Mammoth 800, 5500 CFM User Manual

VHC
!
Energy Recovery Ventilators with Enthalpy Wheels and Integrated Heating and Cooling
Installation, Operation and Maintenance
Capacity: 800 to 5,500 cfm Model: VHC-36, VHC-42, VHC-50
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or death. Read the instal­lation, operation and maintenance instructions in this appendix thoroughly before installing or servicing this equipment.
IMPORTANT
MAMM-VHC-IOM-1A (January 2013)
Table of Contents
Table of Contents .................................................................................................................................................................2
Nomenclature .......................................................................................................................................................................3
Safety Considerations ..........................................................................................................................................................4
General Information ..............................................................................................................................................................4
Unit Application Limitations ............................................................................................................................................4
Installation ............................................................................................................................................................................4
Unit Location Requirements ...........................................................................................................................................4
Roofcurbs Supplied by Mammoth (External Applications Only) ..................................................................................... 5
Roofcurbs Supplied by Others .......................................................................................................................................6
Rigging and Placing the Unit ..........................................................................................................................................6
Field Fabricated Ductwork ..............................................................................................................................................6
Hood Installation .............................................................................................................................................................7
Access Panels ................................................................................................................................................................ 7
Internal Packaging ..........................................................................................................................................................7
Electrical Connections .................................................................................................................................................... 8
Water Source Heat Pump (WSHP) Water Piping and Connections .............................................................................10
Condensate Drain Trap ................................................................................................................................................10
Start-up ...............................................................................................................................................................................11
Pre Start-up Procedure ................................................................................................................................................11
Start-up Procedure .......................................................................................................................................................11
Optional Controls and Accessory Sequence and Interlocks ........................................................................................12
Frost Control .................................................................................................................................................................13
Airow Balancing .......................................................................................................................................................... 14
Service................................................................................................................................................................................15
Quarterly Maintenance .................................................................................................................................................15
Annual Maintenance .....................................................................................................................................................15
Coils .............................................................................................................................................................................15
Testing and Replacement of the Damper Actuator ......................................................................................................16
Motor and Blower Removal – Down, Side and End Supply/Exhaust ...........................................................................16
Motor and Blower Service – Down, Side and End Supply/Exhaust .............................................................................16
Belt Tension Adjustment ..............................................................................................................................................17
Plenum Fan and Motor Removal ..................................................................................................................................17
Plenum Fan and Motor Service .................................................................................................................................... 18
Cassette Removal ........................................................................................................................................................18
Cassette Service ..........................................................................................................................................................19
Appendix A: Service Clearance Dimensions ...................................................................................................................... 20
Appendix B: Hood Installation ............................................................................................................................................21
Appendix C: Rigging Drawing.............................................................................................................................................22
Appendix D: Equipment Data .............................................................................................................................................23
Appendix E: Electrical Data ................................................................................................................................................ 24
Appendix F: Terminal Control Diagrams ............................................................................................................................27
Appendix G: Standard Field Wiring (FW) Terminals ..........................................................................................................30
Appendix H: VHC-36, 42 and 50 Start-up Report and Checklist ........................................................................................ 31
Appendix I: Troubleshooting ...............................................................................................................................................35
Appendix J: Electric Heating Coil and Controls Information ............................................................................................... 37
Appendix K: Water Line Field Mounted Options and Accessories .....................................................................................39
Appendix L: Enthalpy Wheel Pressure Drop vs. Flow Formulae and Curves ...................................................................47
Manufacturer reserves the right to discontinue or change specications or designs without notice or obligation.
MAMM-VHC-IOM-1A (JANUARY 2013)
2
Nomenclature
VHC-XX
Ventilator with heating and cooling
Nominal wheel diameter – 36 – 42 – 50
©Mammoth Inc. 2012. All rights reserved throughout the world.
Illustrations cover the general appearance of Mammoth products at the time of publication and Mammoth reserves the right to make changes in design and construction at any time without notice.
™® The following are trademarks or registered trademarks of their respective companies: Tefzel from DuPont.
