• RoHS compliant products have <G> mark on the spec name plate.
1
1
2
3
4
5
6
7
8
9
0
Alkaline battery (AAA) for remote controller
Drain hose (with insulation)
Special washer (with cushion, 4pcs)
Installation template
Fixing screw for 4 M5 o 30
Band
Fixing screw for 6 4 o 16
Remote controller
Remote controller holder
Fixing screw for 9
MLZ-KA25VA
MLZ-KA35VA
2
1
8
1
4
1
2
1
1
2
MLZ-KA50VA
Vertical vane
Air outlet
Horizontal vane
Air filter
(Catechin air filter, option)
Air cleaning filter
(Anti-Allergy Enzyme
Filter, option)
Safety string
Intake grille
Remote control
receiving section
Display and operation section (When the intake grille is opened)
Operation indicator lamp
Emergency operation switch
Air inlet
PART NAMES AND FUNCTIONS
INDOOR UNIT
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
ACCESSORIES
2
2
T3.15AL 250V
12V 300"
12V 300"
ERZV14D471
230V 6.4W
DC 12V
Item
Model
Fuse
Horizontal vane motor
Vertical vane motor
Varistor
DRAIN PUMP
FLOAT SENSOR
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
(F11)
(MV1)
(MV2)
(NR11)
(DP)
(FS)
Cooling
528/ 480/ 432
35/ 32/ 29
1,120/1,030/950
MLZ-KA35VAMLZ-KA25VAMLZ-KA50VA
Indoor model
Function
Power supply
Single phase
230V,50Hz
0.3
40
—
58
0.3
RC0J30-KC
1,102O175O360
15
5
3
KM07E
Heating
552/ 492/ 420
36/ 32/ 28
1,160/ 1,060/ 930
Air flow(High/Med./Low)
Running current ✽1
Power input ✽1
Auxiliary heater
Power factor ✽1
Fan motor current ✽1
Model
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med./Low)
Fan speed(High/Med./Low)
Fan speed regulator
Remote controller model
K /h
A
W
A(kW)
%
A
mm
kg
dB(A)
rpm
Electrical
data
Capacity
Fan motor
Special
remarks
Cooling
564/ 504/ 438
37/ 34/ 31
1,180/ 1,080/ 960
Single phase
230V,50Hz
0.3
40
—
58
0.3
RC0J30-KC
1,102O175O360
15
5
3
KM07E
Heating
594/ 528/ 462
38/ 35/ 31
1,230/ 1,120/ 1,000
Cooling
684/ 588/ 498
43/ 38/ 34
1,380/1,220/1,070
Single phase
230V,50Hz
0.3
40
—
58
0.3
RC0J30-KC
1,102O175O360
15
5
3
KM07E
Heating
708/ 618/ 528
43/ 39/ 34
1,420/ 1,270/ 1,120
SPECIFICATION
NOTE : Test conditions are based on ISO 5151.
Specifications and rating conditions of main electric parts
Cooling : IndoorDry-bulb temperature 27:Wet-bulb temperature 19:
Heating : IndoorDry-bulb temperature 20:
Refrigerant piping length (one way): 5m
✽1 Measured under rated operating frequency.
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24:
Outdoor Dry-bulb temperature 7:Wet-bulb temperature 6:
3
3
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
COOLING
FUNCTION
43
43
SPL(dB(A))
LINE
High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20:
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
COOLING
FUNCTION
35
36
SPL(dB(A))
LINE
High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20:
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
COOLING
FUNCTION
37
38
SPL(dB(A))
LINE
High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20:
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
INDOOR UNIT
CEILING
GRILLE
MICROPHONE
1.4m
NOISE CRITERIA CURVES
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
4
4
Center of ceiling opening, suspension bolt pitch
and grille are located in one position.
Center of ceiling opening,
suspension bolt pitch and grille
are located in one position.
Air outlet
(Top)
(Front)
Refrigerant
Pipe
Length of drain hose 540
Drain pipe
NOTE : Drain hose can be used by cutting it.
VP20
Liquid
[6.35
[9.52(MLZ-KA25/35)
[12.7(MLZ-KA50)
Gas
Ceiling surface
Drain hose
500mm or less
Hole position for the
installation of grille
Decline 1/100
Drain pipe VP20
How to connect drain pipe on indoor
unit by lifting drain hose.
w Drain hose can be used by cutting it.
Ceiling surface
Suspension bolt M10
Grille
414 Outer side of grille
384 Ceiling opening
308 Suspension bolt pitch
Electrical box
1051 Suspension bolt pitch
Air outlet
(Top)
Wireless
remote controller
(Front)
(Right side)
Grille (MLP-440W)
Electrical box
Receiving section
Drain pipe
VP20
Display and
receiving section
Ceiling
surface
Liquid pipe
[6.35
(Flared)
Gas pipe
MLZ-KA25/35 : [9.52
MLZ-KA50 : [12.7
(Flared)
Drain hose
connecting
part (drain pipe
VP20)
Pipe cover
Drain pan
Outlet opening area
Drain hose
connecting part
Pipe
cover
308
Suspension bolt pitch
Drain hose
No gaps between
the ceiling surface and grille
R6
CL
CL
0.04m
2
13.549.7
20
20
26
26
58
230
2
2
960
78
360
110
170
244
175
112
116
110
38
38
175
180 or more
60
25
48
[58
54.5
1051 Suspension bolt pitch
1160 Ceiling opening
1200 Outer side of grille
Outlet
2020
54.5
15
15
(51.6)
180
1102
1200
414
34
15
5818
158
R6
31
10
0
466.5
466.5
166.5
0
172.4
81.8
173
166.5
OUTLINES AND DIMENSIONS
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
INDOOR UNIT
Unit : mm
5
5
INDOOR UNIT
MLZ-KA25VA
MLZ-KA35VA
WIRING DIAGRAM
MLZ-KA50VA
6
6
Indoor
heat
exchanger
Flared connection
Room temperature
thermistor
RT11
Indoor coil
thermistor
RT13 (sub)
Flared connection
Refrigerant pipe [9.52
(with heat insulator)
Refrigerant pipe [6.35
(with heat insulator)
Indoor coil
thermistor
RT12 (main)
Indoor
heat
exchanger
Flared connection
Room temperature
thermistor
RT11
Indoor coil
thermistor
RT13 (sub)
Flared connection
Refrigerant flow in cooling
Refrigerant flow in heating
Refrigerant pipe [12.7
(with heat insulator)
Refrigerant pipe [6.35
(with heat insulator)
Indoor coil
thermistor
RT12,RT14,
RT15 (main)
REFRIGERANT SYSTEM DIAGRAM
INDOOR UNIT
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
Unit : mm
7
7
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
–
–
–
2 units operation
Same as at left
Solder J1
–
–
3 units operation
Same as at left
Same as at left
Solder J2
–
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
CN211
Fuse (F11)
IC101
T11
VARISTOR (NR11)
Indoor electronic
control P.C. Board
CN151
C111
R111
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
JR05
No modification
Cut off JR05
No modification
Cut off JR05
JR06
No modification
No modification
Cut off JR06
Cut off JR06
JR06
JR05
SERVICE FUNCTIONS
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows. (Refer to 9-7.)
