Mitsubishi Electronics 9800A User Manual

Page 1
MITSUBISHI ELECTRIC AUTOMATION, INC
UNINTERRUPTIBLE POWER SUPPLY SYSTEM
9800A SERIES
OWNERS / TECHNICAL MANUAL
(For parallel operation possible model only.)
MITSUBISHI ELECTRIC 9800A SERIES UPS
ALN-H0776
Page 2
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
i
Preface
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 3
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
TABLE OF CONTENTS
LIST OF TABLES ............................................................................................... iii
LIST OF FIGURES ............................................................................................ iv
HOW TO USE THIS MANUAL ........................................................................... v
1.0 INTRODUCTION ....................................................................................... 1-1
1.1 GENERAL ..................................................................................................1-3
1.2 DEFINITIONS ............................................................................................ 1-4
1.3 OPERATION OVERVIEW ......................................................................... 1-5
1.4 SPECIFICATIONS .................................................................................... 1-12
2.0 OPERATION CONTROLS AND INDICATORS ........................................ 2-1
2.1 LED DISPLAY ........................................................................................... 2-2
ii
2.2 EPO BUTTON ........................................................................................... 2-2
2.3 LIQUID CRYSTAL DISPLAY ..................................................................... 2-3
2.4 EXTERNAL SIGNAL TERMINAL BLOCK ................................................. 2-8
2.5 EXTERNAL COMMUNICATION CONNECTOR ....................................... 2-12
3.0 INSTALLATION AND OPERATION ......................................................... 3-1
3.1 TRANSPORTATION AND INSTALLATION .............................................. 3-1
3.2 INSTALLATION PROCEDURE ................................................................. 3-1
3.3 PROCEDURE FOR CABLE CONNECTIONS ........................................... 3-2
3.4 OPERATING PROCEDURES ................................................................... 3-24
4.0 RESPONSE TO UPS FAILURE ................................................................ 4-1
5.0 PARTS REPLACEMENT .......................................................................... 5-1
6.0 FAULT CODES ......................................................................................... 6-1
7.0 WARRANTY & OUT OF WARRANTY SERVICE ..................................... 7-1
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 4
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
List of Tables
Table 1.1 Power Specifications ................................................................... 1-12
Table 1.2 UPS Module Information.............................................................. 1-12
Table 1.3 Detail of Specifications ................................................................ 1-13
Table 1.4 Rating of Contactor and Fuses .................................................... 1-14
Table 3.1 How to Transport and Install the System..................................... 3-1
Table 3.2 List of UPS Weights (lb.).............................................................. 3-1
Table 3.3 Maximum Permitted Fault Current............................................... 3-2
Table 3.4 Recommended Cable Sizes ........................................................ 3-5
Table 3.5 Crimp Type Compression Lug ..................................................... 3-6
iii
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 5
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
iv
List of Figures
Figure 1.1 Single Line Diagram-Normal Operation .................................................. 1-5
Figure 1.2 Single Line Diagram-Bypass Operation.................................................. 1-6
Figure 1.3 Single Line Diagram-Battery Operation .................................................. 1-7
Figure 1.4 UPS Parts Location ................................................................................ 1-8
Figure 1.5 UPS Parts Location (Continued)............................................................. 1-10
Figure 1.6 External I/F circuit PCB IOAU-04 .......................................................... 1-10
Figure 2.1 Operation/Display Panel ......................................................................... 2-1
Figure 2.2 Main Screen ........................................................................................... 2-3
Figure 2.3 Start/Stop Screen ................................................................................... 2-4
Figure 2.4 PIN Protection Screen ............................................................................ 2-4
Figure 2.5 Bypass Voltage Abnormal Message Screen........................................... 2-4
Figure 2.6 Measurement Screen ............................................................................. 2-4
Figure 2.7 Setup Screen.......................................................................................... 2-5
Figure 2.8 Log Select Screen .................................................................................. 2-5
Figure 2.9 Event Log Screen ................................................................................... 2-5
Figure 2.10 Battery Log Screen ............................................................................... 2-6
Figure 2.11 Main Screen (Battery Operation) .......................................................... 2-6
Figure 2.12 Measurement Screen (Battery Operation) .............................................. 2-6
Figure 2.13 Main Screen (Fault Indication) .............................................................. 2-7
Figure 2.14 Message Screen ................................................................................... 2-7
Figure 2.15 External Signal Terminal Block............................................................... 2-8
Figure 2.16 Control Wiring for External Contacts ...................................................... 2-10
Figure 2.17 Remote "Start" Contact Connections...................................................... 2-11
Figure 2.18 External communication connector......................................................... 2-12
Figure 3.1 UPS Terminal Designation .................................................................... 3-6
Figure 3.2 Diagram of input/output bus bars and terminal blocks .......................... 3-7
Figure 3.3 Diagram of Rectifier Cabinet & Inverter Cabinet Inter-connect ............. 3-19
Figure 3.4 Diagram of Power and Control Wire Connect (Parallel Connection) ...... 3-21
Figure 3.5 Operation Procedures: Start Up/Shut Down Procedure.......................... 3-24
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 6
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
v
How to use this Manual
This manual is designed for ease of use, giving the user easy and quick reference to
information.
This manual uses notice icons to draw attention to the user important information regarding the
safe operation and installation of the UPS. The notice icons used in this manual are explained
below, and should be taken into account and adhered to whenever they appear in the text of
this manual.
Warning: A warning notice icon conveys information provided to protect
the user and service personnel against hazards and/or possible equipment
damage.
Caution: A caution notice icon conveys information provided to protect
the user and service personnel against possible equipment damage.
Note: A Note notice icon indicates when the user should make a reference of
information regarding the UPS operation, load status and display status.
Such information is essential if Mitsubishi field service group assistance and
correspondence is required.
Safety Recommendations: If any problems are encountered while following this manual, Mitsubishi field service group assistance and correspondence is recommended.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 7
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-1
1.0 INTRODUCTION
Your Mitsubishi Uninterruptible Power System (UPS) is designed to provide many years of
reliable protection from power failure, brown-outs, line noise, and voltage transients. To ensure
optimum performance of the equipment, follow the manufacturer's instructions. This manual
contains descriptions required to operate the UPS. Please read this manual carefully and retain
it for future reference.
IMPORTANT SAFETY INSTRUCTIONS
RETAIN THESE INSTRUCTIONS
This manual contains important instructions for the 9800A SERIES Uninterruptible Power
Supply Systems that should be followed during installation and maintenance of the UPS and
batteries.
WARNING 1
Lethal voltages exist within the equipment during operation. Observe all
warning and cautions in this manual. Failure to comply may result in
serious injury or death. Obtain qualified service for this equipment as
instructed.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 8
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-2
WARNING 2
This UPS does not include a Bypass input circuit breaker (MCCB) to
protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be
field supplied and installed. Recommended Breaker (MCCB)'s
Specifications are as follows:
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac) Breaker (A)
100 480 120 150
600 96 125
150 480 180 225
600 144 200
225 480 271 350
600 217 275
300 480 361 500
600 289 400
375 480 451 600
600 361 500
500 480 601 800
600 481 600
750 480 902 1200
600 722 900
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC output MCCB shall be field supplied and installed. The
overcurrent protection device should be installed in the Battery cabinet and rated as
indicated in TABLE 1.4.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 9
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-3
1.1 GENERAL
The Mitsubishi 9800A SERIES UPS is designed to provide continuous and clean electrical
power to a critical load. Additionally the UPS monitors power conditions affecting the load.
In the event of an input power failure, the UPS will supply power to the critical load for the
specified battery time.
If the input power is not restored promptly, back up power from the UPS battery permits
the orderly shutdown of equipment supported by the UPS. The UPS is simple to start-up,
operate and maintain.
The 9800A SERIES UPS is available in seven kVA sizes-100, 150, 225, 300, 375, 500 and
750kVA. Specifications for each kVA model appear in Section 1.4. The principles of
operation described herein are applicable to all models.
This manual provides an overview of the 9800A SERIES components and their functions.
The appearance and purpose of operator controls and indicators is described with
procedures for operation, start-up, shutdown and basic maintenance included.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 10
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-4
1.2 Definitions
UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS
Module Cabinet and associated batteries that function as a system to provide continuous,
conditioned AC power to a load. This is sometimes referred to as the "System".
UPS MODULE CABINET - The metal enclosure which contains the Rectifier, the Inverter,
the Chopper, the Static Transfer Switch, the Internal Bypass line, the operator controls,
and the internal control system required to provide specified AC power to a load.
UPS MODULE - The Rectifier and Inverter assemblies which, under the direction of the
internal control system and operator controls, provide specified AC power to a load.
RECTIFIER - The UPS components which contain the equipment and controls necessary
to convert input AC power to regulated DC power required for battery charging and for
supplying power to the Inverter.
INVERTER - The UPS components which contain the equipment and controls necessary
to convert DC power from the Rectifier, or the battery, to AC power required by the critical
load.
CHOPPER - The UPS components which contain the equipment and controls necessary
to charge the battery and supply power to the Inverter from battery.