MAMM-VHC-IOM-1A (JANUARY 2013)
3
Safety Considerations
!
!
!
Warning, Caution and Important notes appear throughout this manual in specic and appropriate locations to alert In­stalling Contractors and maintenance or service personnel of potential safety hazards, possible equipment damage or to alert personnel of special procedures or instructions that must be followed as outlined below.
WARNING
Identies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Identies an instruction which, if not followed, might se­verely damage the unit, its components, the assembly or nal installation.
General Information
These ventilators can provide 100% outdoor air ventila­tion or, depending on options selected, varying amounts of recirculation between the exhaust and supply airstreams. The VHCs use an enthalpy wheel for total energy recov­ery which provides superior efciency in hot and humid climates. These models are also effective in cold climates and use various types of frost control or defrost to ensure
IMPORTANT
Indicates supplementary information needed to fully com­plete an instruction or installation.
Hazards may exist within this equipment because it con­tains electrical and numerous moving components. Only qualied service personnel should install or service this equipment. Untrained personnel may perform basic main­tenance such as maintaining lters. Observe precautions marked in literature and on labels attached to the unit. Fol­low all safety codes.
WARNING
Disconnect the main power switch to the unit before per­forming service or maintenance. Electric shock can cause personal injury or death.
proper operation when the outside temperatures are ex­tremely low. Units intended for rooftop installations must be installed on a factory or eld supplied roofcurb. This manual contains information on optional components that may or may not be included with this unit. Refer to the sub­mittals for options that pertain to this unit.
Unit Application Limitations
WARNING
Mammoth equipment is not designed to be used for tempo­rary heating, cooling and/or ventilation during construction.
Using Mammoth units for temporary ventilation during construction constitutes a violation of Mammoth warranty terms which indicate that the unit warranty would be void “…if equipment is misapplied or if any alterations are made to the basic design or operating requirements as listed on the original order and shipped from the factory unless
Installation
Unit Location Requirements
Consult local building codes and electrical codes for spe­cial installation requirements and note additional require­ments listed in this manual. In choosing the installation location of the unit, consider the following factors:
approval is received in writing from Mammoth” Fine dust, larger particulate matter, solvents, varnishes and other chemicals may cause lter clogging and elevated cabinet pressures, higher power consumption and possible ir­reparable damage to the desiccant material of the enthalpy wheel, which could reduce energy recovery performance of the wheel and also reduce the heat transfer effectiveness of other components. Potential damages include, but are not limited to, these examples.
The unit should be installed to allow easy access for maintenance and for systems operation. See the ser­vice clearance dimensions in Appendix A.
When possible, mount the unit over an unused area such as a hallway. Although fans and motors are mounted on vibration isolators or are dynamically
MAMM-VHC-IOM-1A (JANUARY 2013)
4
balanced, the unit will be even less perceptible if posi­tioned away from busy ofces.
Locate the unit in an area requiring the least amount of ductwork and direction changes to allow optimum performance, to reduce pressure loss and to use less electricity to achieve proper ventilation. Ductwork must be in accordance with ducting mechanical rules to prevent sound issues and system effects.
The fresh air intake hood must be positioned away from sources of contamination such as hot chimneys or kitchen exhaust vents.
Fresh air intake must also be positioned in a direction opposite to that of prevailing winds to reduce entry of snow or rain.
The unit should be mounted on a level foundation to allow condensation to ow into internal drains. The foundation must provide adequate continuous support to minimize deection of the unit base frame to not more than 1/16” [1.6 mm] over entire length. In addi­tion to these recommendations, a Structural Engineer
Roofcurbs Supplied by Mammoth (External Applications Only)
must be involved to properly size supporting structural elements.
When mounting the unit indoors, if drain connections are required, mount the unit on a housekeeping pad of sufcient height to allow for drain trap height and condensate lines to slope toward the building drain.