Set time : 1-minute ➔ 1-second
Set time : 3-minute ➔ 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, both the P.C. boards of remote controller
and the electronic control P.C. boards must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
shortened by short circuit of JPG and JPS.)
NOTE : For modification, take out the bat-
teries and press the
OPERATE/STOP(ON/OFF) button
2 or 3 times at first.
After modification, put back the
batteries then press the RESET
button.
J1
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
J2
Table 1
How to modify the electronic control P.C. board
Turn OFF the power supply before modification. Cut off “JR05” and “JR06” on the electronic control P.C. board according
to the number of indoor unit as shown in Table 2. (Refer to 9-7.)
Table 2
NOTE : After modification, turn ON the power supply and with the remote controller headed towards the indoor unit, press the
OPERATE/STOP(ON/OFF) button. If one or two beeps is heard from the indoor unit, modification is completed
correctly.
8
JR07
CN106
CN111
CN112 CN113
C111
T11
CN211
CN151
IC101
F11
R111
NR11
7-3. AUTO RESTART FUNCTION
Change dip switch SW3 setting according to the height of ceiling.
Dip switch SW3
Ceiling height
Normal
2.4 m or below
Increase airflow volume
above 2.4 m and 2.7 m or below
How to change Dip switch (SW3) setting (Default setting is Normal)
1. Turn OFF the power supply for the air conditioner.
2. Remove electrical cover A and B.
3. Slide out electronic control P.C. board, and switch
up or down Dip switch (SW3).
4. Put electronic control P.C. board back to
the original position, and install electrical cover A and B.
NOTE:
To prevent damage of P.C. board due to static electricity,
make sure to perform static elimination before setting.
Normal
Increase
airflow volume
Dip switch SW3
Electronic control P.C. board
Electrical
cover B
Electrical
cover A
NOTE: When the ceiling is above 2.7 m, airflow volume may be insufficient even with the Dip switch (SW3)
set to "increase airflow.
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed
are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment
power has restored after power failure. Then, the unit will restart automatically.
Operation
If the main power has been cut, the operation settings remain.
1
2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release “AUTO RESTART FUNCTION”
1Turn off the main power for the unit.
2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
•The operation settings are memorized when 10 seconds have passed
after the indoor unit was operated with the remote controller.
•If main power is turned OFF or a power failure occurs while AUTO
START/STOP timer is active, the timer setting is cancelled.
•If the unit has been off with the remote controller before power failure, the
auto restart function does not work as the power button of the remote controller is off.
•To prevent breaker tripping due to the rush of starting current, systematize
other home appliance not to turn on at the same time.
•When some air conditioners are connected to the same supply system, if
they are operated before power failure, the starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main
voltage-drop or the rush of the starting current by adding to the system
that allows the units to start one by one.
7-4. P.C. BOARD MODIFICATION FOR CHANGING AIRFLOW VOLUME
9
8
(This diagram shows an overall view.)
.)
raverall view.)
Open the front lid.
ON-TIMER button
CLOCK SET button
TIME SET buttons
FORWARD button
BACKWARD button
OFF-TIMER button
WIDE VANE button
RESET button
VANE CONTROL button
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP
(ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of
remote controller
model is on back
MICROPROCESSOR CONTROL
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
WIRELESS REMOTE CONTROLLER
Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP
(ON/OFF) button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not
restart for 3 minutes.
10
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the left side of the indoor unit indicates the operation state.
Difference between target
Operation stateIndication
temperature and
room temperature
This shows that the air conditioner is
operating to reach the target temperature.
Please wait until the target temperature is obtained.
Approximate
2 : or more
Lighted
Blinking
This shows that the room temperature is
approaching the target temperature.
This shows a state of standby for operation.
(For multi system air conditioner)
8-1. COOL () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Coil frost prevention
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
8-2. DRY () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
1. Coil frost prevention
Coil frost prevention is as same as COOL mode. (8-1.1.)
Approximate
2 : or less
Not lighted
8-3. HEAT () OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room
temperature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
8-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION
Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.
Mode selection
(1) Initial mode
When unit starts the operation with AUTO operation from off;
• If the room temperature is higher than the set temperature, operation starts in COOL mode.
• If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.
(2) Mode change
COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 2 degrees
below the set temperature.
HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 2 degrees
above the set temperature.
NOTE :
If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is operating
in (AUTO), cannot change over to the other operating mode (COOLHEAT) and becomes a state of standby.
11
12345
8-5. AUTO VANE OPERATION
1
5
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approximate 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the desired
angle.