STATIC TRANSFER SWITCH - The device which connects the critical load to the bypass
line when the UPS module cannot supply continuous power.
BYPASS LINE - The line which conducts electricity directly from the input power source to the
critical load during Maintenance or whenever the UPS is not completely operational.
INPUT POWER - Power provided by the electrical utility company, or auxiliary generator,
which is connected to the UPS for supplying the critical load.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 11
put
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-5
1.3 Overview
The UPS provides two power paths between the utility source and the critical load.
Figure 1.1 shows the path for normal operation, with the load powered from the inverter.
Figure 1.2 shows the path for bypass operation, with the load supplied through the static
bypass line.
A) Normal operation: Load power supplied by each system UPS inverter.
Figure 1.1 Single Line Diagram - Normal Operation: Load powered by UPS inverters
AC Bypass
In
AC input
CB
User supplied MCCB
CB1
RECTIFIER
CB3
INVERTER
Static Transfer
Switch
52S
Output
52C
CB2
Power Flow
Not in Use
UPS ModuleBattery cabinet
During normal operation, the path through the UPS inverters is used to power the load.
Referring to Figure 1.1: For each system UPS, the Input AC power is converted to DC by
the Rectifier. DC power is utilized to charge the UPS battery and to provide power to the
Inverter. The Inverter converts the DC power to clean AC power to supply the critical load.
The conversion - inversion process eliminates any voltage transients or fluctuations
existing in the input power before it reaches the critical load.
The power drawn by the critical load is equally shared between all system UPS.
In the event of a UPS module failure, the critical load power will be continually supplied
and shared by all other system UPS.
In the event of a load overcurrent, all system UPS will transfer to bypass without
interruption to the critical load.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 12
put
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-6
The Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field
supplied and field installed. (See WARNING 2 on page 1-2)
B) Bypass Operation: Load Power supplied through each system UPS internal static
bypass line.
FIGURE 1.2 Single Line Diagram - Bypass Operation: Load fed through Internal static
bypass line.
AC Bypass
In
AC input
CB
User supplied MCCB
CB1
Static Transfer
Switch
CB3
RECTIFIER
INVERTER
CB2
52S
Output
52C
Power Flow
Not in Use
UPS Module Battery cabinet
Referring to Figure 1.2: The Internal Static Bypass line is a Hard wired line through CB3
and contactor 52S which supplies the critical load with unconditioned input power.
Each system UPS internal static bypass line will equally share the power supplied to the
critical load.
The internal static bypass line will route power to the critical load while the UPS module is
de-energized during Start-up and before the system is fully operational.
Bypass operation will occur In the event of a load overcurrent, with all system UPS
transferring to bypass without interruption to the critical load.
The internal control system determines the operation of the two paths, with the load
powered from the inverter being the normal operation.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 13
put
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
C) Battery operation: Load Power supplied by each system UPS battery and inverter.
FIGURE 1.3 Single Line Diagram - Battery Operation
1-7
AC Bypass
In
AC input
CB
User supplied MCCB
CB1
Static Transfer
Switch
CB3
RECTIFIER INVERTER
CB2
52S
Output
52C
Power Flow
Not in Use
UPS Module Battery cabinet
Referring to Figure 1.3: In the event of AC input source failure or interruption, each
system UPS rectifier will de-energize and each UPS battery will immediately discharge
and supply DC power to the Inverter to maintain continuous AC power to the load. This
operation will continue until:
a) The battery capacity expires and the inverter turns off, or
b) Input power is restored after which the rectifier will power the inverter and critical load
and simultaneously recharge the batteries.
A fully charged battery will provide power for the specified time at the rated load, or longer,
at a reduced load.
When power is restored after a low battery shutdown, each system UPS Rectifier
automatically restarts operation, recharges the batteries and the Inverter is automatically
restarted without operator intervention. Load is automatically assumed by the inverter
without operator intervention.
The power drawn by the load is equally shared between all system UPS during battery
operation.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 14
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
FIGURE 1.4-a UPS Parts Location (100kVA, 150kVA, 225kVA)
Page Number:
1-8
AC capacitors
UPS module FRONT VIEW
Inverter Chopper unit
DC
Rectifier unit
capacitors
1. CPM
52S
CB3
CB1
2. External I/F circuit PCB IOAU-04
52C
3. Grounding Bar
FIGURE 1.4-b UPS Parts Location (300kVA,375kVA)
3. Grounding
UPS module FRONT VIEW
Bar
CB1
CB3
AC capacitors
Rectifier unit
52S
52C
2. External I/F circuit PCB IOAU-04
1.CPM
Inverter Chopper unit
DC capacitors
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 15
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
FIGURE 1.4-c UPS Parts Location (500kVA)
Page Number:
1-9
4. Grounding Bar
CB1
Rectifier unit
AC capacitors
1.CPM
UPS module FRONT VIEW
2. External I/F circuit PCB
IOAU-04
52S
AC capacitors
52C
CB3
Capacitors
DC
Inverter Chopper unit
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 16
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
FIGURE 1.4-d UPS Parts Location (750kVA)
Page Number:
1-10
5. Grounding Bar
52S
CB1
1.CPM
CB3
AC capacitors
UPS module FRONT VIEW
3. External I/F circuit PCB
IOAU-04
AC capacitors
52C
Rectifier unit
DC Capacitors
Inverter Chopper unit
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 17
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
FIGURE 1.5 UPS Parts Location (Continued)
UPS module REAR OF FRONT DOOR (Right side)
6
INVERTER
START
|
SYNC.LED
INVERTER
STOP
Page Number:
1-11
7
|
FIGURE 1.6 External I/F circuit PCB IOAU-04
| FAULT RESET
8
|
MAINTENANCE
SWITCH
9
|
TEST
SWITCH
10
4. External contact signal terminal
|
BOOT
SWITCH
11
IOAU-04
5. RS232C D-sub connector
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 18
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-12
Description of Figures 1.4, 1.5, and 1.6:
1. CPM - Circuit protector for control power supply.
2. Switches on IFGR-G board : FOR SERVICE PERSONNEL ONLY (FIGURE 1.6):
- (4) External contact signal terminal
- (5) RS232C communication connector
3. Grounding bar (G)
4. External contact signal terminal block - Terminal block to connect contact signal
input/output lines to and from the external devices. Refer to Figure 2.15 section 2.4 for
details.
5. RS232C communication connector - Refer to Figure 2.18 section 2.5 for details.
6. Inverter start switch - This switch is used to transfer the UPS from static bypass to
inverter during maintenance purposes. Transfers will lock-out if the bypass voltage is
more than +12%,-12% of nominal.
* Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at
the time of asynchronous operation.
7. “INVERTER STOP” switch - This switch is used to transfer the UPS from inverter to
static bypass during maintenance purposes. Do not operate it under normal operation.
Transfers will lock-out if the bypass voltage is more than +12%,-12% of nominal.
* Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at
the time of asynchronous operation.
8. “FAULT RESET” switch (FOR SERVICE PERSONNEL ONLY) - This switch resets errors
resulting from alarm conditions. (Do not operate this switch while inverter and converter are
in operation.)
9. Maintenance (Set) button (FOR SERVICE PERSONNEL ONLY) - This switch sets the
UPS menu parameters.
10. “Test mode” switch (FOR SERVICE PERSONNEL ONLY) - This switch changes system
operation to the test-mode. (This switch should not be operated by personnel other than
an Authorized Service Engineer).
11. “BOOT” switch (FOR SERVICE PERSONNEL ONLY) - This switch boots the processor
in the main control circuit resulting from alarm conditions. (Do not operate this switch
while inverter and converter are in operation).
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 19
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-13
1.4 Specifications
The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.