When mounting the unit on a roofcurb check the height from the nished roof to the bottom of the intake hood. Consult with Local Authorities or your building code for minimal intake hood height for the water-tight height from and above the nished roof and in snow prone areas, the buildup of snow, to de­termine the height of the roofcurb. Mammoth optional roofcurbs measure 18” [457 mm] in height. If addi­tional height is required from the nished roof to the top of the roofcurb, to the bottom of the intake hood or if other than level, custom height roofcurbs must be ordered.
Roofcurbs supplied by Mammoth should be mounted as follows:
The roofcurb is shipped knocked-down with assembly hardware and instructions provided. The roofcurb must be eld erected, assembled and set in place by the Installing Contractor.
Roofcurb dimensions are submitted with the unit me­chanical drawings which can also be found in the unit control panel pocket or by calling Technical Support personnel from the Mammoth factory.
After the roofcurb has been assembled, ensure that the roofcurb dimensions suit the unit for which it is designated.
The cross members must be positioned as per the roofcurb drawing to properly support the ductwork plenums for bottom vertical return and supply connec­tions and for stability.
Ensure that the assembled roofcurb is square, plumb and level to within 1/16” [1.6 mm] over the entire length. The building structure must provide continu­ous structural support to the full perimeter of the roofcurb and all cross members requiring support. The roofcurb may be shimmed as required to provide continuous support.
The roofcurb must be fastened to the building struc­ture.
The Installing Contractor is responsible for mak­ing the roofcurb water-tight by caulking all roofcurb joints.
IMPORTANT
The following items must be completed prior to setting the unit on the roofcurb:
The roofcurb roong must be completed including insulation, cant strip, ashing and counter-ashing.
Vertical ductwork must be attached to the roofcurb cross members and building structure, not to the unit. See the mechanical drawings for information on roofcurb installation, recommended ductwork attach­ment and dimensions.
If there is no building roof access underneath the unit and drain or piping connections must be made (in the roong), it is recommended to do so before unit installation using the appropriate materials pro­vided by the Installing Contractor.
Remove the length of 3/8” x 1½” [9.5 mm x 38 mm] polyvinyl gasket strip with adhesive backing supplied with the unit and apply a continuous strip to the top perimeter of the roofcurb and duct opening connec­tions for an air and water-tight seal.
IMPORTANT
The gasket between the unit and the roofcurb is critical for an air and water-tight seal. An improperly applied gasket can result in air and water leakage and poor unit perfor­mance. Position the unit with equal spacing all around be­tween the roofcurb and inside unit base rail using ½” [13 mm] wood shims as it is being lowered.
MAMM-VHC-IOM-1A (JANUARY 2013)
5
Roofcurbs Supplied by Others
Roofcurbs supplied by others must be designed with the same dimensions and cross member arrangement as per Mammoth roofcurb drawings and must be designed to evenly withstand perimeter and cross section static loads.
Rigging and Placing the Unit
Inspect the equipment exterior and interior for damage and for shipped loose parts. Ensure there is no damage to internal components such as fans, motors, dampers, en­thalpy wheel, insulation and structures. File a claim with the shipping company if the unit is damaged. Check the pack­ing slip against all items received. If any items are missing, sign the carrier’s bill of lading with the notation “Shipment Received Less Item #___.”
IMPORTANT
The hoods for these units are not installed from the fac­tory and must be installed on site. They should be in­stalled after the unit is installed. Hoods are shipped on top of the unit. When rigging the unit, make sure the hoods are secured and are not damaged by the spreader bars.
See Appendix B for hood installation.
IMPORTANT
Mammoth is not liable for any damages, costs or other is­sues arising from roofcurbs supplied by others.
Spreader bars are required to prevent damage to the roof ange. Rollers may be used to move the unit across the roof. Lifting holes are provided in the base rails as shown in
Appendix C. Refer to submittal documents for overall unit
dimensions and Appendix D for unit weights.
CAUTION
All panels must be in place when rigging.
