General Information ...........................................................................................................................................................4
Recommended Spare Parts ........................................................................................................................................... 4
Unit Inspection on Arrival.............................................................................................................................................5
Unit Application Limitations ........................................................................................................................................5
Unit Location Requirements .........................................................................................................................................5
Rigging, Lifting and Assembling .................................................................................................................................. 6
Suspended Unit Installation .......................................................................................................................................11
Field Fabricated Ductwork..........................................................................................................................................11
Pre Start-up Check.......................................................................................................................................................14
Refrigerant Systems ....................................................................................................................................................17
Belt Driven Fans...........................................................................................................................................................18
Manufacturer reserves the right to discontinue or change specifications or designs without notice or obligation.
VCES-V-CUBE-IOM-1A
2
Nomenclature
VV Y
GSM
0000
L
Model Indicator
ol Panel Location
V − V-Cube
Volume Control
V − Variable air volume C − Constant air volume
Condenser
N − No cooling X − Dx without WiSE coil W − Dx with WiSE coil
Y − Chilled water cooling Z – Remote condenser A − Airside economizer
Nominal Tonnage
Number of Compressors
0 − Air handler T − Tandem compressors H − Heat pump
Voltage
F − 208-230/3/60 L − 220-240/3/60 G − 460-480/3/60
K − 575/3/60 J − 380-415/3/50
Heating Type
E − Electric H − Hot water
S − Steam X − No heat
Frame Size
S − Small M − Medium
L − Large T − Tall
Contr
L – Left handed unit
R – Right handed unit
CES Group, LLC d/b/a Venmar CES furnishes equipment pursuant to its then-current Terms and Conditions of Sale and Limited Warranty, copies of which can be found under the Terms & Conditions of Sale and Warranty link at www.ces-group.com.
Extended warranties, if any, shall be as offered and acknowledged in writing by Venmar CES.
VCES-V-CUBE-IOM-1A
3
Safety Considerations
!
!
Warning, Caution and Important notes appear throughout this manual in specific and appropriate locations to
alert Installing Contractors and maintenance or service
personnel of potential safety hazards, possible equipment
damage or to alert personnel of special procedures or instructions that must be followed as outlined below.
WARNING
Identifies an instruction which if not followed, might cause
serious personal injuries including possibility of death.
CAUTION
Identifies an instruction which if not followed, might severely damage the unit, its components, the assembly or
final installation.
IMPORTANT
Indicates supplementary information needed to fully
complete an instruction or installation.
General Information
This manual is designed to provide general information
on the common operation of all standard and optional
components that may have been installed in the unit. Note
that some sections of this manual may not apply to your
unit. This manual has been designed for a general purpose
and describes all options offered by Venmar CES Inc. that
could be included in the unit. Consult the manual from
the component manufacturer if more detailed technical
information about a specific component is required.
All documentation that was specifically designed for your
unit has been included in the pocket of the control panel,
including (and if applicable):
Hazards may exist within this equipment because it contains electrical and powerful moving components. Only
qualified service personnel should install or service this
equipment. Untrained personnel can perform basic maintenance such as maintaining filters. Observe precautions
marked in literature and on labels attached to the unit.
Follow all safety codes.
WARNING
Disconnect the main power switch to the unit before performing service or maintenance. Electric shock can cause
personal injury or death.
Spare parts should be ordered at the time the installation is accepted by the owner. Spare parts will reduce
the down time in the event of a failure. The list of spare
parts outlined below is considered minimal. Installation in
remote locations or when the operation of heating equipment is essential may require more spare parts than listed.
Please contact the service department at Venmar CES for
recommendations.
VCES-V-CUBE-IOM-1A
Minimum spare parts include:
• One matching set of fan belts (belt driven fans only)
• One set of filters
• One set of shell and tube condenser head gaskets
per condenser (water cooled units only)
4
Unit Inspection on Arrival
Inspect the equipment exterior and interior for any damage that may have occurred during unit shipment and for
shipped loose parts. Ensure there is no damage to any
protruding exterior components such as door handles,
disconnect switch handle, etc. or to internal components
such as fans, motors, heat exchanger, dampers and drains.
Unit Application Limitations
CAUTION
Venmar CES equipment is not designed to be used for
temporary heating, cooling and/or ventilation during construction.
Using Venmar CES units for temporary ventilation during construction is subject to the unit warranty terms and
should be reviewed carefully before proceeding, as this
may void the standard warranty conditions.