TABLE 1.1 Power Specifications
Rated output
Power
100kVA / 80kW
150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
500kVA / 450kW
750kVA / 675kW
Input voltage
3 phase / 3 wire
480V
480V
480V
480V
480V
480V
480V
Bypass input voltage
3 phase / 4 wire
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
Output voltage
3 phase / 3 or 4 wire
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
TABLE 1.2 UPS Module Information
UPS
[kVA]
CABLE
ENTRY
WIDTH
[in / mm]
DEPTH
[in / mm]
HEIGHT
[in / mm]
WEIGHT
[lb./ kg]
HEATING
[kBTU/h]
100 BOTTOM 43.3 / 1100 29.8 / 758 79.7 / 2025 2100 / 950 22.0
150 BOTTOM 47.2 / 1200 29.8 / 758 79.7 / 2025 2820 / 1275 33.0
225 BOTTOM 55.1 / 1400 29.8 / 758 79.7 / 2025 3310 / 1500 45.0
300 TOP 76.8 / 1950 37.7 / 958 79.7 / 2025 4990 / 2260 68.0
375 TOP 76.8 / 1950 37.7 / 958 79.7 / 2025 5250 / 2380 84.0
500 TOP 114.2 / 2900 37.7 / 958 79.7 / 2025 6930 / 3140 98.0
750 TOP 129.9 / 3300 49.5 / 1258 79.7 / 2025 9655 / 4380 136.1
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 20
TABLE 1.3 Detail of Specifications
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
1-14
Rated Output kVA 100 150 225 300 375 500 750 Rated Output kW 80 120 180 270 338 450 675
AC INPUT
Configuration 3 phase, 3 wire Voltage 277/480 V, 346/600 V +15% to -15% Frequency 60 Hz +/-5% Reflected Current THD 6% max. at 100% load; 9% max. at 50% load
STATIC BYPASS INPUT
Configuration 3 phase, 4 wire Voltage 277/480 V, 346/600 V +/-10% Frequency 60 Hz
BATTERY
Type Lead Acid Ride Through Application Specific Nominal Voltage 480 Vdc Minimum Voltage 400 Vdc Number of Cells 240
AC OUTPUT
Configuration 3 phase, 4 wire Voltage 277/480 V, 346/600 V Voltage Stability
+/-1%
Frequency 60 Hz Frequency Stability
+/-0.05% in free running mode
Power Factor 0.8 nominal 0.9 nominal Power Factor range 0.8 to 1.0 lagging (within output kW rating) Voltage THD 2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
Transient Response
+/-2% maximum at 100% load step +/-1% maximum at loss/return of AC power +/-5% maximum at load transfer to/from static bypass
Transient Recovery Less than 20ms Voltage Unbalance 1% maximum at 100% unbalanced load Phase Displacement 1deg. maximum at 100% load Inverter Overload 125% for 10 minutes; 150% for 1 minute System Overload 1000% for 1 cycle
(with bypass available)
500% for 1 cycle
(with bypass available)
Bypass Overload 125% for 10 minutes Withstand Rating 65kA* * : with optional fuse
ENVIRONMENTAL
Cooling Forced Air Operating Temperature
32F to 104F ( 0゚C to 40゚C). Recommended : 68F to 86゚F ( 20C to 30゚C)
Relative Humidity 5% ~ 95% Non Condensing Altitude 0 to 9000 feet No Derating Location Indoor (free from corrosive gases and dust) Paint Color Munsell 5Y7/1 (Beige)
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 21
MITSUBISHI ELECTRIC
TABLE 1.4 Rating of Contactors and Fuses
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-15
NUMBER APPLICATION
100kVA 150kVA 225kVA 300kVA 375kVA 500kVA 750kVA
480V 600V 480V 600V 480V 600V 480V 600V 480V 600V 480V 600V 480V 600V
F
U S E S
CB1 AC input contactor 135A 200A 350A 450A 660A 660A 910A
CB2 Battery disconnect
breaker
CB3 STS contactor 135A 260A
52C Inverter output
contactor
52S Bypass contactor 135A 200A 350A 450A 450A 660A 910A
88RC Control circuit contactor 90A
FCU, FCV, FCW AC input fuse 200A/660V 250A/660V 315A/660V
FIU, FIV, Inverter output fuse 250A/660V 200A/660V 315A/660V 315A/660V 315A/660V 315A/660V 315A/660V
FUA, FUB, FUC Control power fuse 30A/600V
(OPTION)
FSU, FSV, FSW
FZS1, 2, 3 Bypass input ZNR fuse 16A/500V
FBS1, 2, 3 Control power fuse 10A/600V
FZR1, 2, 3 AC input ZNR fuse 16A/500V
FPU, FPV, FPW Parallel control
Bypass input fuse 200A/
circuit fuse
400A 600A 800A 1200A 1600A (MEAU) (MEAU)
135A 200A 350A 450A 450A 660A 910A
660V
- 315A/ 660V
- 250A/
OUTPUT CAPACITY OF EQUIPMENT
660V
- 250A/ 660V
10A/600V
- 315A/ 660V
- 315A/ 660V
*Rating would be changed.
315A/
660V
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 22
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
2.0 OPERATOR CONTROLS AND INDICATORS
The 9800A Series operator controls and indicators are located as follows:
Circuit breakers and contactors: Inside the module
UPS status indicators: Outside of front door
FIGURE 2.1 Operation/Display Panel (Front panel)
3
2
1
LOAD ON
INVERTER
BATTERY
OP.
LOAD ON
BYPASS
LCD
FAULT
UPS
FAULT
Page Number:
2-1
4
5
6
7
EMRG.STOP
540V
8
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 23
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
2.1 LED Display
1) Load on inverter [ LOAD ON INVERTER ](green)
Illuminates when power is supplied from inverter to the critical load.
(Indicates the state of inverter transfer switch "52C".)
2) Battery operation [ BATTERY OP. ](yellow)
Illuminates when power is supplied from batteries following a power failure.
3) Load on bypass [ LOAD ON BYPASS ](green)
Illuminates when power is supplied to load devices by static bypass.
(Indicates the state of bypass transfer switch "52S".)
4) Overload [ OVERLOAD ](red)
Illuminates in overload condition.
5) LCD fault [ LCD FAULT ](red)
Illuminates when an error occurs.
Page Number:
2-2
6) UPS fault [ UPS FAULT ](red) [Annunciator: intermittent or constant tones]
Illuminates when an error occurs in the system. In this case, the details of the error are
indicated on the display panel.
2.2 EPO button (Emergency Power Off button) (7)
When activated, the Emergency Power Off (EPO) function shuts down the UPS module.
The critical load will lose power and also shutdown. The EPO function can be performed
both locally or remotely.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 24
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-3
2.3 Liquid Crystal Display (8)
The Liquid Crystal Display (LCD) panel indicates power flow, measured values,
operational guidance, data records and error messages. The LCD panel has a back-light
which facilitates viewing in different ambient lighting conditions. The LCD will automatically
clear and turn off, if the screen is not activated within 3 minute period. The LCD is turned
back on when it is touched again. The ERROR indicator is cleared after 24 hours and can
be reproduced by pressing any key on the panel.
2.3.1 Menu
A) MAIN MENU (FIGURE 2.2)
The LCD panel indicates power flow and measured values, while also operating the
start/stop function. The LCD panel also allows the user to verify the status and operation
of the UPS Module.
FIGURE 2.2 Main screen
540V
The following will be displayed when the START/STOP key on the LCD panel is
pressed:
1) Start/Stop screen (FIGURE 2.3)
The display indicates the start and stop operations for the UPS system. If this
operation is PIN protected, the user is required to enter the security PIN before the
screen can be accessed. Refer to (FIGURE 2.4).
When in remote mode, the message “REMOTE operating model” will appear on this
Screen. The user cannot operate the start and stop functions without changing the
setup from remote mode to local mode.
When bypass voltage is abnormal, the message “Bypass voltage abnormal” will appear.
-Start: When the bypass voltage is abnormal, the LCD asks the operator if an
interrupted transfer is acceptable (Load may be lost). (FIGURE 2.5)
-Stop: When the bypass voltage is abnormal, the user cannot transfer from inverter
to bypass line.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 25
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-4
FIGURE 2.3 Start/Stop screen
FIGURE 2.4 PIN protection screen FIGURE 2.5 Bypass voltage abnormal
message screen
B) MEASUREMENT MENU (FIGURE 2.6)
This screen shows details of measured values. Bypass voltage, input voltage, output
line to line voltage and output frequency are displayed. Output currents are displayed as
RMS values.
FIGURE 2.6 Measurement screen
540V
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 26
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-5
C) SETUP MENU (FIGURE 2.7)
This screen prompts the user to select: (a) whether the start & stop operation will be
performed by local or remote operation; (b) date & time adjustment; (c) battery
equalizing charge. The battery equalizing charge operation key will appear when battery
equalizing charge is set up (Setup is based on battery type).
FIGURE 2.7 Setup screen
D) LOG MENU (FIGURE 2.8)
This menu shows operation / failure and battery discharge records.
FIGURE 2.8 Log select screen
1.) Event log (FIGURE 2.9)
Operation and failure records are indicated. Maximum of 50 events are displayed.
FIGURE 2.9 Event log screen
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 27
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
2.) Battery log (FIGURE 2.10)
This screen displays the cumulative battery discharging record.
FIGURE 2.10 Battery log screen
2.3.2 INPUT POWER FAILURE
During an Input Power Failure, the UPS inverter will be powered by the UPS batteries.
9800A SERIES UPS
Page Number:
2-6
The following will be displayed on the main and measurement screen (Indication of
battery operation and remaining battery life).
FIGURE 2.11 Main screen FIGURE 2.12 Measurement screen
(Battery operation) (Battery operation)
480V
480V
The LCD will display a battery low voltage message when the battery capacity is near
depletion. The End of Battery Discharge announcement is displayed when the battery
end voltage is reached. At this time, the inverter will perform an electronic shutdown to
prevent battery loss of life typical from extreme deep discharge conditions. When the
input power is restored, the inverter will automatically restart to power the load, and
the batteries will be simultaneously recharged. The End of Battery announcement is
shown at the bottom of the screen.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 28
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
2.3.3 FAULT INDICATION (FIGURE 2.13)
MESSAGE and “SILENCE ALARM buttons will appear on the main menu when
UPS failure condition has occurred.