Confirming of standard position is performed in the following cases:
(a) When the power supply turns on.
(b) When the operation starts or finishes (including timer operation).
(c) When the test run starts.
(d) When multi-standby starts or finishes.
(e) When the swing operation finishes.
(4) VANE AUTO () mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
(1) In COOL and DRY operation
(2) In HEAT operation
(5) STOP (operation OFF) and ON-TIMER standby
In the following cases, the horizontal vane returns to the closed position.
(a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When ON-TIMER is ON standby.
(6) SWING MODE ()
By selecting SWING mode with VANE CONTROLbutton, the horizontal vane swings vertically. The remote controller
displays “”. SWING mode is cancelled when VANE CONTROLbutton is pressed once again.
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher.
Also the horizontal vane swings in various cycle.
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the air
conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL
button is pressed or change to other operation mode.
Vane angle is fixed to Angle 1.
Vane angle is fixed to Angle 5.
12
2. Vertical vane
Float sensor
Water surface
Fixed point, when water level rises
Fixed point, when water level lowers
(1) Press WIDE VANE button to change horizontal airflow direction.
•The vertical vane moves for about 30 seconds.
(After 30 seconds, the vertical vane moves to its original position. In this case, press WIDE VANE button again.)
(2) Press WIDE VANE button again to set horizontal airflow direction.
•The vertical vane stops and the airflow direction is set.
(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane set to the desired
angle.
Confirming of standard position is performed in the following cases:
(a) When OPERATE/STOP(ON/OFF) button is pressed (POWER ON).
(b) When SWING is started.
8-6. Drain pump/ float sensor control
1. Drain pump
Operating condition:
1. During COOL, DRY, or emergency COOLoperation
2. When float sensor detects water level above fixed point during :
(a) HEAT operation.
(b) emergency HEAT operation.
(c) standby when during multi system operation.
(d) standby when ON timer is set.
(e) operation STOP.
Drain pump operates in conditions 1 or 2.
Operation stop condition:
Condition other than 1 or 2 indicated above.
2. Float sensor
Float moves with the up and down of water surface inside the drain pan, and judges water level.
(Fixed point differs at raised and lowered water levels.)
8-7. TIMER OPERATION
1. How to set the time
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of
TIME MONITOR, so set the current time correctly with CLOCK SET button.
How to set the current time
(1)Press the CLOCK set button.
(2)Press the TIME SET buttons (and ) to set the current time.
• Each time FORWARD button () is pressed, the set time increases by 1minute, and each time BACKWARD button
() is pressed, the set time decreases by 1minute.
• Pressing those buttons longer increases / decreases the set time by 10 minutes.
Press the CLOCK set button.
13
EMERGENCY
OPERATION switch
Operation indicator lamp
Operation modeCOOLHEAT
Set temperature24:24:
Fan speedMediumMedium
Horizontal vaneAutoAuto
The operation mode is indicated by the Operation
indicator lamp on the indoor unit as following
Not lighted
Lighted
Operation Indicator lamp
Press again <HEAT>
Press once <COOL>
Press once again <STOP>
START
STOP
ON timer setting
START
STOP
(1) Press ON-TIMER button( ) during operation.
(2) Set the time of the timer using TIME SET buttons (and ) . w
OFF timer setting
(1) Press OFF-TIMER button ( ) during operation.
(2) Set the time of the timer using TIME SET buttons (and ). w
w Each time FORWARD button () is pressed, the set time increases by 10 minutes; each time BACKWARD button
() is pressed, the set time decreases by 10 minutes.
2. Cancel
To cancel ON timer, press ON-TIMER button ( ).
To cancel OFF timer, press OFF-TIMER button( ).
TIMER is cancelled and the display of set time disappears.
PROGRAM TIMER
• OFF timer and ON timer can be used in combination. The timer of the set time that is reached first will operate first.
• “” and “” display show the order of OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting
is cancelled. As these models are equipped with an auto restart function, the air conditioner starts operating with
timer cancelled when power is restored.
8-8. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor
unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote
controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at
High speed and the system is in continuous operation (The thermostat in ON).
After 30 minutes of test run operation, the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of
24°C. The fan speed shifts to Med.
The coil frost prevention works even in emergency operation, and defrosting too.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO () mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any
signal from the remote controller. In case of latter, normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.
14
9
Housing point
RESET button
Insert the negative pole of the
batteries first. Check if the polarity
of the batteries is correct.
OPERATIONINDICATOR
Not lighted
Blinking
Lighted
TROUBLESHOOTING
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing
1) Before servicing the air conditioner, be sure to turn off the unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the
electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 9-2, 9-3 and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the other
for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units cannot operate
and indicate as shown in the figure below. In this case, please set all the indoor units to the same operation mode.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced.
This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by
the battery replacement.
connect indoor units beyond the outdoor unit capacity.
Operation indicator lamp flashes as shown in the figure below.
•When indoor units start operation while the defrosting of outdoor unit is being done, it takes a few minutes (maximum
10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant
flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
15
9-2. Failure mode recall function
Operational procedure
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
W1. Regardless of normal or abnormal, a short
beep is emitted once as the signal is received.
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycleRepeated cycle
ON
OFF
No beepBeeps
Repeated cycle
2.5-second OFF
Blinking at 0.5second interval
2.5-second OFF3-second ON
Blinking at 0.5second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5second interval
No beepBeeps
Repeated cycle
2.5-second OFF3-second ON
Blinking at 0.5second interval
Repeated cycle
Beeps
Does the left lamp of OPERATION INDICATOR lamp
on the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal.
Beep are emitted at the same timing
as the blinking of the left lamp of
OPERATION INDICATOR lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does the left lamp of OPERATION
INDICATOR lamp stay ON for 3 seconds?
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and confirm the
abnormal point with the indoor unit failure mode table (9-2. 3.).
Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply.
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same
time, press RESET button.