Field Fabricated Ductwork
On vertical discharge units, secure all ducts to the roofcurb and building structure. Do not secure ductwork to the unit. For unit and duct opening sizes see submittal drawings. Insulate and weatherproof all external ductwork, joints and roof openings with counter-ashing and mastic in accor­dance with applicable codes. Ductwork running through roof decks must comply with local re codes. Ducts pass­ing through unconditioned spaces must be insulated and covered with a vapor barrier. Flexible connectors should be installed close to the unit in the duct leading to occupied spaces to minimize noise transmission.
Duct Design Considerations
The discharge ductwork immediately downstream from the fan is critical for successful applications. Poorly designed ductwork can degrade fan performance and contributes to excessive pressure drop and noise.
When designing ductwork in the eld, it is important to use a straight discharge duct of the correct dimensions to obtain maximum fan performance. The straight section of ductwork helps the airow to develop a uniform velocity prole as it exits the fan and allows the velocity pressure to recover into static pressure. See Figure 1.
Centrifugal fan
Figure 1: Duct design
For 100% recovery of velocity pressure into static pres­sure, the straight portion of the discharge duct must be at least 2.5 times the discharge diameter to the length of the straight portion of ductwork.
As an example of how to size the straight portion of duct, assume the fan has a 13.5”x 9.5” discharge outlet = 0.89
Cutoff
100% effective duct length 2½ diameters at 2,500 FPM
Discharge duct
IMPORTANT
This information is referenced from AMCA Fans and Sys­tems Publication 201.
ft2.
MAMM-VHC-IOM-1A (JANUARY 2013)
6
Refer to Table 1 for the effect of undersized equivalent duct diameter.
Table 1: Effect of Undersized Equivalent Duct Diameter
Pressure recovery
12%
No Duct
Effective
Duct
0% 50% 80% 90% 100%
25%
Effective
Duct
50%
Effective
Duct
100%
Effective
Duct
Hood Installation
Calculate Equivalent Duct Diameter
The equivalent duct diameter of the fan outlet.
= (4ab + n) = (4 x 13.5 x 9.5)
n
= 12.75 = ~13
So the straight duct length required would be:
= 2.5 x 13 = 32.5” long [2.7 feet]
0.5
0.5
Intake and exhaust hoods for these models are shipped separately from the unit. To install hoods see Appendix B. A quick connect for the damper motors is provided to con-
Access Panels
Handles for lift off exterior access panels with screw door fasteners are provided but must be installed on site. Han­dles and fasteners are secured inside the unit.
Internal Packaging
Open access doors or panels and remove all packaging from the unit. Note that there is packaging for wheel sup­port during shipping. Removal of all packaging is critical.
nect to the main body of the unit. Make sure that all screws are secured to maintain proper support and keep seals water-tight.
IMPORTANT
Securing door fasteners too tightly has negative effects on the door gasket and should be avoided.
MAMM-VHC-IOM-1A (JANUARY 2013)
7
Electrical Connections
!
WARNING
When installed, the appliance must be electrically grounded in accordance with local codes or, in the ab­sence of local codes, with the National Electrical Code, ANSI/NFPA70, and/or the Canadian Electrical Code CSA C22.1. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. Failure to follow this warning could result in the Installer being liable for personal injury of others.
Power Supply
Units are available in all voltages and phases. Please see
Appendix E for electrical data. These units may or may not
have a factory installed disconnect switch. If disconnect is eld supplied, provide a disconnect as per local electrical codes and NEC. Use copper conductors only.
All eld wiring must comply with NEC and local require­ments. In Canada, electrical connections must be in accor­dance with CSA C22.1 Canadian Electrical Code Part One.
Units equipped with electric preheaters and/or post heaters have either single-point or two-point power connections.
See Appendix E, submittal data and/or nameplate to de-
termine which. All units equipped with two-point electric heaters require two-point power connection—one to the unit control panel and one to the electric heater fed from a single eld supplied disconnect.
Field Connection
A high voltage connection hole is located on the outside of the unit with knock-out; see submittal drawings for location. A eld installed disconnect switch must use a liquid-tight connector between the disconnect switch and the outside panel of the unit eliminating any water penetration into the control box. A wiring diagram is located within the control panel area of the unit.
