Mammoth 800, 5500 CFM User Manual

Page 1
VHC
!
Energy Recovery Ventilators with Enthalpy Wheels and Integrated Heating and Cooling
Installation, Operation and Maintenance
Capacity: 800 to 5,500 cfm Model: VHC-36, VHC-42, VHC-50
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or death. Read the instal­lation, operation and maintenance instructions in this appendix thoroughly before installing or servicing this equipment.
IMPORTANT
MAMM-VHC-IOM-1A (January 2013)
Page 2
Table of Contents
Table of Contents .................................................................................................................................................................2
Nomenclature .......................................................................................................................................................................3
Safety Considerations ..........................................................................................................................................................4
General Information ..............................................................................................................................................................4
Unit Application Limitations ............................................................................................................................................4
Installation ............................................................................................................................................................................4
Unit Location Requirements ...........................................................................................................................................4
Roofcurbs Supplied by Mammoth (External Applications Only) ..................................................................................... 5
Roofcurbs Supplied by Others .......................................................................................................................................6
Rigging and Placing the Unit ..........................................................................................................................................6
Field Fabricated Ductwork ..............................................................................................................................................6
Hood Installation .............................................................................................................................................................7
Access Panels ................................................................................................................................................................ 7
Internal Packaging ..........................................................................................................................................................7
Electrical Connections .................................................................................................................................................... 8
Water Source Heat Pump (WSHP) Water Piping and Connections .............................................................................10
Condensate Drain Trap ................................................................................................................................................10
Start-up ...............................................................................................................................................................................11
Pre Start-up Procedure ................................................................................................................................................11
Start-up Procedure .......................................................................................................................................................11
Optional Controls and Accessory Sequence and Interlocks ........................................................................................12
Frost Control .................................................................................................................................................................13
Airow Balancing .......................................................................................................................................................... 14
Service................................................................................................................................................................................15
Quarterly Maintenance .................................................................................................................................................15
Annual Maintenance .....................................................................................................................................................15
Coils .............................................................................................................................................................................15
Testing and Replacement of the Damper Actuator ......................................................................................................16
Motor and Blower Removal – Down, Side and End Supply/Exhaust ...........................................................................16
Motor and Blower Service – Down, Side and End Supply/Exhaust .............................................................................16
Belt Tension Adjustment ..............................................................................................................................................17
Plenum Fan and Motor Removal ..................................................................................................................................17
Plenum Fan and Motor Service .................................................................................................................................... 18
Cassette Removal ........................................................................................................................................................18
Cassette Service ..........................................................................................................................................................19
Appendix A: Service Clearance Dimensions ...................................................................................................................... 20
Appendix B: Hood Installation ............................................................................................................................................21
Appendix C: Rigging Drawing.............................................................................................................................................22
Appendix D: Equipment Data .............................................................................................................................................23
Appendix E: Electrical Data ................................................................................................................................................ 24
Appendix F: Terminal Control Diagrams ............................................................................................................................27
Appendix G: Standard Field Wiring (FW) Terminals ..........................................................................................................30
Appendix H: VHC-36, 42 and 50 Start-up Report and Checklist ........................................................................................ 31
Appendix I: Troubleshooting ...............................................................................................................................................35
Appendix J: Electric Heating Coil and Controls Information ............................................................................................... 37
Appendix K: Water Line Field Mounted Options and Accessories .....................................................................................39
Appendix L: Enthalpy Wheel Pressure Drop vs. Flow Formulae and Curves ...................................................................47
Manufacturer reserves the right to discontinue or change specications or designs without notice or obligation.
MAMM-VHC-IOM-1A (JANUARY 2013)
2
Page 3
Nomenclature
VHC-XX
Ventilator with heating and cooling
Nominal wheel diameter – 36 – 42 – 50
©Mammoth Inc. 2012. All rights reserved throughout the world.
Illustrations cover the general appearance of Mammoth products at the time of publication and Mammoth reserves the right to make changes in design and construction at any time without notice.
™® The following are trademarks or registered trademarks of their respective companies: Tefzel from DuPont.
MAMM-VHC-IOM-1A (JANUARY 2013)
3
Page 4
Safety Considerations
!
!
!
Warning, Caution and Important notes appear throughout this manual in specic and appropriate locations to alert In­stalling Contractors and maintenance or service personnel of potential safety hazards, possible equipment damage or to alert personnel of special procedures or instructions that must be followed as outlined below.
WARNING
Identies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Identies an instruction which, if not followed, might se­verely damage the unit, its components, the assembly or nal installation.
General Information
These ventilators can provide 100% outdoor air ventila­tion or, depending on options selected, varying amounts of recirculation between the exhaust and supply airstreams. The VHCs use an enthalpy wheel for total energy recov­ery which provides superior efciency in hot and humid climates. These models are also effective in cold climates and use various types of frost control or defrost to ensure
IMPORTANT
Indicates supplementary information needed to fully com­plete an instruction or installation.
Hazards may exist within this equipment because it con­tains electrical and numerous moving components. Only qualied service personnel should install or service this equipment. Untrained personnel may perform basic main­tenance such as maintaining lters. Observe precautions marked in literature and on labels attached to the unit. Fol­low all safety codes.
WARNING
Disconnect the main power switch to the unit before per­forming service or maintenance. Electric shock can cause personal injury or death.
proper operation when the outside temperatures are ex­tremely low. Units intended for rooftop installations must be installed on a factory or eld supplied roofcurb. This manual contains information on optional components that may or may not be included with this unit. Refer to the sub­mittals for options that pertain to this unit.
Unit Application Limitations
WARNING
Mammoth equipment is not designed to be used for tempo­rary heating, cooling and/or ventilation during construction.
Using Mammoth units for temporary ventilation during construction constitutes a violation of Mammoth warranty terms which indicate that the unit warranty would be void “…if equipment is misapplied or if any alterations are made to the basic design or operating requirements as listed on the original order and shipped from the factory unless
Installation
Unit Location Requirements
Consult local building codes and electrical codes for spe­cial installation requirements and note additional require­ments listed in this manual. In choosing the installation location of the unit, consider the following factors:
approval is received in writing from Mammoth” Fine dust, larger particulate matter, solvents, varnishes and other chemicals may cause lter clogging and elevated cabinet pressures, higher power consumption and possible ir­reparable damage to the desiccant material of the enthalpy wheel, which could reduce energy recovery performance of the wheel and also reduce the heat transfer effectiveness of other components. Potential damages include, but are not limited to, these examples.
• The unit should be installed to allow easy access for maintenance and for systems operation. See the ser­vice clearance dimensions in Appendix A.
• When possible, mount the unit over an unused area such as a hallway. Although fans and motors are mounted on vibration isolators or are dynamically
MAMM-VHC-IOM-1A (JANUARY 2013)
4
Page 5
balanced, the unit will be even less perceptible if posi­tioned away from busy ofces.
• Locate the unit in an area requiring the least amount of ductwork and direction changes to allow optimum performance, to reduce pressure loss and to use less electricity to achieve proper ventilation. Ductwork must be in accordance with ducting mechanical rules to prevent sound issues and system effects.
• The fresh air intake hood must be positioned away from sources of contamination such as hot chimneys or kitchen exhaust vents.
• Fresh air intake must also be positioned in a direction opposite to that of prevailing winds to reduce entry of snow or rain.
• The unit should be mounted on a level foundation to allow condensation to ow into internal drains. The foundation must provide adequate continuous support to minimize deection of the unit base frame to not more than 1/16” [1.6 mm] over entire length. In addi­tion to these recommendations, a Structural Engineer
Roofcurbs Supplied by Mammoth (External Applications Only)
must be involved to properly size supporting structural elements.
• When mounting the unit indoors, if drain connections are required, mount the unit on a housekeeping pad of sufcient height to allow for drain trap height and condensate lines to slope toward the building drain.
• When mounting the unit on a roofcurb check the height from the nished roof to the bottom of the intake hood. Consult with Local Authorities or your building code for minimal intake hood height for the water-tight height from and above the nished roof and in snow prone areas, the buildup of snow, to de­termine the height of the roofcurb. Mammoth optional roofcurbs measure 18” [457 mm] in height. If addi­tional height is required from the nished roof to the top of the roofcurb, to the bottom of the intake hood or if other than level, custom height roofcurbs must be ordered.
Roofcurbs supplied by Mammoth should be mounted as follows:
• The roofcurb is shipped knocked-down with assembly hardware and instructions provided. The roofcurb must be eld erected, assembled and set in place by the Installing Contractor.
• Roofcurb dimensions are submitted with the unit me­chanical drawings which can also be found in the unit control panel pocket or by calling Technical Support personnel from the Mammoth factory.
• After the roofcurb has been assembled, ensure that the roofcurb dimensions suit the unit for which it is designated.
• The cross members must be positioned as per the roofcurb drawing to properly support the ductwork plenums for bottom vertical return and supply connec­tions and for stability.
• Ensure that the assembled roofcurb is square, plumb and level to within 1/16” [1.6 mm] over the entire length. The building structure must provide continu­ous structural support to the full perimeter of the roofcurb and all cross members requiring support. The roofcurb may be shimmed as required to provide continuous support.
• The roofcurb must be fastened to the building struc­ture.
• The Installing Contractor is responsible for mak­ing the roofcurb water-tight by caulking all roofcurb joints.
IMPORTANT
The following items must be completed prior to setting the unit on the roofcurb:
• The roofcurb roong must be completed including insulation, cant strip, ashing and counter-ashing.
• Vertical ductwork must be attached to the roofcurb cross members and building structure, not to the unit. See the mechanical drawings for information on roofcurb installation, recommended ductwork attach­ment and dimensions.
• If there is no building roof access underneath the unit and drain or piping connections must be made (in the roong), it is recommended to do so before unit installation using the appropriate materials pro­vided by the Installing Contractor.
• Remove the length of 3/8” x 1½” [9.5 mm x 38 mm] polyvinyl gasket strip with adhesive backing supplied with the unit and apply a continuous strip to the top perimeter of the roofcurb and duct opening connec­tions for an air and water-tight seal.
IMPORTANT
The gasket between the unit and the roofcurb is critical for an air and water-tight seal. An improperly applied gasket can result in air and water leakage and poor unit perfor­mance. Position the unit with equal spacing all around be­tween the roofcurb and inside unit base rail using ½” [13 mm] wood shims as it is being lowered.
MAMM-VHC-IOM-1A (JANUARY 2013)
5
Page 6
Roofcurbs Supplied by Others
Roofcurbs supplied by others must be designed with the same dimensions and cross member arrangement as per Mammoth roofcurb drawings and must be designed to evenly withstand perimeter and cross section static loads.
Rigging and Placing the Unit
Inspect the equipment exterior and interior for damage and for shipped loose parts. Ensure there is no damage to internal components such as fans, motors, dampers, en­thalpy wheel, insulation and structures. File a claim with the shipping company if the unit is damaged. Check the pack­ing slip against all items received. If any items are missing, sign the carrier’s bill of lading with the notation “Shipment Received Less Item #___.”
IMPORTANT
The hoods for these units are not installed from the fac­tory and must be installed on site. They should be in­stalled after the unit is installed. Hoods are shipped on top of the unit. When rigging the unit, make sure the hoods are secured and are not damaged by the spreader bars.
See Appendix B for hood installation.
IMPORTANT
Mammoth is not liable for any damages, costs or other is­sues arising from roofcurbs supplied by others.
Spreader bars are required to prevent damage to the roof ange. Rollers may be used to move the unit across the roof. Lifting holes are provided in the base rails as shown in
Appendix C. Refer to submittal documents for overall unit
dimensions and Appendix D for unit weights.
CAUTION
All panels must be in place when rigging.
Field Fabricated Ductwork
On vertical discharge units, secure all ducts to the roofcurb and building structure. Do not secure ductwork to the unit. For unit and duct opening sizes see submittal drawings. Insulate and weatherproof all external ductwork, joints and roof openings with counter-ashing and mastic in accor­dance with applicable codes. Ductwork running through roof decks must comply with local re codes. Ducts pass­ing through unconditioned spaces must be insulated and covered with a vapor barrier. Flexible connectors should be installed close to the unit in the duct leading to occupied spaces to minimize noise transmission.
Duct Design Considerations
The discharge ductwork immediately downstream from the fan is critical for successful applications. Poorly designed ductwork can degrade fan performance and contributes to excessive pressure drop and noise.
When designing ductwork in the eld, it is important to use a straight discharge duct of the correct dimensions to obtain maximum fan performance. The straight section of ductwork helps the airow to develop a uniform velocity prole as it exits the fan and allows the velocity pressure to recover into static pressure. See Figure 1.
Centrifugal fan
Figure 1: Duct design
For 100% recovery of velocity pressure into static pres­sure, the straight portion of the discharge duct must be at least 2.5 times the discharge diameter to the length of the straight portion of ductwork.
As an example of how to size the straight portion of duct, assume the fan has a 13.5”x 9.5” discharge outlet = 0.89
Cutoff
100% effective duct length 2½ diameters at 2,500 FPM
Discharge duct
IMPORTANT
This information is referenced from AMCA Fans and Sys­tems Publication 201.
ft2.
MAMM-VHC-IOM-1A (JANUARY 2013)
6
Page 7
Refer to Table 1 for the effect of undersized equivalent duct diameter.
Table 1: Effect of Undersized Equivalent Duct Diameter
Pressure recovery
12%
No Duct
Effective
Duct
0% 50% 80% 90% 100%
25%
Effective
Duct
50%
Effective
Duct
100%
Effective
Duct
Hood Installation
Calculate Equivalent Duct Diameter
The equivalent duct diameter of the fan outlet.
= (4ab + n) = (4 x 13.5 x 9.5)
n
= 12.75 = ~13
So the straight duct length required would be:
= 2.5 x 13 = 32.5” long [2.7 feet]
0.5
0.5
Intake and exhaust hoods for these models are shipped separately from the unit. To install hoods see Appendix B. A quick connect for the damper motors is provided to con-
Access Panels
Handles for lift off exterior access panels with screw door fasteners are provided but must be installed on site. Han­dles and fasteners are secured inside the unit.
Internal Packaging
Open access doors or panels and remove all packaging from the unit. Note that there is packaging for wheel sup­port during shipping. Removal of all packaging is critical.
nect to the main body of the unit. Make sure that all screws are secured to maintain proper support and keep seals water-tight.
IMPORTANT
Securing door fasteners too tightly has negative effects on the door gasket and should be avoided.
