain the mail address from the provider. When a mail server is existing on the LAN, obtain the mail address from the LAN administrator.
- Set the [Pop receive interval] within 3 minutes. However to monitor operating status [Operation Monitor], set it within 1 minute.
- Setting of initial information to G-50A can not be executed from Maintenance Tool. Make sure to set it from the G-50A initial setting tool locally. If dialup connection environment is available, it can be set from a remote position. (For detail, please refer to 6-1 Mail Basic Setting in the instruction manual of the G-50A initial setting tool.)
The communication speed under E-mail connection mode largely depends on the transfer rate of each mail server. Under the circumstance, the action of Maintenance Tool may take a lot of time under some internet environments or routing mail servers.
For the system composition, please refer to the system diagram of (2)-2 in 1.1.2.
(1) After clicking "G-50(Network)" on the selection screen of
Monitor mode, and click "REMOTE CONNECTION(E-mail)."
Last click " ."
(2) The mail connection setting screen is displayed.
Here, set the mail information on G-50A to be connected, and that on the Maintenance Tool.
Notice For each mail address, it is required to obtain and set an
exclusive one. To transmit mail via an internet provider, obtain the mail address from the provider. When a mail server is existing on the LAN, obtain the mail address from the LAN administrator.
(a)Setting of the mail information on G-50
1) To assign the G-50A connected in the past After assigning “Customer name” from the pull down menu, select G-50 name.”
2) To connect to new G-50A Click to open the address book, and register and select the mail address of G-50A.
*The 10 Customer names in the past are displayed on the pull down menu. To assign earlier G-50A,
open the address book to select.
15
(b) Address book
[
The mail address of G-50A for each project can be registered.
As shown in the sample examples, register the name and mail address of G-50A after preparing the
Customer name] folder.
[Entering order]
1) Preparing the Customer folder
Pressing displays the input screen of customer name, and then enter the name.
The setting can also be made from the file menu or the sub-menu displayed by right-clicking.
Further deletion processing can be made with or Del-key, and rename processing with button.
2) Name and address setting of G-50A
Double-clicking at a position desired to enter provides the input mode. Set the name and address accordingly. *Be sure to set the name of G-50A also. The deleting processing can be executed with the ,
Del-key, or Edit menu. It can also be performed by the Delete setting of the sub menu displayed by right-clicking.
[Selection order]
-Selection of G-50A to be connected with Click the customer name folder desired to connect to open
the address book of the project. After fitting the cursor to the name of address of G-50A, click [SELECT] button.
(c)Advanced setting screen
Clicking [Open Advanced] opens Advanced screen where the mail information about Maintenance Tool may be set. When the mail information about Maintenance Tool has not been set, Advanced screen is displayed always under opened state.
- Setting of mail information on Maintenance Tool
1) POP server (Receiving)
- POP server address Set the IP address of the receiving mail server (POP3) of Maintenance Tool or domain name.
- POP account Set the POP account (user ID) for mail receiving.
- POP password Set the user password for mail receiving.
- POP receive interval Select the mail receiving interval. The default value represents 5sec. It can be selected within a range of 5 ~180sec. Extend the interval when the server is crowded.
2) SMTP server (Transmitting)
- SMTP server address Set the IP address of transmitting mail server of Maintenance Tool.
3) Mail address
- Set the mail address of Maintenance Tool. Clicking [Close Advanced] closes Advanced screen.
(3) After setting the mail information about the G-50 connected and that about Maintenance Tool, click [CONNECT].
16
1.4.4 Starting the Off-Line Monitor
When offline analysis is adapted to the data collected under ONLINE MODE.
(1) Clicking "Offline Analyze" on the selection screen of Monitor
mode. Last click " ."
1.4.5 Using the Wide area access mode
Under the "Wide area access mode," the access method for remote connection can be registered to the database of each customer enabling easy online connection with the air conditioning system of the customer desired to be accessed.
[Remote access method]
- LAN : Accessing by directly connecting Maintenance Tool PC and G-50A with LAN (WAN).
- Dialup : Accessing by dialup connection to G-50A via public network.
- E-mail : Accessing by E-mail communication to G-50A via mail server.