FIGURE 2.13 Main screen (Fault indication)
Page Number:
2-7
540V
The following will be displayed when the message key on the LCD panel is pressed.
1)
Message (FIGURE 2.14)
The display shows a fault code, the description of the fault and a guidance of what
action is to be taken by the user. A maximum of 10 faults is displayed at one time. If
an input power failure occurs during a fault condition, the fault indication and input
power failure announcement are alternatively displayed at 5 second intervals.
FIGURE 2.14 Message screen
2) Silence alarm
This key will appear when a failure occurs. The audible alarm (announcing the failure)
can be silenced by pressing this key.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 29
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-8
2.4 External Signal Terminal Block
The UPS is equipped with a series of input/output terminals for external annunciation of
alarms and for remote access of certain UPS functions. The layout of terminals is shown in
Figure 2.15. with a functional description of the input/output port presented. OUT1 to
OUT6 are user programmable, but are factory default set being also shown in Figure 2.15.
FIGURE 2.15-1 External Signal Terminal Block (NEC Class2)
TN1
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
2
4
6
8
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
FAULT
OUT1: LOAD ON BYPASS
OUT2: LOAD ON INVERTER
OUT3: BATTERY OPERATION
OUT4: RECTIFIER OPERATION
OUT5: BATTERY LOW VOLTAGE
OUT6: OVERLOAD
OUT7: SPARE
OUT8: SPARE
OUT9: SPARE
UPS
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 30
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-9
FIGURE 2.15-2 External Signal Terminal Block (NEC Class2)
TN2
10
12
14
16
18
20
22
24
26
28
30
2
4
6
8
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
IN1: REMOTE INVERTER START
IN2: REMOTE INVERTER STOP
IN3: BATTERY TEMP. HIGH
IN4: POWER DEMAND
IN5: SPARE
IN6: SPARE
IN7: SPARE
IN8: SPARE
IN9: SPARE
REMOTE EPO
CB2 UVT
CB2 AX
52L AX
52C AX
(User supplied dry contact)
(User supplied sensor and dry contact)
(User supplied dry contact)
(User supplied dry contact)
UPS
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 31
N
MITSUBISHI ELECTRIC
A) Output Contacts (for external alarm annunciation)
Output contacts consist of form “A” dry type contacts. Rated capacity of all output
contacts is NEC Class2 (30Vdc/1Adc). All dry contacts should be operated at their
rated values or lower. Figure 2.16 illustrates a typical installation. The external relay
can also be a lamp, LED, computer, etc.
FIGURE 2.16 Control Wiring for External Contacts
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-10
UPS Cabinet
Terminal
Relay Contact
Details of output alarm contacts : TN1
Terminals 1 to 2
Terminals 5 to 6
Terminals 9 to 10
, 3 to 4 "UPS failure" contact
Activated when a major fault has occurred with the system.
, 7 to 8 "Load on Bypass" contact (OUT1)
Activated when the power is supplied from the static bypass input.
, 11 to 12 "Load on Inverter" contact (OUT2)
Activated when the power is supplied by the inverter.
Terminal
User supplied
External to UPS Cabinet
Relay
Coil
EC Class 2
Power Source
Terminals 13 to 14
Activated when the battery is operating following an AC power failure.
Terminals 17 to 18
Activated when the rectifier is operating.
Terminals 21 to 22
Activated when the battery voltage drops below discharge end voltage level
during inverter operation (i.e. During AC fail condition).
Terminals 25 to 26
Activated when an overload has occurred to the system.
Terminals 29 through 40
, 15 to 16 "Battery Operation" contact (OUT3)
, 19 to 20 "Rectifier Operation" contact (OUT4)
, 23 to 24 "Battery Low Voltage" contact (OUT5)
, 27 to 28 "Overload" contact (OUT6)
"Spare" contact (OUT7 through OUT9)
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 32
t
y
y
t
t
y
t
MITSUBISHI ELECTRIC
NOTE: The UPS is equipped with a selectable output contact feature. The
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-11
above alarms are the default settings. Contact MITSUBISHI
ELECTRIC AUTOMATION, INC. for setup information.
B) Input Contacts (for remote access of UPS)
External contacts are provided by the user of the UPS system. Terminal voltage at the
UPS is 24Vdc. Provide external dry contact accordingly.
NOTE:
Do not apply voltages to remote access input terminals. Damage to
UPS may result.
Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to
the remote start/stop terminals, the same wiring arrangement is used for emergency
stop; battery liquid low; and battery temperature high.
FIGURE 2.17 Remote "Start" Contact Connections
UPS Cabine
Rela
External to UPS Cabine
Star
Coil
Common
24 VDC
Relay Coil current : 8.3mA
Details of input contacts for remote access : TN2
Terminals 1 to 2 Remote "Inverter Start" input terminal (IN1)
Used to start inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.
Terminals 3 to 4 Remote "Inverter Stop" input terminal (IN2)
Used to stop inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.
Terminals 5 to 6 "Battery Temp. High" contact input (IN3)
Input fed by a thermocouple that monitors battery temperature. The
Use Momentar
User supplied
Star Switch
0.5S - 4S ON OFF
Switches Onl
converter float voltage level is reduced for battery over-temperature
conditions. External thermocouple is user supplied
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 33
)
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
2-12
Terminals 7 to 8 "Power Demand Command" contact input (IN4)
This contact is used to control the input power. Power demand is turned ON
when the contact is closed, and power demand is turned OFF when the
contact is open.
Terminals 9 to 18 "Spare" contact input (IN5 through IN9)
Terminals 19 to 20 "Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.
NOTE:
The UPS is equipped with a selectable output contact item. The above
items are the default settings. Contact MITSUBISHI ELECTRIC
NOTE :
AUTOMATION, INC. for setup information.
In all cases, a switch having a protective cover is recommended in
order to reduce the possibility of accidental operation.
2.5 External communication connector
This is an RS232C port for “DiamondLink”* monitoring software.
The layout of connector is shown in Figure 2.18.
FIGURE 2.18 External communication connector (NEC Class2)
D-SUB 9Pin (male
Pin 1. : Not used
Pin 2. RXD : Receive data
6 7 8 9
1 2 3 4
Pin 3. TXD : Transmit data
Pin 4. : Not used
Pin 5. GND : Signal ground
Pin 6. : Not used
Pin 7. : Not used
Pin 8. : Not used
Pin 9. : Not used
PCB IOAU-04
* Consult MITSUBISHI ELECTRIC AUTOMATION, INC. for details on
DiamondLink”
monitoring software and its capabilities.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 34
3
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
3.0 INSTALLATION AND OPERATION
3.1 Transportation and Installation
TABLE 3.1 How to transport and install the system
Transportation Installation
Page Number:
-1
Transport unit with forklift.
Carry with overhead crane using
eyebolts provided.
Using the pre drilled holes (4 - 24) in the
UPS channel base, anchor the unit using
appropriate hardware. (Not provided)
Note :
Do not transport in a horizontal position. Cabinets must be maintained
upright within +/- 15° of the vertical during handling.
3.2 Installation Procedure
UPS Capacity (kVA) 100 150 225 300 375 500 750
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights.
TABLE 3.2 List of UPS weights
Weight (lb.) 2100 2820 3310 4990 5250 6930 9655
B) Minimum clearance required for ventilation
Right side
Left side
Back side
Top side
25 mm (not required when sidecars are used)
25 mm (not required when sidecars are used)
0.0 mm
600 mm (for air flow)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
1000 mm 100kVA, 150kVA, 225kVA
1075 mm 300kVA, 375kVA, 500kVA, 750kVA
Sides
Rear
0.0 mm
0.0 mm
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 35
3
MITSUBISHI ELECTRIC
D) External Battery Supply
Please refer to the following when installing and maintaining batteries:
1. The customer shall refer to the battery manufacturer's installation manual for
battery installation and maintenance instructions.
2. The maximum permitted fault current from the remote battery supply, and the
DC voltage rating of the battery supply over-current protective device are
shown in Table 3.3.
TABLE 3.3 Maximum Permitted Fault Current
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
-2
UPS CAPACITY
(kVA)
DC VOLTAGE
RATING (V)
MAXIMUM PERMITTED
FAULT CURRENT (A)
100 480 25000
150 480 25000
225 480 25000
300 480 25000
375 480 25000
500 480 25000
750 480 25000
3.3 Procedure for Cable Connections *
i. Confirm the capacity of the UPS being installed. Identify the input/output power
terminal blocks as shown in the appropriate Figures 3.1 through 3.2-a~g,Figure 3.3. and
Figure 3.4a~c. (Note *
Figure 3.4a~c shows power and control wire for parallel system.)
ii. Connect the internal control wire and power wire.