MAMM-VHC-IOM-1A (JANUARY 2013)
7
Page 8
Electrical Connections
!
WARNING
When installed, the appliance must be electrically grounded in accordance with local codes or, in the ab­sence of local codes, with the National Electrical Code, ANSI/NFPA70, and/or the Canadian Electrical Code CSA C22.1. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. Failure to follow this warning could result in the Installer being liable for personal injury of others.
Power Supply
Units are available in all voltages and phases. Please see
Appendix E for electrical data. These units may or may not
have a factory installed disconnect switch. If disconnect is eld supplied, provide a disconnect as per local electrical codes and NEC. Use copper conductors only.
All eld wiring must comply with NEC and local require­ments. In Canada, electrical connections must be in accor­dance with CSA C22.1 Canadian Electrical Code Part One.
Units equipped with electric preheaters and/or post heaters have either single-point or two-point power connections.
See Appendix E, submittal data and/or nameplate to de-
termine which. All units equipped with two-point electric heaters require two-point power connection—one to the unit control panel and one to the electric heater fed from a single eld supplied disconnect.
Field Connection
A high voltage connection hole is located on the outside of the unit with knock-out; see submittal drawings for location. A eld installed disconnect switch must use a liquid-tight connector between the disconnect switch and the outside panel of the unit eliminating any water penetration into the control box. A wiring diagram is located within the control panel area of the unit.
A low voltage Field Wiring (FW) interface is provided near the control Panel (PNL) terminals for shipped loose or eld supplied controls, sensors or interlock connections. The location of the eld wiring and panel terminals may vary depending upon options selected as illustrated in Figure 2. The low voltage eld wiring entry is made through the side of the unit below the input power supply connection (see
Appendix G) which runs through the outside casing and
requires a liquid-tight connector or conduit to avoid water penetration.
Installer must provide wiring for controls that are supplied optionally and shipped loose or eld supplied. All eld sup­plied low voltage wiring must be Class 2. Mark the Field Wiring terminals schematic (Appendix G) with the con­nections completed and leave with the unit for start-up and service.
Units will require a start contact interlock from a remote time clock, light sensor, occupancy sensor, manual selec­tor switch or remotely through BACnet from a Building Management System (BMS) depending on ventilation control scheduling mode required. Select required inter­lock and ventilation control scheduling mode from descrip­tion below.
See Appendix F and Appendix G for wiring terminal con-
trol diagram examples and standard Field Wiring (FW) ter­minal and interlock connections available.
Units Supplied with DDC Control Package
The DDC control package enables stand alone opera­tion of the VHC unit and includes a factory installed, pro­grammed and run tested stand alone microprocessor based controller, all necessary sensors and interfaces to provide control of optional post conditioning functions. See the VHC-36, 42 and 50 DDC Control Package Manual (VCES-DDC-IOM-1 (500020459)) for overview, installation and start-up.
An intelligent programmable interface device (BacStat II) with built in room sensor is included for communication, display, setpoint control and to allow for servicing and is shipped loose for eld wiring and installation at the unit or remotely. Determine required location for installation and connect using two twisted pair cables, the rst for power connection. The LinkNet cable needs to be balanced 100 to 120 ohm nominal impedance twisted shielded pair cable, nominal capacitance of 16 PF/FT or lower.
Units Supplied with an Electro-mechanical Controls (EMC) Package
The EMC controls package or dry contact control option include: all relays, motor starters, motor overloads, damper actuators, heating and cooling initiate contacts and se­lected option pickup points. All necessary connections are wired to a terminal strip in the control panel for eld wiring connections to a Building Management System (BMS), for eld supplied DDC or standard controls and thermostats. See the Control Contractor’s ow and wiring schematics for connection details.
Ventilation Control Scheduling Modes
Occupied Ventilation (Ov)
If the occupancy contact closes or a jumper is placed across terminals FW 304–305 this will enable the unit to run in 100% fresh air mode. Free cooling and defrost will initiate based on the setpoint.
Unoccupied Recirculation (Ur)
If the unoccupied recirculation contact closes or a jumper is placed across terminals FW 305–306 the unit will turn off unless there is a call for heating/cooling or dehumidication across the heating/cooling or dehumidication contacts.
MAMM-VHC-IOM-1A (JANUARY 2013)
8
Page 9
This must come from an optional thermostat or humidistat. The unit will run in recirc mode upon a call.
Occupied Recirculation (Or) (DDC Control Package only)
If the occupied recirculation contact closes or a jumper is placed across terminals, heat wheel starts (not in free cool­ing), defrost recirculation damper closes (if equipped), out­side and exhaust air dampers (if equipped) begin to open; after outside air damper opens fully the supply blower starts; after exhaust air damper opens fully the exhaust blower starts, the occupied recirculation damper opens and outside and exhaust dampers modulate to the minimum setpoints.
Unoccupied (Un)
If the contact opens or jumper removed on any of the ter­minals 304, 305, 306, 307 or 308 the unit will turn off.
PNL
PNL
FW
FW
Figure 2: Possible terminal strip locations in electrical panel
MAMM-VHC-IOM-1A (JANUARY 2013)
9
Page 10
Water Source Heat Pump (WSHP) Water Piping and Connections
[76 mm]
Before connecting piping to the unit, the water supply line and return line must be ushed to eliminate the foreign material. In low temperature applications, the water supply line and return line should be insulated to prevent con­densate and antifreeze solution should be used to protect water-to-refrigerant heat exchanger from freezing damage. See submittal drawings for water piping connection loca­tion. The concentration of water/glycol solution depends on the eld application. On open loop systems, a water strainer (16–20 mesh minimum, 20–40 mesh best) is rec­ommended to be installed in the water inlet line to the unit to eliminate contaminants and it must be used for units having water-to-refrigerant brazed plate heat exchanger. A water ow switch is recommended to be installed in line to prevent possible freeze-up due to loss of water ow. An air vent must be installed on the high side of the water line to discharge the non-condensable air in order to avoid
Condensate Drain Trap
Cooling coil drain pan is provided with a 1¼” MPT drain connection. A drain trap and condensate line of equal size must be eld provided on the drain connection to prevent air or sewer gases from being pulled into the unit caused by the negative (suction) pressure and forcing water out of the pan into the unit.
A label with recommended trap height is provided on the unit as per Figure 3.
Condensate drain must be trapped as shown.
Refer to IOM for further instructions and maintenance.
Le drain de condensation doit être fabriqué et intallé tel que
le croquis ci-bas. Voir le manuel d’installation,
opération et maintenance pour instructions.
Curb
6.578”
[167.08 mm]
support
3.375”
[85.73 mm]
6.0” [191 mm] minimum
unexpected high head pressure and poor cooling/heating performance. Manual shut-off valves are recommended to be installed for the convenience of future service.
A circuit balancing valve with pressure and temperature gauge connections is recommended to be installed in the water line for balancing and service.
See Appendix K for water line eld mounted options and
accessories.
CAUTION
In areas where scaling can become serious, a periodic cleaning for the water-to-refrigerant heat exchanger is recommended. Standard water coil cleaning procedure should be followed which must be done by a qualied ser­vice mechanic.
The trap height allows for the maximum suction pressure after the cooling coil with intake damper, dirty pre and nal high efciency lters, high efciency heat wheel plus 1” w.c. per ASHRAE guidelines for outdoor units with intake hood or indoor unit with up to 0.5” w.c. external static intake duct.
Slope the drain lines downward in direction of ow 1/8 inch per foot referring to local codes for proper drainage require­ments. Installing a plug for cleaning of the trap is recom­mended. Prime the trap by lling with water before start-up. Winterize the drain line before freezing on outdoor units.
Check and clear drains annually at start of cooling sea­son. Drainage problems can occur should drains be in­active and dry out, or due to reduced water ow caused by buildup of algae. Regular maintenance will prevent these from occurring.
Unit baserail
Curb
Figure 3: Condensate drain trap label
MAMM-VHC-IOM-1A (JANUARY 2013)
3.0” minimum
PN 500005436
10
Page 11
Start-up
Pre Start-up Procedure
Before requesting start-up, check that the installation is complete and unit is ready. Complete the pre start-up check list below and in the Appendix H for each unit as items are checked.
1. Set the electrical disconnect to the ‘Off’ position.
2. Check the unit for obstructive packaging, objects near or in blowers, dampers, heat wheel, etc. Remove all red tie down bolts on fan assemblies and heat wheel if so equipped.
3. Check that the fans and heat wheel are rotating freely.
4. Check blower wheels and drive set screws. Tighten if required.
5. Check belt alignment and tension.
6. Check that the air lters are installed and clean. Re­place if necessary.
7. Check coils (if equipped) if ns have been damaged in transit or construction and are clean. Straighten ns with n comb and clean coil if required.
8. Check the refrigerant components and piping that they are in good condition and have no damage or leaks from shipping or installation.
9. Check that the water strainer has been installed for a WSHP with a brazed heat exchanger.
10. Check that ductwork is connected and complete.
11. Check that condensate drain connections have been trapped, installed correctly and lled.
12. Check that all shipped loose or eld supplied compo­nents have been correctly installed and wired and that start interlocks have been completed for the ventilation control desired.
13. Check that the standard eld wiring (FW) terminal diagram has been marked up accordingly and left with the unit.
14. Check that all power supplies and control wiring have been inspected and approved by the Local Authorities having jurisdiction.
15. Check all factory and eld wiring connections for tight­ness. Tighten if necessary.
16. Check that all fuses are properly installed in holders.
17. Check the voltage at the disconnect switch against the nameplate and against phase-to-phase readings on three-phase. If the voltage is not within 10% of rated or 2% of phase-to-phase, have the condition corrected before continuing start-up.
18. Check that all eld piping and venting installation and connections for the heating and cooling options have been completed and test.
19. Set the heating and cooling enable switches to the ‘Off’ position.
Start-up Procedure
To ensure proper operation of each unit, qualied person­nel should perform the start-up and complete the checklist below and the start-up report in Appendix H for permanent record. A completed checklist will provide valuable informa­tion for personnel performing future maintenance.
IMPORTANT
A completed copy must be sent back to the factory for warranty validation and for factory assistance.
All units are factory run tested. Blowers, heat wheel and compressors (if equipped) are set up to run correct when power is connected. If any one blower is running back­wards or compressor is making loud noises disconnect power and switch two leads (on three-phase power) to en­sure proper rotation and avoid damage.
If units are equipped with compressors power must be turned on for 24 hours prior to a call for cooling, for the compressor crank case heaters to be energizing to prevent possible damage.
The BacStat II interface module (if equipped with DDC con­trol package and mounted remotely) may be temporarily connected at the unit for checkout. Ensure it is connected to the Net 2 contacts otherwise it will not give readings.
1. Before proceeding complete the pre start-up check­list.
2. Check that all access panels or doors are closed.
3. Turn the main disconnect to the ‘On’ position.
4. Set the timer, selector switch or BMS contact to the ventilation control scheduling mode selected and check operation according to sequence. Only one of the following modes selected can have their contacts closed or jumped. a. Occupied ventilation (Ov): With the occupancy
contact closed or a jumper placed across termi­nals, heat wheel starts (not in free cooling), de­frost recirculation damper closes (if equipped), outside and exhaust air dampers open fully, the supply blower starts and after exhaust air damper opens fully, the exhaust blower starts.
b. Unoccupied recirculation (Ur): With the unoc-
cupied recirculation contact closed or a jumper
MAMM-VHC-IOM-1A (JANUARY 2013)
11
Page 12
placed across terminals, heat wheel stops, defrost recirculation damper opens, outside and exhaust air dampers (if equipped) begin to close and supply blower starts.
c. Occupied recirculation (Or) (DDC control pack-
age only): With the occupied recirculation contact closed or a jumper placed across termi­nals, heat wheel starts (not in free cooling), de­frost recirculation damper closes (if equipped), outside air damper (if equipped) opens. After outside air damper opens supply blower starts, exhaust air damper (if equipped) opens; after exhaust air damper opens, exhaust blower starts, occupied recirculation damper opens, outside and exhaust air dampers modulate to the damper minimum setpoints.
5. Check that dampers are operating properly.
6. Check that blowers and heat wheel are rotating in the correct direction.
7. For occupied recirculation scheduling mode the out­side air and exhaust air dampers must be adjusted during start-up to achieve the required outside and ex­haust air volumes. See Airow Balancing for further information.
8. Re-check the voltage at the disconnect switch against the nameplate and against phase-to-phase read­ings on three-phase with all blowers operating. If the voltage is not within 10% of rated or 2% of phase-to­phase have the condition corrected before continuing start-up.
9. Check amperage draw to each motor on each phase against motor nameplate FLA. If signicantly different, check ductwork static and/or take correc­tive action.
10. Before activating the compressor on WSHP units, are water shut-off valves open and is water circulating through the water-to-refrigerant heat exchanger.
11. Enable cooling and check if the sound of the compres­sor is normal or if there is excessive vibration.
12. Check all eld and factory refrigerant and water piping connections for leaks and correct.
13. Enable heating options, see start-up and check out in­structions in Appendix J for electric coil and complete.
14. Check the operation of the control options provided on the unit. A functional description is provided below and in the VHC-36, 42 and 50 DDC Control Package Manual.
15. Check the setpoints on the DDC Points Reference, adjust and record changes as required.
16. When unit has achieved steady state take measure­ments and complete the readings section of the start-
up report in Appendix H and send copy of the start-up
report to Mammoth to validate warranty. Maintain a copy of the report at the unit for future reference.
Optional Controls and Accessory Sequence and Interlocks
Free Cooling
Power connected, unit ventilating, free cooling call. Wheel stops rotating.
Variable Speed Setpoint Free Cooling
Power connected, unit ventilating. Wheel modulates to keep discharge temperature air at setpoint.
Unit Fault
An external unit fault can be initiated by removing the dry contact jumper to the eld wire terminal in the control panel. This contact is normally closed and requires an open contact to initiate a fault and shut down the unit.
Dirty Filter Sensor
The VHCs can be equipped with dirty lter sensors which monitor the pressure across the lters and close the con­tacts when the lters become restricted with dirt. Field wired connections can be made to the terminal interface
MAMM-VHC-IOM-1A (JANUARY 2013)
for both the supply and exhaust lter sensors (electro-me­chanical controls [EMC] units only).
Remote Fan Control
Remote fan control can be achieved by connecting dry contacts to the terminal interface (during occupied or un­occupied recirculation). These controls could also be the following: SPDT switch, dehumidistat, CO2 sensor, light sen­sor, heat sensor, timer, Building Management System, etc.