2 First, release RESET button.
And release the other two buttons after all LCD except the set
temperature in operation display section of the remote controller is
displayed after 3 seconds.
Deleting the memorized
abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure
mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is
displayed) with the remote controller headed towards the indoor unit. W1
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4Release the failure mode recall function according to "Releasing the failure mode recall
function" mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature
is displayed) with the remote controller headed towards the indoor unit. W1
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some
abnormalities that are not memorized in the indoor unit.
Confirm if outdoor unit is abnormal according to the flow chart of the
detailed outdoor unit failure mode recall function.
The outdoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the
outdoor unit failure mode table (Refer to outdoor unit service manual).
Make sure to check at least two consecutive blinking cycles. W3
As for outdoor unit, refer to outdoor unit service manual.
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though OPERATION INDICATOR lamp indication listed on the troubleshooting check table (9-4.) disappears, the
memorized failure details can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
16
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2.Blinking pattern when outdoor unit is abnormal:
Yes
(Blinks)
No
(OFF)
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF3-second ON
Blinking at 0.5second interval
No beepBeeps
Repeated cycle
2.5-second OFF3-second ON
Blinking at 0.5-
second interval
Repeated cycle
W1. Regardless of normal or abnormal, 2 short
beeps are emitted as the signal is received.
Does OPERATION INDICATOR lamp on the indoor
unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal.
Beeps are emitted at the same timing as the
blinking of OPERATION INDICATOR lamp. W2
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Repair the defective parts.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 25:. W1
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
The outdoor unit is abnormal.
Check the blinking pattern, and confirm the abnormal point with the
outdoor unit failure mode table (Refer to outdoor unit service manual).
Make sure to check at least two consecutive blinking cycles. W2
Release the failure mode recall function according
to the left mentioned procedure.
Confirm that the remote controller is in the failure mode recall
function.
The outdoor unit might be abnormal.
Confirm if outdoor unit is abnormal according to the following procedures.
17
3. Indoor unit failure mode table
12-time flash
2.5-second OFF
Replace the indoor electronic control
P.C. board.
Indoor control system
When it cannot be read properly data in the
nonvolatile memory of the indoor electronic
control P.C. board.
When the rotational frequency feedback
signal is not emitted during 12-second the
indoor fan operation.
2-time flash
2.5-second OFF
Refer to the characteristic of the main 1,2
indoor coil thermistor and the sub indoor
coil thermistor (9-7.).
Indoor coil thermistor
(Main 1, 2 and sub)
When the indoor coil thermistor short or
open circuit is detected every 8 seconds
during operation.
3-time flash
2.5-second OFF
Refer to 9-6.D "How to check mis-wiring
and serial signal error".
Serial signal error
When the serial signal from the outdoor unit is
not received for a maximum of 6 minutes.
1-time flash
every 0.5-second
Refer to the characteristics of the room
temperature thermistor (9-7.).
Room temperature
thermistor
When the room temperature thermistor
short or open circuit is detected every 8
seconds during operation.
Not lighted–Normal–
Left lamp of
OPERATION
INDICATOR lamp
13-time flash
2.5-second OFF
Replace to the characteristic of the main
3 indoor coil thermistor (9-7.).
Indoor coil thermistor
(Main 3)
When the indoor coil thermistor short or
open circuit is detected every 8 seconds
during operation.
11-time flash
2.5-second OFF
Refer to 9-6 A "Check of indoor
fan motor"
Indoor fan motor
Not lighted
Not lighted
Not lighted
Not lighted
Not lighted
Not lighted
Not lighted
Right lamp of
OPERATION
INDICATOR lamp
Countermeasure
Abnormal point
(Failure mode)
Check point
• Check float sensor and drain pump.
• Check the connectors of float sensor
and drain pump.
• Refer to 9-6.E "Check of float sensor".
• Float sensor is open.
• Float sensor detects abnormal water level.
5-time flash
2.5-second OFF
Drain pump
Float sensor
Not lighted
NOTE:Blinking patterns of this mode differs from the ones of Troubleshooting check table(9-4.).
18
9-3. Instruction of troubleshooting
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Outdoor unit
operates only
in Test Run
operation.
w1
Check room
temperature
thermistor.
Refer to 9-7.
"Test point
diagram and
voltage".
Indoor unit operates.
Outdoor unit doesn't
operate normally.
Outdoor unit
doesn't
operate
even in
Test Run
operation.
w1
Refer to
"How to check
inverter/
compressor".
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
Refer to
"Check of
R.V. coil".
Indoor unit
doesn't receive
the signal from
remote controller.
Indoor unit
operates, when
EMERGENCY
OPERATION
switch is pressed.
Refer to 9-6.B
"Check of
remote controller
and receiver
P.C. board".
OPERATION INDICATOR
lamp on the indoor unit is
flashing on and off.
Indoor unit
doesn't operate,
when
EMERGENCY
OPERATION
switch is pressed.
1. Check indoor / outdoor
connecting wire.
(Check if the power
is supplied to the
indoor unit.)
2. Refer to 9-6.C
"Check of indoor
electronic control
P.C. board and indoor
fan motor".
If blinking of OPERATION
INDICATOR lamp cannot be
checked, it can be checked with
failure mode recall function.
w1
"Test Run operation" means the
operation within 30 minutes after
EMERGENCY OPERATION switch
is pressed.
Refer to outdoor unit service manual.
Left lamp
Flash on and off
at 0.5-second
intervals
Cause:
Indoor/
Outdoor unit
• Mis-wiring
or trouble
of serial signal
Refer to 9-6.
D "How to
check
mis-wiring
and serial
signal error
(when
outdoor unit
doesn't work)".
Left
2-time flash
Cause:
Indoor unit
• Trouble of
room temp erature/
indoor coil
thermistor
Check room
temperature
thermistor
and indoor
coil thermistor.
Refer to 9-7.
"Test point
diagram and
voltage".
lamp
Left
lamp
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
Refer to 9-6.