(1) Control wire Inter-connect
1. CB2 Auxiliary to terminal 1, 2.
2. CB2-UVT to terminal 3, 4.
3. Parallel configuration Wiring (Refer to Figure 3.4a~c )
- CLC CB 52L1-AX, 52L2-AX …. 52Ln-AX to UPSn TB1 (1,2 terminals)
- Parallel Control CN92, CN93, In, Out cables between UPS modules
(2) Power wire Inter-connect
a.) From user’s distribution panel
1. X1 (A-phase) to A bus bar in UPS rectifier section.
2. X2 (B-phase) to B bus bar in UPS rectifier section.
3. X3 (C-phase) to C bus bar in UPS rectifier section.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 36
3-3
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
b.) DC Input to UPS
1. Positive cable to BP bus bar in UPS rectifier section.
2. Negative cable to BN bus bar in UPS rectifier section.
c.) From UPS AC Output Terminals to Critical Load Cabinet (CLC) UPS AC
Output Terminals (Refer to Figure 3.4a~c)
iii. Connect the grounding conductor from the input service entrance to the UPS ground
bar.
iv. Two (2) sources feeding the UPS
:
(1) Connect the rectifier input power cables from the input service entrance to the
rectifier input power terminals, identified as A, B, C in Figures 3.2-a~g. Input
cables must be sized for an ampere rating larger than the maximum input drawn
by the rectifier. (Refer to equipment nameplate for current ratings.) Confirm that
an external bypass input circuit breaker (MCCB) is installed (refer to WARNING 2,
page 1-2). Connect the bypass input power cables from the input service entrance
to the bypass input power terminals, identified as A40, B40, C40 and N40 in
Figures 3.2-a~g. Bypass input cables must be sized for an ampere rating larger
than the maximum output current capacity of the UPS. Refer to Table 3.4 for
recommended cable sizes.
(2) Connect the external signal terminal block as desired. Refer to section 2.4 and
2
Figure 2.15 for functional description. 2mm
, or less, shielded conductor is
recommended.
v. One (1) source feeding the UPS
:
(1) Confirm that an external input circuit breaker sized to protect both the rectifier
input and the bypass line is installed. (Refer to equipment nameplate for current
ratings.) Connect the bypass input power cables from the input service entrance
to the bypass input power terminals, identified as A40, B40, C40 and N40 in
Figures 3.2-a~g Input cables must be sized for an ampere rating larger than the
maximum current capacity of the UPS. Refer to Table 3.4 for recommended cable
sizes.
(2) Using adequately sized conductors and referring to the appropriate figure
identified in Figures 3.2-a~g, connect jumper bypass terminals A40, B40, C40 to
rectifier input power terminals A, B, C as identified in Figures 3.2-a~g.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 37
3
MITSUBISHI ELECTRIC
(3) Connect the external signal terminal block as desired. Refer to section 2.4 and
Figure 2.15 for functional description. 2mm
recommended.
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
2
, or less, shielded conductor is
Page Number:
-4
NOTES:
1. Confirm that all UPS internal contactors (breakers) "CB1", "CB2", and
"CB3" are open before energizing UPS.
2. UPS power terminals are supplied with stud type fittings. It is recommended
that compression lugs be used to fasten all input/output power cables.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 38
3-5
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
TABLE 3.4 Recommended Cable Sizes
kVA
Capacity
100kVA 480V 480V 1 AWG
150kVA 480V 480V 3/0 AWG
225kVA 480V 480V 300 MCM
300kVA 480V 480V 2x4/0 AWG
375kVA 480V 480V 3x300 MCM
500kVA 480V 480V 3x250 MCM
600V 600V 2x350 MCM
750kVA 480V 480V 3x500 MCM
Input
Voltage
600V 600V 2 AWG
600V 600V 2/0 AWG
600V 600V 250 MCM
600V 600V 2x3/0 AWG
600V 600V 2x4/0 AWG
600V 600V 3x350 MCM
Output
Voltage
Input Side * 1, 2 Output Side * 1, 2 Bypass Side * 1, 2 DC Input Side * 1, 2
Cable
Size
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
or larger
Torque
in. lbs
200 - 269
in. lbs
200 - 269
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 – 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
Cable
Size
1 AWG
or larger
2 AWG
or larger
3/0 AWG
or larger
2/0 AWG
or larger
350 MCM
or larger
250 MCM
or larger
2x3/0 AWG
or larger
400 MCM
or larger
2x250 MCM
or larger
2x3/0 AWG
or larger
2x400 MCM
or larger
2x300 MCM
or larger
3x500 MCM
or larger
3x350 MCM
or larger
Torque
in. lbs
200 - 269
in. lbs
200 - 269
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
2x250 MCM
2x400 MCM
2x300 MCM
3x500 MCM
3x350 MCM
*1 - The cables must be selected to be equal to or larger than the sizes listed in the table. *2 - Voltage drop across power cables not to exceed 2% of nominal source voltage. *3 - Allowable ampere-capacities based on 90C insulation at ambient temperature of 30゚C. Not more than 3 conductors in a raceway without de-rating.
Note: Copper conductors assumed.
Cable
Size
1 AWG
or larger
2 AWG
or larger
3/0 AWG
or larger
2/0 AWG
or larger
350 MCM
or larger
250 MCM
or larger
2x3/0 AWG
or larger
400 MCM
or larger
or larger
2x3/0 AWG
or larger
or larger
or larger
or larger
or larger
Page Number:
Torque
in. lbs
200 - 269
in. lbs
200 - 269
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
Cable
Size
3/0 AWG
or larger
3/0 AWG
or larger
350 MCM
or larger
350 MCM
or larger
2x4/0 AWG
or larger
2x4/0 AWG
or larger
2x400 MCM
or larger
2x400 MCM
or larger
3x350 MCM
or larger
3x350 MCM
or larger
3x500 MCM
or larger
3x500 MCM
or larger
5x500 MCM
or larger
5x500 MCM
or larger
Torque
in. lbs
200 - 269
in. lbs
200 - 269
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 39
3-6
put
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
TABLE 3.5 Crimp Type Compression Lug
Page Number:
WIRE
SIZE
WIRE
STRAND
RECOMMENDATION CRIMP TOOL REQUIRED
BURNDY TYPE Y35 OR Y46
(CODE) CLASS VENDOR CAT. NO. COLOR KEY DIE INDEX
1 B
I
1/0 B
I
2/0 B
I
3/0 B
I
4/0 B
I
250 MCM B
I
300 MCM B
I
350 MCM B
I
400 MCM B
I
500 MCM B
I
BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY BURNDY
ILSCO BURNDY
YA1C
CRA-1L
YA25-LB
YA25
CRA-1/OL
YA25-LB
YA26
CRA-2/OL
YA27-LB
YA27
CRB-3/OL
YA28-LB
YA28
CRB-4/OL
YA29-LB
YA29
CRA-250L
YA30-LB
YA30
CRA-300L
YA32-LB
YA31
CRA-350L
YA34-LB
YA32
CRA-400L
YA36-LB
YA34
CRA-500L
YA38-LB
GREEN GREEN
--­PINK PINK
---
BLACK BLACK
---
ORANGE ORANGE
---
PURPLE PURPLE
---
YELLOW YELLOW
---
WHITE WHITE
---
RED RED
---
BLUE BLUE
---
BROWN BROWN
---
11 / 375 11 / 375
1019 12 / 348 12 / 348
1020
13 13
1021 14 / 101 14 / 101
1022
15 15
1023
16 16
1024 17 / 298 17 / 298
1026 18 / 324 18 / 324
1027 19 / 470 19 / 470
1027 20 / 299 20 / 299
1029
NOTE: When using crimp type lugs, the lugs should be crimped to the specifications given in the
manufacturer's instructions for both crimp tool and lug.
FIGURE 3.1 UPS Terminal Designation
AC input
Terminals: A, B, C
AC Bypass
In
Terminals: A40,B40,C40,N40
CB1
CB3
Terminals: BP,BN
CB2
Static Transfer
Switch
52S
52C
Output
Terminals: A50,B50,C50, N50
UPS ModuleBattery cabinet
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 40
3
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
-7
FIGURE 3.2-a-1 Diagram of input/output bus bars and terminal blocks (100kVA, 150kVA, 225kVA UPS, Input voltage 480Vac)
Location of bus bars and terminal blocks Detailed Terminals
External wiring block
100kVA : 43.3” (1100mm) 150kVA : 47.2” (1200mm) 225kVA : 55.1” (1400mm)
UPS module
AC Input A,B,C
AC Output A50,B50,C50
Bypass Input A40,B40,C40
H=79.7” (2025mm)
D=29.9” (760mm)
N40,N50
Battery Input BN,BP
For power terminals, use 3/8” (10mm) Diameter bolts.