Installation
Unit Location Requirements
File a claim with the shipping company if the unit is damaged. Check the packing slip against all items received. If
any items are missing sign the carrier’s bill of landing with
the notation “Shipment Received Less Item #_____.” Contact the factory immediately if damage is found. No return
shipment will be accepted without authorization.
Fine dust, larger particulate matter, solvents, varnishes and
other chemicals may cause filter clogging and elevated
cabinet pressures, higher power consumption and possible
irreparable damage to a variety of other key components
that may be present in the system. Potential damages include, but are not limited to, these examples.
Consult local building codes and electrical codes for special installation requirements and note additional requirements listed in this manual. In choosing the installation
location of the unit, consider the following factors:
• The unit should be installed to allow easy access for
maintenance and for systems operation.
• Clearance around the unit should be per the recommended clearances indicated on the mechanical/submittal drawings (varies per unit frame size) in order
to allow easy access for maintenance and for system
operation. For clearances to remove specific components, please consult factory.
• Locate the unit in an area requiring the least amount
of ductwork and direction changes to allow optimum
performance, to reduce pressure loss and to use less
electricity to achieve proper ventilation. Ductwork
must be in accordance with ducting mechanical rules
to prevent sound issues and system effects.
• The unit should be mounted on a level foundation
to allow condensation to flow into internal drains.
The foundation must provide adequate continuous
support to the full perimeter of the base and all cross
members requiring support to minimize deflection
of the unit base frame to not more than 1/16” [1.6
mm] over the entire length and width. In addition to
these recommendations, a Structural Engineer must
be involved to properly size supporting structural elements.
• Once the unit is in place within the mechanical
equipment room, mount the unit on a housekeeping
pad of sufficient height in order to allow for drain
trap height and condensate lines to slope toward the
building drain; install condensate pumps to reduce
height of the housekeeping pads or drill holes in the
concrete pad or mechanical room floor for sufficient
trap height.
VCES-V-CUBE-IOM-1A
5
Rigging, Lifting and Assembling
IMPORTANT
• Carefully read all the instructions contained herein.
Before proceeding with any work, correlate these
instructions with the information provided on the
curb and equipment shop drawing for the specific
project.
• These instructions outline the suggested method of
rigging, lifting and installing a Venmar CES unit. All
local codes and fire regulations must be verified and
adhered to by the Installing Contractor.
• Before assembling, hoisting or setting any pieces of
the supporting curbs or units, verify that the proper
unit is being directed to the correct location, as designated by the architectural and engineering design
drawings.
• Safety first: Ensure that all safety practices recommended by local safety associations are continuously in use.
• If any questions arise during the installation procedure, please contact the factory.
• The Installing Contractor is responsible for the unit
being air and water-tight including all section joints
on the unit.
• All holes that have been made by the Installing or
Electrical Contractor after receiving and installing
the unit must be well sealed to prevent air and/or
water infiltration.
All rigging equipment and labor (as applicable) is provided
by the Installing Contractor as detailed below. It is highly
recommended that extra quantities of all items listed be
on hand. The rigging procedure and/or equipment used to
lift the unit may differ depending on the physical dimensions of the unit, its location, the jobsite, the Installing
Contractor and Crane Operator preferences.
• Lifting crane of the appropriate capacity.
• Adjustable spreader bars.
• Cables (cables, chains or straps).
• All tools required to pull the sections together
(chains, chain blocks, chain type come alongs, etc.).
• All construction equipment and labor required to
complete the work according to local codes.
• Condensate and/or P-trap piping hardware.
• All tools and materials required for level unit installation.
Installation and Assembly Materials for
Multisection (Modular) Units
• Polyvinyl gasket with adhesive strip (½” x 1½” [13 x
38 mm] x required length) applied between unit sections (for split section joints and duct opening connections).
• 3/8” x 2½” Grade 5 full thread zinc plated bolts,
with two washers and one nut each (to secure sections together).
• Adseal 1800 series (from Adchem Adhesives) clear
silicone based sealant or equivalent (for side and top
joints).
Rigging, Lifting and Assembling Instructions
Depending on size, the unit or unit sections of a multi-section (modular) unit will arrive at the jobsite on a standard
flatbed or special low bed trailer. Each unit or unit section
is identified with labels, as per the mechanical drawings.
At ground level, ensure that any crating used for shipping
purposes is removed if there is a possibility that it will interfere with the placing or assembling of the unit or unit
sections on the structural steel or housekeeping pad.
