McQuay AHP018ARAY Installation Manual

Installation and Maintenance Manual IM-801
AHP Split System Heat Pumps
1-1/2 to 5 tons
Group: Unitary
Part Number: IM-801
Date: August 2005
Supersedes: January 2005
IM-801 Page 1
Table of Contents
MODEL NOMENCLATURE. . . . . . . . . . . . . . . . . . . . . . . . . . 3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
GENERAL WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SCROLL COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
EVAPORATOR COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INDOOR CFM AND HEATING CAPACITY
DETERMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
REFRIGERANT CHARGE DETERMINATION AND
ADJUSTMENT - HEAT PUMP - COOLING CYCLE . . . . . .10
HEAT PUMP - HEATING CYCLE . . . . . . . . . . . . . . . . . . . .11
STARTUP PROCEDURE AND CHECK LIST . . . . . . . . . . .11
OPERATION - DEFROST CONTROL . . . . . . . . . . . . . . . .12
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
THERMOSTAT DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . .15
"McQuay" is a registered trademark of McQuay International.
"Illustrations and information cover the McQuay International products at the time of publication and we reserve the right to make changes in
Page 2 IM-801
design and construction at any time without notice."
© 2004 McQuay International
MODEL NOMENCLATURE
M
A
N
1 2 3 4 4 4 6 6 6
0*
A
*
odel
HP= Air Cooled Heat Pump
ominal Capacity (tons)
8 = 1-1/2 4 = 2 6 = 3 2 = 3-1/2 8 = 4 9 = 4 0 = 5 1 = 5 2 = 5
10 SEER Size 048 and 060 only.
Table 1: Unit Nameplate Model Number Identifier
Unit Nameplate McQuay Model Number
CPLE18-1C AHP018ARAY CPLE24-1C AHP024ARAY CPLE30-1C AHP030ARAY CPLE36-1C AHP036ARAY CPLE42-1C AHP042ARAY CPLE48-1C AHP048ARAY CPLE48-3C AHP048APAY CPLE60-1C AHP060ARAY CPLE60-3C AHP060APAY CPLJ18-1B AHP018ARBY CPLJ24-1B AHP024ARBY CPLJ30-1B AHP030ARBY CPLJ36-1B AHP036ARBY CPLJ42-1B AHP042ARBY CPLJ48-1B AHP048ARBY CPLJ60-1B AHP060ARBY CPLT24-1B AHP024ARCY CPLT30-1B AHP030ARCY CPLT36-1B AHP036ARCY CPLT42-1B AHP042ARCY CPLT48-1B AHP048ARCY CPLT60-1B AHP060ARCY
AHP 018
RAY
Future Use SEER
A = 10 B = 12 C = 13
Voltage/Phase
P = 208-230/3/6 R = 208-230/1/60
Vintage
IM-801 Page 3
INTRODUCTION
General Description
These installation instructions cover the outdoor installation of split system heat pumps from ½ to 5 tons. See the product cat­alog applicable to your model for information regarding speci­fications applicable to your model and accessories.
Receiving Inspection
McQuay products are carefully inspected prior to shipment and the carrier has assumed responsibility for loss or damage upon acceptance of the shipment.
Upon receiving your shipment, check all items carefully against the Bill of Lading. Inspect the unit and/or accessories for shipping damage as soon as they are received. Immedi­ately file claims for loss or damage, either shipping or con­cealed, with the shipping company.
Check the unit nameplate to verify the model number and elec­trical characteristics are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufacturer disclaims all responsibility for the installation of incorrectly shipped units.
Codes and Regulations
This product is designed and manufactured to permit installa­tion in accordance with National Codes. System design should, where applicable, follow information presented in accepted industry guides such as the ASHRAE Handbooks. It is the installer' s responsibility to install the product in accor­dance with National Codes and/or prevailing local codes and regulations. The manufacturer disclaims all responsibility for equipment installed in violation of any code or regulations.
IMPORTANT
The United States Environmental Protection Agency (EPA) regulations cover introduction and disposal of refrigerants in this unit. Failure to follow those regulations can harm the environment and lead to substantial fines. Because regulations can change, a certified technician should perform any work done on this unit. If you have any questions, please contact the local office of the EPA.
Important Message to the Installer
This equipment is to be installed by an experienced installation company and fully trained personnel. Carefully read all instructions and take into account any special considerations prior to installing the unit. Give this manual to the owner and explain its provisions.
Important Message to the Owner
Read these instructions carefully and keep them near the prod­uct for future reference. Although these instructions are addressed primarily to the installer, useful maintenance infor­mation is included. Have the installer acquaint you with the operation of the product and periodic maintenance require­ments.
Recognize Safety Symbols, Words, and Labels
The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner's and installer's responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of property damage and/or product damage, serious personal injury or death. Improper installation, operation and mainte­nance can void the warranty.
DANGER
Immediate hazards which WILL result in property damage, product damage, severe personal injury and/ or death.
WARNING
Hazards or unsafe practice CAN result in property damage, product damage, sever personal injury and/or death.
CAUTION
Hazards or unsafe practices which CAN result in property damage, product damage, and/or personal injury.