UPS module
AC Input
A B C
AC Output
A50 B50 C50
Bypass Input
A40 B40 C40
N40 N50
DC Input
BN BP
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 41
3-8
r
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.2-a-2 Diagram of Power Wire & Control Wire Inter-Connect (100kVA, 150kVA, 225kVA UPS, Input voltage 480Vac)
DC circuit breake
UVT
External signal terminal IOAU-04 – [TN2]
Auxiliary
24
23
22
21
BN
BP
“+”Positive“-“Negative
User supplied
User supplied
UPS module
Wall mounted DC breaker
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 42
3-9
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.2-b-1 Diagram of input/output bus bars and terminal blocks (100kVA, 150kVA, 225kVA UPS, Input voltage 600Vac)
Location of bus bars and terminal blocks Detailed Terminals
100kVA : 79.3” (2014mm) 150kVA : 83.2” (2113mm) 225kVA : 99.1” (2520mm)
Input cabinet
External wiring block
UPS module
AC Input H1,H2,H3
H=79.7” (2025mm)
D=29.9” (760mm)
AC Output A50,B50,C50
N40,N50
Bypass Input A40,B40,C40
Battery Input BN,BP
For power terminals, use 3/8” (10mm) Diameter bolts.
Input
UPS module
cabinet
AC Input
H1 H2 H3
AC Output
A50 B50 C50
Bypass Input
A40 B40 C40
N40 N50
DC Input
BN BP
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 43
3-10
C circu
er
pu
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.2-b-2 Diagram of Power Wire & Control Wire Inter-Connect (100kVA, 150kVA, 225kVA UPS, Input voltage 600Vac)
User supplied
X1 X2 X3
H1 H2 H3
t transformer
In
Input Cabinet
External signal terminal IOAU-04 – [TN2]
24
23
22
21
A B C
UPS module
BPBN
User supplied
D
it break
UVT
Auxiliary
“+”Positive“-“Negative
User supplied
Wall mounted DC breaker
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 44
3
y
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
-11
FIGURE 3.2-c-1 Diagram of input/output bus bars and terminal blocks (300kVA, 375kVA UPS, Input voltage 480Vac)
Location of bus bars and terminal blocks Detailed Terminals
Battery Input BN,BP
76.8” (1950mm)
N50
AC Input A,B,C
Bypass Input A40,B40,C40
UPS module
H=79.7” (2025mm)
D=37.8” (960mm)
External wiring block
AC Output A50,B50,C50
DC Input
BN BP
AC Input
A B C
B
pass Input
A40 B40 C40
UPS module
N50
AC Output
A50 B50 C50
UPS Power Terminals use 1/2” (13mm) Diameter bolts.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 45
3
er
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
-12
FIGURE 3.2-c-2 Diagram of Power Wire & Control Wire Inter-Connect (300kVA, 375kVA UPS, Input voltage 480Vac)
External signal terminal
IOAU-04 – [TN2]
BPBN
24
23
22
21
DC circuit break
UVT
Auxiliary
“-“Negative
“+”Positive
User supplied
User supplied
UPS module
Wall mounted DC breaker
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 46
3-13
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.2-d-1 Diagram of input/output bus bars and terminal blocks (300kVA, 375kVA UPS, Input voltage 600Vac)
Location of bus bars and terminal blocks Detailed Terminals
H=79.7” (2025mm)
D=37.8” (960mm)
300kVA : 120.8” (3068mm) 375kVA : 130.8” (3322mm)
DC Input
BN BP
Bypass Input
A40 B40 C40
N50
AC Output
A50 B50 C50
Input cabinet
N50
Battery Input BN,BP
AC Input H1,H2,H3
Bypass Input A40,B40,C40
UPS module
External wiring block
AC Output A50,B50,C50
AC Input
H1 H2 H3
Input cabinet
UPS module
UPS Power Terminals use 1/2” (13mm) Diameter bolts.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 47
3
C circu
er
pu
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
-14
FIGURE 3.2-d-2 Diagram of Power Wire & Control Wire Inter-Connect (300kVA, 375kVA UPS, Input voltage 600Vac)
External signal terminal
A B C
IOAU-04 – [TN2]
BPBN
24
23
22
21
D
Auxiliary
it break
UVT
X1 X2 X3
User supplied
H1 H2 H3
In
t transformer
Input Cabinet
UPS module
MITSUBISHI ELECTRIC 9800A SERIES UPS
“-“Negative
“+”Positive
User supplied
User supplied
Wall mounted DC breaker
Page 48
3-15
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.2-e-1 Diagram of input/output bus bars and terminal blocks (500kVA, 750kVA UPS, Input voltage 480Vac)
Location of bus bars and terminal blocks Detailed Terminals
51.2” (1300mm)
Battery Input BN,BP
AC Input A,B,C
N40,N50
AC Output A50,B50,C50
UPS module
H=79.7” (2025mm)
D=37.8" (960mm)
63.0” (1600mm)
External wiring block
Bypass Input A40,B40,C40
AC Input A B C
DC Input
BN BP
UPS module
AC Output
A50B50C
50
N40N
50
A40B40C
40
Bypass
Input
UPS Power Terminals use 1/2” (13mm) Diameter bolts.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 49
3-16
r
r
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.2-e-2 Diagram of Power Wire & Control Wire Inter-Connect (500kVA, 750kVA UPS, Input voltage 480Vac)
External signal terminal
BP BN
IOAU-04 – [TN2]
24
23
22
21
DC circuit breake
UVT
Auxiliary
User supplied
UPS module
User supplied
Floor mounted DC breaker
MITSUBISHI ELECTRIC 9800A SERIES UPS
Positive Bus Bar Negative Bus Ba
Page 50
3
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
-17
FIGURE 3.2-f-1 Diagram of input/output bus bars and terminal blocks (500kVA, 750kVA UPS, Input voltage 600Vac)
Location of bus bars and terminal blocks Detailed Terminals
Input cabinet
AC Input H1,H2,H3
168.2” (4270mm)
N40,N50
AC Output
Battery
A50,B50,C50
Input BN,BP
UPS module
H=79.7” (2025mm)
D=37.8" (960mm)
External wiring block
Bypass Input A40,B40,C40
AC Input
A B C
Input cabinet
DC Input
BN BP
UPS module
AC Output
A50B50C
50
N40N
50
A40B40C
40
Bypass
Input
UPS Power Terminals use 1/2” (13mm) Diameter bolts.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 51
3-18
r
C circu
er
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.2-f-2 Diagram of Power Wire & Control Wire Inter-Connect (500kVA, 750kVA UPS, Input voltage 600Vac)
User supplied
X1 X2 X3
H1 H2 H3
Input transformer
External signal terminal IOAU-04 – [TN2]
D
24
BPBN
A B C
23
22
21
Auxiliary
it break
UVT
User supplied
Positive Bus Bar Negative Bus Ba
User supplied
Input Cabinet
UPS module
MITSUBISHI ELECTRIC 9800A SERIES UPS
Floor mounted DC breaker
Page 52
3-19
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.3-a Diagram of Rectifier Cabinet & Inverter Cabinet Inter-Connect 1 (500kVA, 750kVA UPS)
MITSUBISHI ELECTRIC 9800A SERIES UPS
N50
Page 53
3-20
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
FIGURE 3.3-b Diagram of Rectifier Cabinet & Inverter Cabinet Inter-Connect 2 (500kVA, 750kVA UPS)
Ground Bus Bar
Ground Bus Bar
Rectifier Cabinet
CON2
CON1
CON3
CON4
CON5
CN1
CN3
CN11 CN4 CN5
Inverter Cabinet
RYER-E
CN9
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 54
3
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
-21
CRITICAL LOAD CABINET
FIGURE 3.4-a Diagram of Power Wire Connect ( Parallel connection )
52MB
input
AC
UPS-1
Bypass
CB1
Converter
Inverter
52S
AC output
52L
1
52C
UPS-2
Bypass
CB2
Battery
52S
52CS
input
AC
CB1
Converter
Inverter
AC output
52L
2
CB2
52C
Battery
Bypass
*1
52S
UPS-n
AC
input
CB1
Converter
Inverter
AC output
52L
*1
n
52C
CB2
Battery
*1 n : Maximum = 8
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 55
3
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
-22
FIGURE 3.4-b Diagram of Power Wire & Control Wire Connect ( Parallel connection )
UPS-1
CN92
CN93
IN
OUT
AC Output
A50
B50
C50
N40/N50
IOAU-04 TN2
25 26
UPS-2
CN92
CN93
IN
OUT
AC Output
A50
B50
IOAU-04
TN2
25 26
Critical Load Cabinet
1 2 3 4 5 6 7 8
UPS-1 AC Output
A
B
C
N
UPS-2 AC Output
A
B
52L1-AX
52L2-AX
C50
N40/N50
C
N
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 56
3-23
UPS-1
IOAU-04 TN2
CN92
CN93
IN
OUT
25 26
MITSUBISHI ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
FIGURE 3.4-c Diagram of Power Wire & Control Wire Connect ( Parallel connection )
AC Output
UPS-1
UPS-2
CN92
CN93
IN
OUT
UPS-n
25 26
IOAU-04 TN2
*2
UPS-3 CN93
UPS-(n-1)CN92
UPS-3 OUT
UPS-(n-1) IN
*1
25 26
IOAU-04 TN2
CN92
CN93
IN
OUT
UPS-2
A
B
C
N
A
B
C
N
Critical Load Cabinet
TB1
1 2 3 4
15 16
52L1-AX
52L2-AX
*1
52Ln-AX
AC Output
A50
B50
C50
N40/N50
N40/N50
AC Output
A50
B50
C50
AC Output
A50
B50
C50
N40/N50
MITSUBISHI ELECTRIC 9800A SERIES UPS
UPS-n
A
B
C
N
*1
*1 n : Maximum = 8 *2 Return from the last
UPS module to the first UPS module (continuous loop).