CO2 Ventilation Control
VHCs can be directly controlled by a CO2 controller (acces­sory or eld supplied) that can be connected to the supply and exhaust high speed contact terminals (VFD units only).
As the CO2 levels exceed acceptable limits, dry contacts
close raising high speed fan ventilation. See Appendix F,
CO2 Ventilation Control. Alternatively a eld supplied CO2
controller output can be connected to the BMS which can then be connected to the supply and exhaust fan modu­lating signal input terminals (VFD units only). As the CO2
12
Page 13
levels rise and fall the BMS must modulate the signal to the supply and exhaust fans to change the ventilation rate proportionally. See Appendix G. The minimum VFD speed is factory default set to 40 Hertz.
Smoke Detector
VHCs can be equipped with a duct mount smoke detector which will monitor the air when passing through the duct system into the unit. When sufcient smoke is detected, an alarm condition is activated. By connecting the occupied terminals to the NC alarm auxiliary contacts on the duct sensor, an alarm condition will open the auxiliary contact and stop operation of the VHC. Locate in a normally oc­cupied area of premises. Recommended for compliance to NFPA-90A and IMC code 606.
Cooling Override (DDC Controls Units Only)
These terminals are available for a room or return air sum­mer thermostat. All thermostats are eld installed and wired.
Dehumidication (DDC Controls Units Only)
IMPORTANT
Removal of dry contacts that close on high speed termi­nals is required for VFDs to modulate.
These terminals are available for a room or return air dehu­midistat. All dehumidistats are eld installed and wired.
Heating Override (DDC Controls Units Only)
These terminals are available for a room or return air winter thermostat. All thermostats are eld installed and wired.
For standard eld wiring terminals diagram, refer to Appen-
dix G.
Frost Control
During cold temperatures, defrost and frost prevention are controlled by the unit’s integrated controls as follows.
Preheat will prevent frost formation on the enthalpy wheel to maintain proper operation and provide continuous venti­lation and make-up air. This prevention occurs when a pre­heater is energized to maintain an outdoor air temperature higher or when the wheel speed is reduced to maintain an exhaust air temperature higher than minimum required for the enthalpy wheel to operate frost free.
The requirement for frost control is based upon the outdoor air temperature and humidity content of the return air. In areas where the winter outdoor air condition falls below 5°F [−15°C] or the return air relative humidity is above 30%, frost control is probably required.
Preheat Frost Prevention
Preheat frost prevention is an outdoor air temperature controlled function that allows for continuous ventilation by ensuring a minimum enthalpy wheel entering air tempera­ture of 5° F [−15°C]. The temperature sensor is located be­tween the open wire electric heating coil and the enthalpy
wheel. The electric heating coil is selectable in 1 kW incre­ments and available in two-stage, four-stage or SCR con­trol. With staged control, one stage cycles to maintain 5° F [−15°C] temperature to the enthalpy wheel as the other stages are continuously on as the outdoor air temperature drops. If the selected kW is insufcient, based upon the entered design conditions, selection software automatically
adjusts the minimum kW required to maintain the minimum
wheel entering air temperature.
Non-defrost
No frost control is required in areas where the winter out­door air condition stays above 5°F [−15°C] and the return air humidity level is below 30%.
MAMM-VHC-IOM-1A (JANUARY 2013)
13
Page 14
!
Airow Balancing
IMPORTANT
On initial power up, the unit will perform a system check and operate at high speed for ve seconds.
For proper performance the unit must operate and be balanced at the design supply and exhaust airow rates. Permanent or temporarily eld supplied and installed ow measuring stations (FMS) can be used to measure airow or by using other ASHRAE suggested methods. Where space is limited in the outdoor air or exhaust air ducts for measurements, pressure drop readings can be taken across the enthalpy wheel rotor and airow extrapolated from the curves in Appendix L for the wheel effectiveness category or thickness. Heat recovery performance is tested in accordance to AHRI Standard 1060 and is accurate to within +/− 5% if there is no dirt buildup in the heat recovery wheel rotor.
When FMS are used it is important to locate it in the “warm side” ductwork to minimize the effects of differences in air density especially during cold outside conditions. Air den­sity variations can affect the FMS by more than 15%. The FMS should be located downstream from straight sections of duct and not immediately after fans or obstructions that will cause turbulent ow.
coils or reheat to protect building systems must be eld provided.
Setting Flow Rate
Units supplied with belt driven double width double inlet fans have an adjustable motor sheave factory set at the midpoint of travel at rpm for the ow rate and external static specied. With optional VFD driven motors this factory set­ting is at 60 Hz. For 100% outdoor and exhaust, ow rate should be balanced with motors operating at high speed and at 60 Hz by adjusting the motor sheave pitch diameter. The VFD can be used for ne tuning depending on se­quence.
With the optional direct driven plenum supply fan the VFD is used for speed setting and balancing at the required Hertz.
With the optional internal bypass the airow rate may be reduced. Consult the factory for setting the ow rate during internal bypass.
WARNING
Disconnect the main power switch to the unit before per­forming service and maintenance procedures.
Imbalanced airow may cause supply air temperatures to be below freezing. Adequate freeze protection such as glycol or low limit temperature protection for downstream
MAMM-VHC-IOM-1A (JANUARY 2013)
14
Page 15
Service
Quarterly Maintenance
Quarterly maintenance (every three months) should include:
Air Filters
The standard medium efciency lters and optional high ef­ciency lters are disposable and should be replaced every three months. More frequent replacement may be required under extremely dirty operating conditions.
To replace the lters, open the lter access door, grasp the lters and pull straight out. The lters will slide completely
Annual Maintenance
Annual maintenance should include:
Aluminum Enthalpy Wheel
No cleaning of the enthalpy wheel is required as it is self-cleaning due to the opposing airows. If it is desired to clean the enthalpy wheel, use low pressure air or a vacuum. Wash the cassette panels with a soft cloth and mild cleaning solution. Visually inspect the cassette brush seals (shown in Figure 4), perimeter seal and drive belt for proper operation.
out of the unit. Slide the new lters into the frame and close the lter access door.
Cassette Panels and Interior of Unit
Remove the lters from the unit. Wipe the foil faced insu­lation, or the optional interior galvanized liner, surfaces and cassette panels with a soft cloth and mild cleaning solution.
System Operation Check
Verication of all control modes should be checked to en­sure proper operation. Refer to Start-up section.
Rotor
Brush seal
Fans
Blower wheels and fan housing should be checked for dirt buildup. If they are dirty, it will be necessary to remove the blower assembly to clean the dust out through the fan mouth.
Dirt on the surface of the coil reduces its ability to transfer heat which lowers the efciency of the unit, resulting in poor air quality and expensive operating costs. Because of the condensate on the coil, the dirt often becomes wet and contributes to the growth of microbial organisms. Negligence in maintenance may result in serious health related indoor air quality problems.
The coil should be kept clean for maximum performance. To achieve maximum efciency, clean the coil often during periods of high demand or when dirty conditions prevail. Mammoth recommends cleaning the coil a minimum of once per year to prevent dirt buildup in the coil ns where it may not be visible.
Coil ns can be cleaned by using steam with detergent, hot water spray or a commercial chemical coil cleaner. After cleaning the coil, be sure to rinse thoroughly.
Figure 4: System operation check
Coils
Cleaning Procedure
CAUTION
Do not use acidic chemical coil cleaners. Do not use al­kaline chemical coil cleaners with a pH value greater than
8.5 or lower than 6 (after mixing) without using an alu-
minum corrosion inhibitor in the cleaning solution. Using these types of cleaners may result in unit damage.
1. Shut down the unit by closing the main disconnect at the power inlet.
2. Open panels or doors to gain access to both sides of the coil section.
3. Remove soft debris from both sides of the coil with a soft brush.
MAMM-VHC-IOM-1A (JANUARY 2013)
15
Page 16
WARNING
!
Disconnect the main power switch to the unit before per­forming service and maintenance procedures.
4. Using a steam cleaning machine, clean the leaving airside of the coil rst (going downward) then clean the entering airside. Use a block-off to prevent the steam from penetrating a dry section of the unit.
5. Allow the unit to dry thoroughly before restoring power.
Testing and Replacement of the Damper Actuator
6. Damaged coil ns (excluding brazed aluminum) should be straightened by using a n comb.
7. Close all panels and doors once the coil is dry.
8. Restore electrical power to the unit.
After disconnecting the power from the unit, determine if the actuator is defective. Disconnect the 24 volt power source. Connect the actuator directly to a 24 volt power source with an appropriate cable. If the damper operates correctly, the problem is either in the wiring connections or main circuit board.
Motor and Blower Removal – Down, Side and End Supply/Exhaust
Disconnect the four-wire service connector from the motor (#1, Figure 5). Loosen the four bolts (#2, Figure
5) and all screws that fasten the blower to the ex collar.
Motor and Blower Service – Down, Side and End Supply/Exhaust
The belt tension is adjusted by the positioning of the ro­tating motor base plate. Loosen the two adjustment bolts (#4, Figure 5) on the base plate. Rotate the motor and base plate to achieve the maximum belt deection as described under belt tension adjustment below. Tighten the adjustment bolts (#4, Figure 5). Verify that the sheave and pulley faces are still parallel. The fan rpm can be adjusted to achieve the design airow by setting the adjustable sheave on the motor shaft. The pulley set screw torque setting is 110 in.-lbs to 130 in.-lbs.
If the actuator does not work, it must be replaced. Loosen the nuts on the jack shaft clamp and remove the actua­tor. Tighten the clamp on the damper jack shaft. Test for proper operation.
Slide the fan assembly out of the unit. The fan assembly may have to be lifted over the fan assembly plate bolts (#3, Figure 5).
Figure 5: Motor and blower orientation for down, side and end supply/exhaust options
MAMM-VHC-IOM-1A (JANUARY 2013)
16
Page 17
!
Belt Tension Adjustment
!
WARNING
Disconnect the main power switch to the unit before per­forming service and maintenance procedures.
1. Measure the belt span with a span scale (see Figure
6).
2. Divide the belt span by 64 to determine the belt deec­tion needed to check tension.
3. Set the O-ring on the span scale to the required de­ection value.
4. Set the small O-ring at zero on the force scale.
5. Place the scale end of the tension checker squarely on one belt at the center of the belt span. Apply force on the plunger until the bottom of the large O-ring is even with the top of the next belt or until it is even with a straight edge laid across the sheaves.
6. Read the force scale under the small O-ring to determine the force required to give the needed deection.
7. Compare the force scale reading in Step 6 with the correct value for the belt style and cross section. The force scale reading should be between the minimum and maximum values shown in Table 2.
8. If the deection value is below the minimum, tighten the belts. If the deection value is above the maxi­mum, loosen the belts. The tension on new belts
Plunger with
deflection force scale (lbs)
Small O-ring Large O-ring
Body with deflection
distance scale (inches)
Figure 6: Belt tension adjustment
Table 2: Recommended Deection Force
V-belt
Cross
Sec-
tion
Small
Sheave
Diameter
Range
Recommended Deection Force
(lbs)
Initial
Installation
Re-tensioned
Maximum Minimum
3.0” to 3.4” 3.3 2.9 2.2
3.6” to 4.2” 3.5 3.1 2.4
A
4.6” to 6.0” 3.7 3.3 2.5
4.6” to 5.4” 6.0 5.1 4.0
B
5.6” to 7.4” 6.3 5.5 4.2
8.6” to 9.4” 6.6 5.7 4.4
should be checked during the rst day of operation, at the end of the rst week and monthly thereafter.
Belt Span
Force
Deflection
Plenum Fan and Motor Removal
Disconnect the four-wire service connector between the motor and the VFD (#1, Figure 7). Remove the four bolts (#2, Figure 7) and slide the motor and plenum fan past the inlet cone, then lift out of the unit. A 1¾” socket is required to remove the fan from the motor shaft.
WARNING
No lubrication is necessary during servicing.
MAMM-VHC-IOM-1A (JANUARY 2013)
17
Page 18
Plenum Fan and Motor Service
!
!
!
WARNING
Disconnect the main power switch to the unit before per­forming service and maintenance procedures.
Both motor shaft and fan bore must be completely free of paint, grease, oil and dirt. If necessary, clean the surfaces with non-petroleum based solvent, such as isopropyl alco­hol. Insert the bushing into the fan, making sure the mating hub is ush against the shoulder at the ats. Position the assembly at the desired location on the motor shaft and hand tighten nut (clockwise) until the assembly becomes snug on the shaft.
WARNING
Do not hammer or use any type of impact to force the bushing along the shaft.
WARNING
The shaft must fully engage the shaft gripping area of the bushing.
Using a torque wrench and a 1¾” socket, tighten the nut to the proper installation torque. See Table 3 for torque value.
Table 3: Torque Value
Shaft Size ft-lb
5/8” to 3/4” 100
13/16” to 1” 125
1-1/16” to 1¼” 167
Fan should overlap inlet cone by 3/8” [9 mm] and have a clearance of 1/16” [2 mm]. Motor/fan assembly position is adjustable by loosening the four bolts (#3, Figure 7) and sliding shelf forwards and back.
Figure 7: Plenum fan and motor
Cassette Removal
After disconnecting the power from the unit, open the ser­vice door for the cassette access. Disconnect the service connector between the motor and the control box. Remove the exhaust lters and slide the cassette out of the unit.
MAMM-VHC-IOM-1A (JANUARY 2013)
Take care to not damage the rotor face or any of the cas­sette seals. Proper support must be provided so the cas­sette is not dropped.
18
Page 19
Cassette Service
!
WARNING
Disconnect the main power switch to the unit before per­forming service and maintenance procedures.
Perimeter Seal Replacement
CAUTION
When handling the enthalpy wheel, ensure not to damage the face of the wheel.
To replace the perimeter seal, the enthalpy wheel must be removed from the frame. Disconnect the service connector to the drive motor of the enthalpy wheel cassette. Remove the cassette from the unit and stand the assembly on the oor or roof. Remove the dust cap (#1, Figure 8) from the bearing on the drive motor side of the cassette. Remove the bolt (#2, Figure 8) from the end of the wheel shaft with a socket or wrench on the drive motor side. Repeat this procedure for the other side of the cassette assembly. Re­move the four bolts (#3, Figure 8) with a socket or wrench. Remove the beam and bearing assembly from the end of the wheel shaft. Loosen the four Nyloc nuts (#1, Figure 9) holding the drive motor using a socket or wrench. Rotate the drive motor in the slots to loosen the drive belt and remove the belt. Lift the enthalpy wheel out of the frame with assistance and set aside. Remove the perimeter seal halves (#4, Figure 8) from the cassette frame assembly. Install the two new perimeter seal halves by pressing them into place, cutting to the correct length as is necessary. The perimeter seals are non-adjustable. Complete the installa­tion by reversing the above procedure.
