Mitsubishi MLZ-KA25VA-E1, MLZ-KA35VA-E1, MLZ-KA50VA-E1 Service Manual

CEILING CASSETTE TYPE, HEAT PUMP AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Ceiling cassette type Models
No. OBH483
MLZ-KA25VA ­MLZ-KA35VA ­MLZ-KA50VA -
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
E1
E1
E1
Outdoor unit service manual MXZ-A•VA Series (OB377)
CONTENTS
1. PART NAMES AND FUNCTIONS······················2
2. SPECIFICATION·················································3
3. NOISE CRITERIA CURVES·······························4
4. OUTLINES AND DIMENSIONS·························5
5. WIRING DIAGRAM ············································6
6. REFRIGERANT SYSTEM DIAGRAM················7
7. SERVICE FUNCTIONS ······································8
9. TROUBLESHOOTING······································15
10. DISASSEMBLY INSTRUCTIONS·····················30
PARTS CATALOG (OBB483)
NOTE:
• RoHS compliant products have <G> mark on the spec name plate.
1
1 2 3 4 5 6 7 8 9
0
Alkaline battery (AAA) for remote controller Drain hose (with insulation) Special washer (with cushion, 4pcs) Installation template Fixing screw for 4 M5 o 30 Band Fixing screw for 6 4 o 16 Remote controller Remote controller holder Fixing screw for 9
MLZ-KA25VA MLZ-KA35VA
2 1 8 1 4 1 2 1 1 2
MLZ-KA50VA
Vertical vane
Air outlet
Horizontal vane
Air filter (Catechin air filter, option)
Air cleaning filter (Anti-Allergy Enzyme Filter, option)
Safety string
Intake grille
Remote control receiving section
Display and operation section (When the intake grille is opened)
Operation indicator lamp
Emergency operation switch
Air inlet
PART NAMES AND FUNCTIONS
INDOOR UNIT
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
ACCESSORIES
2
2
T3.15AL 250V
12V 300" 12V 300"
ERZV14D471
230V 6.4W
DC 12V
Item
Model
Fuse Horizontal vane motor Vertical vane motor Varistor DRAIN PUMP FLOAT SENSOR
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
(F11) (MV1) (MV2)
(NR11)
(DP)
(FS)
Cooling
528/ 480/ 432
35/ 32/ 29
1,120/1,030/950
MLZ-KA35VAMLZ-KA25VA MLZ-KA50VA
Indoor model
Function
Power supply
Single phase
230V,50Hz
0.3 40
58
0.3
RC0J30-KC
1,102O175O360
15
5
3
KM07E
Heating
552/ 492/ 420
36/ 32/ 28
1,160/ 1,060/ 930
Air flow(High/Med./Low) Running current 1 Power input 1 Auxiliary heater Power factor 1 Fan motor current 1 Model Dimensions WOHOD Weight Air direction Sound level(High/Med./Low) Fan speed(High/Med./Low)
Fan speed regulator Remote controller model
K /h
A
W
A(kW)
%
A
mm
kg
dB(A)
rpm
Electrical
data
Capacity
Fan motor
Special
remarks
Cooling
564/ 504/ 438
37/ 34/ 31
1,180/ 1,080/ 960
Single phase
230V,50Hz
0.3 40
58
0.3
RC0J30-KC
1,102O175O360
15
5
3
KM07E
Heating
594/ 528/ 462
38/ 35/ 31
1,230/ 1,120/ 1,000
Cooling
684/ 588/ 498
43/ 38/ 34
1,380/1,220/1,070
Single phase
230V,50Hz
0.3 40
58
0.3
RC0J30-KC
1,102O175O360
15
5
3
KM07E
Heating
708/ 618/ 528
43/ 39/ 34
1,420/ 1,270/ 1,120
SPECIFICATION
NOTE : Test conditions are based on ISO 5151.
Specifications and rating conditions of main electric parts
Cooling : Indoor Dry-bulb temperature 27:Wet-bulb temperature 19: Heating : Indoor Dry-bulb temperature 20: Refrigerant piping length (one way): 5m
1 Measured under rated operating frequency.
Outdoor Dry-bulb temperature 35:Wet-bulb temperature 24: Outdoor Dry-bulb temperature 7:Wet-bulb temperature 6:
3
3
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
COOLING
FUNCTION
43 43
SPL(dB(A))
LINE
High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
35 36
SPL(dB(A))
LINE
High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
37 38
SPL(dB(A))
LINE
High
FAN SPEED
HEATING
Heating : Dry-bulb temperature 20:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
INDOOR UNIT
CEILING
GRILLE
MICROPHONE
1.4m
NOISE CRITERIA CURVES
MLZ-KA25VA
MLZ-KA35VA
MLZ-KA50VA
4
4
Center of ceiling opening, suspension bolt pitch and grille are located in one position.
Center of ceiling opening, suspension bolt pitch and grille are located in one position.
Air outlet
(Top)
(Front)
Refrigerant
Pipe
Length of drain hose 540 Drain pipe
NOTE : Drain hose can be used by cutting it.
VP20
Liquid
[6.35
[9.52(MLZ-KA25/35) [12.7(MLZ-KA50)
Gas
Ceiling surface
Drain hose
500mm or less
Hole position for the installation of grille
Decline 1/100
Drain pipe VP20
How to connect drain pipe on indoor unit by lifting drain hose. w Drain hose can be used by cutting it.