Unit or unit sections shall be lifted by cables attached to all
the lifting lugs. Consult the mechanical drawings located
in the pocket of the control panel for the number of lifting lugs, number of sections and unit weight. For multisection (modular) unit check for additional lugs located
between split sections. Lifting lugs are factory bolted to
the unit or unit section base.
CAUTION
All lifting lugs provided must be used when rigging units
or unit sections. Rigging and lifting unit or unit sections
without using all lifting lugs provided will compromise
the structural integrity of the unit or unit section. Never
lift, rig or ceiling suspend from the top of the unit or unit
sections. Using a forklift or similar device for moving,
lifting or rigging unit or unit sections is prohibited. The
use of a forklift or other similar device is only allowed for
modular unit sections that are mounted on wooden skids
within the factory prior to shipment. The sections must
be forklifted individually along its longest side only.
When lifting the unit or unit sections, use adjustable
spreader bars, pulleys, cables (straps or chains) in order
to properly distribute the load, applying an even vertical
lifting force only at all the lifting lugs to prevent structural
damage to the unit or unit section or prevent cables from
rubbing against the cabinet (see Figure 1). Provide additional blocking and coverings (as required) to prevent
damage to the unit finish and/or components. The adjustable spreader bars are required to maintain a clearance
between the cables and the unit or unit section of at least
12” [305 mm] beyond the sides. Venmar CES will not be
responsible for any damage caused to the unit casing during the lifting process. Main areas where damage may
occur are: electrical panels, filter gauges, roofing corners,
door handles and paint finish. The lifting point must be at
the center of gravity to ensure that the unit or unit section
is level during hoisting and prior to setting. When commencing to hoist, take up the slack in the hoisting cables
slowly and gradually increase the cable tension until the
full unit or unit section weight is suspended. Avoid sudden, jerking movements. Do not permit the unit or unit
VCES-V-CUBE-IOM-1A
6
section to be suspended by the lifting lugs for an extended
See Detail A
period of time. Once the unit or unit section leaves the
trailer, ensure it is level at all times.
Adjustable
spreader bars (typ.)
Pulleys (typ.)
Detail A
Use clevis and
clevis pin to attach
cable to lifting lugs.
12”12”
Pulleys
Adjustable
spreader bars
12” min.
6” max.
Figure 2: Set the next section approximately 6” [152 mm]
from the first section.
3. Corner reinforcement brackets or angle bars may
have been used to support multi-section (modular)
unit walls during transportation, rigging and lifting
at the split. The brackets shown in Figure 3 are for
larger units. Simple angle bars are used for smaller
units (not shown). The corner reinforcement brackets
or angle bars are no longer required after rigging and
lifting and must be removed.
IMPORTANT
After the corner reinforcement brackets or angle bars
have been removed from the split section, set the screws
along with the rubber washers that were holding the
brackets or angle bars back in place for water-tightness.
Figure 1: Use adjustable spreader bars, pulleys and cables
attached to all lifting lugs to apply an even lifting force.
Assembling a Multi-section (Modular) Unit
Special attention must be taken to ensure that a multisection (modular) unit has an air and water-tight seal at
every section split. Follow the next set of instructions for
assembling a multi-section (modular) unit.
1. Remove the yellow lifting lugs located on the section
joint (if any) once the first section is set in place.
IMPORTANT
Yellow lifting lugs located on the section joint (if any)
must be removed once the first section is set in place to
allow the next section to be pulled to the first.
2. Set the second section approximately 6” [152 mm]
from the first section (see Figure 2). Remove the
yellow lifting lugs located on the section joints (if
any) from the second section to allow sections to be
pulled together.
VCES-V-CUBE-IOM-1A
Figure 3: Corner reinforcement brackets or angle bars to
be removed from the split section. Reset the screws with
rubber washer in place for water-tightness.
4. Verify that these two sections are aligned square at
the joint in all three directions.
7
5. For modular integrated water cooled units, the
acoustical butyl sealant
1½”
Detail at A
5b
½” x 1½”
polyvinyl gasket
compressor/condenser section should first be mated
to the coil section as outlined in Figure 2 prior to
mounting the fan section. The internal water and refrigerant piping must then be completed in the field
by the Installing Contractor. Once the field piping
is complete a bead of Adcoustik butyl sealer should
be applied to the top of the condenser/compressor
section as illustrated in Figure 4a. The fan/blower assembly should then be gently lowered on top of the
compressor/condenser section as shown in Figure 4b.