Face Seal Replacement and Adjustment
CAUTION
When handling the enthalpy wheel, ensure not to damage the face of the wheel.
To replace the face seals, the cassette assembly must be removed from the unit. Disconnect the service connector to the drive motor of the enthalpy wheel cassette. Remove the cassette from the unit and stand the assembly up on the oor or roof. Remove the screws holding the face seals (#5, Figure 8). Replace the two seals (supply and exhaust sides), cutting to length as required. Adjust the seals in the slots so that the brush just touches the face of the wheel. Complete the installation by reversing the above proce­dure.
Enthalpy Wheel Drive Belt Replacement and Tensioning Adjustment
CAUTION
When handling the enthalpy wheel, ensure not to damage the face of the wheel.
The enthalpy wheel drive belt can be tightened by slid­ing the cassette assembly only part way out of the unit. Disconnect the service connector to the drive motor of the enthalpy wheel cassette. Slide the cassette assembly out of the unit enough to access the drive motor. Loosen the four Nyloc nuts (#1, Figure 9) holding the drive motor using a socket or wrench. Rotate the drive motor to loosen the belt and replace the belt if necessary. Rotate the drive motor in the slots to tighten the drive belt. Secure the motor in its new location by tightening the four Nyloc nuts (#1, Figure 8). Complete the installation by reversing the above procedure.
Figure 8: Cassette and drive
Figure 9: Tension adjustment
MAMM-VHC-IOM-1A (JANUARY 2013)
19
Page 20
Appendix A: Service Clearance Dimensions
34.0” [864]
Reverse cassette
removal
Exhaust blower
Defrost or unoccupied recirc damper
34.0” [864]
**46.0”
[1,168]
* Clearance for enthalpy wheel removal. ** Clearance for S-OA intake hood.
Supply filters
Electric preheat
34.0” [864]
Enthalpy wheel
Standard cassette
removal
Figure A1: VHC with water source heat pump (WSHP)
*56.0” [1,422]
Occupied
recirc or
return
damper
Cooling/heating coil
*56.0” [1,422]
Power line input control wiring
36.0” [914]
Water inlet and outlet connections
WSHP Module
Supply blower
CompressorCompressor
Control box
Coaxial coil
Exhaust filters
Electric post heat
Note: All dimensions in [ ] are millimeters.
MAMM-VHC-IOM-1A (JANUARY 2013)
20
Page 21
Appendix B: Hood Installation
Figure B1: Outdoor VHC hood installation
IMPORTANT
Complete wire connections between the unit and the hood by matching the correct wire colors on the actuator with the wire colors on the schematic.
MAMM-VHC-IOM-1A (JANUARY 2013)
21
Page 22
Appendix C: Rigging Drawing
Spreader bars
Figure C1: VHC rigging
MAMM-VHC-IOM-1A (JANUARY 2013)
22
Page 23
Appendix D: Equipment Data
Table D1: VHC-36, 42 and 50 Equipment Data
VHC-36 VHC-42 VHC-50
Fans
Supply type – Belt drive, ODP
Wheel type Forward curved Forward curved Forward curved
Bearing Pillow block Pillow block Pillow block
Motor (HP) 0.5 to 5 0.5 to 5 1 to 10
Supply type – Direct drive, ODP
Wheel type Backward inclined airfoil Backward inclined airfoil Backward inclined airfoil
Motor (HP) 0.5 to 5 0.5 to 5 1 to 10
Exhaust type – Belt drive, ODP
Wheel type Forward curved Forward curved Forward curved
Bearing Pillow block Pillow block Pillow block
Motor (HP) 0.5 to 5 0.5 to 5 1 to 10
Energy Recovery Module
4” wheel depth medium efciency
Wheel size 36” x 4” [914 x 102 mm] 42” x 4” [1,067 x 102mm] 50” x 4” [1,270 x 102 mm]
Cassette size
6” wheel depth standard efciency
Wheel size 36” x 6” [914 x 152 mm] 42” x 6” [1,067 x 152 mm] 50” x 6” [1,270 x 152 mm]
Cassette size
8” wheel depth high efciency
Wheel size 36” x 8” [914 x 203 mm] 42” x 8” [1,067 x 203 mm] 50” x 8” [1,270 x 203 mm]
Cassette size
Wheel substrate Aluminum Aluminum Aluminum
Wheel desiccant Silica gel Silica gel Silica gel
Wheel performance 0.20 to 0.90” w.g. 0.20 to 0.90” w.g. 0.30 to 1.00” w.g.
Filters
Supply and return
2” [51 mm] MEF (MERV 7 30–35%) 4” [102 mm] MEF (MERV 7 30–35%)
Supply only
4” [102 mm] prelter MEF (MERV 7 30–35%) 4” [102 mm] prelter HEF (MERV 14 80–85%)
Maximum Weight
Base unit, no heating or cooling 1,800 lbs [818 kg] 2,000 lbs [909 kg] 2,200 lbs [1,000 kg]
WSHP – add 590 lbs [268 kg] 755 lbs [343 kg] 890 lbs [405 kg]
Max unit 2,884 lbs [1,311 kg] 3,351 lbs [1,523 kg] 3,850 lbs [1,750 kg]
Roofcurb – add 210 lbs [95 kg] 250 lbs [114 kg] 270 lbs [123 kg]
40” x 40” x 4.5” [1,016 x 1,016 x 114 mm]
40” x 40” x 6.5” [1,016 x 1,016 x 165 mm]
40” x 40” x 8.5” [1,016 x 1,016 x 216 mm]
1 of 20” x 20” [508 x 508 mm] & 1 of 16” x 20” [406 x 508 mm] 1 of 20” x 20” [508 x 508 mm] & 1 of 16” x 20” [406 x 508 mm]
1 of 20” x 20 “ [508 x 508 mm] & 1 of 16” x 20” [406 x 508 mm] 1 of 20” x 20” [508 x 508 mm] & 1 of 16” x 20” [406 x 508 mm]
46” x 46” x 4.5” [1,168 x 1,168 x 114 mm]
46” x 46” x 6.5” [1,168 x 1,168 x 165 mm]
46” x 46” x 8.5” [1,168 x 1,168 x 216 mm]
1 of 18” x 24” [457 x 610 mm] & 1 of 24” x 24” [610 x 610 mm] 1 of 18” x 24” [457 x 610 mm] & 1 of 24” x 24” [610 x 610 mm]
1 of 18” x 24” [457 x 610 mm] & 1 of 24” x 24” [610 x 610 mm] 1 of 18” x 24” [457 x 610 mm] & 1 of 24” x 24” [610 x 610 mm]
54” x 54” x 4.5” [1,372 x 1,372 x 114 mm]
54” x 54” 6.5” [1,372 x 1,372 x 165 mm]
54” x 54” x 8.5” [1,372 x 1,372 x 216 mm]
4 of 16” x 24” [406 x 635 mm]
4 of 16” x 24” [406 x 635 mm]
4 of 16” x 25” [406 x 635 mm]
4 of 16” x 25” [406 x 635 mm]
MAMM-VHC-IOM-1A (JANUARY 2013)
23
Page 24
Appendix E: Electrical Data
!
Table E1: Full Load Amperage (FLA)
HP
0.5 4.5 4.0 1.8 2.2 1.1 0.9
0.75 5.4 6.0 2.7 2.7 1.4 1.1
1.0 6.8 7.0 3.4 3.4 1.7 1.4
1.5 10.2 10.2 5.0 5.0 2.5 2.0
2.0 14.0 14.0 6.4 6.0 3.0 2.4
3.0 17.8 17.0 10.6 10.6 4.8 3.4
5.0 22.0 22.0 15.3 12.8 6.4 5.1
7.5 32.0 32.0 25.0 19.2 9.6 7.8
10.0 29.3 26.8 13.4 10.3
208/1/60 230/1/60 208/3/60 230/3/60 460/3/60 575/3/60
Blower Motor
Wheel Drive Motor and Controls
2.4 2.2 2.4 2.2 1.1 0.9
The blower motor FLA values show in in the above table are for one motor only.
Voltage
Electric Preheat and Post Heat Calculation
FLA = W / (1.73 x voltage)
IMPORTANT
Electric preheaters and post heaters range from 1 to 120 kW (see below for heater limitations) and actual FLA values of individual heaters will vary based upon the size, tem­perature rise and voltage. Consult the factory for actual FLA values. All electric heaters require three-phase voltage.
WARNING
All units equipped with two-point electric post heaters require two-point power connections, one to the control panel and one to the electric heater fed from a eld sup­plied single disconnect.
CAUTION
All electrical installations and wiring require correct wire gauge sizing and protection according to local building codes.
Electric Preheaters and Post Heaters
Electric preheaters and post heaters are available in:
• Single-point or two-point power connection
• Two-stage, four-stage* or SCR control
IMPORTANT
Four-stage electric post heaters are only available with kW ratings higher than 10 kW.
Electric Heater Performance Calculations
Temperature Rise (°F) = kW x 3,160 cfm
kW = cfm x temperature rise (°F) 3,160
Electric single point preheaters and post heaters have the following limitations:
• 208 VAC – 24 kW maximum
• 230 VAC – 27 kW maximum
• 460 VAC – 67 kW maximium
• 575 VAC – 84 kW maximum
Table E2: Electric Preheater and Post Heater Limitations
VHC-36 up to
VAC
50 kW
24 24 24
208
50 70 120
27 27 27
230
50 70 120
50 70 67
460
50 70 120
50 70 84
575
50 70 120
Shaded areas – single-point post heater limitations White areas – two-point post heater limitations
VHC-42 up to 70 kW
VHC-50 up to 120 kW
• 1 kW increments for all three-phase voltages.
MAMM-VHC-IOM-1A (JANUARY 2013)
24
Page 25
Table E3: Compressor Run Load Amperage (RLA)
Water Cooled Single Circuit
2 Two-stage 16.7 11.2 4.5 3.7
3 Two-stage 16.7 13.5 6.1
4 Two-stage 23.0 17.6 9.2
5 VRC
®
20.4 9.7
6 VRC 23.2 11.2
8 VRC 24.0 12.6
10 VRC 33.3 17.9 12.8
12 VRC 48.1 18.6 14.7
14 VRC 51.3 23.1 19.9
16 VRC 55.8 26.9 23.7
Water Cooled Dual Circuit
6
8
10
12
14
16
21
Crossed out areas indicate unavailable compressor selection. Values indicated are for single compressor only.
On/off 13.2 6.0
VRC 11.7 6.2
On/off 14.5 6.2
VRC 17.9 7.8
On/off 20.5 9.6
VRC 20.4 9.7
On/off 23.2 10.6
VRC 23.2 11.2
On/off 25.0 14.7
VRC 24.0 12.6
On/off 29.5 14.7
VRC 24.0 12.6
On/off 33.3 17.9 12.8
VRC 33.3 17.9 12.8
MAMM-VHC-IOM-1A (JANUARY 2013)
25
Page 26
Table E4:
For Dual Circuit On/off Units
6 tons Two 3 ton on/off compressors
8 tons Two 4 ton on/off compressors
10 tons Two 5 ton on/off compressors
12 tons Two 6 ton on/off compressors
14 tons Two 7 ton on/off compressors
16 tons Two 8 ton on/off compressors
21 tons Two 10 ton on/off compressors
For Dual Circuit VRC® Units
6 tons
8 tons
10 tons
12 tons
14 tons
16 tons
21 tons
One 3 ton on/off compressor One 3 ton VRC compressor One 4 ton on/off compressor One 4 ton VRC compressor One 5 ton on/off compressor One 5 ton VRC compressor One 6 ton on/off compressor One 6 ton VRC compressor One 7 ton on/off compressor One 7 ton VRC compressor One 8 ton on/off compressor One 8 ton VRC compressor One 10 ton on/off compressor One 10 ton VRC compressor
Minimum Current Ampacity (MCA) Calculation
1.25 x FLA of larger hp motor or compressor = _____
1.25 x heater FLA = + _____ Sum of all other motors FLA = + _____ Wheel drive motor and standard controls FLA = + _____ Calculated total MCA = _____
Finding the Actual MOP Value
From the calculated MOP value, select the next smallest value of protection from the Standard Overcurrent Protec­tion chart below to get the actual MOP value (maximum value of overcurrent device).
IMPORTANT
If this method leads to an actual MOP value being smaller than the calculated total MCA, then a larger value must rather be selected, such that the actual MOP is at least equal to the calculated total MCA.
Table E5: Standard Overcurrent Protection
3 40 250
4 45 300
5 50 350
6 60 400
7 70 450
8 80 500
9 90 600
10 100 650
12 110 700
15 125 750
20 150 800
25 175 850
30 200 900
35 225 1,000
Maximum Overcurrent Protection (MOP) Calculation
2.25 x FLA of larger hp motor or compressor = _____ Electric heater FLA = + _____ Sum of all other motors FLA = + _____ Wheel drive motor and standard controls FLA = + _____ Calculated total MCA = _____ Actual MOP (from Table E5) = _____
MAMM-VHC-IOM-1A (JANUARY 2013)
26
Page 27
Appendix F: Terminal Control Diagrams
Occupied Ventilation
Occupied ventilation is achieved by closing the occupancy contact to the terminal interface shown in Figure F1. These terminals require a dry contact which could be provided by a number of types of controls such as a timer, light sensor, occupancy sensor, Building Management System or other. The unit will not operate unless these contacts are closed.
301 302
OCCUPANCY
CR
CONTACT
Note: This is the only connection needed to start single-speed units.
304 305 305 306 307 308 320 321 322 323 324 325 374 375 376 377
12
9
6
234
5
1
301 302 304 305 305 306 307 308 320 321 322 323 324 325 326 327 328 329
Figure F2: Occupied ventilation for DDC controls package and electro-mechanical controls (EMC)
Figure F1: Occupied ventilation for DDC controls package and electro-mechanical controls (EMC)
Occupied Timer Sensor
Occupied ventilation is achieved by connection to the terminal interface shown in Figure F2. These terminals re­quire a dry contact which could be provided by a number of types of controls such as a timer, light sensor, occupancy sensor, Building Management System, or other. The unit will not operate unless these contacts are closed.