Page 57
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
3.4 Operating Procedures
A) Start-up Procedure
a) Verify that Critical Load Cabinet (CLC) Circuit Breakers 52L1, 52L2…and 52Ln are
closed.
b) Verify that the External Bypass Input Circuit Breaker for each unit is closed
(Breaker is user supplied.)
c) If a dual source is feeding the UPS, close the External AC Rectifier Input Circuit
Breaker manually (user supplied).
Start-up of UPS-1
1. Verify that Control Circuit Breakers (CPM) is closed. (When Inverter is stopped, the Control Circuit Breaker is not normally opened)
2. The pre-charging cycle will begin and Input Contactor (CB1) will close automatically.
3. Close Battery Disconnect Circuit Breaker (CB2).
4. The inverter can now be started.
Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start operation can only be performed remotely. If local inverter start operation is required
(at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL”
mode for the purpose of this start up procedure.
5. On the LCD panel, select “START/STOP MENU” and press the “START” key.
6. The Inverter will start within 5 seconds. Start up is complete.
Start-up of next UPS
The next UPS can be started in the same way as UPS-1.
FIGURE 3.5-a Start-up Procedure
540V
Page Number:
3-24
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 58
B) Shut-down Procedure
Shut-down of UPS-1
MITSUBISHI ELECTRIC
If a total UPS shutdown is required, verify that the critical load is OFF.
1. Press the "START/STOP MENU" from the Main Menu on the LCD.
Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the
inverter stop operation can only be performed remotely. If local inverter stop operation is
required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL” mode for the purpose of this stop procedure.
2. Press both "STOP" keys simultaneously on the LCD.
3. In general, only the Inverter will be stopped and the Rectifier will remain energized to charge the batteries.
Opening the user supplied External Input AC Circuit Breaker (if dual source used), the External Bypass Input Circuit Breaker and the DC Disconnect Circuit Breaker, CB2, will shut down the load.
4. If stopping both the Rectifier and Charger is required, open the Battery Disconnect circuit breaker (CB2) manually.
5. If a dual source is feeding the UPS, open the External AC Rectifier Input Circuit Breaker (user supplied) manually.
6. If turning off all power to the critical load is desired, open the External Bypass Input Circuit Breaker (user supplied) manually.
Shut-down of next UPS
The next UPS can be shut down in the same way as UPS-1. The parallel UPS system will be in bypass operation when all inverters stops.
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
3-25
FIGURE 3.5-b Shut-down Procedure
540V
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 59
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
C) Bypass Operation Procedure
UPS-1
1. Check for “SYNC” on the LCD.
2. Press the "START/STOP MENU" from the LCD Main Menu.
3. Press the "STOP" key on the LCD.
Next UPS
Stop the next UPS in the same way as UPS-1.
The paralleling UPS system will be in bypass operation when all inverters stop.
** Transfer from bypass to inverter.
UPS-1
1. Press the "START/STOP MENU" from the LCD Main Menu.
2. Press the "START" key on the LCD.
Next UPS
Start the next UPS in the same way as UPS-1.
The paralleling UPS system will be in inverter operation when all inverters start.
Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start or stop operation can only be performed remotely. If local inverter start or stop operation
is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select “LOCAL” mode for the purpose of this stop procedure.
Page Number:
3-26
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 60
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
4.0 RESPONSE TO UPS FAILURE
UPS FAULT
Page Number:
4-1
Annunciator Silence
Recording of Fault
Primary Action
Information to Service Center
Note
The error code indicated on the LCD display panel at the time of a UPS alarm condition is very important. In order to reduce repair time, please include this information, along with the operation status and load status for all correspondence with Mitsubishi’s field service group.
Depress “SILENCE ALARM” key on MAIN menu.
Refer to the list of fault codes in section 6.0 for error
description.
Take necessary action according to display guidance.
When a faults occur, contact the Authorized Mitsubishi
Service Representative or call Mitsubishi at
1-800-887-7830.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 61
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
5-1
5.0 PARTS REPLACEMENT
Contact Mitsubishi or its Authorized Service Center on all issues regarding the replacement
of parts.
A) Battery
Battery lifetime may vary according to the frequency of use and the average ambient
operating temperature. The end of battery life is defined as the state of charge resulting
in an ampere-hour capacity less than, or equal to, 80% of nominal capacity.
Replace battery if its capacity is within this percentage.
B) UPS Component Parts
Contact Mitsubishi or its Authorized Service Center for a complete parts replacement
schedule. Recommended replacement time interval varies with operating environment.
Contact Mitsubishi or its Authorized Service Center for application specific
recommendations.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 62
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
6.0 FAULT CODES
This section covers fault codes, their description and required action.
At time of error :
A) Verify and record the occurrence of the alarm. Note details of alarm message
displayed on the LCD display panel.
Contact Mitsubishi Electric Automation, Inc. at 1-800-887-7830.
B) If a circuit breaker (MCCB) has tripped, depress the toggle to reset the breaker
before closing it again.
Page Number:
6-1
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 63
6
MITSUBISHI ELECTRIC
Failure
Code List
Note 9 Note 1 Note 2 Note 3
Code
indication
UF003
UF006
UF055
UF059
UF102 DC OVERVOLTAGE Over voltage of DC voltage
UF103 DC UNDERVOLTAGE Low voltage of DC voltage
UF108
UF151
UF152
UF153 CB2 ABNORMAL
UF156
UF157
UF161
UF162 BATTERY ABNORMAL
UF163
Table 6.1 Fault Code
Status message Contents Guidance Buzzer
CONVERTER
ABNORMAL
CONVERTER
ABNORMAL
CONVERTER
ABNORMAL
INPUT CIRCUIT
ABNORMAL
CHOPPER
OVERCURRENT
DC VOLTAGE
ABNORMAL
DC VOLTAGE
ABNORMAL
CB2 TRIPPED(BATTERY
OVERTEMP.)
BATTERY
OVERTEMPERATURE
CB2 TRIPPED(DC VOLT.
ABNORMAL)
BATTERY VOLTAGE
ABNORMAL
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Preliminary charge impossible
Mixed operation (60 minutes)
Mixed operation (1 minute)
Input circuit abnormality
Chopper output overcurrent
Does not return to float voltage
after power supply is resumed
(24 hours)
Does not return to equalizing
voltage after power supply is
resumed
Battery disconnect circuit breaker
CB2 has tripped.
Battery temperature abnormality
(UF157) lasted a long time
(Note 5)
Battery temperature abnormality
Does not return to float voltage
after power supply is resumed
(48 hours) (Note 5)
Battery abnormal detected by
battery self test.
Battery voltage abnormality
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CHECK
BATTERY
CHECK
BATTERY
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
Page Number:
-2
External
send-out
contact
[2] Major Lit on
[2] Major Lit on
[1] Minor Flicker
[1] Minor Flicker
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[1] Minor Flicker
[1] Minor Flicker
[1] Minor Flicker
[1] Minor Flicker
Minor
[1]
Note 4
[1] Minor Flicker
[1] Minor Flicker
[1] Minor Flicker
Failure
lamp
Flicker
UF165 IGBT FAULT (CHOPPER)
MITSUBISHI ELECTRIC 9800A SERIES UPS
IGBT module (Chopper)
overcurrent
CALL SERVICE
ENGINEER
[2] Major Lit on
Page 64
6-3
MITSUBISHI ELECTRIC
UF166 IGBT FAULT (A) IGBT module (A) overcurrent
UF167 IGBT FAULT (B) IGBT module (B) overcurrent
UF168 IGBT FAULT (C) IGBT module (C) overcurrent
UF201
UF202
UF203
UP204
UF209 52C ABNORMAL 52C not turned ON
UF210 52C ABNORMAL 52C not turned OFF
UF213
UF214
UF255 52C ABNORMAL
UF256
UF257 52C ABNORMAL
UF258 LOAD ABNORMAL
UF259
UF260 LOAD SHORT
UF301
UF302
UF303
INVERTER
OVERVOLTAGE
INVERTER
UNDERVOLTAGE
INVERTER
OVERCURRENT
OUTPUT CIRCUIT
ABNORMAL
INV. OR CONV.