Finally the top and bottom sections should be joined
together with bolts, nuts and washers as per Figure
4c. After reassembly, the unit will require pump
down (evacuation) and refrigerant charging. Factory
shall provide dry nitrogen “holding” charge only. Refrigerant, additional copper piping and insulation for
field connections shall be supplied by others. Filter
drier shall be shipped loose for field installation.
½” [13 mm] bead of
ADBOND 1465
Figure 4c: Secure the top and bottom sections together
with bolts, nuts and washers. Do not over tighten.
6. Install the ½” x 1½” [13 x 38 mm] 6. polyvinyl gasket
with adhesive strip directly on one side of the split
section perimeter frames and middle interior partitions as shown in Figure 5a through Figure 5d.
Figure 4a: Apply a ½” bead of Adcoustik butyl sealer atop
of the condenser/compressor section prior to placing the
fan/blower section above it.
Figure 4b: Gently lower the fan/blower section atop of the
compressor/condenser section.
1½”
A
5a & 5c
5d
Figure 5: General gasket layout
IMPORTANT
Make sure to have full contact between strips wherever a
discontinuity is present, for air- and water-tightness.
¼”
Figure 5a: Install a polyvinyl gasket strip on each vertical
outside wall ¼” [6.4 mm] from the outside side edge from
top to bottom of the side joint. When compressed, a small
gap will remain which will allow the Adseal 1800 series
silicone based sealant or equivalent to seal the vertical side
edges (explained in Figure 8).
VCES-V-CUBE-IOM-1A
8
Bottom
of frame
Top of
frame
7. Use tools (chains, chain blocks, 7. chain type come
along, etc.) connected to the side lifting lugs (attached to the base) on both sides of the unit to pull
the second or next section to the first end section
evenly until both sections are ¼” [6.4 mm] apart on
the full joint perimeter as in Figure 6. Remove any
yellow side lifting lugs that interfere with the chains
for pulling sections together. When joining sections
together, always apply the pulling force to the lifting
lugs attached to the unit structural base, never to the
corner posts and pull uniformly from both sides of
the unit section.
Figure 5b: Install two horizontal polyvinyl gasket strips
along the base frame, one at the top and one at the
bottom of the base frame between the two vertical side
gasket strips so there is full contact between gasket strips
for air- and water-tightness.
Figure 5c: Install one horizontal polyvinyl gasket strip
along the top frame between the two vertical side gasket
strips so there is full contact between gasket strips for airand water-tightness.
IMPORTANT
Unit sections must be drawn together using the lifting
lugs attached to the unit structural base only.
CAUTION
Do not use the vertical side casing framing or bolt holes
to pull sections together as this may cause the corner
posts to warp and break their air- and water-tight seal.
Displacement
Tools supplied
by others
Figure 6: Use tools (chains, chain blocks, chain type come
along, etc.) hooked to the unit lifting lugs attached to the
structural base on both sides of the unit to pull the second
or next section to the first section evenly.
Middle
internal
partition(s)/divider(s)
Figure 5d: Where two or more internal air tunnels/corridors are present, install the gasket strips on the middle
internal horizontal and/or vertical partition(s)/divider(s),
between the perimeter gasket strips so there is full contact
between gasket strips for air- and water-tightness.
VCES-V-CUBE-IOM-1A
8. With the sections pulled together, use the 3/8” x
2½” bolts, nuts and washers to secure the sections
together along the sides as in Figure 7. Start at the
bottom and gradually tighten all bolts to apply an
even load along both sides and along the top (not
at one place) until sections or gasket is compressed
within ¼” [6.4 mm].
9
Figure 7: Secure the sections pulled together with bolts,
1/8” x 1” neoprene
SOFT SEAL gasket
nuts and washers. Do not over tighten.
CAUTION
Do not over tighten the side bolts as this may cause the
corner posts to warp and break their air- and water-tight
seal.
9. After two sections are assembled, verify that the
assembly is level and square. If an adjustment is required, make certain to address it immediately, not at
the end of the final assembly.
10. If multi-section unit has more than two sections follow Steps 1 through 9 for each additional section,
always pulling the next section from the first end section.
11. Apply a generous bead of Adseal 1800 series clear
silicone based sealant (or equivalent) to the exterior
side frame joint seams to completely cover the section split gasket and in such a way that the silicone
bead meets with both frames as in Figure 8. The
bead of clear silicone based sealant should fill the ¼”
gap, as shown in Figure 8.