IMPORTANT
DDC units can be turned on/off through software.
Unoccupied Recirculation
Supply fan recirculation for heating and cooling can be achieved by connecting dry contact controls to the terminal interface provided in the control panel area. This terminal requires a dry contact closure from a eld provided and wired device.
301 302 304 305
UNOCCUPIED RECIRCULATION
CR
CONTACT (OPTIONAL)
305 306 307 308 320 321 322 323 324 325 326 327 328 329
MAMM-VHC-IOM-1A (JANUARY 2013)
Figure 10: Unoccupied recirculation for DDC controls units
27
Page 28
301
301 302 304 305 305 306 307 308 320 321 322 323 324 325 374 375 376 377
302 304
UNOCCUPIED
CR
RECIRCULATION CONTACT (OPTIONAL)
305 305 306 307 308 320 321 322 323 324 325 326 327 328 329
Figure F3: Unoccupied recirculation for electro-mechanical controls (EMC) units
VFD High Speed Control
High speed fan control can be achieved by connecting dry contact controls to the eld wired (FW) terminals 374 and 375 for the supply fan and 376 and 377 for the exhaust fan. Only VFD units have the high speed option. These controls could also be the following: DPST switch, dehumidistat,
CO2 sensor, light sensor, heat sensor, timer, Building Man-
agement System, etc.
301 302 304 305 305 306 307 308 320 321 322 323 324 325 374 375 376 377
OCCUPANCY
CR
CONTACT
SUPPLY BLOWER
CR
HIGH SPEED CONTACT
EXHAUST BLOWER
CR
HIGH SPEED CONTACT
Figure F4: VFD high speed control
MAMM-VHC-IOM-1A (JANUARY 2013)
CO2 Ventilation Control
VHCs can be directly controlled by a CO2 controller (acces­sory or eld supplied) that can be connected to the supply and exhaust high speed contact terminals (VFD units only).
As the CO2 levels exceed acceptable limits, dry contacts
close raising high speed fan ventilation. See Figure F5. Alternatively a eld supplied CO2 controller output can be connected to the BMS which can then be connected to the supply and exhaust fan modulating signal input terminals (VFD units only). As the CO2 levels rise and fall the BMS must modulate the signal to the supply and exhaust fans to change the ventilation rate proportionally. See Appendix G. The minimum VFD speed is factory default set to 40 Hertz.
IMPORTANT
Removal of dry contacts that close on high speed termi­nals is required for VFDs to modulate.
TB-1
TB-2
TB-1
TB-2
TB-3
RELAY CR1
TB-4
HIGH SPEED
CONTROL
TB-5
Figure F5: CO2 ventilation control
OCCUPANCY
CR
CONTACT
HIGH SPEED CONTROL (SUPPLY BLOWER)
3
RELAY CR1
5
4
RELAY CR1
6
HIGH SPEED CONTROL (EXHAUST BLOWER)
28
Page 29
Smoke Detector
Locate in a normally occupied area of premises. Recom­mended for compliance to NFPA-90A and IMC Code 606.
VHCs can be equipped with a duct mount smoke detector which will monitor the air when passing through the duct system into the VHC. When sufcient smoke is detected, an alarm condition is activated. By connecting the occupied timer/sensor contacts to the NC alarm auxiliary contacts on the duct sensor, an alarm condition will open the auxiliary contact and stop operation of the VHC.
IMPORTANT
This wiring conguration cannot be used on DDC units that are scheduled on/off through software.
1 2 15 16
24V 24V NC C
301 302 410 411
IMPORTANT
On DDC units, there is no dirty lter sensor output to con­nect to. Rather, the dirty lter sensor is connected to the DDC controller and will display a dirty lter alarm on the BacStat II (user interface) when it senses the lter is dirty.
301 302 304 305 305 306 307 308
24 VAC+ OUTPUTS
20 VA MAXIMUM
DIRTY SUPPLY FILTER
DIRTY EXHAUST FILTER
320 321 322 323 324 325 326 327 328 329
Figure F6: Smoke detector
Dirty Filter Sensor
The VHCs can be equipped with dirty lter sensors which monitor the pressure across the lters and close the con­tacts when the lters become restricted with dirt. Field wired connections can be made to the terminal interface for both the supply and exhaust lter sensors.
Figure F7: Dirty lter control
MAMM-VHC-IOM-1A (JANUARY 2013)
29
Page 30
Appendix G: Standard Field Wiring (FW) Terminals
Control Field Wiring (FW)
Low voltage terminal control consists of the following:
Electro-mechanical Controls (EMC) Unit
Inputs
• Occupied ventilation timer/sensor
– Dry contact
• Occupied recirculation (if equipped)
– Dry contact
• Unoccupied recirculation (if equipped)
– Dry contact
• Unit fault
– Dry contact
• Cooling stage 1 (if equipped)
– Dry contact
• Cooling stage 2 (if equipped)
– Dry contact
• Heat enable (if equipped)
– Dry contact
• Modulating heat (if equipped)
– 0 to 10 VDC
• Reheat valve on/off 1 (if equipped)
– Dry contact
• Reheat valve on/off 2 (if equipped)
– Dry contact
• Reheat valve modulating (if equipped)
– 0 to 10 VDC
• Modulating supply motor speed (if equipped)
– 0 to 10 VDC
• Modulating exhaust motor speed (if equipped)
– 0 to 10 VDC
Outputs
• Supply fan on
• Exhaust fan on
• External unit fault
• Defrost on (if equipped with recirculation or exhaust
only defrost options)
• Free cooling on (if equipped with free cooling option)
• Wheel failure (if equipped with wheel rotation sensor option)
• Dirty supply lters (if equipped with dirty lter sensor option)
• Dirty exhaust lters (if equipped with dirty lter sensor option)
• Cooling on (if equipped with cooling)
24 VAC+
24 VAC−
OCCUPANCY
CR
CONTACT
CR
UNOCCUPIED RECIRCULATION CONTACT (OPTIONAL)
COOLING STAGE 1
CR
COOLING STAGE 2
CR
CONTACT (OPTIONAL)
GAS HEAT ENABLE
CR
CONTACT (OPTIONAL)
SCR ELECTRIC POSTHEAT (0–10 VDC+) (OPTIONAL)
SCR ELECTRIC POSTHEAT (0–10 VDC−) (OPTIONAL)
SCR ELECTRIC POSTHEAT (SHIELD) (OPTIONAL)
REHEAT VALVE 1
CR
CONTACT (OPTIONAL)
REHEAT VALVE 2
CR
CONTACT (OPTIONAL)
24 VAC+
OUTPUTS
MAXIMUM
HOT GAS REHEAT MODULATING (0–10 VDC+) (OPTIONAL)
HOT GAS REHEAT MODULATING (0–10 VDC−) (OPTIONAL)
SUPPLY BLOWER MODULATING (0–10 VDC+) (OPTIONAL)
SUPPLY BLOWER MODULATING (0–10 VDC−) (OPTIONAL)
SUPPLY BLOWER MODULATING (SHIELD) (OPTIONAL)
EXHAUST BLOWER MODULATING (0–10 VDC+) (OPTIONAL)
EXHAUST BLOWER MODULATING (0–10 VDC−) (OPTIONAL)
EXHAUST BLOWER MODULATING (SHIELD) (OPTIONAL)
FREE COOLING ON (OPTIONAL)
DIRTY SUPPLY FILTER (OPTIONAL)
DIRTY EXHAUST FILTER (OPTIONAL)
WHEEL FAILURE (OPTIONAL)
SUPPLY BLOWER ON
EXHAUST BLOWER ON
COIL LOW LIMIT (OPTIONAL)
CR
20 VA
CR
CR
ELECTRIC HEAT STAGE 3
CR
CONTACT (OPTIONAL)
ELECTRIC HEAT STAGE 4
CR
CONTACT (OPTIONAL)
COOLING STAGE 1 (ON) (OPTIONAL)
HEATING (ON) (OPTIONAL)
GAS HEAT MODULATING (0–10 VDC−) (OPTIONAL)
GAS HEAT MODULATING (0–10 VDC+) (OPTIONAL)
COOLING STAGE 2 (ON) (OPTIONAL)
COMPRESSOR ONE STATUS (OPTIONAL)
COMPRESSOR TWO STATUS (OPTIONAL)
CR
CR
CR
CONTACT (OPTIONAL)
GAS HEAT STAGE 2 (OPTIONAL)
SCR ELECTRIC HEAT ENABLE CONTACT (OPTIONAL)
ELECTRIC HEAT STAGE 1
CR
CONTACT (OPTIONAL)
ELECTRIC HEAT STAGE 2 CONTACT (OPTIONAL)
SUPPLY BLOWER HIGH SPEED CONTACT (OPTIONAL)
EXHAUST BLOWER HIGH SPEED CONTACT (OPTIONAL)
UNIT FAULT
Figure G1: Electro-mechanical controls (EMC)
301 302 304A 304 305 305 306 307 308 309 310 311 312 313 314 315 320 321 322 324 325 326 329 352 353 354 355 356 357 358 359 360 361 362 363 364 368 370 371 372
373 374 375 376 377 410 411 501 502
502-S 503 504-S 504
IMPORTANT
All output controls are 24 VAC unless otherwise indicated.
MAMM-VHC-IOM-1A (JANUARY 2013)
30
Page 31
Appendix H: VHC-36, 42 and 50 Start-up Report and Checklist
IMPORTANT
• Complete this form for each unit and email, fax or mail to Mammoth immediately after start-up to vali­date warranty and to provide valuable information for personnel performing future maintenance or for fac­tory assistance to address below.
• Read the Installation, Operation and Maintenance Instructions Manual and the VHC-36, 42 and 50 DDC Control Package Manual (if equipped) before proceeding.
• Leave a copy of this report with the owner and at the unit for future reference and permanent record.
• To ensure proper operation of each unit qualied personnel should perform the start-up, complete the checklist and report.
• All units are factory run tested. Blowers, heat wheel and compressors (if equipped) are set up to run correct when power is connected. If any blower is running backwards or compressor is making loud noises disconnect power and switch two leads (on three-phase power) to ensure proper rotation and avoid damage.
• If units are equipped with compressors, power must be turned on for 24 hours prior to a call for cooling for the compressor crank case heaters to be ener­gizing to prevent possible damage.
• The BacStat II interface module (if equipped with DDC control package and mounted remotely) may be temporarily connected at the unit for checkout. Ensure it is connected to the Net 2 contacts other­wise it will not give readings.
Mammoth Inc.
13200 Pioneer Trail, Suite 150 Eden Prairie, MN 55347-4125 Phone: 952-358-6600
Fax: 952-358-6700
Unit Identication Information
Project: _______________________________________ Model Number: _________________________________ Serial Number: __________________________________ Tag: __________________________________________ Jobsite Contact: _________________________________ Job Name: _____________________________________ Job Address: ___________________________________ Telephone: _____________________________________ Email: _________________________________________
Table H1: Pre Start-up Checklist
Checklist Item Yes N/A
1 Is the electrical disconnect set to the ‘Off’ position? 2 Have obstructive packaging, objects, tie downs on fans and heat wheel been removed? 3 Are fans and heat wheel rotating freely? 4 Are fan wheels and drive set screws tight? 5 Are belt alignment and tension correct? 6 Are air lters installed, clean or replaced? 7 Have coils been checked for n damage and dirt, straightened and cleaned? 8 Are refrigerant components and piping in good conditions, no damage or leaks caused by shipment or installation?
9 Has a water strainer been installed for WSHP with brazed heat exchanger? 10 Is ductwork connected and complete? 11 Are condensate drain connections trapped, installed correctly and lled?
Are all shipped loose or eld supplied components correctly installed and wired and are the start interlocks com-
12
pleted for the ventilation control desired?
13 Has the eld wiring (FW) terminal diagram been marked up accordingly and left with the unit? 14 Has power supply and control wiring been inspected and approved by the Local Authorities? 15 Have factory and eld wiring connections been checked and tightened? 16 Are all fuses properly installed in holders? 17 Is voltage at the disconnect switch within 10% of nameplate and phase-to-phase readings within 2% of nameplate? 18 Are eld piping and venting installation and connections for heating and cooling options completed and tested? 19 Are heating and cooling enable switches set to the ‘Off’ position?
MAMM-VHC-IOM-1A (JANUARY 2013)
31
Page 32
Serial Number: __________________________________
Table H2: Start-up Checklist
Checklist Item Yes N/A
1 Before proceeding, complete the pre start-up checklist.
2 Close all access panels or doors.
3 Turn the main disconnect to the ‘On’ position.
Set the timer, selector switch or BMS to close the contact for the scheduling mode desired and check opera­tion and sequence.
Occupied ventilation (Ov): With the occupancy contact closed or a jumper placed across terminals, heat wheel starts (not in free cooling), defrost recirculation damper closes (if equipped), outside and exhaust air dampers (if equipped) begin to open; after outside air damper opens fully the blower starts and after the exhaust air damper opens fully the exhaust blower starts.
Unoccupied recirculation (Ur): With the unoccupied recirculation contact closed or a jumper placed across ter-
4
minals, heat wheel stops, defrost recirculation damper opens, outside and exhaust air dampers (if equipped) begin to close and supply blower starts.
Occupied recirculation (Or) (DDC controls package only): With the occupied recirculation contact closed or a jumper placed across terminals, heat wheel starts (not in free cooling), defrost recirculation damper closes (if equipped), outside air damper (if equipped) opens; after outside air damper opens supply blower starts, exhaust air damper (if equipped) opens. After exhaust air damper opens exhaust blower starts, occupied recir­culation damper opens, outside and exhaust air dampers modulate to the damper minimum setpoints.
5 Are dampers operating properly?
6 Are fans and heat wheel rotating in the correct direction?
For occupied recirculation mode adjust outside air and exhaust air damper positioner to achieve the required
7
air volume. Re-check the voltage at the disconnect switch against the nameplate and against phase-to-phase readings on
8
three-phase with all blowers operating. If the voltage is not within 10% of rated or 2% of phase-to-phase have the condition corrected before continuing start-up. Check amperage draw to each motor on each phase against motor nameplate FLA. If signicantly different
9
check ductwork static and/or take corrective action. Before activating the compressor on WSHP units, are water shut-off valves open and is water circulating
10
through the water-to-refrigerant heat exchanger.