OVERTEMPERATURE
COOLING FAN
ABNORMAL
OUTPUT VOLTAGE
ABNORMAL
Output voltage bus
abnormal
UPS CONTROL CIRCUIT
ERROR
UPS CONTROL CIRCUIT
ERROR
UPS CONTROL CIRCUIT
ERROR
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Output overvoltage during inverter
power supply (+ 15%)
Output low voltage during inverter
supply (-15%)
Inverter output overcurrent
Cross current fell out of 30%
Overheating of main circuit parts
Abnormality of cooling fan inside
panel
52C turned OFF during inverter
power supply
Inverter output voltage fell out of
+/- 5%
52C not turned OFF when manual
transfer
More than 4 overcurrents for 10
minutes
Inverter output voltage bus
abnormality
After UA810 occurred, Bypass
Abnormal occurred within 1
second. (#1)
Control microcomputer
abnormality
Control microcomputer
abnormality
Control microcomputer
abnormality
Page Number:
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CHECK LOAD [1] Minor Flicker
CALL SERVICE
ENGINEER
CHECK LOAD [1] Minor Flicker
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[1] Minor Flicker
[1] Minor Flicker
[1] Minor Flicker
[1] Minor Flicker
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
UF304
UPS CONTROL CIRCUIT
ERROR
MITSUBISHI ELECTRIC 9800A SERIES UPS
Parallel control circuit abnormality
CALL SERVICE
ENGINEER
[2] Major Lit on
Page 65
6
MITSUBISHI ELECTRIC
UF305
UF306
UF309
UF352
UF402 52S ABNORMAL
UF403 CB3 ABNORMAL
UF451 52S ABNORMAL
UF452 CB3 ABNORMAL CB3 open
UPS CONTROL CIRCUIT
ERROR
UPS CONTROL CIRCUIT
ERROR
INVERTER VOLTAGE
ABNORMAL
CONTROL POWER
SUPPLY ABNORMAL
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Control clock abnormality
Control power source circuit
abnormality
Inverter output voltage abnormality
before inverter power supply
Control circuit abnormality
52S not turned OFF, or 52S turned
OFF without any command
CB3 not turned OFF
52S not turned ON, or 52S turned
ON without any command when
manual transfer
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
(#2)
ENGINEER
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
Page Number:
-4
[2] Major Lit on
[2] Major Lit on
[2] Major Lit on
[1] Minor Flicker
[2] Major Lit on
[2] Major Lit on
[1] Minor Flicker
[1] Minor Flicker
UF453 52L OPERATION ERR. 52L operated abnormality CHECK 52L [2] Major Lit on
UA801
UA806
UA808
UA809
UA810 INVERTER OVERLOAD
UA811 OVERLOAD TRANS. Overload transfer - [1] Alarm
UA812
UA813
UA814
AC INPUT VOLTAGE OUT
OF RANGE
INVERTER OVERLOAD
> 100%
INVERTER OVERLOAD
> 125%
INVERTER OVERLOAD
> 150%
BYPASS VOLTAGE OUT
OF RANGE
BYPASS PHASE
ROTATION ERROR
BYPASS FREQUENCY
OUT OF RANGE
AC input voltage fell out of +/- 15%
range
Overload exceeded 105% (Note 7)
Overload exceeded 125% (Note 7)
Overload exceeded 150% (Note 7)
Momentary over-current during
Inverter power.
Bypass voltage fell out of +/- 20%
range
Phase rotation is inverted when
bypass voltage is normal
Bypass frequency fell out of
inverter synchronization follow-up
range
CHECK INPUT
POWER
SOURCE
WARNING :
DECREASE
LOAD
WARNING :
DECREASE
LOAD
WARNING :
DECREASE
LOAD
WARNING :
DECREASE
LOAD
CHECK
BYPASS INPUT
CHECK
BYPASS INPUT
CHECK
BYPASS INPUT
[1] Alarm -
[1] Alarm -
[1] Alarm -
[1] Alarm -
[1] Alarm -
[1] Alarm -
[1] Alarm -
[1] Alarm -
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 66
6-5
MITSUBISHI ELECTRIC
UA817
UA819
UA820
UA824 CB2 OPEN
UA831
UA834
UA841
UA842
EMERGENCY STOP
ACTIVATED
REMOTE START
BUTTON ABNORMAL
REMOTE STOP BUTTON
ABNORMAL
EMERGENCY BYPASS
SWITCH ON
BATTERY DEPLETED
INV. STOPPED
CONVERTER OPE.
PROHIBITION
OUTPUT CIRCUIT
ABNORMAL
9800A SERIES UPS
Page Number:
OWNERS / TECHNICAL MANUAL
Emergency stop applied - - Alarm -
There is an error with the remote
start switch.
There is an error with the remote
stop switch.
Battery disconnect circuit breaker
CB2 turned OFF
Emergency bypass switch turned
to <Emergency>
DC voltage dropped below
discharge end during inverter
operation
Converter operation interlock
applied
Load bus voltage sensor
abnormality
CALL SERVICE
ENGINEER
CALL SERVICE
ENGINEER
TURN ON CB2 [1] Alarm -
- [1] Alarm -
- - Alarm -
- - Alarm -
- - Alarm -
[1] Alarm -
[1] Alarm -
#1: It has the possibility that output short-circuits. #2:Check the CB3 and Bypass Thyristors.
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 67
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
6-6
(Note 1) Audible annunciator: [1] intermittent sound, [2] continuous sound.
(Note 2) 1) "Major" is defined as major failure. Inverter transferred to the static bypass line;
2) "Minor" is defined as a minor failure. UPS continues to operate normally, but
cause of alarm must be identified;
(Note 3) Indicates one of two possible LED illumination patterns - continuously on (lit) or
intermittent (flicker).
(Note 4) External send-out possible by option setting.
(Note 5) Trips the battery breaker CB2.
(Note 6) For other than sealed-type battery.
(Note 7) If the specified time elapses, will transfer to the bypass power supply.
(Note 8) Shows only when corresponding option settings are made.
(Note 9) Code indication means:
UA+++----------------------- Alarm
UF+++----------------------- Failure
U%0++ ---------------------- Rectifier circuit failure
U%1++ ---------------------- DC circuit failure
U%2++ ---------------------- Inverter circuit failure
U%3++ ---------------------- Control circuit failure
U%4++ ---------------------- Bypass system failure
U%8++ ---------------------- Alarm
U%+00 - U%+49 -------- Major failure
U%+50 - U%+99 -------- Minor failure
*) “+” denotes any numeral from 0 to 9
*) “%” denotes either “A” or “F”
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 68
7.0 Warranty & Out of warranty Service
MITSUBISHI ELECTRIC
OWNERS / TECHNICAL MANUAL
9800A SERIES UPS
Page Number:
7-1
The Mitsubishi Electric UPS Systems Group Service Department has many Authorized Service
Centers place strategically throughout the US, Canada and Latin America. For both in warranty and
out of warranty service, please contact Mitsubishi Electric Automation, Inc. at (847) 478-2500. To
register your UPS for warranty purposes, please complete the warranty registration form and fax it to
the Mitsubishi Electric UPS Systems Group, Service Department fax line shown on the registration
form. (Next page)
For warranty purposes, it is essential that any and all service work that may be required on your
Mitsubishi brand UPS equipment is performed by a Mitsubishi Electric Authorized Service Center.
The use of non-authorized service providers may void your warranty.
Mitsubishi Electric Automation Inc,
UPS Systems Group Service Department
500 Corporate Woods Parkway,
Vernon Hills, Illinois 60061, USA
Phone: (847) 478-2500
Fax: (847) 478-2290
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page 69
ELECTRIC
OWNERS / TECHNICAL MANUAL
MITSUBISHI
9800A SERIES UPS
Page Number:
7-2
Mitsubishi Electric Automation, Inc.
UNINTERRUPTIBLE POWER SUPPLIES
500 Corporate Woods Parkway, Vernon Hills, IL 60061 Phone: (847) 478-2643, Fax: (847) 478-2290
UPS Warranty Registration
__ Register UPS for Warranty __ Address Change
To validate the Warranty on your UPS this form must be filled out completely by
Customer and returned.
CUSTOMER INFORMATION
Your Name:
Company Name:
Division / Department:
Address:
City:
Country: Province:
State: Zip Code:
Job Title:
Business Phone: Ext: Fax:
E-Mail: @
UPS Model #: Capacity (kVA): UPS Serial #:
Start-Up Date: / /
Signature:
Which ONE of These Best Describes Your Organization’s Number of Employees at This Location is: Primary Business Classification?
{Energy Producer} __ Education/Univ. Service __ 1 – 19 __ 100 - 249 __1000 or more
__ Utility {Service} __ 20 – 49 __ 250 - 499 __ Alternate Energy __ Consulting __ 50 – 99 __ 500 - 999
{Manufacturing Co.} __ Engineering
__ OEM __ Outsourcing Overall how was Start-Up performed:
__ Process __ Financial/Legal/Insurance __Unsatisfactory __ Satisfactory __ Exceeded
__ Consumer Goods {Government}
__ Electronics __ Military Would you like to receive future product updates and
__ Power Quality Equipment __ Municipals news?
__ Commercial Business __ Federal/State/Local __Yes __ No
__ Electrical Contractor __ Communications
__ Healthcare __ Distributors/Reps
__ Internet __ Other __________________
{Expectations}
Authorized Mitsubishi Service Company (if known):
Internet Address:
Date: / /
After Start-Up has been done Fax completed Form to:
(847) 478-2290
MITSUBISHI ELECTRIC 9800A SERIES UPS
Loading...