- Modem (MN Converter) : Accessing by connecting Modem to MN Converter via public telephone
circuit.
After the online connection performed by any of the above methods, you may use the similar function as that obtainable in the normal online connection. While under the offline mode, customer information will be provided to the monitored data enabling only to select a specified customer for display.
Note : Even when connecting under the wide area access mode, cautions will be applied as same as under the normal connection mode. You are kindly requested to observe the cautions described in the connection method under normal mode as well. (1.4.1 - 1.4.3)
17
1.4.5.1 Online Connection
(1) Clicking “Online Connection (Wide area access mode)”on the
section screen of Monitor mode.
Last click " ."
(2) The customer registration screen will be displayed.
Register customer information in the order of [1] -> [2] -> [3] hierarchically.
[1] Area name
[2] Customer name
(a) Creating the [Area name] folder
1) When [Wide Area] is being focussed, the sub-menu will be displayed by right-clicking.
2) Select [Create Area …].
3) As the screen to enter the AREA name appears, set a proper Area name and press [OK] to create the Area folder.
(b) Creating the [Customer name] folder
1) Right-clicking the [Area name folder] to be registered displays the sub-menu.
2) Select [Create Custormer …].
3) As the screen to enter the Customer name appears, set a proper customer name.
* In addition to the above mouse operation, the creation of [AREA name] and [Customer name] can be
set from the menu bar (File) By applying the same operation procedure(right-clicking, menu bar, tool bar), each folder can be deleted. Also the name of each folder can be changed.
Caution :
If a folder is deleted, all information (customer name, air conditioning system name, etc.) will be deleted similarly.
[3] Air conditioning system name
& connection method
or tool bar (Figure).
18
(c) Setting the [Air conditioning system name]
1) Under the state when the [Customer name folder] desired to be set on the air conditioning system is focussed, the sub-menu will be displayed by right-clicking the air conditioning system list at the right screen.
2) Selecting [Create ...] displays [Setting screen of air conditioning system].
[Setting screen of air conditioning system]
1) Set the system name.
2) Select the method to connect with the system.
- To connect by using LAN (WAN) address of G-50 to be connected. (Same as
1.4.3.1)
- To connect by using Dial-up [Connection name] of dialup router of the local G-50 being previously set on the dialup connection screen of Windows. And enter [User name] and [Password] for the connection with the dialup router, and lastly enter the IP address of G-50. (Same as1.4.3.2)
- To connect under E-mail mode E-mail address of G-50 to be connected.(Refer to1.4.3.3.)
- To connect remotely with MN Converter and Modem, select [Modem(MN Converter)].
3) Enter special notes if any on the comment column.
After entering and selecting the above, press [OK].
Set various information as required by repeating the items (a)-(c) above. Using the area selecting section allows you to extract the only area desired to display.
, enter the IP
, select the
, enter the
19
(d) Other setting
You may select the mail address of maintenance tool PC itself and the Com port to be used. * To use the E-mail mode, mail setting is essentially required.
[Mail setting of maintenance tool PC]
1)
POP server (Receiving)
- POP server address Set the IP address of the receiving mail server(POP3) of Maintenance Tool or domain name.
- POP account Set the POP account (user ID) for mail receiving.
- POP password
Set the user password for mail receiving.
- POP receive interval
Select the mail receiving interval. The default value represents 5sec. It can be selected within a range of 5 ~180sec. Extend the interval when the server is crowded.
2) SMTP server (Transmitting)
- SMTP server address
Set the IP address of transmitting mail server of Maintenance Tool.
3) Mail address
- Set the mail address of Maintenance Tool.
Clicking [Close Advanced] closes Advanced screen.
[Setting of Com port]
To connect Mode, select the Com port to be used.
(3) Focussing on the air conditioning system desired to be
connected and pressing [Connect] will start the procedure for connection. After completing the normal connection, the screen moves to the online main screen allowing normal online operation. However when the connection method uses [Modem(MN Converter)], the screen of the Modem remote connection will appear. In this case, select the Modem to be connected and proceed the connection procedure.(Refer to 1.4.2.2.)
1.4.5.2 Offline Analyze
(1) Clicking “Offline Analyze (Wide area access mode)”on the
section screen of Monitor mode.
Last click " ."
20