Ceiling surface
Suspension bolt M10
Grille
414 Outer side of grille
384 Ceiling opening
308 Suspension bolt pitch
Electrical box
1051 Suspension bolt pitch
Air outlet
(Top)
Wireless remote controller
(Front)
(Right side)
Grille (MLP-440W)
Electrical box
Receiving section
Drain pipe VP20
Display and receiving section
Ceiling surface
Liquid pipe [6.35 (Flared)
Gas pipe MLZ-KA25/35 : [9.52 MLZ-KA50 : [12.7 (Flared)
Drain hose connecting part (drain pipe VP20)
Pipe cover
Drain pan
Outlet opening area
Drain hose connecting part
Pipe cover
308
Suspension bolt pitch
Drain hose
No gaps between the ceiling surface and grille
R6
CL
CL
0.04m
2
13.549.7
20
20
26
26
58
230
2 2
960
78
360
110
170
244
175
112
116
110
38
38
175
180 or more
60
25
48
[58
54.5
1051 Suspension bolt pitch
1160 Ceiling opening
1200 Outer side of grille
Outlet
2020
54.5
15
15
(51.6)
180
1102
1200
414
34
15
58 18
158
R6
31
10
0
466.5
466.5
166.5
0
172.4
81.8
173
166.5
OUTLINES AND DIMENSIONS
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
INDOOR UNIT
Unit : mm
5
5
INDOOR UNIT
MLZ-KA25VA MLZ-KA35VA
WIRING DIAGRAM
MLZ-KA50VA
6
6
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13 (sub)
Flared connection
Refrigerant pipe [9.52 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12 (main)
Indoor heat exchanger
Flared connection
Room temperature thermistor RT11
Indoor coil thermistor RT13 (sub)
Flared connection
Refrigerant flow in cooling Refrigerant flow in heating
Refrigerant pipe [12.7 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Indoor coil thermistor RT12,RT14, RT15 (main)
REFRIGERANT SYSTEM DIAGRAM
INDOOR UNIT
MLZ-KA25VA MLZ-KA35VA
MLZ-KA50VA
Unit : mm
7
7
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
CN211
Fuse (F11)
IC101
T11
VARISTOR (NR11)
Indoor electronic control P.C. Board
CN151
C111
R111
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
JR05
No modification
Cut off JR05
No modification
Cut off JR05
JR06 No modification No modification
Cut off JR06 Cut off JR06
JR06
JR05
SERVICE FUNCTIONS
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, both the P.C. boards of remote controller and the electronic control P.C. boards must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
shortened by short circuit of JPG and JPS.)
NOTE : For modification, take out the bat-
teries and press the OPERATE/STOP(ON/OFF) button 2 or 3 times at first. After modification, put back the batteries then press the RESET button.
J1
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
J2
Table 1
How to modify the electronic control P.C. board
Turn OFF the power supply before modification. Cut off JR05 and JR06 on the electronic control P.C. board according to the number of indoor unit as shown in Table 2. (Refer to 9-7.)
Table 2
NOTE : After modification, turn ON the power supply and with the remote controller headed towards the indoor unit, press the
OPERATE/STOP(ON/OFF) button. If one or two beeps is heard from the indoor unit, modification is completed correctly.
8
JR07
CN106
CN111
CN112 CN113
C111
T11
CN211
CN151
IC101
F11
R111
NR11
7-3. AUTO RESTART FUNCTION
Change dip switch SW3 setting according to the height of ceiling.
Dip switch SW3 Ceiling height
Normal
2.4 m or below
Increase airflow volume above 2.4 m and 2.7 m or below
How to change Dip switch (SW3) setting (Default setting is Normal)
1. Turn OFF the power supply for the air conditioner.
2. Remove electrical cover A and B.
3. Slide out electronic control P.C. board, and switch up or down Dip switch (SW3).
4. Put electronic control P.C. board back to the original position, and install electrical cover A and B.
NOTE:
To prevent damage of P.C. board due to static electricity, make sure to perform static elimination before setting.
Normal
Increase airflow volume
Dip switch SW3
Electronic control P.C. board
Electrical cover B
Electrical cover A
NOTE: When the ceiling is above 2.7 m, airflow volume may be insufficient even with the Dip switch (SW3) set to "increase airflow.
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The AUTO RESTART FUNCTION sets to work the moment power has restored after power failure. Then, the unit will restart automatically.
Operation
If the main power has been cut, the operation settings remain.
1 2 After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to release AUTO RESTART FUNCTION
1Turn off the main power for the unit. 2Solder the Jumper wire to JR07 on the indoor electronic control P.C. board. (Refer to 9-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed
after the indoor unit was operated with the remote controller.
If main power is turned OFF or a power failure occurs while AUTO
START/STOP timer is active, the timer setting is cancelled.
If the unit has been off with the remote controller before power failure, the
auto restart function does not work as the power button of the remote con­troller is off.
To prevent breaker tripping due to the rush of starting current, systematize
other home appliance not to turn on at the same time.
When some air conditioners are connected to the same supply system, if
they are operated before power failure, the starting current of all the com­pressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
7-4. P.C. BOARD MODIFICATION FOR CHANGING AIRFLOW VOLUME
9
8
(This diagram shows an overall view.)
.)
ra verall view.)
Open the front lid.
ON-TIMER button
CLOCK SET button
TIME SET buttons FORWARD button BACKWARD button
OFF-TIMER button
WIDE VANE button
RESET button
VANE CONTROL button
Signal transmitting section
Operation display section
Temperature buttons
OPERATE/STOP (ON/OFF) button
FAN SPEED CONTROL button
OPERATION SELECT button
ECONO COOL button
Indication of remote controller model is on back
MICROPROCESSOR CONTROL
MLZ-KA25VA MLZ-KA35VA MLZ-KA50VA
WIRELESS REMOTE CONTROLLER
Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
10
Loading...