Replacement Parts
Replacement parts can be obtained by contacting McQuay at 1
-800-37-PARTS. When contacting McQuay for service or replacement parts, refer to the model number and serial num­ber of the unit as stamped on the nameplate attached to the unit.
GENERAL WARNINGS
WARNING
Do not allow combustible materials, gasoline or other flammable liquids or vapors in the vicinity of this unit. Property damage, severe personal injury or death can result. Identify all cut-off devices, switches, etc. that serve your comfort equipment.
WARNING
Do not connect duct work to any other heat-producing device such as fireplace insert, stove, etc. Such connection can cause property damage, fire, carbon monoxide poisoning, explosion, personal injury or death.
SCROLL COMPRESSORS
Read the following before installing units with scroll compres­sors.
Pump Down Procedure
Scroll-equipped units should never be used to evacuate the air conditiong system. Vacuums this low can cause internal elec­trical arcing, resulting in a damaged or failed compressor.
Crankcase Heater
Scroll-equipped units do not have, and do not require, a crank­case heater.
Unbrazing System Components
If the refrigerant charge is removed from a scroll equipped unit by bleeding the high side only, it is sometimes possible for the scrolls to seal, preventing pressure equalization through the compressor. This may leave the low side shell and suction line tubing pressurized. If a brazing torch is then applied to the low side while the low side shell and suction line contains pressure,
Page 4 IM-801
the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame. To prevent this occur­rence, it is important to check both the high and low side with a manifold gauge before unbrazing, or in the case of repairing a unit on an assembly line, bleed refrigerant from both the high
and low side.
WARNING
Before unbrazing, check pressure on both high and low side. Incorrect charge removal can leave pressurized refrigerant and oil, which can ignite in contact with brazing heat, causing property damage and severe personal injury.
INSTALLATION
The manufacturer intends this unit to be used only with com­ponents indicated. An improper match voids the warranty. See the unit catalog for Performance Values and Approved System Matches.
Pre-Installation Checkpoints
Perform pre-installation checkpoints before attempting any installation. Consider the following check points:
• Structural strength of supporting members
• Clearances and provision for servicing
• Power supply and wiring
• Air duct connections
• Drain facilities and connections
Clearance
The outdoor heat pump unit is designed to be located outside the building with unobstructed condenser air inlet and dis­charge. Additionally, the unit must be situated to permit access for service and installation. Condenser air enters from three sides. Air discharges upward from the top of the unit. Refrig­erant tube electrical connections are made on the right side of the unit as you face the compressor compartment. The best and most common application is for the unit to be located 10” from a back wall with the connection side facing the wall. This “close to the wall” application minimizes exposed tubing and wiring and reduces the space for children to run around the unit, which can damage the tubes or wiring.
Figure 1. Clearances and Accessibility
10"
Service Access 18" Min.
20"
Close to the wall application provides free, unobstructed air to the other two sides. In more confined application spaces, such as corners, provide a minimum 10” clearance on all air inlet sides. Allow 18” minimum for service access to the compres­sor compartment and controls.
The top of the unit should be completely unobstructed. If units are to be located under an overhang, there should be a mini­mum of 36” clearance and provisions made to deflect the warm discharge air out from the overhang.
Location
Consider the effect of outdoor fan noise on the conditioned space and any adjacent occupied space. Place the unit so the discharge does not blow toward windows less than 25 feet away.
Set the outdoor unit on a solid, level foundation - preferably a concrete slab at least 4 inches thick. The slab should be above ground level and surrounded by a graveled area for good drain­age. Any slab used as a unit foundation should not adjoin the building, as it is possible that sound and vibration may be transmitted to the structure. For rooftop installation, use steel or treated wood beams as a unit support for load distribution.
Heat pumps require special location consideration in areas of heavy snow accumulation and/or areas with prolonged contin­uous subfreezing temperatures. Heat pump unit bases are cut­out under the outdoor coil to permit drainage of frost accumulation. The unit must be situated to permit free, unob­structed drainage of the defrost water and ice. A minimum 3" clearance under the outdoor coil is required in the milder cli­mates.
In more severe weather locations, elevate the unit to allow unobstructed drainage and air flow. Table 2 lists recommended elevation minimums:
Table 2: Elevation Minimums
Design Temperature Suggested Minimum Elevation
+15
-5
o
below -5
and above
o
to + 14
o
o
2 1/2"
8"
12"
Elevation Limitations
If the outdoor unit is mounted above the air handler, the maxi­mum lift should not exceed 70 feet (suction line). If the air handler is mounted above the outdoor unit, the lift should not exceed 50 feet (liquid line).
Note: When installing systems where the indoor - outdoor
sections are separated by more than 15 feet, observe the maximum elevation separations limitations.
Service Access 18" Min.
IM-801 Page 5
10"
10"
10"
Figure 2. Maximum Refrigerant Line Lengths
CONDENSING UNIT
PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FOR EVERY 10' OF LINE
LIQUID LINE
EVAPORATOR BLOWER
CCAUTION
Before starting equipment after prolonged shut­downs or at the time of initial start up, verify that the circuits to the units are closed for at least 24 hours.