11 Enable cooling and check if the sound of the compressor is normal or if there is excessive vibration.
12 Check all eld and factory refrigerant and water piping connections for leaks and correct.
13
Enable heating options, see start-up and check out instructions in Appendix J for electric coil and complete.
14 Check the operation of the control options provided on the unit.
15 Check the setpoints on the DDC Points Reference, adjust and record changes as required.
16 When unit has achieved steady state take measurements and complete readings section of start-up report.
MAMM-VHC-IOM-1A (JANUARY 2013)
32
Page 33
Start-up Readings
• Allow unit to reach steady state before taking readings.
• Complete based on options included with the unit.
Table H3: Start-up Readings
Mode of Operation Heating Cooling
Nameplate voltage
Power supply
Power supply with all loads
connected
Airside
WSHP waterside
Voltage at discon­nect no motors
Voltage at full load L1/L2/L3
Supply fan
Exhaust fan
Condenser fan #1 amp draw – L1/L2/L3 Condenser fan #2 amp draw – L1/L2/L3
Airow CFM
Temperature °F db/wb
Static pressure
inches w.c.
US GPM Entering temperature – °F Leaving temperature – °F Entering pressure – PSI Leaving pressure – PSI
L1–L2 L2–L3 L1–L3
Fan load amps Amp draw L1/L2/L3 Overload amp setting RPM Hertz Full load amps Am draw L1/L2/L3 Overload amp setting RPM Hertz
Supply Exhaust Occupied recirculation Outdoor entering Supply enthalpy wheel entering Supply enthalpy wheel leaving Cooling coil leaving Heating coil leaving Reheat coil leaving Supply leaving Return entering Exhaust enthalpy wheel leaving
Outdoor duct
Supply enthalpy wheel entering Supply enthalpy wheel leaving Supply fan entering Supply duct Return duct Exhaust enthalpy wheel entering Exhaust enthalpy wheel leaving Exhaust duct
Serial Number: __________________________________
MAMM-VHC-IOM-1A (JANUARY 2013)
33
Page 34
Table H3: Start-up Readings
Circuit #1
Compressor refrigerant
side
Circuit #2
Stage 1 2 3 4 5 6
Electric heating
Amp draw – L1 Amp draw – L2 Amp drave – L3
Serial Number: __________________________________
Mode of Operation Heating Cooling
Discharge pressure – PSI Suction pressure – PSI Discharge temperature – °F Suction temperature – °F Superheat – °F Subcooling – °F
Site glass oil level
Site glass clear __Yes __No Amps – L1/L2/L3 Discharge pressure – PSI Suction pressure – PSI Discharge temperature – °F Suction temperature – °F Superheat – °F Subcooling – °F
Site glass oil level
Site glass clear __Yes __No Amps – L1/L2/L3
__½ __¾ __F
__½ __¾ __F
This unit has been checked out and started according with the above procedures and completed forms and is operating satisfactorily. After 24 hours of satisfactory op­eration, shut down the unit and check all foundation bolts, shaft bearings, drive set screws, valve train and terminals. Tighten where required.
Additional Comments: ____________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
______________________________________________
MAMM-VHC-IOM-1A (JANUARY 2013)
Start-up
By ___________________________________________ Company Name ________________________________ Date __________________________________________ Email _________________________________________ Telephone _____________________________________
34
Page 35
Appendix I: Troubleshooting
Table I1: VHC-36, 42 and 50 Troubleshooting
Problem Cause Solutions
Unit will not turn on.
Unit will not turn off.
Air from supply diffusers too cold. Imbalance of supply and exhaust air.
Unit makes an annoying noise.
Enthalpy wheel freezing.
Enthalpy wheel not running.
Motor and blower not functioning.
Only supply fan will turn on.
Only exhaust fan will turn on.
Damper will not open.
Damper opens when it should be closed.
Compressor will not turn.
Occupancy contact open. Check external wiring. Unoccupied recirc contact open. Check the wiring in the control panel. Occupancy contact closed. Check the external wiring. Unoccupied recirc contact closed. Check the wiring on the control panel.
Check lters and heat exchanger for blockage. Check balance of airows. Install post heat module.
Blower wheel out of alignment.
Enthalpy wheel wiper seal not func­tioning properly.
Imbalance of supply and exhaust air.
Defrost damper not functioning. Check for operation of damper actuator. Preheater not functioning. Check for operation of damper actuator. Unit is in free cooling. Check jumper wire for proper operation. Unit is in recirc defrost. Check unit circuit breaker. Drive motor capacitor failure. Check motor electrical connections.
Drive motor failure.
Drive motor relay in control box. Check relay wiring. Drive belt. Check for drive belt derailment off drive pulley or failure. Drive pulley. Check for securely fastened pulley on motor shaft. Electrical supply interrupted. Check unit circuit breaker. Fan motor capacitor. Check motor electrical connections. Fan motor failure. Check capacitor connections. Fan motor contactor failure. Check contactor wiring. Check contactor operation. Fan drive belt. Check for a tripped overload relay.
Fan drive pulleys.
Unit is in recirc defrost (recirc units). Wait until unit is out of defrost.
Unit is in unoccupied recirc (recirc
units).
Damper end switch not made.
Unit is in defrost (exhaust units). Motor wiring incorrect.
Damper end switch not made. Check exhaust air damper for proper wiring. Electrical supply interrupted. Check wiring on damper actuator. Defrost relay in control box. Check relay wiring. Check relay operation.
Wires are reversed. Reverse wires #2 and #3 on damper actuator.
No power.
Wiring is incorrect. Verify if compressor is wired correctly. Controlled temperature lower (cool­ing) or higher (heating) than thermo­stat setting. Compressor failed. Replace compressor.
Remove the motor/blower assembly. Adjust blower wheel.
Check for proper seal operation.
Check lters and heat exchanger for blockage. Check balance of airows.
Check capacitor connections. Check motor operation with a new capacitor.
Check for securely fastened pulley(s) on motor or fan shaft(s). Set screw setting at 100 in-lbs to 130 in-lbs.
Check external wiring.
Check outdoor air damper for proper wiring. Check that the end switch is making.
Check connection to motor.
Ensure main disconnect is on and measure main termi­nal block for voltage.
Adjust thermostat setting.
MAMM-VHC-IOM-1A (JANUARY 2013)
35
Page 36
Table I1: VHC-36, 42 and 50 Troubleshooting
Problem Cause Solutions
Check if voltage is too low, wiring is incorrect, wire gauge is sized correctly; replace blown fuse. See solution for high pressure switch open and low pressure switch open. Reverse any two phases on the three-phase com­pressor.
Compressor runs but stops quickly.
Compressor makes an abnormal sound.
Overload, fuse burnout.
Low or high pressure switch acti­vated.
Reverse scroll operation.
Compressor quality issue. Replace compressor.
Excessive compressor vibration. Compressor screw is loose. Tighten the screw. Compressor is running but there is no pressure buildup.
Compressor system is normal but amps are too high.
High pressure switch is open in cool­ing operation.
Scroll reverse operation.
Incorrect compressor voltage. Replace with correct voltage compressor.
Lack of water ow (WSHP).
Water ow rate is too small (WSHP).
Condenser is too dirty (AC system). Clean condenser coil. Refrigerant overcharge. Charge correct amount of refrigerant.
Non-condensable air accumulates in the coaxial coil.
Reverse any two phases on the three-phase com­pressor.
Check if the motorized water valve is opening complete­ly and conrm loop water pumps are running. Check if pump sized correctly. If water strainer is in­stalled in line, check if strainer is too dirty.
Vacuum system, recharge refrigerant.
Coaxial coil scaled. Clean coaxial coil.
Check if wiring is correct, replace any failed compo­nents. Check outside air damper operation and replace actua­tor if failed.
Check if components (coil, wheel, lter) are too dirty, motor is running at low speed or not and check if there
High pressure switch is open in heat­ing operation.
Supply fan failure.
Outside air damper not open.
Dx coil is too dirty. Clean Dx coil.
Supply airow is too small.
is too much pressure loss in supply duct.
Refrigerant overcharge. Charge correct amount of refrigerant. TXV failed in closed position. Replace TXV. Supply blower failure. Replace TXV or lter drier.
Low pressure switch is open in cool­ing operation.
Insufcient supply airow.
Loss of refrigerant charge.
Check if components (coil, wheel, lter) are too dirty, motor is running at low speed or not and check if there is too much pressure loss in supply duct. Check and repair any leaks in the piping and rell refrigerant.
TXV failed in closed position. Replace TXV. Blocked TXV or lter drier. Replace TXV or lter drier.
Check if motorized water valve is opening completely and conrm loop water pumps are running. Check if pump is sized correctly or if water strainer is blocked.
Consult factory for operation out of application range.
Check and repair any leaks in the piping and rell refrigerant.
Low pressure switch is open in heat­ing operation.
Lack of water ow (WSHP).
Insufcient water ow (WSHP).
Water entering temperature too low (WSHP).
Loss of refrigerant charge.
MAMM-VHC-IOM-1A (JANUARY 2013)
36
Page 37
Appendix J: Electric Heating Coil and Controls Information
This electric heating coil module covered by this appendix is a component of a “Listed” product, subject to the guide­lines of application as designated by the Certifying Agency and outlined in the appliance Manufacturer’s installation and operation instructions.
The information provided in this appendix applies to the electric heating coil module, installed in the appliance and to its operation, maintenance and service. Refer to the ap­pliance manufacturer’s instructions for information related to all other components.
1 – Mechanical Installation of Electric Coil Heaters
1.1 Handling
1.1.1 Remove the shipping covers just before installa­tion.
1.1.2 Inspect the heater carefully and report any dam­age to the manufacturer.
Do not install a damaged heater.
1.2 Installation
Heater Position
1.2.1 The axis of the duct must always be perpendicular to the face of the heater.
1.2.2 The heating elements must always be installed horizontally.
Model SC or ST (Slip-in Type)
1.2.3 Cut an opening in the side of the duct.
1.2.4 Slip the heater into the duct until the hole is com­pletely covered by anges around the heater.
1.2.5 Fasten the heater to the duct with sheet metal screws and seal openings with a suitable sealing compound.
1.2.6 If the heater is heavy, use additional hangers to support the heater.
Model FC or FT (Flanged Type)
1.2.7 Flange both ends of the duct outwards on three sides to match the heater’s anges.
1.2.8 Fasten the heater to the duct with sheet metal screws (for heavy heaters, use nuts and bolts and additional hangers to support the heater).
IMPORTANT
• Do not install spray humidiers upstream of duct. Install it downstream instead.
• Do not cover the control box with thermal insulating materials.
• Use special air intake louvers of weatherproof con­struction for preheat duct heaters to avoid intake of water or snow particles.
• Make sure that motorized damper blades are not blocked with snow or dirt. Inspect the dampers regu­larly to ensure a suitable airow.
1.2.9 Seal openings with a suitable sealing compound.
2 – Electrical Installation of Electric Coil Heaters
2.1 Disconnect Power Source
Disconnect all power sources before opening the control box and working within.
2.2 Read Nameplate
Read the nameplate carefully and consult wiring diagram before starting to wire.
2.3 Supply Wires
Use only wires suitable for 167°F [75°C]. Wires shall be sized according to the Canadian Electrical Code require­ments. All wires must be brought in through knock-outs.
2.4 Disconnecting Means
Install a disconnect switch close to the heater according to the code unless a disconnect switch is already built into the heater.
2.5 Control Circuit Wiring
Use Class 2 wiring for control circuit connections to the duct heater.
2.6 Magnetic Contactors
If magnetic contactors are mounted outside of the duct heater, use only contactors approved for:
• 250,000 operations when controlled by auto-reset thermal cut-out (A) and by other switching devices in series with this cut-out (thermostat, step controller, airow switch, etc.).
• 100,000 operations when controlled by auto-reset thermal cut-out (A) alone.
• 100,000 operations when controlled by auto-reset thermal cut-out (A) plus manual reset cut-out in series (A & M).
• 6,000 operations when controlled by manual reset cutout (M) alone.
2.7 External Controls Ratings
Rating of external control devices shall be suitable for han­dling the VA ratings as marked on the nameplate; other­wise, a backup relay must be used.
2.8 Airow Interlock
Heaters are generally supplied with one extra terminal marked for fan interlock or air sensing device connection. Remove jumper between terminals I and C before con­necting the fan interlock. Select a suitable airow sensing device of the differential pressure sensing type, with snap acting contacts. A slow make, slow brake device may cause undue cycling and in some instances chattering of the contactors. When fresh air dampers are used, make
MAMM-VHC-IOM-1A (JANUARY 2013)
37
Page 38
sure the heater is properly interlocked to prevent it from being energized before the damper is fully open.
3 – Operating Electric Coil Heaters
3.1 Minimum Airow
Ensure that sufcient airow as marked on the name­plate is passing through the heater. Airow should be evenly distributed across the entire face of the heater. Use air turning vane at duct elbows and splitter damper at duct branch-offs to streamline the airow in the heater. Use suitable airow sensing device or interlock the heater with fan. An insufcient airow will lead to the opening of the auto-reset thermal cut-out or damage to the heating elements.
3.2 Warning
The air owing through the duct where the heater is in­stalled shall not contain any combustible particles, nor any ammable vapor or gas.
3.3 Air Temperature
The air temperature should not exceed 120°F [49°C] at the heater outlet.
3.4 Minimum Static Pressure and Air Direction
The heater is protected by a differential pressure switch. To keep the contact of this switch closed, it is necessary to maintain a minimum total pressure of 0.07” of water for a constant ow.
3.5 Manual Reset Thermal Cut-out
This protection device is standard on all heaters of less than 300 volt and 30 kW and is optional on all other heat­ers. Please check the auto-reset thermal cut-out before re­setting the manual thermal cut-out. If any defect has been detected in the auto-reset thermal cut-out, it will be neces­sary to replace it before resetting the manual reset thermal cut-out.
Two weeks after start-up, all electric connections to contactors should be checked and tightened up. Before each heating season, check the resistance between the heating elements and ground. It is also recommended to check the electrical connections to heating elements, magnetic contactors and main power lugs. This inspection is recommended monthly during the rst four months of operation. After that, two inspections per heating season are sufcient.
4.3 Checkpoints
• Check all fuses.
• Check the resistance to ground for each circuit.
• Check the resistance phase-to-phase for each circuit.
• Check the tightening of connections at all contactors
and heating elements.
• Check all contactors.