12. All lifting lugs removed on the exterior of the base
for pulling sections together must be returned or if
not desired the bolts must be set back in place. Once
removed the bolts must be returned and sealed with
clear silicone based sealant for water-tightness. All
other lifting lugs from the unit base may be removed
if desired or left in place. When removing lifting lugs
on the exterior of the base, set the bolts back in
place and seal with clear silicone based sealant for
water-tightness.
Bead of Adseal 1800
clear silicone based
sealant
Figure 9: a) Install the gasket strips on the inside edges
of the inside caps; b) Install caps in place with self-drilling
screws; c) Apply a continuous bead of Adseal 1800 clear
silicone based sealant (or equivalent) to the inside cap
seams and partition(s)/divider(s).
Figure 8: Apply a continuous bead of Adseal 1800 clear
silicone based sealant (or equivalent) to the exterior side
frame joints and for indoor units along the top frame
joints.
VCES-V-CUBE-IOM-1A
¼” bead Adseal
1800 clear silicone
based sealant
10
Suspended Unit Installation
min.
!
To install units that will be permanently suspended, the
units must be set on structural steel beams that are supported by vertical rods. Venmar CES recommends beams
under the full perimeter and all cross members requiring
support. In addition to these recommendations, a Structural Engineer must be involved to properly size the supporting structural elements. Note that the locations of the
beams shall be coordinated with the location of access
doors to prevent any interference (see Figure 10). Single
section unit shown; for multi-sectional unit suspension,
consult factory.
Field Fabricated Ductwork
Anchor
40”
Figure 10: Indoor suspended installation
40”
min.
On indoor or indoor vertical duct connections, make connections to the casing by applying Adseal 1800 silicone
based sealant or equivalent around the connection and
screwing flanged ducts directly to the casing and/or flange
with self-drilling sheet metal screws. It is important to seal
all duct connections to prevent air leakage and system
performance problems. Ductwork must be supported by
the building structure.
For duct connection sizes, see the mechanical drawings.
Insulate and weatherproof all external ductwork, joints
and roof openings with counter-flashing and mastic in
accordance with applicable codes. Ductwork running
Electrical Connections
WARNING
When installed, the unit must be electrically grounded in
accordance with local codes or, in the absence of local
codes, with the National Electrical Code, ANSI/NFPA70,
and/or the Canadian Electrical Code CSA C22.1. Unit
cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if an
electrical fault should occur. Failure to follow this warning
could result in the installer being liable for personal injury
of others.
The unit is factory wired (unless otherwise specified)
except for power connections, shipping split locations,
shipped loose sensors/items or remote control options
as indicated in the electrical schematics and sequence of
control. The unit may or may not have an optional factory
installed door interlocking disconnect in the control panel.
through roof decks must comply with local fire codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
The ventilation system should be designed according to
maximum airflow needs. To minimize noise level and loss
of pressure, ducts should be designed for a maximum air
velocity of 1,200 feet per minute, keeping the direction
and transition changes to a minimum. To further reduce
noise transmission, line the first 15 feet [4,572 mm] of
duct with acoustic insulation. Elbows with a turning radius
equal to or greater than 1, or 90º elbows with turning
vvanes, should also be used.
If the unit control panel disconnect is not supplied the
Electrical Contractor must provide and install disconnect
outside of the unit as per local electrical codes and run the
power supply wiring to the control panel.
• For multi-section (modular) units, the Electrical Contractor must join the low voltage wiring between unit
sections using quick connections supplied by Venmar
CES and join the high voltage wiring between sections at the junction boxes or extend coiled wiring.
• Check nameplate for correct power supply requirements.
• See electrical schematics and sequence of control lo
cated in the control panel pocket for field wiring of
power connections, shipped loose sensors, items or
remote control interlocks. The Electrical Contractor
must locate, install and wire sensors, items or remote
VCES-V-CUBE-IOM-1A
11
control interlocks as per electrical schematics and sequence of control.
• Numbered terminals strips are included in the control
panel for ease of connection and service.
• All field wiring and components must comply with
NEC and local requirements. In Canada, electrical
connections must be in accordance with CSA C22.1
Canadian Electrical Code Part One.
• Install copper wiring of proper size to handle current
load.
• Mounting of field provided components in the control panel is allowed as long as their space was considered during the submittal process. Non considered
electrical components are not allowed in the control
panel. It is the responsibility of the Control Contractor to provide his own power source(s) for any field
added electrical components. The control panel
mounted transformers are not rated for external
components power supply unless otherwise listed on
the electrical schematics.
Electrical Field Connections
Shipped loose sensors, items or remote control wiring
can be located next to the power feed cable provided it
is inserted in shielded cable that will protect it from electromechanical interference. Ensure the power feed cable
ground is securely connected to the terminals located in
the control panel.