CONDENSING UNIT
ADDITIONAL SUCTION LINE OIL
70' MAX
CONDENSING UNIT
LIQUID LINE SUCTION LINE OIL TRAPS WHEN INDOOR UNIT IS 4 FEET OR MORE BELOW OUTDOOR UNIT
INVERTED LOOP
LIQUID LINE
SUCTION LINE
TRAP FOR EACH 20' RISE OF PIPE
EVAPORATOR BLOWER
EVAPORATOR BLOWER
8'
50' MAX
ELECTRICAL
WARNING
Before attempting any service or adjustments, lock and tag out all gas and electrical supplies. Failure to follow this warning can cause property damage, personal injury and or death.
The supply power, voltage, frequency and phase must coincide with those listed on the nameplate. Carefully check all wiring against the manufacturer’s diagrams or with the diagram on the unit’s access panel. Field wiring must be connected in accordance with the National Code or other local codes that may apply. Verify that the equipment is adequately grounded per local code requirements. Use only copper wire between the disconnect and unit.
Over-current protection less than what is recommended in the unit catalog could result in unneccessary fuse failures and ser­vice calls. The manufacturer is not responsible for equipment damage resulting from not using the recommended size protec­tive devices as listed on the unit rating plate.
This unit has undergone a run test prior to packaging for ship­ment. This equipment has been started at minimum rated volt­age and checked for satisfactory operation. Do not attempt to operate this unit if the available voltage is not within the mini­mum and maximum shown on nameplate.
The condensing unit control wiring requires a 24-Volt mini­mum and a 40 VA service from the indoor transformer as shown on the wiring diagram.
COMPONENTS
Contactor
This control is activated (closed) by the room thermostat for both heating and cooling. It is de-energized (open) during emergency heat. The contactor has a 24-Volt coil and supplies power to the compressor and outdoor fan motor.
Crank Case Heater
The heater is factory wired so it is in operation whenever the main power supply to the unit is “ON”. It warms the compres­sor crankcase, preventing liquid migration and subsequent compressor damage. It is connected electrically to the contac­tor L1 and L2 terminals.
Condenser Motor
This is activated by the contactor during heating and cooling except during defrost and emergency heat operation.
Compressor
This is activated by the contactor for heating and cooling except during emergency heat. It is protected by an internal overload device.
Defrost Control
This provides time/temperature initiation and termination of the defrost cycle.
Loss of Charge Protector
If the system loses refrigerant charge, the control will open to allow the compressor contactor to open.
Outdoor Thermostats
These optional controls are used to prevent full electric heater operation at varying outdoor ambient (0°F to 45°F). They are normally open above their set points and closed below to per­mit staging of indoor supplemental heater operation.
Reversing Valve Coil
This is activated by the thermostat (system’s switch) during cooling only and during defrost. It positions the reversing valve pilot valve for cooling operation.
PIPING
Once located, the outdoor unit is ready to be interconnected with the indoor section, using the refrigeraion tubing sizes noted in the “Long Line Recommendations” Table. Use only refrigeration grade (dehydrated and capped) copper tubing.
CCAUTION
Keep refrigeration tubing clean and dry prior to and during installation to avoid equipment damage.
Use insulation of at least 1/2” wall thickness on the vapor gas line to prevent condensation when cooling and heat loss when heating. Install the insulation on the tubing prior to unit instal-
Page 6 IM-801
lation. Run the insulation the entire length of the installed line. Cover the end of the tubing over which the insulation is slipped so no foreign material is introduced to the interior of the tubing. The outdoor units are equipped with two refriger­ant line service valves. As shipped, the valves are in the front­seated or “down” position.
Line Set Installation Instructions
Use the following instructions to install line sets:
1. Cut tubing square. Verify it is round and free of burrs at the connecting ends. Clean the tubing to prevent contaminants from entering the system.
2. Wrap a wet rag around the copper valve stub before braz-
ing.
3. Braze or silver solder the joint.
4. After brazing, quench with a wet rag to cool the joint.
Evacuate and charge the connecting lines as outlined in these instructions.
5. Remove the valve top cap. It is important to keep the cap
in a clean area to provide proper sealing once replaced.
6. Using a standard L-shaped Allen wrench, break open the
valve body. To expedite opening the valve body after it is broken, use a ratchet wrench with a short Allen stub. Please note that it is normal to see oil on the valve stem body once the cap is removed.
7. Replace the valve cap and tighten with a wrench. Verify
that the the cap is sealed.
Table 3: Long Line Recommendations
REFRIGERANT LINE LENGTH (Ft)
Cond
Unit
Ton s
1 1/2 5/8 1/4 3/4 3/8 3/4 3/8
2 5/8 1/4 3/4* 3/8 3/4 3/8
2 1/2 3/4 3/8 3/4** 3/8 7/8 3/8
3 3/4 3/8 3/4** 3/8 7/8 3/8
3 1/2 3/4 3/8 7/8** 3/8 1 1/8 3/8
4 7/8 3/8 1 1/8 3/8 1 1/8 3/8
5 7/8 3/8 1 1/8 3/8 1 1/8 3/8
0-24 25-49 50-74***
Line Diameter (In. OD)
Suct Liq Suct Liq Suct Liq
* 7/8" required for full ratings ** 1 1/8" required for full ratings
EVAPORATOR COIL
CCAUTION
Evaporator coils are shipped under high pressure. Use extreme care and follow the installation instruc­tions provided with the evaporator coil to avoid per­sonal injury.