4.4 Off-season Maintenance
Where tubular heating elements are used, it is strongly rec­ommended that you start the heating system from time to time. This precaution will prevent moisture from percolating through the terminal gaskets into the heating element and accumulating in the insulating powder. Should a heater be shut off for a long period, we recommend that you check carefully the resistance to ground for each circuit. It is im­portant not to power a heater when too low a resistance to ground has been measured. It is also recommended to pay attention to any other heater operating in normal condi­tions. Control components such as step controllers or mod­ulating valves (SCR) should be maintained and checked according to respective Manufacturer’s instructions. Any defective components should be replaced only with identi­cal original parts.
4 – Maintenance
All electric coil heaters have been designed to operate long term without problems. Those responsible for equipment and maintenance should be aware of the following sugges­tions.
4.1 Visual Inspection
It is strongly recommended to complete a periodic inspec­tion. This precautionary step will help to keep your instal­lations operating well. Note these eventual rst signs of problems:
• Accumulation of dust on the heating elements.
• Signs of overheating on the heater frame.
• Traces of water or rust on the control box.
4.2 Electrical Inspection
MAMM-VHC-IOM-1A (JANUARY 2013)
38
Page 39
Appendix K: Water Line Field Mounted Options and Accessories
IMPORTANT
• Water source heat pump external water supply and return piping shall be in accordance with National and Local Codes. Line sizing, pressure limiting devices, backow preventers, strainers, valves, ow temperature and pressure measuring, freeze protection and all other safety or control piping requirements for system operation are the sole re­sponsibility of the Installing Contractor and/or Design Engineer.
• Some external piping components and control inter­locks are offered as an option or accessory for partly eld and factory installation and are summarized in Table K1. A detailed functional description follows.
• On open loop systems, a eld supplied and installed water strainer (16–20 mesh minimum) is recom­mended in the water inlet or supply line to the unit to eliminate contaminants and must be used for 14, 16 and 21 ton dual circuit WSHP units which utilize a brazed plate heat exchanger condenser.
• Air vents must be eld installed on the high side of the water supply or inlet line to discharge the noncondensable air in order to avoid unexpected high head pressure and poor cooling/heating perfor­mance.
• Manual shut-off valves in supply and return water lines are recommended to be eld installed for isola­tion and service.
• A circuit balancing valve with pressure and tempera­ture gauge connections is recommended to be eld supplied and installed for balancing and service. The water supply must be sized for the minimum ow as indicated on the submittals.
• Prior to connection of condensing water supply, ver­ify water pressure is less than the maximum pres­sure for components in the water line. To prevent injury or death due to instantaneous release of high pressure water, relief valves should be eld supplied and installed in system water piping.
• Maximum working pressure, pressure drop or Cv factors for condenser and optional or accessory components are given in tables below.
Table K1: WSHP Water Line Option or Accessory
Function Field Installed Factory Installed
Head pressure
control
Water shut-off
Freeze protection
Three-way water control valve with modulating actuator
Two-way water shut-off valve with on/off actua-
tor
Water ow switch
Head pressure control DDC program logic Refrigerant pressure
transducer
Water on/off control DDC program logic
Unit on/off control DDC program logic Water outlet tempera-
ture sensor
Functional Descriptions
Head Pressure Control
A three-way modulating head pressure control valve is re­quired to maintain stable operation of the refrigeration sys­tems when operated on ground loop water systems when the design water temperature is below 65°F in the cooling mode. A refrigerant pressure sensor on the compressor discharge is used to modulate the water ow to the con­denser using a 2 to 10 VDC signal to articially keep the compressor discharge pressure at a high enough operat­ing condition to prevent the low pressure refrigerant switch from tripping.
The three-way modulating head pressure control valve consists of a 24 VAC NEMA 1 or 2 modulating actua­tor with a temperature rating of −22°F to 122°F [−30°C to 50°C], nickel plated forged brass valve with stainless steel ball, stem and replaceable valve cartridge assembly which is an option and must be externally eld mounted. For outdoor applications a NEMA 4x rated actuator must be installed. The hydronic valves are intended for use in a normal indoor/outdoor environment for hot or cold water or glycol solutions to 60% concentration with a medium temperature rating of 0°F to 212°F [−18°C to 100°C]. The valve and actuator are preassembled for 100% ow to the coil with minimum of 2 VDC signal. The refrigerant pres­sure sensor is internally factory mounted, prewired and programmed for the DDC to control the three-way valve. A 6 foot coiled wiring harness is factory supplied with the unit, located in the compressor compartment for eld extension and wiring to the actuator.
See Table K2 for three-way valve sizing and performance data. Dimensions, technical and installation data follow. See the wiring schematic for connection and the VHC-36, 42 and 50 DDC Control Package Manual for sequencing information.
Water Shut-off
A two-way motorized on/off water shut-off valve is required to isolate water owing through both the economizer coil (if equipped) and water-to-refrigerant condenser for conser­vation when the unit is off. The water shut-off valve must be placed upstream of the economizer coil and three-way economizer control valve and the three-way modulating head pressure control valve (if equipped). The motorized water valve must open 90 seconds prior to compressor start-up and remain open ve seconds after the compres­sor is shut off.
The two-way motorized water shut-off valve is an acces­sory item and consists of a 24 VAC NEMA 1 or 2 on/off ac­tuator with a temperature rating of −22°F to 122° F [−30°C to 50°C], nickel plated forged brass valve and replaceable valve cartridge assembly which is an accessory and must be externally eld mounted. For outdoor applications a
MAMM-VHC-IOM-1A (JANUARY 2013)
39
Page 40
NEMA 4x rated actuator must be installed. The hydronic valves are intended for use in a normal indoor/outdoor en­vironment for hot or cold water or glycol solutions to 60% concentration with a medium temperature rating of 0°F to 212°F [−18°C to 100°C]. The actuator must be eld wired to the standard eld wiring (FW) terminals #435, 436 and 437 depending on valve size. The valve and actuator are preassembled for 0% ow to the coil when the unit does not require heating or cooling.
See Table K3 for two-way valve sizing, performance data and dimensions; installation and technical data is included with accessory parts. See the wiring schematic for connec­tion information.
Table K2: Three-way Valve Sizing and Performance Data
Tons
2 6 4.3 400 3.0 600 ½
3 9 9.2 400 3.0 600 ½
4 12 3.0 400 4.7 600 ¾
5 15 5.0 400 7.4 600 ¾
6 18 7.0 400 7.4 600 1
8 24 7.7 400 7.4 600 1
10 30 4.3 400 10.0 400 1¼
12 36 7.0 100 19.0 400 1¼
14 42 6.0 400 19.0 400 1¼
*Maximum close off pressure 200 psi.
Minimum US
GPM
Condenser Pressure
Drop (PSI)
Freeze Protection
A water ow switch and a temperature sensor as an op­tion and mounted on the water return or leaving side of the condenser are used to monitor the presence or absence of ow and the water temperature which will shut down the compressor and unit for freeze protection. The ow switch also features an adjustment which allows the user to change the switch from normally open (NO) to normally closed (NC).
The temperature sensor is factory mounted and wired in­ternally. The ow switch must be externally eld mounted in the leaving or return water line and eld wired to the standard eld wiring (FW) terminal strip as per wiring sche­matic. See performance, dimensions and installation data at the end of this appendix.
Condenser
Maximum
Pressure (PSI)
Three-way Head Pressure Control Valve
C
v
Maximum Pressure
(PSI)*
Size FPT
Table K3: Two-way Valve Sizing and Performance Data
Tons
2 6 4.3 400 24 600 ¾
3 9 9.2 400 24 600 ¾
4 12 3.0 400 24 600 ¾
5 15 5.0 400 24 600 ¾
6 18 7.0 400 19 400 1¼
8 24 7.7 400 19 400 1¼
10 30 4.3 400 19 400 1¼
12 36 7.0 100 37 400 1½
*Maximum close off pressure 200 psi.
MAMM-VHC-IOM-1A (JANUARY 2013)
Minimum US
GPM
Condenser Pressure
Drop (PSI)
Condenser
Maximum
Pressure (PSI)
Two-way Water Shut-off Valve
C
v
Maximum Pressure
(PSI)*
Size FPT
40
Page 41
Table K4: Three-way Technical Data
Service Chilled or hot water, 60% glycol
A-port B-port
Flow characteristic
Equal percent­age
Action 90° rotation Sizes ½”, ¾”, 1”, 1¼”, 1½”, 2” Type of end tting NPT female ends Materials
Body Forged brass, nickel plated Ball and stem Stainless steel Seats PTFE Characterizing disc Tefzel
®
Packing 2 EPDM O-rings, lubricated
Body pressure rating 600 PSI 400 PSI
½”–1” 1¼”–2” Media temperature range 0°F to 212°F [−18°C to 100°C] Close off pressure – 200 PSI Maximum differential pres­sure (∆P)
Leakage
½”–2”
30 PSI for typical applications
A to AB B to AB
0% <2%
A-port B-port Cv rating
See product chart
for values
Modied for con­stant common port ow
70% of A to AB Cv
Table K5: Indoor Three-way Valve Actuator Technical and Dimensional Data (2 to 5 tons)
Control On/off, oating point Nominal voltage 24 VAC 50/60 Hz Nominal voltage range 19.2–28.8 VAC Power consumption 1 W Transformer sizing 1 VA (Class 2 power source)
Screw terminals accessible after
Electrical connection
Input impedance 0.36kΩ Angle of rotation 90° Position indication Integrated into handle Manual override Push down handle
Running time
Humidity 5–95% non-condensing Ambient temperature −22° to 122°F [−30°C to 50°C] Storage temperature −40°F to 176°F [−40°C to 80°C] Housing NEMA 1/IP40 Housing rating UL94-5V (B)
Agency listing*
Noise level Max. 35 db (A) Quality standard ISO 9001
*Rated impulse voltage 330V, control pollution degree 2, type of action 1
removal of small cover (3 feet, 10 feet, 16 feet cables optional)
90 seconds at 60 Hz, 108 seconds at 50 Hz
cULusa ac. to UL60730-1A/-2- 14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC
2.50”
[63.5 mm]
2.82”
[71.6 mm]
B
C
3.25”
[82.6 mm]
A
Figure K1: Indoor three-way valve actuator (2 to 5 tons)
Table 4: Indoor Three-way Valve Dimensions (2 to 5 tons)
Value Nominal Size Dimensions (Inches [mm])
Inches DN [mm] A B C
½” 15 mm 2.41” [61.1] 1.39” [35.2] 1.20” [30.6] ½” 15 mm 2.38” [60.4] 1.72” [43.7] 1.26” [32.1] ¾” 20 mm 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
MAMM-VHC-IOM-1A (JANUARY 2013)
41
Page 42
Table K6: Outdoor Three-way Valve Actuator Technical
C
and Dimensional Data (2 to 5 tons)
Control 2–10 VDC, 4–20 mA
Power supply
Power consumption
Transformer sizing 5 VA (Class 2 power source) Electrical connection Screw terminal (for 26–14 GA wire) Overload protection Electronic throughout 0° to 95° rotation Input impedance 100 kΩ [0.1 mA], 500Ω Angle of rotation 90°, adjustable with mechanical stop Direction of rotation Reversible with switch Position indication Visual pointer Manual override External push button
Running time
Humidity 100% RH Ambient temperature −22°F to 122°F [−30°C to 50°C] Storage temperature −40°F to 176°F [−40°C to 80°C]
Housing type
Housing material Polypropylene
Agency listings
Quality standard ISO 9001
2.99”
[76 mm]
0.62” [16 mm]
B
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Running Holding
2.5 W 0.4 W
95 seconds constant independent
of load
UL Type 4X/NEMA 4X/IP66 and
IP67
cULus acc. to UL 60730-1A/- 2-14,
CAN/CSA E60730-1, CSA C22.2
No. 24-93, CE acc. to 89/336/EEC
9.76”
[248 mm]
9.21”
[234 mm]
5.28”
[134 mm]
1.0”
[25.5 mm]
Table K2: Indoor Three-way Valve Actuator Technical and Dimensional Data (6 to 8 tons)
Power supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Operating range Y Feedback output U Input impedance Angle of rotation Direction of rotation Position of indication Manual override Running time
LRB24-SR
LRX24-SR
Humidity
Ambient temperature Storage temperature Housing Housing material
Agency listings
Noise level Quality standard
Electrical connection
2.6”
[66 mm]
24 VAC ± 20% 50/60 Hz 24 VDC ± 10% Running Holding
1.5 W 0.4 W 3 VA (Class 2 power source) ½” conduit connector 18 GA, ple­num rated cable 3 feet [1 m] _3 ft [1 m] _10 ft [3 m] _16 ft [5 m] Electronic throughout 0° to 95°
rotation
2–10 VDC, 4–20 mA 1–10 VDC, max. 0.5 mA 100Ω [0.1 mA], 500Ω 90° adjustable with mechanical stop Reversible with protected switch Handle External push button Constant independent of load
95 seconds
_150 sec. _95 sec. _60 sec. _45 sec. _35 sec. 5% to 95% RH non-condensing (EN
60760-1)
−22°F to 122°F [−30°C to 50°C]
−40°F to 176°F [−40°C to 80°C] NEMA 2/IP54 UL94-5VA cULus acc. to UL60730-1A/-2- 14, CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 9/336/EEC <35 db (A)
ISO 9001
Screw terminal (for 26–14 GA wire) protected (NEMA 2/IP20)
7.97” [200 mm]
C
A
Figure K2: Outdoor three-way valve actuator (2 to 5 tons)
Table K1: Outdoor Three-way Valve Dimensions (2 to 5 tons)
Value Nominal Size Dimensions (Inches [mm])
Inches DN [mm] A B C
½” 15 mm 2.41” [61.1] 1.39” [35.2] 1.20” [30.6] ½” 15 mm 2.38” [60.4] 1.72” [43.7] 1.26” [32.1] ¾” 20 mm 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
1” 25 mm 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
MAMM-VHC-IOM-1A (JANUARY 2013)
3.22”
[82 mm]
B
1.69”
[42 mm]
A
[59.4 mm]
Figure K3: Indoor three-way valve actuator (6 to 8 tons)
Table K3: Indoor Three-way Valve Dimensions (6 to 8 tons)
Value Nominal Size Dimensions (Inches [mm])
Inches DN [mm] A B C
½” 15 mm 2.41” [61.1] 1.39” [35.2] 1.20” [30.6] ½” 15 mm 2.38” [60.4] 1.72” [43.7] 1.26” [32.1] ¾” 20 mm 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
1” 25 mm 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
2.34”
42
Page 43
[134 mm]
Table K4: Outdoor Three-way Valve Actuator Technical and Dimensional Data (6 to 8 tons)
Power supply
Power consumption
Transformer sizing 5 VA (Class 2 power source) Electrical connection Screw terminal (for 26–14 GA wire)
Overload protection
Operating range Y 2–10 VDC, 4–20 mA Input impedance 600Ω Angle of rotation 90° adjustable with mechanical stop Direction of rotation Reversible with switch Position indication Visual pointer Manual override External push button
Running time
Humidity 100% RH Ambient temperature −22°F to 122°F [−30°C to 50°C] Storage temperature −40°F to 176°F [−40°C to 80°C] Housing type UL Type 4X/NEMA 4X/IP66 & IP67 Housing material Polypropylene
Agency listings†
Quality standard ISO 9001
† Rated impulse voltage 800V, type of action 1, control population degree 3.
