Mammoth G-141-MHC Instructions Manual

Important: These instructions are for the use of
specially trained personnel, experienced in the installation of this equipment and related system components. Some states require licensing of installation and service personnel. Unqualified individuals should not attempt to interpret these instructions or install this equipment. Read instructions carefully before unpacking, installing and operating this heat pump unit.
Inspection: This heat pump has been factory inspected prior to shipment. However, we recommend you check the carton before unloading
WATER SOURCE HEAT PUMPS
100 Percent Outside Air Units Sizes 071 thru 381
Installation, Operation and Maintenance Instructions
Voltage:
F = 208-230/60/3 G = 460/60/3 K = 575/60/3 J = 380/50/3
Unit Size (Nominal Cooling):
071 = 72,250 Btu/hr. cooling 111 = 111,000 Btu/hr.cooling 141 = 148,000 Btu/hr.cooling
181 = 183,000 Btu/hr cooling
221 = 226,000 Btu/hr cooling
271 = 270,000 Btu/hr cooling
321 = 330,000 Btu/hr cooling
381 = 381,000 Btu/hr cooling
Unit Type:
MHC = 100% Outside Air, Standard Temperature Range Design Series “C”
MLC = 100% Outside Air, Low Temperature Geothermal, Design Series “C”
and note any transit damage on all copies of the bill of lading. Also inspect the unit for concealed shipping damage after removing packaging. Transit damage claims must be filed promptly with the freight company by the purchaser.
Handling: Always handle with care and in the horizontal position as shipped on the pallet. Moving the heat pump on its side or dropping it may damage internal parts.
Location: Unit must be installed indoors in any area allowing adequate room for mounting of unit and with access for maintenance and service.
Nomenclature
G - 141 - MHC
Mammoth is committed to a policy of continuous. product improvements, and thus reserves the right to.change specifications and design without notice.
© 1/2003 Mammoth Inc.
(P/N 71144921)
Mammoth Inc.
www.mammoth-inc.com
U-5
2 U-5 IOM
Installation
Definition
Twin circuit 100% Outside Air unit with one fan outlet and two independent refrigerant circuits.
Unit placement – ceiling hung
Mammoth’s 100% outside air heat pump can be hung from the ceiling using the mounting rails attached to the unit and with vibration isolation grommets shipped inside the unit’s electric compartment.
1. Fit the grommets into the
3
4-inch diameter holes
on the mounting rails. Use
5
16-inch or 3⁄8-inch threaded rods (supplied by others) to hang the unit from the ceiling. Cover the entire bottom of the 1
1
4-inch diameter grommet with a washer
(supplied by others).
Figure 1. Ceiling-hung placement
Note: Never attempt to raise, lower or adjust the pitch of the unit by turning the units on the hanger rods without first taking the weight of the unit completely off the vibration isolation grommets.
2. Mount the unit with a 5-degree (maximum) pitch toward the condensate drain connection. Outside air units are available with an optional bottom drain connection. In the ceiling-mounted arrangement this option will allow for more effective condensate removal.
3. See unit data sheet for dimensional information.
Unit placement – slab-mounted
Mammoth’s 100% outside air heat pump can also be installed on a flat level surface. It is recommended that vibration mounts be placed under the unit to prevent transmission of vibrating to the building structure. The standard side drain connection is required in this arrangement.
See unit data sheet for further dimensional details.
Water Out
Water In
Mounting Rail
GROMMET DETAIL
Threaded Rod
(By Others)
Low V oltage
Connection
Main Power Connection
Condensate Connection
Threaded Rod
(By Others)
See Grommet
Mounting Rail
Detail
Base
Retaining Nuts
(By Others)
Mounting Rail
Vibration Isolation Grommet
Washer (By Others) Must Cover
Entire Bottom of Grommet
U-5 IOM 3
Ductwork
Water supply
Fasten the supply ductwork to the collar provided. Use a flexible duct connection between the unit and the supply duct. Make sure the blower wheel turns freely and is centered before making the connection.
If a return air is used, it may be fastened to the flanges on the filter guides. Make sure there is easy access for filter replacement.
The discharge or supply air duct should be insulated and have at least on 90-degree bend prior to the first discharge grille. Heat pump life expectancy and efficiency depends on adequate airflow. For nominal cfm information see unit data sheet.
The heat pump must not be operated without water flowing through its water-to-refrigerant heat exchanger coils. Severe damage to the unit may result.
For proper water flow rates, refer to the unit specification sheet.
Condensate drain
See Figures 2 and 3
The condensate drain is set up for
7
8-inch O.D.
copper connection. The condensate pipe or hose installed must have a minimum 3-inch trap in the condensate line. All condensate piping must pitch
Figure 2. Condensate trap detail – bottom drain
Figure 3. Condensate trap detail – side drain
Application limits
COOLING
STD. TEMP. LOW TEMP.
MINIMUM ENTERING WATER/BRINE 55 F 30 F MAXIMUM ENTERING WATER 110 F 110 F MINIMUM ENTERING AIR 60 F 60 F MAXIMUM ENTERING AIR 100 F 100 F
HEATING
STD. TEMP. LOW TEMP.
MINIMUM ENTERING WATER/BRINE 50 F 25 F MAXIMUM ENTERING WATER 90 F 90 F MINIMUM ENTERING AIR 40 F* 40 F* MAXIMUM ENTERING AIR 80 F 80 F
Only one maximum condition can exist at the same time.
*Note: The minimum entering air temperature must not fall below 40 F.