The indoor coil is pressurized. The copper caps must be punc­tured to permit a gradual escape of the pressure prior to un­sweating caps. Immediately couple the tubing to the indoor unit to avoid exposing the coils to moisture. A properly sized filter drier is furnished in the condenser. When heating the copper to make solder connections, use a dry nitrogen flow through the line to prevent oxidization inside of the copper.
Hard solder (Sil-Fos) is recommened, to provide a longer last­ing joint.
INDOOR CFM AND HEATING CAPACITY DETERMINATION
Prior to using the methods described below to check the sys­tem’s charge, it is important to verify the operating capacity of the system and that the system is delivering sufficient air across the indoor coil (CFM). The following procedures are suggested methods for determining the system’s operating capacity and CFM.
Airflow Determination - Indoor Coil
The heat pump system has been designed for optimum perfor­mance with an airflow across the indoor coil equaling approxi­mately 400 CFM/TON (e.g. A 2 TON system should have 2 x 400 CFM/TON = 800 CFM). The system’s airflow can be determined by several methods.
Airflow Test Instruments
There are a number of readily available instruments that can be used in the field for airflow determination such as Barometers, Volume-Aire Air Balancers, Anemometers, and Velometers. When using these devices, it is important to follow the instruc­tions provided by their manufacturer.
Temperature Rise Resistive Heat Method
Although it is not as accurate as the use of test equipment, the Temperature Rise Method can be used to determine the indoor airflow in a system employing electric resistance heat as the backup heat source.The following formula is used:
WHERE
KW = The indoor section’s measured input = Volts x Amps
Volts = The measured Volts at the Indoor Section
Amps = The measured Amps at the Indoor Section
Temperature Rise =
3413 = BTU per KW
1.08 = Specific Heat Air Constant
e.g. :
The input power to the indoor section = 10 KW
The Temperature Rise = 20°F
Refer to the Airflow Measurement Table.
Note: The compressor circuit (outdoor unit) must be
The temperature of the supply air - the temperature of the return air
“OFF” so that the Temperature Rise measured across the indoor unit is due only to the electric heat.
IM-801 Page 7
Use the following instructions to determine the temperature rise across the indoor section:
1. Use the same thermometer for the measuring the return and supply air temperatures to avoid thermometer error.
2. Measure the temperatures within 6 feet of the indoor sec-
tion and downstream from any mixed air source. Verify that the thermometer is not exposed to any radiant heat areas.
3. Verify that the air temperature is stable before making mea-
surement.
Figure 3. Temperature Rise Measurement
Temperature Rise Heat Pump Only Method
The Temperature Rise Resistive Heat Method can be used to determine the heating capacity of the heat pump system in the heat pump “only” mode. The results obtained using this method should agree within 10% of the data published in the unit catalog for the combination of indoor and outdoor sec­tion.
Note: When using the following procedure to determine
the system’s capacity, verify that the indoor section backup heat source is de-energized.
1. Use the same procedure described in the Temperature Rise Resistive Heat Method to determine the system’s CFM and temperature rise across the indoor section.
2. Determine the BTU output of the system for the measured Temperature Rise and system CFM by using the following formula:
BTU = CFM x TEMPERATURE x 1.08
Page 8 IM-801
Table 4: Airflow Measurements
IM-801 Page 9
REFRIGERANT CHARGE DETERMI­NATION AND ADJUSTMENT - HEAT PUMP - COOLING CYCLE
Weigh In Charge Method
To verify that the heat pump system is properly charged, weigh in the amount of refrigerant specified on the outdoor section nameplate, with additional adjustments for line size, line length and other system components. Heat Pump units are supplied with an R-22 charge sufficient for a typical matching evaporator and approximately 15 ft. of inner-connecting tub­ing. Systems having more than 15 ft of interconnecting refrig­erant lines require an additional charge allowance of R-22.
Table 5: Line Charge Allowance (R-22-oz./lb.)
LINE O.D. (IN) LIQUID LINE SUCTION LINE
1/4 0.22
3/8 0.58
1/2 1.14
5/8 1.86 0.04
3/4 0.06
7/8 0.08
1 1/8 0.15
1 3/8 0.22
Superheat Method
The following information has been developed to determine the proper charge for McQuay heat pump systems that are already in operation.
Note: Many field variations exist that may affect the oper-
ating temperature and pressure readings of a heat pump system. All McQuay heat pump systems use fixed orifice refrigerant control devices. The follow­ing procedure has been developed for this type of refrigerant control device.
1. With both base valves fully open, connect a set of service gages to the base valves’ service ports, being careful to purge the lines.