Electrical Contractor must provide wiring for controls that
are supplied optionally and shipped loose or field supplied. Mark the electrical schematic with the connections
completed and leave them with the unit for start-up and
service.
CAUTION
High voltage power lines, shipped loose sensors, items
or remote control option field wiring entry points may
only be field extended through the cabinet within designated areas. The unit cabinet and/or floor must be
wisely penetrated in order to keep their integrity. Access
openings in the floor can only be cut or drilled for piping
and wiring (high and low voltage) in the designated rectangular areas within an upturned 1” [25.4 mm] flange
as provided during the submittal process and located on
the mechanical drawings. Access openings must be sized,
field cut or drilled by the Installing Contractor within the
rectangular flanged area then sealed air- and water-tight.
If insulation was removed to create floor access openings,
insulation must be put back in place to avoid condensation. Do not cut or drill holes through floor of unit in non
designated areas without consulting the factory first. The
structural integrity of the floor may be compromised and
possible leaks develop.
VCES-V-CUBE-IOM-1A
12
Coil or Water Cooled Condenser (WCC) Piping Connections
CAUTION
Internal coil (water, steam or non-integrated direct expansion), WCC piping connections within the unit may
only be field extended through the cabinet within designated areas. Connections to the unit coil (water, steam
or nonintegrated direct expansion, WCC) are by others.
External supply and return piping connection, provision,
design and all other safety (such as dielectric couplings
or other), freeze protection or electrical control requirements for system operation are the sole responsibility of
the Installing Contractor and/or Design Engineer. Refer to
ASHRAE handbooks and local building codes for correct
piping and electrical control for proper installations. Refer
to the mechanical drawings for coil performance design
information.
Connections to the unit coil (water, steam or non-integrated direct expansion, WCC or humidifier) are by others.
Refer to the mechanical drawings and the instructions
on the casing for correct orientation of external piping.
External supply and return piping connection, provision,
design and all other safety, freeze protection or electrical
control requirements for system operation are the sole
responsibility of the Installing Contractor and/or Design
Engineer. Refer to ASHRAE handbooks and local building
codes for correct piping and electrical control for proper
installations. Refer to the mechanical drawings for coil performance design information.
For WCC units, see Appendix A. See the piping schematics
for optional piping components and sequence of operation for electrical control options or interlocks supplied
with the unit.
CAUTION
A water and glycol mixture is used for factory tests and
to prevent any possibility of freezing during transit and/
or storage. In units that include factory installed water
piping, some glycol may remain in the system. Flush the
system in the field, prior to installation, if no glycol traces
are desired. In low temperature applications, the water
supply line and return line should be insulated to prevent
condensate and an antifreeze solution should be used to
protect water-to-refrigerant heat exchanger from freezing damage.
IMPORTANT
A hydrostatic test must be performed in the field by the
Installing Contractor at 1.25 times the operating pressure
on all equipment involving piping connections to verify
that the installed unit and its connections to the network
are free of leaks prior to the unit being set in operation.
This test shall be performed after the unit is completely
piped to the network and shall cover the connections
between the unit and the network, as well as all internal
components of the unit.
Condensate Drain Trap and Lines
Cooling coils, humidifiers or other options that can produce condensation are provided with a drain pan with a
1¼” [32 mm] MPT (Male Pipe Thread) drain connection.
A drain trap and condensate line of equal size must be
field provided by the Installing Contractor on the drain
connections and coupled to the building drainage system
to prevent air or sewer gases from being pulled into the
unit caused by the negative (suction) pressure and forcing
water out of the pan into the unit or from air escaping
into the drain caused by positive pressure. See Appendix
B for illustrations and dimensional information on positive
and negative pressure trapping height. Slope the drain
lines downward in direction of flow not less than 1/8” per
foot toward the building drainage system; otherwise, use
a condensate pump. Refer to local codes for proper drainage requirements. Installing a plug for cleaning of the trap
is recommended. Fill the P-traps with water before starting
the unit. Check and clear drains annually at start of cooling season. Drainage problems can occur should drains be
inactive and dry out or due to reduced water flow caused
by buildup of algae. Regular maintenance will prevent
these from occurring.
VCES-V-CUBE-IOM-1A
13
Start-up
Pre Start-up Check
Before requesting start-up, check that the installation is
complete and unit is ready. Complete the pre start-up
below (if items are applicable) and the checklist in Appen-
dix C for each unit. For torque values on set screws, belt
tension, etc. check under Operation and Maintenance.