A"Check of
indoor fan
motor".
Left lamp
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
Left lamp
5-time flash
Cause:
Outdoor unit
• Outdoor
power
system
abnormality
Refer to
"How to check
the inverter/
compressor".
19
Left lamp
6-time flash
Cause:
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
Refer to
"Check of
outdoor
thermistors".
Left lamp
7-time flash
Cause:
Outdoor unit
• Trouble of
outdoor
control
system
Replace the
inverter P.C.
board or
the outdoor
electronic
control P.C.
board.
Left lamp
9-time flash
Cause:
Indoor unit
• Trouble of
float sensor
or drain
pump
Refer to 9-6.
E"Check of
float sensor".
Check the
drain pump.
Left lamp
14-time flash
Cause:
Outdoor unit
• Other
abnormality
• Check the
stop valve.
Check
"Flow chart of
the detailed
outdoor unit
failure mode
recall function."
No.
1
3
6
7
SymptomOperation indicator lamp
Check point
Countermeasure
Left lamp flashes.
0.5-second ON
0.5-second OFF
Mis-Wiring
or serial
signal
Outdoor
power
system
Outdoor
thermistors
Outdoor
control
system
Indoor coil
thermistor
When the serial signal from the outdoor unit is
not received for a maximum of 6 minutes.
The compressor stops 3 times consecutively
for over current protection or start-up failure
protection within 1 minute after start-up.
When the outdoor thermistors short or open
circuit during the compressor operation.
When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or of the outdoor electronic control P.C. board.
• Refer to "Check of outdoor
thermistor".
Refer to outdoor unit service
manual.
• Refer to "Check of inverter/
compressor".
Refer to outdoor unit service
manual.
Check the stop valve.
• Replace the inverter P.C.
board or the outdoor
electronic control P.C. board.
Refer to outdoor unit service
manual.
• Refer to 9-6.D "How to check
mis-wiring and serial signal
error".
4
Indoor fan
motor
8
Abnormal
point
Room
temperature
thermistor
Left lamp flashes.
2-time flash
2.5-second OFF
When the indoor coil or the room temperature
thermistor is shorts or opens circuit.
• Refer to the characteristics of
indoor coil thermistor, and the
room temperature thermistor
on 9-7.
Left lamp flashes.
3-time flash
2.5-second OFF
When the rotational frequency feedback
signal is not emitted during the indoor fan
operation.
• Refer to 9-6.A "Check of
indoor fan motor".
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Left lamp flashes.
5-time flash
2.5-second OFF
Left lamp flashes.
6-time flash
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Other
abnormality
An abnormality other than above mentioned is
detected.
• Confirm the abnormality in
detail using the failure mode
recall function.
Refer to outdoor unit service
manual.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
9
10
5
Left lamp flashes.
4-time flash
2.5-second OFF
Indoor
control
system
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
Indoor unit
and outdoor
unit do not
operate.
• Replace the indoor electronic
control P.C. board.
Outdoor
control
system
When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or of the outdoor electronic control P.C. board.
• Check the blinking pattern of
the LED on the inverter P.C.
board or the outdoor
electronic control P.C. board.
2
Outdoor unit
does not
operate.
Left lamp lights up.
• Float sensor is open.
• Float sensor detects abnormal water level.
• Check float sensor
characteristics.
• Check drain pump.
• Check drain pipe.
• Check the connectors of float
sensor and drain pump.
• Refer to 9-6.E"Check of float
sensor".
Indoor unit
and outdoor
unit do not
operate.
Left lamp flashes.
9-time flash
2.5-second OFF
Drain
pump
Left lamp flashes.
7-time flash
2.5-second OFF
Left lamp flashes.
14-time flash
2.5-second OFF
9-4. Troubleshooting check table
OPERATION INDICATOR
Not lighted
Blinking
Lighted
· Flashing of OPERATION INDICATOR lamp (left-hand side lamp)
indicates abnormalities.
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
NOTE : When the indoor unit has started operation and the above failures are detected (the first detection after the power
ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp
flashing.
20
OPERATION INDICATOR
No.
SymptomOperation indicator lamp
Check point
Countermeasure
Abnormal
point
1
MXZ type
Operation
mode
setting
Outdoor unit
operates but
indoor unit
does not
operate.
When the operation mode of the each indoor
unit is differently set to COOL(includes DRY)
and HEAT at the same time, the operation
mode of the indoor unit that has operated at
first has the priority.
• Unify the operation mode.
Refer to outdoor unit
service manual.
2.5-second OFF
Right lamp flash
Part nameFigureCheck method and criteria
Indoor fan motor
Measure the resistance with a tester. (Part temperature 10˚C ~ 30˚C)
Measure the resistance between the terminals with a tester.
(Part temperature 20°C ~ 30°C)
Vertical vane
motor (MV2)
Measure the resistance between the terminals with a tester.
(Part temperature 20°C ~ 30°C)
Normal
GRAY-GRAY
Measure the resistance between the terminals with a tester.
(Part temperature 10°C ~ 30°C)
520" ~ 620"
Color of the lead wire
Normal
BRN-other one
Each phase 380"
Color of the lead wire
Normal
BRN-other one
Each phase 300"
Color of the lead wire
Check 9-6. A.
Float sensor (FS)
Drain pump (DP)
RED
YLW
BRN
ORN
GRN
ROTOR
Disconnect connector and check with a tester.
Check open or short according to the float position.
Float sensorFloat sensor
Float
Float
Float
position
NormalShortOpen
Lighted
Blinking
Not lighted
· Flashing of OPERATION INDICATOR lamp (right-hand side lamp) indicates
abnormality.
· OPERATION INDICATOR lamp (left-hand side lamp) is lighted.
NOTE : When the indoor unit has started operation and the above failures are detected (the first detection after the power
ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp
flashing.