If the outside air is cooler than 40 F it must be preconditioned or the unit must be shut off. Mammoth offers both optional electric and hot water preheat coils for this situation. See page 5 for additional information on the heaters.
away from the unit for proper drainage by gravity and as required by local codes. Condensate drains are available as either standard side connection or optional bottom connection.
Closed loop systems
1. Unit should be left unconnected or isolated using gate valves as the building water loop is initially flushed.
2. Water system should be filled with 1 lb. trisodium phosphate for every 50 gallons of water.
3. The piping should then be purged of trapped air, supplemental heater set to maintain 110 F and the solution circulated for approximately 8 hours.
4. The system should then be drained completely and the entire flushing process repeated, if necessary.
5. After completely cleaned and drained, fill loop with water at an alkaline level of approximatelly pH 7.5.
6. Connect heat pump the the piping loop.
7. Make sure all entrained air is purged from loop. Determine that specified flow rate through each unit is established.
Bottom of Unit
2-inch Min. Trap
3"
7/8" O.D. Condensate
1.5-inch Min. Internal Trap (By Others)
4 U-5 IOM
Electrical service and fuses
Warning: Turn off electrical power before servicing
controls. Severe electrical shock may result unless power is turned off.
Unit must be installed in compliance with NEC and local codes.
Route wires through a properly sized disconnect switch. Consult the wiring diagrams that are found in this manual and inside the cover of the electrical box to complete the connection. see nameplate for proper fuse sizing, minimum circuit ampacity and voltage requirements. An auxiliary electrical heater must be installed with a power supply separate from the heat pump.
All factory installed electric preheat coils require a separate power supply. See the unit specification sheet for more information.
Control wiring
All of the heat pump functions are controlled by remote thermostat and must be wired as shown, using approved 18-gauge copper wire.
Electric supply
Changing filters
The filters can be accessed from either side of the unit. The filter access panels (see Figure 4) are held in place by several sheet metal screws. After one of the access panels have been removed the filters will slide out.
The same access panel that allows access to the standard 2-inch filters also allows access to the optional 4-inch thick panel filters.
Figure 4. Access panels
Optional hose kits
The flexible water hoses are 2-foot stainless steel hoses for water connections to the heat pump and adapters. Use two properly sized wrenches, one on the unit FPT fitting and one on the hexagonal fitting on the hose, when connecting hoses. Do not use wrench on hose or sleeve that crimps the fitting onto the hose. Hoses must not be subjected to stress of being pulled taut, twisted or kinked. Connections should not be over tightened.
Before pressurizing the water system, closely inspect hoses and fittings to be sure there are no cuts, abrasions, twists, kinks, stretch and hoses will not be in contact with any sharp surface or edge while in use. Also available for heat pumps is a condensate hose and two hose clamps.
For Mammoth hose kit information as to installation and specifications, see data sheets C-91 and C-93.
Preheat Section
Filter Access Section
U-5 IOM 5
Optional preheat section
The preheat section is located after the outside air damper section and the filter section. It can be access via access panels on either side of the heat pump (see Figure 4).
Electric Preheat — Optional
The Mammoth 100% Outdoor Air unit provides optional electric heat to preheat the outdoor air to a point where efficient compressor heating can take place.
The electric heater is a pre-assembled package designed to be installed internal to the unit. The elements are constructed of nichrome wire and include thermal limits, duct high limit, air proving switch, and nonfused disconnect switch. The heater operation is determined by outside air temperature, to maintain a minimum 40 F entering air temperature to the airside coil.The minimum entering air temperature to the air coil is 40 F to allow operation of the mechanical refrigeration for heating.
Figure 5. Optional preheat wiring diagram
The heater includes its own control box separate from the unit’s electrical panel. It is mounted on the outside of the unit casing, which houses all the heater control components and safety devices. The heater is U.L. listed. A separate power source from the unit is required.
Hot Water Preheat — Optional
The Mammoth 100% Outdoor Air unit provides optional hot water coils to preheat cold outdoor air to a point where efficient compressor heating can take place.
The hot water coil is constructed of aluminum fins bonded to seamless copper tubes.
Units with the optional temperature control system include a two-way, two-position, spring return valve actuator. The valve actuator is controlled to maintain a minimum 40 F entering air temperature to the air coil to allow operation of the mechanical refrigeration for heating. A freezestat closes the outdoor air dampers and stops the fan and compressor if mixed air is below 33 F.
6 U-5 IOM
Figure 6. 100% outside air unit wiring diagram
208/230 or 460 VOLTS
60 HERTZ, 3 PHASE
SEE NOTE 2
CIRCUIT #1
COOLING ONLY (FIRST STAGE)
WITH HOT GAS REHEAT
(DEHUMIDIFICATION)
F
SEC
#1
COMPRESSOR
T3
T1
T2
T3
T2 T1
L3 L2
L1
1M
L3
L2
L1
POWER
BLOCK
50 VA
TRANSFORMER
24 VA C
75 VA
TRANSFORMER
24 VA C
TERMINAL
STRIP
24 VA C
COMPRESSOR #1 COMPRESSOR #2
FAN
REVERSING VALVE (CIRCUIT #2)
RESET LIGHT
DEHUMIDIFICATION (CIRCUIT #1)
C1
R
PINK/BLACK STRIPE
Y1
Y2
G
O
L
H
E
C2
1
2
BLUE YELLOW BLUE PINK BLACK PURPLE ORANGE
PINK/BLACK STRIPE
#1
#2
SEE NOTES
1, 4 & 5
SEE NOTES
1, 4 & 5
BLACK
BLACK
BLACK
YELLOW
BLUE
1R
3
1
4
5
2
CS
LP
HP
Loading...
+ 14 hidden pages