1. Check the electrical disconnect is in 1. the ‘Off’ position.
2. Check the split section joints are properly installed on
multi-section units.
3. Check that all holes that have been made by the
Installing Contractor after receiving the unit in the
casing, partitions or floor have been well sealed to
prevent air and/or water infiltration.
4. Check the unit for obstructive packaging, objects
near or in fans, dampers, etc.
5. Remove all retaining bolts on fan bases.
a. Check that the fan impellers are rotating freely.
b. Check fan impeller and drive set screws. Tighten
if required.
c. Check the fan bearing set screws or locking col-
lars. Tighten if required.
d. Check fan belt alignment and tension.
6. Check that the air filters are installed and clean.
Replace if necessary. See Appendix D for optional
downstream high efficiency HEPA filter installation (if
supplied).
a. Check all face-mounted filters are attached with
four clips each.
b. Check each sliding filter has a retainer at the end
track and well attached blank-offs.
c. Check that the filter pressure differential gauges,
switches or sensors are free of dirt and set at a
value satisfactory to the end user to trigger a filter change.
7. Check coils if fins have been damaged in shipping,
installation or building construction and are clean.
Straighten fins with fin comb and clean coil if required.
a. Check all pipe connections are tight and that no
damage has occurred during shipping or installation.
b. Check that the piping to the coils and WCC have
been completed, piping lines have been flushed,
filled, vented and tested at 1.25 times the operating pressure.
c. Refer to Appendix A for WCC piping installation
and check that it is complete.
8. Scroll compressor RIS vibration isolator bolts are factory tightened to the correct torque setting for operation and do not require field adjustment.
a. Check that refrigerant components and piping
are in good condition and have no damage or
leaks from shipping or installation.
b. Check that the clearance around the water
cooled condenser (WCC) is in accordance with
minimum recommended clearances.
9. Check motorized damper control arms, control rods
and shafts for tightness.
a. Check that non motorized dampers rotate freely.
10. Check that ductwork is connected, complete and
free of obstructions.
11. Check that condensate drain connections have been
trapped, installed correctly and filled.
12. Check that all shipped loose or field supplied components have been correctly installed and wired.
13. Check that the wiring diagram has been marked up
accordingly and left with the unit.
14. Check that all power supplies and control wiring
have been inspected and approved by the Local Authorities having jurisdiction.
15. Check all factory and field wiring connections for
tightness. Tighten if necessary.
16. Check that all fuses are properly installed in holders.
17. Check the voltage at the disconnect switch against
the nameplate and against phase-to-phase readings
on three-phase. If the voltage is not within 10% of
rated or 2% of phase-to-phase, have the condition
corrected before continuing start-up.
18. Check that all field piping and venting installation
and connections for the heating and cooling options
have been completed and tested.
19. Set the heating and cooling enable switches to the
‘Off’ position.
VCES-V-CUBE-IOM-1A
14
Start-up Procedure
!
To ensure proper operation of each unit, qualified personnel should perform the start-up as outlined below (based
on options included with unit) and complete the Start-up
Report and Checklist in Appendix C for permanent record.
A completed report and checklist will provide valuable information for personnel performing future maintenance.
IMPORTANT
• A completed copy of the Start-up Report and
Checklist must be sent back to the factory for warranty validation and for factory assistance.
• General information on the factory installed and
programmed DDC control system regarding the
navigation and monitoring of the unit with the
standard keypad are provided in separate documents. For more specific information regarding the
sequence of control, the different options of control
or network communications, see these documents
included with the unit in the control panel pocket.
• If units are equipped with compressors, power must
be turned on for 24 hours prior to a call for cooling,
for the compressor crankcase heaters to be energizing to prevent possible damage.
WARNING
• Electric shock can cause personal injury or death.
• Only qualified service personnel should install and
service this equipment.
• The keypad must be used to check operation according to sequence and to adjust setpoints while
power is on for start-up and while performing service.
• All units are factory run tested. Fans, compressors
and condenser fans (if equipped and refrigerant piping is not split for shipment) are set up to run correct
when power is connected. If any one fan is running
backwards or compressor is making loud noises, disconnect power and switch two leads (on three-phase
power) to ensure proper rotation and avoid damage.
With multi-section units with split wiring connections
check rotation of fans, compressors and condenser
fans for correct rotation to ensure wiring connections
are correct.