9-5. Trouble judgement criteria of main parts
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
21
CN211
Fuse (F11)
IC101
T11
VARISTOR (NR11)
Indoor electronic
control P.C. Board
CN151
C111
R111
wIf more than 12 seconds passes after EMERGENCY OPERATION switch
is pressed, the voltage mentioned in above 2) goes 0V DC although the
indoor electronic control P.C. board is normal.
Pay careful attention to the high voltage on
the fan motor connector CN211.
Yes
No
No
No
(Changed)
Yes
(Unchanged)
Is there anything that interferes the
rotation of the line flow fan?
Turn OFF the power supply.
Remove the object and
adjust the line flow fan.
Turn ON the power supply, wait 5 seconds or more, and then press
EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds
after EMERGENCY OPERATION switch is pressed.
If more than 12 seconds passes by, turn OFF the power supply and
turn ON it again, then measure the voltage. w
1) Measure the voltage between CN211 1(+) and 3(-).
2) Measure the voltage between CN211 5(+) and 3(-).
Is there 311V DC between
CN211 1 (+) and 3 (-), and does
the voltage between CN211 5(+)
and 3(-) rise to the range between 3
and 6V DC within 12 seconds after
EMERGENCY OPERATION switch
is pressed?
Yes
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
6(+) and 3(-) while the fan
motor is rotating.
Is 0V DC or 15V DC
held unchanged?
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan does not operate.
JR06
JR05
9-6. Troubleshooting flow
When the left lamp of OPERATION INDICATOR lamp flashes 3 times and the right lamp of OPERATION INDICATOR
lamp is not lighted.
Indoor fan does not operate.
A
Check of indoor fan motor
22
Indoor unit operates by pressing EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check of remote controller and receiver P.C. board
B
w Check if the remote controller is exclusive for this air conditioner.
Press OPERATE/STOP(ON/OFF) button on the remote controller.
Is the LCD display on the the
remote controller visible?
Yes
Remove the batteries, then set them back
and press RESET button. (Refer to 9-1.4.)
Check if the unit operates with the remote
controller.
Does the unit operate with the
remote controller?
Yes
OK
No
(not clear)
No
Replace the batteries. (Refer to 9-1.4.)
Turn on a radio to AM and press
OPERATE/STOP(ON/OFF) button
on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of
inverter or of rapid-start type within
the range of 1m?
No
Replace the indoor electronic
control P.C. board.
No
Yes
Replace the remote controller.
● Reinstall the unit away from lights.
● Attach a filter on receiving part.
23
The unit cannot be operated with the remote controller.
Also, OPERATION INDICATOR lamp does not light up by pressing EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board and indoor fan motor
C
Turn OFF the power supply.
Remove indoor fan motor connector CN211 and vane
motor connector CN151 from the indoor electronic
control P.C. board and turn ON the power supply.
Does the unit operate with the remote controller?
Does OPERATION INDICATOR lamp light up by
pressing EMERGENCY
OPERATION switch?
No
Turn OFF the power supply.
Measure the resistance between CN211
3 and 4 of the indoor fan motor connector.
Yes
Turn OFF the power supply.
Measure the resistance of the horizontal vane
motor coil and the vertical vane motor coil.
Refer to 9-5.
Replace the varistor(NR11) and fuse(F11).
Yes
Short/ open circuit:
Replace the indoor fan motor.
Short/ open circuit:
Replace the horizontal vane motor, the vertical
vane motor coil and the indoor electronic
control P.C. board.
Turn OFF the power supply.
Check both “parts side” and “pattern
side” of the indoor electronic control P.C.
board visually.
Indoor electronic
control P.C. Board
Fuse (F11)
VARISTOR (NR11)
Are the varistor(NR11) burnt
and the fuse(F11) blown?
Be sure to check both the fuse
and the varistor in any case.
Is the fuse(F11) blown only?
Measure the resistance between
1(+) and 3(-) of the indoor fan
motor connector (to CN211 on the
indoor electronic control P.C. board).
w1, w2
Is the resistance 1M'
or more?
Replace the fuse (F11).
Measure the cement resistance R111 on
the indoor electronic control P.C. board.
Replace the indoor electronic control P.C. board.
JR06
JR05
IC101
Yes
Yes
No
No
w1. The fan motor connector's 1 lead wire is red, whereas 3 is black.
w2. Connect "+" of the tester to fan motor connector's 1 lead
wire, and "-" to 3 lead wire, otherwise the resistance cannot be
measured properly.
No
Replace the fuse (F11) and the indoor fan motor.
Is the resistance
approx. 4'?
Yes
No
Replace the indoor electronic control P.C. board
and the indoor fan motor.
R111
C111
T11
CN151
CN211
24
When the left lamp of OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Is there rated voltage of
230V AC in the power
supply?
Is there any mis-wiring,
poor contact, or wire
disconnection of the
indoor/outdoor
connecting wire?
W1. Mis-wiring may damage indoor electronic control
P.C. board during operation.
Be sure to confirm the wiring is correct before the
operation starts.
No
Yes
No
Yes
Yes
No
No
Yes
No
Yes
As for outdoor unit, refer to outdoor unit service manual.
Turn OFF the power supply.
Turn ON the power supply.
Is there 230V AC between
outdoor terminal block S1 and
S2?
Does the left lamp of OPERATION INDICATOR
lamp light up? <Confirmation of the power
supply to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power
supply.
Is the serial signal error indicated 6 minutes later?
Turn OFF the power supply.
Check once again if the indoor/outdoor
connecting wire is not wrongly connected.
Short-circuit the outdoor terminal block S2
and S3.
W1
Check the wiring.
Correct them.
Is the serial
signal error
indicated 6
minutes later?
Yes
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn it ON again.
· Press EMERGENCY OPERATION switch.
· Reinstall either the unit or the light away
from the other.
· Attach a filter on receiving section of the indoor unit.
Outdoor unit does not operate.
D
How to check mis-wiring and serial signal error
25
When the left lamp of OPERATION INDICATOR lamp flashes 9-time.