2. Allow the system to operate at least 10 minutes or until the pressures stabilizes.
3. Temporarily install a thermometer on the suction (large) line near the condensing unit base valve. Make sure that there is good contact between the thermometer and the refrigerant line and wrap the thermometer and line with insulating tape to provide accurate readings.
4. Determine the systems superheat as follows:
a. Read the system’s suction pressure.
b. Using Table 6, determine the system’s saturated suction
temperature.
c. Read the suction line temperature.
d. The system’s superheat = the suction line temperature -
the saturated liquid temperature.
Table 6: Saturated Suction Pressure (R-22)
SUCTION PRESSURE PSIG
50 26
53 28
55 30
58 32
61 34
63 36
66 38
69 40
72 42
75 44
78 46
81 48
SATURATED SUCTION
TEMPERATURE
o
F
5. Adjust the charge as necessary by adding charge to lower the superheat or bleeding the charge to raise the superheat.
Table 7: System Superheater.
AMBIENT CONDENSER INLET
TEMPERATURE
o
F DB
100
95
90
85
80
75 5 10172529
70 5 14202832
65 13 19 26 32 35
60 17 25 30 33 37
RETURN AIR TEMPERATURE
65 70 75 80 85
579
71218
5 101720
5 122126
o
F DB
55
CCAUTION
Remove the service gauge set from the lines care­fully. Escaping liquid refrigerant can cause burns.
Expansion Valve System-Subcooling Charge Method
1. Fully open both base valves.
2. Connect service gauge manifold to base-valve service parts verify that lines are purged. Run system at least 10 min­utes to allow pressure to stabalize.
3. Temporarily install the thermometer to liquid (small) line near the condensing unit. Be sure that the contact between thermometer and line is good. Wrap the thermometer with insulating material to provide an accurate reading.
4. Referring to Table 8, adjust charge to obtain a temperature 12-15°F below the saturated liquid temperature.
Example:
If liquid pressure is 260 psig, refer to Table 8. 260 psig = 120° saturated temperature. Subtract the liquid line temperature obtained from thermostat connected to the liquid line. The liq­uid line temperature must be 12° - 15° cooler than the refriger­ation saturation temperature. If the liquid line temperature is warmer than 12° - 15°, add charge to decrease. If the tempera­ture of the liquid line is cooler than 12° - 15°, recover charge from the system.
Page 10 IM-801
Table 8: Saturated Liquid Temperature
LIQUID PRESSURE PSIG
200 102 210 105 220 108 230 111 240 114 250 117 260 120 270 123 280 126 290 128 300 131
SATURATED TEMPERATURE
o
F
HEAT PUMP - HEATING CYCLE
As in the cooling mode, the proper method of verifying that the system is properly charged is by weight, with the additional charge adustments for line size, line length, and other system components.
Hot Gas Method
The following procedure can be employed as a method to check for system charge in the heating mode by measuring the hot discharge gas at the compressor.
1. Allow the system to operate at least 20 minutes.
2. Attach and insulate an electronic thermometer probe to the vapor service valve (large line) at the base valve. NOTE - Make sure that the probe is well insulated from the outdoor air.
3. Allow the system to operate at least 10 minutes. Then, use an accurate electronic thermometer to measure the temper­ature of the discharge gas at the probe.
4. Using the electronic thermostat, measure the outdoor ambi­ent temperature.
5. For verification, the temperature measured on the hot gas line should be equal to the outdoor ambient temperature plus 110°F +/- 4°F. (e.g: if the Outdoor Ambient is 45°F, then the temperature measured by the thermometer probe should be 155°F for a system that is properly charged). If the temperature measured by the thermometer’s probe is higher than the outdoor ambient plus 110°F, the system charge should be adjusted by adding refrigerant to lower the temperature. If the temperature measured is lower than the outdoor ambient plus 110°F, the system charge should be adjusted by recovering charge to raise the temperature
Note: When adjusting the charge in this manner, allow the
system to operate for at least 10 minutes before tak­ing the next temperature reading.
STARTUP PROCEDURE AND CHECK LIST
CCAUTION
Turn off power at all disconnects.
1. Set first-stage thermostat heat anticipator to .12 and turn
thermostat system switch to “COOL” and fan switch to “AUTO”.
2. Turn cooling temperature setting as high as it will go.
3. Inspect all registers and set them to the normal open posi­tion.
4. Turn on the unit electrical supply at the fused disconnect switch, both for the indoor unit and the outdoor unit.
5. Turn the fan switch to the “ON” position. The blower should operate 10 to 15 seconds later.
6. Turn the fan switch to the “AUTO” position. The blower should stop 90 seconds later.
Note: If outdoor temperature is below 55°F, proceed to
step 9. Do not check the cooling mode.
7. Slowly lower the cooling temperature until the first mer­cury bulb makes contact. The compressor, indoor blower, and outdoor fan should now be running. Verify cool air is being supplied by the unit.
8. Turn the system switch to “HEAT” and the fan switch to “AUTO”.
9. Slowly raise the heating temperature setting. After the heat­ing first-stage mercury bulb (upper) makes contact, stop moving the lever. The compressor, indoor blower and out­door fan should now be running. After giving the unit time to settle out, verify heated air is being supplied by the indoor unit.
