Installation Manual
JY992D95701E
This manual contains text, diagrams and explanations which will guide the reader in the correct installation, safe use and operation of the F93*GOT-BWD-E and should be read and understood before attempting to install or use the unit. Further information can be found in the associated manuals list below.
Specifications are subject to change without notice
Guidelines for the Safety of the User and Protection of the F930GOT-BWD-E
This manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use that product in a safe and
co-ordinated manner in compliance to established safety practices.
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
Note:
the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
cause physical and property damage.
WILL
2) Indicates that the identified danger could
POSSIBLY
cause physical and property
damage.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application.

Associated Manuals

Manual Name Manual Number Description
F930GOT Series
|
(F93*GOT-BWD-E)
JY997D95701
Installation Manual
GOT-F900
~
OPERATION MANUAL (describes GT Designer2)
GOT-F900 Series
~
Operation Manual
GOT-F900 Series
~
Hardware Manual (connection diagram)
GT Designer2 Version1
|
Operating Manual
GT Designer2 Version1
|
Reference Manual
GT Designer
|
Operating Manual
JY997D09101
(separate volume)
JY992D94701
(separate volume)
JY992D94801
(separate volume)
(PDF files on CD-ROM included with product)
(PDF files on CD-ROM included with product)
Included with the screen creation software
JY992D68301
FX-PCS-DU/WIN-E
|
SOFTWARE MANUAL
~
Indispensable manual
|
Refer to the Programming manual (ΙΙ) or relevant hardware manuals for details concerning the applicable PLC.
Either manual is necessary.
(included with the
screen creation
software)
Describes the specifications, wiring, and installation of F930GOT Series graphic operation terminal. (hardware)
Describes the operation and use of the GOT­F900 Series graphic operation terminals and GT Designer2.
Describes the operation and use of the GOT­F900 Series graphic operation terminals, GT Designer and FX-PCS-DU/WIN-E.
Describes wiring and installation of the GOT­F900 Series graphic operation terminals.
Describes the operation of GT Designer2 (SW*D5C-GTD2-E) and data transfer to the GOT-900 Series.
Describes the specifications and setting of object functions in GT Designer2 (SW*D5C-GTD2-E).
Describes the operation of GT Designer (SW*D5C-GOTR-PACKE) and data transfer to the GOT-900 Series. (Refer to the help file)
Describes the operation of FX-PCS-DU/WIN-E screen creation software.

1. Introduction

2 4 V D C
9 ( 0 . 3 5 " )
2 3 ( 0 . 9 1 " )
2 3 ( 0 . 9 1 " )
1 3 6 ( 5 . 3 5 " )
8 5 ( 3 . 3 5 " )
7 5 ( 2 . 9 5 " )
5 ( 0 . 2 0 " ) o r l e s s
d )
b )
c )
f )
e )
g )
9 ( 0 . 3 5 " )
The F930GOT-BWD-E (hereafter called “GOT or F930GOT”) is to be mounted on the face of a control panel or operations panel, and connected to the programming port (CPU port) or the communication port (communication port) of a PLC. Various devices can be monitored and PLC data changed via the GOT screens. Several display screens are built-in to the GOT, and additional personalized screens can be created by the user.
1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs as well as a host of third party manufactured units. Further information can be found in GOT-F900 Series Hardware Manual.
2) PLC user programs can be downloaded, uploaded and monitored using programming software GX-Developer or FX­PCS/WIN-E on a personal computer via the GOT. Further information can be found in the GOT-F900 Series Operation Manual.
3) Display screens are created using the following software.
Software Name Version
GT Designer2 SWD5C-GTD2-E ( indicates version)
GT Designer SWD5C-GOTR-PACKE ( indicates version)
FX-PCS-DU/WIN-E