7. Recheck the voltage at the disconnect switch against
the nameplate and against phase-to-phase readings
on three-phase with all fans operating. If the voltage
is not within 10% of rated or 2% of phase-to-phase
have the condition corrected before continuing startup.
8. Check amperage draw to each motor on each phase
against motor nameplate FLA. If significantly different check ductwork static and/or take corrective action.
9. Feel the compressor crankcases. They should be
warm if the disconnect has been on for at least 24
hours. This will assure that no refrigerant liquid is
present in the crankcase which could cause compressor damage or failure to occur on start-up.
10. Before activating the compressor(s), ensure that any
water shut-off valves are open and that water is
circulating through the water-to-refrigerant heat exchanger. Check the incoming line water pressure to
ensure it is within design and acceptable limits.
11. Enable cooling and check that compressors and condenser fans are rotating in the correct direction.
12. Check if the sound of the compressor is normal or if
there is excessive vibration.
13. Check all field and factory refrigerant and water piping connections for leaks and correct.
14. Check the operation of the control options provided
on the unit.
15. Check the reference setpoints on the keypad operation guide against the sequence of operation, adjust
and record changes as required.
16. When unit has achieved steady state take measurements and complete the readings section of the
start-up report in Appendix C.
17. Set the keypad to each mode of operation and check
the operation according to sequence.
18. For recirculation scheduling mode the outside air and
exhaust air dampers must be adjusted during start-up
to achieve the required outside and exhaust air volumes. See Airflow Balancing for further information.
19. Send copy of the completed start-up reports to Venmar CES to validate warranty. Maintain a copy of the
reports at the unit for future reference.
1. Before proceeding complete the Pre 1. Start-up
Checklist.
2. Check that all access panels or doors are closed.
3. Open the access door to the main control panel to
access the keypad interface device.
4. Bump-start the unit to verify that the fan wheel(s) are
rotating in the correct direction.
5. Set the keypad to occupied mode with heating and
cooling disabled and fan(s) enabled.
6. Check that dampers are operating properly.
VCES-V-CUBE-IOM-1A
15
Airflow Balancing
!
IMPORTANT
Before measuring supply and exhaust flows, the building
must be in its normal state:
• Hermetically close doors and windows.
• Shut down hot air generators and combustion
water heaters.
• Install all ventilation system components: filters,
grilles, diffusers, etc.
For proper performance the unit must operate at the specified supply and exhaust flow rates as shown in the mechanical drawings. Unit fan speed(s) and damper positions
are theoretically set at the factory based on the ductwork
static pressures and flow rates specified in the mechanical
drawings. If conditions change or verification is required,
airflow measurements should be taken using AMCA suggested methods. This would normally be a velocity traverse
measurement or flow measuring station (FMS) installed in
the ducts. Where space is limited in the outdoor air and
exhaust air, pressure drop readings can be taken across
the energy recovery heat exchanger (with economizer heat
recovery bypass dampers closed, if equipped) and com-
pared to the submittal documents. Heat recovery performance is tested in accordance to AHRI Standard 1060 and
is accurate to within +/− 5% if there is no dirt buildup in
the heat recovery heat exchanger. Should flow rates need
to be reset, adjust the outside air, exhaust air or mixed air
dampers, variable speed sheaves, VFD fan speed setpoint
positions or change the sheaves.
Flow measuring stations (FMS) and magnahelic gauges can
also be used to measure supply and exhaust flow. It is important to locate the FMS in the “warm side” ductwork to
minimize the effect of differences in air density, especially
when balancing during extremely cold outside conditions
or to take temperature readings and make the necessary
corrections if installed in the “cold side” ductwork. Air
density variations can affect the FMS by more than 15%.
The FMS should be located downstream in straight sections of duct and not immediately after fans or obstructions that will cause turbulent flow.
If the unit has been in operation before the air balancing,
ensure the unit filters are clean or include pressure drop
readings across the filter banks with the report.
Maintenance
Long-term Storage Maintenance Procedures
WARNING
Many of the following steps need to be performed with
the unit powered off and locked out. Disconnect the
main power switch to the unit before performing service
and maintenance procedures.
Maintenance Summary Chart
Please refer to Appendix G for a recommended list of
routine maintenance items and time intervals. A more detailed description of maintenance items follows.
Please refer to Appendix F: Extended Dormant Unit Maintenance Procedure and Checklist, for maintenance instructions to follow if the unit is to be stored for a period of
time exceeding one month. Following the instructions in
this appendix will assist in preventing potential unit damage that may result from an extended storage period.
VCES-V-CUBE-IOM-1A
16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.