10.If the outdoor ambient is above 70°F, the compressor may trip on internal overload.
11.In the event that the outdoor ambient temperature is too high to allow a thorough heating cycle check, postpone the test until conditions are more suitable. However, do not fail to perform a through heating cycle check.
12.If the unit operates properly on the heating cycle, raise the heating temperature until the heating second-stage mercury bulb (lower) makes contact.
13.Supplementary resistance heat, if installed, should now come on. Verify it is operating correctly. If outdoor thermo­stats are installed, the outdoor ambient temperature must be below the set point of these thermostats for heaters to oper­ate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient temperature is mild.
14.For thermostats with an emergency heat switch, return to Step #9. The emergency heat switch is located at the bot­tom of the thermostat. Move this switch to emergency heat. The heat pump will stop, the indoor blower will continue to run, all heaters will come on and the thermostat emergency heat light will come on.
15.If checking the unit on the heating cycle in the winter (when the outdoor coil is cold enough to actuate the defrost control), observe at least one defrost cycle to verify that the unit defrosts properly.
16.Check to see if all supply and return air grilles are adjusted and the air distribution system is balanced for the best com­promise between heating and cooling.
17.Check for air leaks in the ductwork.
IM-801 Page 11
18.Verify that the heat pump is free of “rattles” and the tubing in the unit is free from excessive vibration. Also verify that tubes or lines are not rubbing against each other, sheet metal surfaces or edges. If so, correct the issue.
19.Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.
20.Instruct the owner on the unit operation, filter servicing, correct thermostat operation, etc. The foregoing “Start-up Procedure and Check List” is recommended to serve as an indication that the heat pump system will operate normally.
OPERATION - DEFROST CONTROL
Timing
When operating, the power to the circuit board is controlled by a temperature sensor that is clamped to a return bend on the outdoor coil. Timing periods of 30, 60, or 90 minutes may be selected by connecting the circuit board jumper wire to 30, 60 or 90 respectively. Accumulation of time for the selected tim­ing period begins when the sensor closes (approximately 28°F) and when the wall thermostat is calling for heat. At the end of the timing period, a defrost cycle will be initiated, provided the sensor remains closed. When the sensor opens (approximately 65°F), the defrost cycle is terminated. If the defrost cycle is not terminated due to the sensor temperature, a 10 minute override interrupts the defrost period.
apply to the heat pump when it is on the cooling cycle. Most apply to the heating cycle, except that “condenser” becomes “evaporator”, “evaporator” becomes “condenser” and “cool­ing” becomes “heating”. When the heat pump is on the heat­ing cycle, it is necessary to redirect the refrigerant flow through the refrigerant circuit external to the compressor. This is accomplished with a reversing valve. Thus, the hot dis­charge vapor from the compressor is directed to the inside coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses into liquid. It then goes through a capillary tube, or expansion valve, to the outside coil (con­denser on the cooling cycle) where the liquid is evaporated, and vapor goes to the compressor.
When the solenoid valve is operated either from heating to cooling or vice versa, it moves the pilot valve, thus putting suction pressure (low pressure) on one side of the piston of the reversing valve. Because discharge pressure (high pressure) is on the other side of the piston, the piston slides to the low pres­sure side and reverses the flow of the refrigerant in the circuit.
The following figures show a schematic of a heat pump on the cooling cycle and the heating cycle.
Figure 4. Heat Pump Refrigeration Circuit
Field Testing / Trouble Shooting
A. Run unit in heat mode.
B. Check unit for proper charge. Note: Bands of frost indicate
low refrigerant charge
C. Shut off power to unit.
D. Disconnect outdoor fan by removing the purple lead from
“DF2” on defrost control.
E. Restart unit and allow frost to accumulate.
F. After a few minutes of operation, the defrost thermostat
should close. To verify this, check for 24 volts between “DFT” and “C” on the board. If the temperature at the ther­mostat is less than 28°F and the thermostat is open, replace the thermostat as it is defective.
G. When the defrost thermostat has closed, short the “test”
pins on the board until the reversing valve shifts, indicating defrost. This could take up to 21 seconds depending on what timing period the board is set on. After defrost initia­tion, the short must instantly be removed or the defrost period will only last 2.3 seconds.
H. After the defrost has terminated, check the defrost thermo-
stat for 24 volts between “DFT” and “C”. The reading should indicate 0 volts (open sensor).
I. Shut off power to unit.
J. Replace the outdoor fan motor lead and turn on the power.
General Explanation and Guidance
The heat pump operates similar to a summer air conditioning unit when it is on the cooling cycle. Therefore, all of the charts and data for service that apply to summer air conditioning also
Page 12 IM-801
In addition to a reversing valve, a heat pump is equipped with an expansion device and check valve for the inside coil, and similar equipment for the outside coil. It is also provided with a defrost control system.
The expansion device performs the same function on the heat­ing cycle as on the cooling cycle. The check valves are required due to the reverse flow of refrigerant when changing from cooling to heating or vice versa.