1.1 Product Lists

GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
GOT-F900 and GOT-A900 Series (for Windows) screen creation software. SW1-H edition of SW1D5C-GOTR-PACKE or later
GOT-F900 Series (for Windows) screen creation software. SW0PC-FXDU/WIN-E version 2.20 or later
P L C
P r o g r a m m i n g p o r t
G O T
Production Name Description
F930GOT-BWD-E Graphic operation terminal main unit
0
, FX0S, FX1S, FX0N, FX1N, FX2N
FX-50DU-CAB0
Communication cable (GOT ↔ CPU port in FX
2NC
or FX
series PLC) The connector on the GOT side is wired straight. Cable length is 3m (9' 10").
FX-50DU-CAB0/EN
Communication cable (GOT ↔ CPU port in FX
2NC
or FX
series PLC)
0
, FX0S, FX1S, FX0N, FX1N, FX2N
The connector on the GOT side is wired straight. Cable length is 3m (9' 10").
0
, FX0S, FX1S, FX0N, FX1N, FX2N
FX-50DU-CAB0-**M
Communication cable (GOT ↔ CPU port in FX
2NC
or FX
series PLC) The connector on the GOT side is wired straight. ** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"),
30M: 30m (98' 5")
FX-40DU-CAB
FX-40DU-CAB-**M
Communication cable (GOT ↔ CPU port in FX, FX The connector on the GOT side is wired straight. Cable length is 3m (9' 10").
Communication cable (GOT ↔ CPU port in FX, FX The connector on the GOT side is wired straight.
2C
, A or QnA series PLC)
2C
, A or QnA series PLC)
** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5")
QC30R2
Communication cable (GOT ↔ CPU port in Q series PLC) The connector on the GOT side is wired straight. Cable length is 3m (9' 10").
FX-232CAB-1 Data exchange cable (GOT ↔ Personal computer <9-pin D-sub>)
2NC
FX
-32BL Battery for Alarm history and current time data retention.
F9GT-30PSC Transparent protection sheet for F930GOT (5 pieces)
F9GT-30LTB Backlight for F930GOT
Caution
During abnormal communication (including cable breakages) when monitor is executed within the GOT, communication between the GOT and programmable controller CPU is interrupted. It is then impossible to operate switches or devices in the PLC through the GOT. Communication and normal operation resumes when the GOT system is correctly configured. DO NOT configure emergency stop or safety features to operate through the GOT, and be sure that there is no adverse consequences in the event of a GOT - PLC communications malfunction.
Note;
Do not lay signal cables near high voltage power cables or allow them to share the same trunking duct, otherwise, effects of noise or surge induction are likely to take please. Keep a safe distance of more than 100 mm from these wires.
Operate touch switches on the display screen by hand. DO NOT use excessive force, or attempt operate them with hard or pointed objects. The tip of a screw driver, pen or similar object for example may break the screen.

1.2 Dimensions and Each Part Name

2 4 V D C
9 ( 0 . 3 5 " )
2 3 ( 0 . 9 1 " )
2 3 ( 0 . 9 1 " )
1 3 6 ( 5 . 3 5 " )
8 5 ( 3 . 3 5 " )
7 5 ( 2 . 9 5 " )
5 ( 0 . 2 0 " ) o r l e s s
d )
b )
c )
f )
e )
g )
9 ( 0 . 3 5 " )
Dimensions: mm (inches) MASS (Weight): 0.3 kg (0.66 lbs)
Accessory: Mounting brackets, Tightening bolt (M3, 4 bolts),
Packing seal for dust and water resistance
a )
5 ( 0 . 2 0 " )
1 4 6 ( 5 . 7 5 " )
4 9 ( 1 . 9 3 " )
7 5 ( 2 . 9 5 " )
6 5 ( 2 . 5 6 " )
a) Display
b) Mounting bracket and tightening bolt
c) Communication ports
Por t Description
RS-422
RS-232C
RS-422 port for connecting PLC (including1:N connection) or communication (computer link) unit <9-pin D-sub>
RS-232C port for connecting either a personal computer, printer, bar-code reader or 1:N connection <9-pin D-sub>
d) Communication cable
e) DC power supply terminal (M3)
2NC
f) FX
-32BL battery
g) Packing seal

2. Specifications

2.1 General Specifications

Item Specifications
Operating Temperature 0 ~ 50 °C (32 ~ 122 °F)
Storage Temperature -20 ~ 60 °C (-4 ~ 140 °F)
Humidity 35 ~ 85% Relative Humidity, No condensation
Operating atmosphere
Vibration Resistance
- intermittent vibration
Vibration Resistance
- Continuous vibration
Shock Resistance
Noise Immunity 1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator
Dielectric Withstand Vol tag e
Insulation Resistance 5 MΩ > at 500 V DC, tested between power terminals and ground
Ground Grounding resistance of 100 Ω or less. (Class D)
Protection IP 65F
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electroconductive dust particles and must be no direct sunlight. (Same as for saving)
10 ~ 57 Hz: 0.075 mm Half Amplitude 57 ~ 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
10 ~ 57 Hz: 0.035 mm Half Amplitude
57 ~ 150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
2
147m/s
Acceleration,
3 times in each direction X, Y, and Z
500 V AC > 1 min, tested between power terminals and ground