Turn OFF the power supply and check
connectors CN145 and CN1N1 visually.
Disconnect float sensor from CN145 of
indoor electronic control P.C. board.
Measure the resistance between 1 and 2.
Is the drain pump
operating?
Turn ON the power supply. Press
EMERGENCY OPERATION switch
(COOL) and perform emergency COOL
operation. Measure the voltage between
CN1N1 1 and 2.
Yes
Yes
No
No
Is there 230V AC
between CN1N1 1 and
2?
Is there large amount
of water in drain pan?
*1 Refer to 9-5. when
float sensor can be checked.
Yes
Replace the indoor
electronic control P.C. board.
Replace the indoor
electronic control P.C. board.
Check power supply voltage.
No
Replace the float sensor.
Yes
Remove clog from drain
hose.
No
Replace the drain pump.
No
No
Is the drain hose
clogged?
Yes
Yes
Yes
No
Replace the indoor
electronic control P.C. board.
Are the lead wires
disconnected?
Are there abnormality in
the soldering part of
connectors?
Is the resistance 1Ω or
less? *1
Connect the lead wire.
Solder the connector.
Indoor electronic control P.C. board
CN1N1
CN145
During HEAT
When one unit is operated in standard operating temperature, the compressor operates in minimum frequency,
and the room does not warm.
During COOL
When one unit is operated, air coming out is not cold (same as FAN operation), and the room does not cool.
Heat exchanger of the unit not operating freezes. This may cause malfunction of compressor.
• Mis-wiring or incorrect piping is difficult to determine, because operation is almost normal when all indoor units operate.
Indoor unit and outdoor unit do not operate.
Check of float sensor
E
When heating or cooling, room does not get warm or cool.
How to Check mis-wiring or incorrect piping
F
Refer to outdoor unit service manual.
26
<Only for multi units>
Electromagnetic noise enters into TV sets or radios
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the
antennas and the indoor
unit within 3m, or is the
distance between the
antennas and the outdoor
unit within 3m?
Is the distance between the
TV sets or radios and the
indoor unit within 1m, or is
the distance between the TV
sets or radios and the
outdoor unit within 3m?
Is the indoor/outdoor
connecting wire of the air
conditioner and the wiring of
the antennas in close?
Is the unit earthed?
Earth the unit.
Extend the distance between
the antennas and the indoor
unit, or the antennas
and the outdoor unit.
Extend the distance between
the TV sets or radios and the
indoor unit, or the TV
sets or radios and the
outdoor unit.
Extend the distance between
the indoor/outdoor connecting
wire of the air conditioner and
the wiring of the antennas.
Replace or repair the antenna.
Replace or repair the coaxial cable.
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in
the antenna wiring?
Even if all of the above conditions is fulfilled, the electromagnetic noise may enter, depending on
the electric field strength or the installation condition (combination of specific conditions such as
antennas or wiring).
Check the followings before asking for service.
1.Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ;
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring
from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation check for
the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button
on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During
operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the
outdoor unit stops but the indoor/outdoor communication still runs on. In this situation check for
the electromagnetic noise.
After checking the above, consult the service representative.
Release of Auto reset
function
Solder the Jumper
wire to JR07. (Refer to 7-3.)
Timer short mode point
}
JPG, JPS (Refer to 7-1.)
Emergency operation switch
CN145
Float
sensor
CN1N1
Drain
pump
R111
JR05 JR06
}
Modification point for
individual operation
(Refer to 7-2.)
GND DC 12V DC
CN151
Horizontal vane motor
Vertical vane motor
Indoor fan motor CN211
6over 15V DC
53-6V DC
415V DC
3
1325V DC
28
10
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the
locking mechanism.
1Slide the sleeve.
2Pull the terminal while
pushing the locking
lever.
1Hold the sleeve, and
pull out the terminal
slowly.
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
INDOOR UNIT
OPERATING PROCEDURE
1. Opening the intake grille
(1) Press the area indicated “PUSH” on the intake grille until
a click is heard (Figure 1).
(2) Hold the tabs on both sides of the intake grille and pull it
down.
2. Removing the intake grille
(1) Press the area indicated “PUSH” on the intake grille
until a click is heard.
Hold the tabs on both sides of the intake grille and pull it
down (Figure 1).
(2) Pull the hinges of the intake grille toward you (Figure 2).
(3) Unhook the safety strings supporting the intake grille from
the front panel (Figure 3).
Figure 1
Figure 2
Photo 1
Places for installing
the Anti-Allergy Enzyme filter (Option)
Remote
control
receiving
section
Electrical
box
Safety strings for
preventing the
intake grille from
falling
PHOTOS
Places for installing
the air filters
(Catechin air filter, option)
Intake grille
Figure 3
29
OPERATING PROCEDUREPHOTOS
Places for
securing
the grille
Close-up
Points for securing the grille
Points for securing the grille
Drain pan
Ceiling surface
Make sure
that these
surfaces are
flush with
each other.
(0~3 mm)
Make sure
that these
surfaces are
flush with
each other.
(0~3 mm)
Stopper
Horizontal vane
Hooks
Temporary holding tabs
Screw cap
Screw cap
3. Checks before setting in place
(1) Before installing the grille, make sure the indoor unit is
square with the ceiling opening (or parallel to the wall-ceiling joint).
(2) Check that the four points for securing the grille are in
contact with the ceiling surface. Use the installation
template supplied with the indoor unit to arrange the four
points for securing the grille within 0 to 3 mm from the
ceiling surface (Figure 4, 5).
(3) Check that the insulation for the refrigerant pipes, drain
pipes, etc. are in place and that wiring connections and
arrangements are complete.
4. Removing the horizontal vane
(1) Slide each stopper of the horizontal vane.
(2) Remove the horizontal vane (Figure 6).
NOTE :
To install, follow the removal procedure in reverse.