When the heat pump is on the heating cycle, at which time the outdoor coil is functioning as an evaporator, the temperature of the refrigerant in the outdoor coil must be below the tempera­ture of the outdoor air in order for the refrigerant in the outdoor coil to extract heat from the air. Thus, the greater the difference in outdoor temperature and outdoor coil temperature, the greater the heating capacity of the heat pump. Since this is characteristic of heat pumps, it is good practice to provide sup­plementary heat for all heat pump installations in areas where the temperature drops below 45°F. It is also good practice to provide sufficient supplementary heat to handle the entire heat­ing requirements in case of a of heat pump failure (e.g. a com­pressor failure, refrigerant leak, etc).
Because the temperature of the liquid refrigerant in the outdoor coil during the heating cycle is generally below the freezing point, frost forms on the surfaces of the outdoor coil under cer­tain weather conditions of temperature and relative humidity. Therefore, it is necessary to reverse the flow of refrigerant to provide hot gas in the outdoor coil and melt the frost accumu­lation. This is accomplished by reversing the heat pump to the cooling cycle. At the same time, the outdoor fan stops to has­ten the temperature rise of the outdoor coil and lessen the time required for defrosting. The indoor blower continues to run and the supplementary heaters are energized.
MAINTENANCE
General
Outdoor units do not require a planned maintenance program under normal operating conditions. However, not less than once each cooling season, the unit should be inspected and, if necessary, cleaned. Particular attention should be given to the air inlet side of the outdoor coil to verify that leaves, grass, etc., are not being drawn into the unit. Restricting air flow across the coil will result in loss of system capacity, high oper­ating pressures and excessive operating costs. If the outdoor unit is installed adjacent to a grassy area, lawn mowers should be routed so the discharge of the mower will be directed away from the unit. Air filters must be installed in the system at some point upstream to the indoor coil. Inspect and, if neces­sary, replace and/or clean air filters at least once a month.
If disposable filters are used, an adequate supply of clean, unused filters of the correct size should be available.
CCAUTION
Equipment should never be operated without filters.
Permanent type filters may be vacuumed and/or washed; but they should not be reinstalled until thoroughly dry. Most air fil­ters are marked to indicate the direction of airflow and this should be carefully noted when they are being installed.
CCAUTION
Never turn a dirty filter to allow airflow in the oppo­site direction.
The blower and motor bearings are permanently lubricated and do not require additional lubrication.
The owner should have at least one set of replacement fuses of the size supplied with the original equipment.
CWARNING
Do not replace fuses with sizes other than those supplied. Improper current protection can cause equipment damage, severe personal injury or death.
Common Causes of Unsatisfactory Operation of Heat Pumps on the Heating Cycle
A. Dirty filters or inadequate air volume through the
indoor coil. When the heat pump is on the heating cycle,
the indoor coil is functioning as a condenser. Therefore, the filters must always be clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high-pressure cutout.
B. Outside air into return duct. Cold outside air should not
be introduced in the return duct close enough to the indoor coil to reduce temperature of the air entering the coil below 65°F during the heating cycle. Air below this temperature will cause low discharge pressure, low suction pressure and excessive defrost cycling that will result in low heating out­put. It may also cause false defrosting.
C. Undercharge. Undercharge on the heating cycle will cause
low discharge pressure, resulting in low suction pressure and frost accumulation on the lower part of the outdoor coil.
D. Poor “terminating” defrost thermostat contact. The
defrost thermostat must make good thermal contact on the return bend. Otherwise, it may not terminate the defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure during the defrost cycle.
E. Causes of Malfunctioning Reversing Valve:
1. Solenoid not energized. In order to determine if the solenoid is energized, touch the nut that holds the sole­noid cover in place with a screwdriver. If the nut mag­netically holds the screwdriver in the Cooling mode, the solenoid is energized.
2. No voltage to solenoid. Check the voltage and if there is no voltage, check the wiring circuit.
3. Valve will not shift:
a. Undercharged: check for leaks.
b Valve Body Damaged: Replace valve.
c. Unit Properly Charged: If it is on the heating
cycle, raise discharge pressure by restricting air­flow through the indoor coil. If the valve does not shift, tap it lightly on both ends with a screw­driver handle.
IM-801 Page 13
WIRING DIAGRAM
C M O U T D O O R F A N M O T O R
C O M P C O M P R E S S O R
C C O N T A C T O R
D C D E F R O S T C O N T R O L
L V D R L O W V O L T A G E D E F R O S T D E L A Y
C H C R A N
K C A S E H E A T E R
I O I N T E R N A L O V E R L O A D
L P L O W P R E S S U R E S W I T C H
O T O U T D O O R T H E R M O S T A T ( O P T I O N A L )
R C C F R U N C A P A C I
T O R F O R C O M P R E S S O R A N D F A N
D F T D E F R O S T T H E R M O S T A T
R V C R E V E R S I N G V A L V E C O I L
S C S T A R T C A P A C I T O R F O R C O M P R E
S S O R ( O P T I O N A L )
S R S T A R T R E L A Y F O R C O M P R E S S O R ( O P T I O N A L )
H V D R H I G H V O L T A G E D E F R O S T R E L A Y
L 2
C
T 2
S C
R C C F
1
S R
S
C O M P .