2.99”
[76 mm]
0.62” [16 mm]
B
C
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Running Holding
2.5 W 0.4 W
Electronic throughout 0° to 95°
rotation
95 seconds constant independent
of load
cULus acc. to UL60730-1A/-2-
14,CAN/CSA E60730-1, CSA C22.2
No. 24-93, CE acc. to 89/336/EEC
9.76”
[248 mm]
9.21”
[234 mm]
1.0”
[25.5 mm]
A
Figure K4: Outdoor three-way valve actuator (6 to 8 tons)
5.28”
Table K6: Indoor Three-way Valve Actuator Technical and Dimensional Data (10 to 21 tons)
Power supply
Power consumption
Transformer sizing 3 VA (Class 2 power source)
Electrical connection
Overload protection
Operating range Y 2–10 VDC, 4–20 mA Feedback output U 1–10 VDC, max. 0.5 mA Input impedance 100Ω [0.1 mA], 500Ω Angle of rotation 90° adjustable with mechanical stop Torque 180 in-lb [20 Nm] Direction of rotation Reversible with switch Position indication Handle Manual override External push button
Running time
Humidity
Ambient temperature −22°F to 122°F [−30°C to 50°C] Storage temperature −40°F to 176°F [−40°C to 80°C] Housing NEMA 2/IP54 Housing material UL94-5VA
Agency listings†
Noise level <45 db (A) Quality standard ISO 9001
† Rated impulse voltage 800V, control pollution degree 3, type of action1 (1.B for -S models)
3.46”
[88 mm]
3.3”
[84 mm]
B
24 VAC ± 20% 50/60 Hz 24 VDC ± 10% Running Holding
2.5 W 0.4 W
½” conduit connector 18 GA ple­num rated cable _3 ft [1 m] _10 ft [3 m] _16 ft [5 m] Electronic throughout 0° to 95°
rotation
95 seconds constant independent
of load 5% to 95% RH non-condensing (EN 60730-1)
cULus acc. to UL60730-1A/-2­14,CAN/CSA E60730-1, CSA C22.2 No. 24-93, CE acc. to 89/336/EEC
8.5” [216 mm]
1.35”
[35 mm]
2.49”
[63.4 mm]
Table K5: Outdoor Three-way Valve Dimensions (6 to 8 tons)
Value Nominal Size Dimensions (Inches [mm])
Inches DN [mm] A B C
1¼” 32 mm 3.96” [100.6] 2.21” [56.2] 2.14” [54.3] 1½” 40 mm 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
2” 50 mm 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
MAMM-VHC-IOM-1A (JANUARY 2013)
C
A
Figure K5: Indoor three-way valve actuator (10 to 21 tons)
Table K7: Indoor Three-way Valve Dimensions (10 to 21 tons)
Value Nominal Size Dimensions (Inches [mm])
Inches DN [mm] A B C
1¼” 32 mm 3.96” [100.6] 2.21” [56.2] 2.14” [54.3] 1½” 40 mm 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
2” 50 mm 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
43
Page 44
Table K8: Outdoor Three-way Valve Actuator Technical and Dimensional Data (10 to 21 tons)
Power supply
Power consumption
Transformer sizing 5 VA (Class 2 power source)
Electrical connection
Overload protection
Operating range Y 2–10 VDC, 4–20 mA Feedback output U 1–10 VDC, max. 0.5 mA Input impedance 100Ω [0.1 mA], 500Ω
Angle of rotation
Torque 160 in-lb [16 Nm] Direction of rotation Reversible with switch Position indication Pointer Manual override External push button
Running time
Humidity
Ambient temperature −22°F to 122°F [−30°C to 50°C] Storage temperature −40°F to 176°F [−40°C to 80°C] Housing IP66/67 UL Type 4X, NEMA 4X Housing material UL94-5VA
Agency listings†
Noise level <45 db (A) Servicing Maintenance free Quality standard ISO 9001 Weight 3.3 lbs [1.5 kg]
† Rated impulse voltage 800V, type of action 1, control pollution degree 3
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Running Holding
2.5 W 0.4 W
Screw termianl (for 26–14 GA wire)
½” conduit connector
Electronic throughout 0° to 95°
rotation
Max 95° adjustable with mechani-
cal stop
95 seconds constant independent
of load
5% to 95% RH non-condensing
(EN 60730-1)
cULus acc. to UL60730-1A/-2-
14,CAN/CSA E60730-1, CSA C22.2
No. 24-93, CE acc. to 89/336/EEC
Table K9: Outdoor Three-way Valve Dimensions (10 to 21 tons)
Value Nominal Size Dimensions (Inches [mm])
Inches DN [mm] A B C
1¼” 32 mm 3.96” [100.6] 2.21” [56.2] 2.14” [54.3] 1½” 40 mm 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
2” 50 mm 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
Table K10: Actuator Specications
Torque 162 in-lbs [18 Nm]
Angle of rotation
95° (adjustable with mechanical
stops)
Fits shaft diameter 9/16”...3/4”
Manual override External push button
Direction of rotation External switch
Dimensions
10.66” x 5.28” x 4.88” [271 x 134 x 124 mm]
Electrical connection Terminal strip
Overload connection Electronic throughout rotation
Add on: 1 or 2 SPDT, 3A (0.5A
Auxiliary switch(es)
inductive) at 250V one switch adjustable 25° to 85°
Housing specications NEMA 4/4X, IP66/IP67
cULus according to UL 30730-
Agency listings
1A/- 2-14, CAN/CSA E60730­1:02, CE according to 2004/108/ EC and 2006/95/EC
Control shaft length
Minimum ¾”
Maximum 2¼”
B
AM..N4
1.52”
2.01”
4.88”
5.15”
9.56”
10.66”
1.10”
5.28”
0.21”
5.52”
4.41”
9/10”...3/4”
3/8”...9/10”
9/10”...3/4”
Figure K6: Outdoor three-way valve actuator (10 to 21 tons)
MAMM-VHC-IOM-1A (JANUARY 2013)
C
Figure K7: Actuator
A
44
Page 45
Water Valve Piping Arrangement
option
ABAAAB
A AB 0%AB 100%
Two-way valves should be installed with the disc upstream.
Flow direction
AAB
Belimo
A
AA
%A
It is important to follow the proper piping arrangement for both two-way and three-way water valves. Incorrect piping arrangements will damage the unit. The eld piping sche­matic is illustrated below.
Correct Piping
1 input, 2 outputs
Return
Refrigerant components
Access valve
P
Switch low optional pressure valve kit
Pressure transducer factory mounted at compressor discharge port
Scroll compressor
Access valves
Crank case heater
P
Switch high pressure
Pressure transducer
P
T
Unit water inlet
Unit water outlet
Head pressure control valve option
Modulating three-way valve
C
Flow switch
H
J
On/off valve accessory
Motorized valve water shut-off
B
B
Field mounted
Strainer
Water inlet
Water inlet
K
A
Figure K8: Water valve piping arrangement
For Two-way Valve
Two-way valves should be installed in accordance to the arrow direction marked on the valve body for the water inlet or supply line. Two-way valves should be installed with the disc upstream. If installed with disc downstream, ow curve will be deeper. If installed “backwards” it is not necessary to remove and change. No damage or control problems will occur.
Figure K9: Two-way valve arrangement
Coil
B
Supply
A
AB
Figure K11: Correct three-way diverting valve piping
Incorrect Piping
1 input, 2 outputs
Return
Coil
A
Supply
B
AB
Figure K12: Incorrect three-way diverting valve piping
Valve and Actuator Installation
Mount the valve directly in the pipe where the assembly will not block the system vent or other components. Do not grip the actuator while making and tightening up plumbing con­nections. Either hold valve body in your hand or attach ad­justable wrench across the hexagonal or at faces on the valve body. If assembling valve train on bench, take care
For Three-way Valve
Three-way valves must be installed with the ‘AB’ marked or common port to the supply water line, the ‘A’ marked or control port to the coil and the ‘B’ marked, ‘Bypass’ or middle port to the return water line.
CAUTION
If the valve is piped incorrectly, it must be re-piped as it may restrict ow and cause damage to the unit.
Diverting
AAB
The A-port must be piped to the coil to maintain proper control.
Figure K10: Three-way valve arrangement
MAMM-VHC-IOM-1A (JANUARY 2013)
B
A
AB 100
B
B
A
B 0%
B
AB 70%AB 0%
B
Figure K13: Valve installation
not to deform the body with a vise.
45
Page 46
A
A-AB = 100%
!
2-7/16” [62 mm]
3
1
A-AB = 100%
CCW
4 x 90°
2
AB
5
B
4
B-AB = 0%
A
AB
One screw attaches
1
actuator to valve
Four actuator mounting
2
positions
3
Two-way flow pattern
Three-way flow pattern
4
(mixing shown)
Top of valve stem indicates
5
direction of flow (Flow A to AB shown)
Note: For diverting flow, flow enters in AB and diverts to A and B ports.
CCW
Figure K14: Valve and actuator assembly and installation
Water Flow Switch
Flow Switch Dimensions
¼ (6) travel to normally closed position
(2) 22 AWG Leadwires 18 (460) long
1/8 NPT – switch shown in normally open position
Lower body
7/8 hex
½ NPTM
Figure K15: Valve and actuator assembly and installation
Flow Switch Installation
The ow switch must be externally eld mounted in the leaving or outlet water line. Before installation, the ow switch vane must be trimmed for the size of piping being used. A full size, trimmable stainless steel vane is provided with a removable laminate template. This template is cali­brated for brass or ductile iron reducing tee and forged steel straight tee/brushing combination which allows for eld installation in pipeline from ½” to 2” diameter. See Table K11 for approximate actuation and deactivation val­ues.
1. Carefully unpack the ow switch and remove any packing material from the lower housing. Trim the vane at the appropriate mark for the size of piping being used.
2¼” [57 mm]
1” [25 mm]
2-7/8” [73 mm]
Vane
WARNING
Mechanical shock or vibration can cause permanent damage to the switch. Avoid dropping the unit on hard surfaces.
2. Apply thread tape or sealant to the ½” male NPT mounting threads and install the ow switch in the sys­tem piping with the arrow on the side pointing in the direction of ow.
3. The ow switch must be eld wired to the standard eld wiring (FW) terminal strip as per wiring schematic for 24 VAC.
4. Avoid exceeding any of the maximum electrical ratings which can lead to failure.
5. After installation, set the switch action to normally open or normally closed. To change the switching from normally open to normally closed, loosen, but do not remove the two screws on the top cap. Slide the reed switch assembly to expose the switch ac­tion selected. Tighten screws when adjustment is
Table K11: Flow Switch Performance Data Table
Cold Water Flow Rates –
Approximate Actuation/Deactuation
Pipe Trim NO NC
½” L
¾” J
1” H
1¼” E
1½” C
2” Full
GPM upper, LPM lower
complete.
2.6/2.3 2.6/2.5
9.8/8.7 9.8/9.5
3.1/2.7 3.1/2.8
11.7/10.2 11.7/10.6
4.8/4.5 4.8/4.4
18.2/17.0 18.2/16.7
6.2/5.6 6.1/5.6
23.5/21.2 23.1/21.2
8.2/7.7 8.2/7.7
31.0/29.1 31.0/29.1
9.5/9.1 9.5/9.0
36.0/34.4 36.0/34.1
MAMM-VHC-IOM-1A (JANUARY 2013)
46
Page 47
Appendix L: Enthalpy Wheel Pressure Drop vs. Flow Formulae and
Curves
Enthalpy Wheel Pressure Drop vs. Flow
Formula
Flow in cfm = pressure drop measured in ” w.c. / pressure drop coefcient based on enthalpy wheel size
Table L1: Enthalpy Wheel Pressure Drop Coefcient
Enthalpy Wheel Size
(diameter x depth in inches)
Pressure Drop
Coefcient
36 x 4 0.00029551
36 x 6 0.00032675
36 x 8 0.00038283
42 x 4 0.00021504
42 x 6 0.00023397
42 x 8 0.00027220
50 x 4 0.00014783
50 x 6 0.00016034
50 x 8 0.00018639
Enthalpy Wheel Pressure Drop vs. cfm
Curves (based on wheel diameter x depth (inches))
1.0
0.9
0.8
0.7
0.6
0.5
0.4
Pressure Drop [in. w.g.]
0.3
0.2
0.1
0.0 0 500 1,000 1,500 2,000 2,500 3,000
Airflow [cfm]
Figure L1: Pressure drop – 36” enthalpy wheel diameter
36” x 8” (High)
36”x 6” (Standard)
36” x 4” (Medium)
1.0
0.9
0.8
0.7
0.6
0.5
0.4
Pressure Drop [in. w.g.]
0.3
0.2
0.1
0.0 0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000
Airflow [cfm]
42” x 8” (High)
42”x 6” (Standard)
42” x 4” (Medium)
Figure L2: Pressure drop – 42” enthalpy wheel diameter
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
Pressure Drop [in. w.g.]
0.3
0.2
0.1
0.0 0 1,000 2,000 3,000 5,000 6,0004,000
Airflow [cfm]
50” x 8” (High)
50”x 6” (Standard)
50” x 4” (Medium)
Figure L3: Pressure drop – 50” enthalpy wheel diameter
MAMM-VHC-IOM-1A (JANUARY 2013)
47
Page 48
[email protected] www.mammoth-inc.com
Mammoth, Inc. has a policy of continuous improvement and reserves
the right to change design and specications without notice.
©2013 Mammoth, Inc.
MAMM-VHC-IOM-1A
January 2013
Loading...