Make sure a click is heard from each stopper when
attaching the vane.
5. Removing the grille
(1) Open the intake grille.
(2) Remove the screw cap in the center of air outlet
(Figure 8).
(3) Remove the fixing screws (1 and 2 in Figure 7).
(4) Remove the temporary holding tabs of the grille.
Figure 4
Figure 5
Figure 6
6. Installing the grille
(1) Press the areas indicated “PUSH” on the intake grille
to open.
(2) Remove the screw cap in the center of air outlet.
(3) Open the horizontal vane completely.
(4) Hook the temporary holding tabs of the grille to the
indoor unit (Figure 7).
(5) Place the grille so that it fits properly in the
wall-ceiling joint, and attach the front panel with the fixing
screws 1 provided. Do not fully tighten the screws at this
point.
(6) Tighten the fixing screws 1 in the center three places and
2 (Figure 7).
(7)Tighten the fixing screws 1 in the four places at left and
right side of the indoor unit.
At this point, make sure there are no gaps between the indoor
unit and grille, and between the grille and ceiling surface. If
there are gaps, the wind may come in and it may cause water
to drip (Figure 9).
w Tighten the fixing screw 1 and 2 completely.
Installing the Anti-Allergy Enzyme filter (Option)
Push the Anti-Allergy Enzyme filter into the guide of the grille
until a click is heard (Figure 10).
Figure 7
Figure 8
30
OPERATING PROCEDUREPHOTOS
Indoor unit
No gaps here
Ceiling surfaceGrille (Figure 10)
Anti-Allergy Enzyme filter (Option)
7. Check after installing
(1) Check that there are no gaps between the indoor unit and
grille, and between the grille and ceiling
surface (Figure 9).
(If there are gaps, the wind may come in and dew
condensation may result.)
(2) Is the air filter installed?
(3) Is the Anti-Allergy Enzyme filter (Option) installed?
8. Removing the electronic control P.C. board and display receiver P.C. board
(1) Open the intake grille.
(2) Remove the screws for the electrical cover A and B.
Remove the covers (Photo 2).
(3) Remove the screw for the lamp cover and unhook it.
(4) Pull the electronic control P.C. board slightly toward you
from the electrical box, and disconnect all the connectors
from the electronic control P.C. board.
(5) Remove the electronic P.C. board and display receiver
P.C. board.
9. Removing the heat exchanger and nozzle
(1) Remove the grille.
(2) Remove the room temperature thermistor.
(3) Remove the two claws in the center of the nozzle and the
screws for the drain pan.
(4) Remove the screws for the electrical cover A and B.
Remove both covers.
(5) Disconnect the connectors of the vertical and horizontal
vane motor.
(6) Remove the indoor coil thermistor (main and sub.).
(7) Remove the screws for the drain cover. Remove the drain
cover.
(8) Remove the pipe band.
(9) Remove the screws for the heat exchanger. Remove the
heat exchanger.
(10)Remove the screws for the nozzle. Remove the nozzle.
Figure 9
Figure 10
Photo 2
Electrical cover A
Screws for the electrical cover
Screw for the
electrical over
Electrical cover B
Screw for the
lamp cover
Lamp cover
10. Removing the horizontal and vertical vane motor
unit
(1) Remove the grille.
(2) Remove the drain pan.
(3) Remove the horizontal vane (Figure 6).
(4) Remove the screws for the cover of the horizontal and ver-
tical vane motor unit. Remove the cover.
(5) Remove the screws for the vertical vane motor unit.
Remove the vertical vane motor unit and disconnect the
connectors (Photo 4).
(6) Remove the screws for the horizontal vane motor unit.
Remove the horizontal vane motor unit and disconnect the
connectors (Photo 4).
31
Photo 3
Drain cover
Float sensor
Drain pump
Screw for the
Drain pan
Room temperature thermistor
Nozzle
electrical cover
Cover of the horizontal
and vertical vane motor
Indoor heat
exchanger
OPERATING PROCEDUREPHOTOS
11. Removing the drain pump and float sensor
(1) Remove the grille.
(2) Remove the drain pan.
(3) Disconnect the connector of the drain pump (Photo 5).
(4) Disconnect the connector of the float sensor (Photo 5).
(5) Remove the drain hose (Photo 5).
(6) Remove the screws for the drain pump (Photo 5).
(7) Remove the screws for the cover of the drain pump
(Photo 5).
12. Removing the fan motor and line flow fan
(1) Remove the grille.
(2) Remove the drain pan.
(3) Remove the drain cover.
(4) Remove the pipe band.
(5) Remove the screws for the electrical cover A and B.
Remove both covers.
(6) Remove the screws for the terminal box. Remove the
terminal box.
(7) Untie the safety strings from the clamp (Photo 6).
(8) Hook the safety strings to the tab on the side of the heat
exchanger. (This prevents the heat exchanger from
falling.) Remove the screws for the heat exchanger and
pull the heat exchanger downward.
(9) Remove the screws for the nozzle. Remove the nozzle.
(10)
Pull out the electronic control P.C. board slightly and
disconnect the connector (CN211) of the indoor fan motor.
(11)
Remove the screws for the motor band. Remove the
motor band (Photo 6).
(12)
Remove the indoor fan motor and line flow fan. (No need
to remove the heat exchanger before removing these two
items.)
Photo 4
Vertical vane motor
Photo 5
Screws for
the drain
pump
Drain pump
Screws for the
cover of the
drain pump
Photo 6
Nozzle
Drain hose
Connector for
the float sensor
Fan motor
Horizontal vane motor
Float sensor
Cover of the
drain pump
Screws for
the cover of
the drain
pump
Screws for
the drain
pump
Connector for
the drain pump
Safety string
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Feb. 2007. No. OBH483 8
Made in Japan
Safety string
Line flow fan
New publication, effective Feb. 2007
Specifications subject to change without notice.
Screws for the motor band
Motor band
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.