M A I N
S E E R A T I N G P L A T E
O U T D O O R P O W E R S U P P L Y
5 2
T 1
C
L 1
C
D F 1
H V D R
F
( I F U S E D )
S T A R T A S S I S T
A U X
I O
C
C O N T A C T O R
D O U B L E P O L E
A L T E R N A T E
D F 2
C M
C H
A U X
M A I N
I O
O
B L
Y
C
D C
Y
( I F U S E D )
D F T
L V D R
D F T
R
C
Y
R V C
L P
Y
O
W 2
R
W 2
O
O
R
N O T E S :
I N D O O R P O W E R S U P P L Y
N I T
T F A C T O R Y E Q U I P P E D
2 . S E E I N D O O R A N D O U T D O O R U
T H E R M O S T A T .
T E R M I N A L B L O C K A N D I N D O O R
1 . T O I N D O O R U N I T L O W V O L T A G E
3 . S T A R T A S S I S
O U T D O O R T H E R M O S T A T .
C O N N E C T I O N O F O P T I O N A L
I N S T A L L A T I O N I N S T R U C T I O N S F O R
W H E N R E Q U I R E D .
O T - 1
P U
D F 2
H V D R
L V D R
D C
O T - 2
R
D F 1
W
D F T
O O W 2 R R
C Y
B K
O
B L
R
O T - 3
Y
W 2
W
S E E N O T E 2
R
B L
Y
R
D F T
R
Y
Y
L P
Y
B R
B K
B K
R
B K
Y
Y
C
O
R
C O M P O N E N T C O D E
W I R I N G C O D E
N O T E 1
T 1 T 2
R
T 2
T 1
Y
Y
B R
R
R
C O N T R O L B O X
F A C T O R Y W I R I N G F I E L D W I R I N G
E R N A T E
L 1 L 2
A L T
C
B K
B K
B K
C O N T A C T O R
D O U B L E P O L E
L 2
L 1
B L
P O W E R S U P P L Y
( S E E R A T I N G P L A T E )
U S E L 1 F O R N E U T R A L O R
B L
G R O U N D S U P P L Y I F U S E D
U S E C O P P E R C O N N E C T O R S O N L Y
Y
R
H I G H V O L T A G E H I G H V O L T A G E
L O W V O L A G E L O W V O L T A G E
O P I O N A L H I G H V O L T A G E
O P T I O N A L S T A R T A S S I S T
Y
S T A R T A S S I S T
R V C
B K B K
M A I N
E Q U I P M E N T G R O U N D U S E
C O M P .
A U X
R
C S
Y
C O P P E R C O N D U C T O R S O N L Y
R
B R
P U
A U X
M A I N
A N D T H E R M O S T A T I N " O F F " P O S I T I O N
C O N T R O L S S H O W N W I T H U T I L I T I E S I N " O N " P O S I T I O N
C H
( C R A N K C A S E H E A T I F U S E D )
B K
B K
B K
I O
C M
B K
1
S R
5
2
R
B L
S C
B L A C K
C O L O R C O D E
B K
P U R P L E
R E D
R
B R O W N
O R A N G E
B L U E
Y E L L O W
Y
B L
W H I T E
B R
P U
U S E N . E . C . C L A S S 2 W I R E
O
W
Page 14 IM-801
THERMOSTAT DIAGRAM
e
SYSTEM COMPOSITE DIAGRAM
SAH018 to 060
18-60
10 KW & BELOW
Heat Pump
W2
C
OYR
BL
OR
W
R
Y
R
Y
OR
W
BL
Outdoor Thermostat
(optional) Make On Fall
SAH018 to 060
SYSTEM COMPOSITE DIAGRAM
18-60
10 KW & BELOW
Heat Pump
W2
C
OYR
BL
OR
W
R
Y
R
Y
OR
W
BL
OT1
Note
OT2
#18GA. 7 Wire Needed When 2 Outdoor Thermostat Are Used
Conventional
Room Thermostat
O
#18 GA. 5 Wire
Room Thermostat
O
#18 GA. 5 Wire
W2
CY
GE
R
R
GR
See
BL
Note 3
BR
W
BL
#18GA. 6 Wire Needed When Outdoor Thermostat Is Used
Conventional
CY
W2 G E
See Note 3
R
GR
See Note 2
W
1
EHR
2
4
3
BL
BR
#18 GA. 7 Wire
Pink
#18 GA. 7 Wire
AR Indoor Unit
Pink
R
NOTES:
1. Outdoor Thermostat (OT1) should be the first to close and the first to open.
2. Install jumper if Outdoor Thermostat (OT2) is not used.
NOMENCLATURE :
OT - Outdoor Thermostat (Optional) MOF - Make On Fall EHR - Emergency Heat Relay (Optional)
COLOR CODES
R - Red OR - Orang Y - Yellow W - White BL - Blue G- Green BR - Brown
3. Remove wire when using Outdoor Thermostat. #18 Ga. 7 wire needed when (2) OTs are used.
IM-801 Page 15
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.
www.mcquay.com • 800-432-1342
Loading...