A low voltage Field Wiring (FW) interface is provided near the control Panel (PNL) terminals for shipped loose or eld supplied controls, sensors or interlock connections. The location of the eld wiring and panel terminals may vary depending upon options selected as illustrated in Figure 2. The low voltage eld wiring entry is made through the side of the unit below the input power supply connection (see
Appendix G) which runs through the outside casing and
requires a liquid-tight connector or conduit to avoid water penetration.
Installer must provide wiring for controls that are supplied optionally and shipped loose or eld supplied. All eld sup­plied low voltage wiring must be Class 2. Mark the Field Wiring terminals schematic (Appendix G) with the con­nections completed and leave with the unit for start-up and service.
Units will require a start contact interlock from a remote time clock, light sensor, occupancy sensor, manual selec­tor switch or remotely through BACnet from a Building Management System (BMS) depending on ventilation control scheduling mode required. Select required inter­lock and ventilation control scheduling mode from descrip­tion below.
See Appendix F and Appendix G for wiring terminal con-
trol diagram examples and standard Field Wiring (FW) ter­minal and interlock connections available.
Units Supplied with DDC Control Package
The DDC control package enables stand alone opera­tion of the VHC unit and includes a factory installed, pro­grammed and run tested stand alone microprocessor based controller, all necessary sensors and interfaces to provide control of optional post conditioning functions. See the VHC-36, 42 and 50 DDC Control Package Manual (VCES-DDC-IOM-1 (500020459)) for overview, installation and start-up.
An intelligent programmable interface device (BacStat II) with built in room sensor is included for communication, display, setpoint control and to allow for servicing and is shipped loose for eld wiring and installation at the unit or remotely. Determine required location for installation and connect using two twisted pair cables, the rst for power connection. The LinkNet cable needs to be balanced 100 to 120 ohm nominal impedance twisted shielded pair cable, nominal capacitance of 16 PF/FT or lower.
Units Supplied with an Electro-mechanical Controls (EMC) Package
The EMC controls package or dry contact control option include: all relays, motor starters, motor overloads, damper actuators, heating and cooling initiate contacts and se­lected option pickup points. All necessary connections are wired to a terminal strip in the control panel for eld wiring connections to a Building Management System (BMS), for eld supplied DDC or standard controls and thermostats. See the Control Contractor’s ow and wiring schematics for connection details.
Ventilation Control Scheduling Modes
Occupied Ventilation (Ov)
If the occupancy contact closes or a jumper is placed across terminals FW 304–305 this will enable the unit to run in 100% fresh air mode. Free cooling and defrost will initiate based on the setpoint.
Unoccupied Recirculation (Ur)
If the unoccupied recirculation contact closes or a jumper is placed across terminals FW 305–306 the unit will turn off unless there is a call for heating/cooling or dehumidication across the heating/cooling or dehumidication contacts.
MAMM-VHC-IOM-1A (JANUARY 2013)
8
This must come from an optional thermostat or humidistat. The unit will run in recirc mode upon a call.
Occupied Recirculation (Or) (DDC Control Package only)
If the occupied recirculation contact closes or a jumper is placed across terminals, heat wheel starts (not in free cool­ing), defrost recirculation damper closes (if equipped), out­side and exhaust air dampers (if equipped) begin to open; after outside air damper opens fully the supply blower starts; after exhaust air damper opens fully the exhaust blower starts, the occupied recirculation damper opens and outside and exhaust dampers modulate to the minimum setpoints.
Unoccupied (Un)
If the contact opens or jumper removed on any of the ter­minals 304, 305, 306, 307 or 308 the unit will turn off.
PNL
PNL
FW
FW
Figure 2: Possible terminal strip locations in electrical panel
MAMM-VHC-IOM-1A (JANUARY 2013)
9
Water Source Heat Pump (WSHP) Water Piping and Connections
[76 mm]
Before connecting piping to the unit, the water supply line and return line must be ushed to eliminate the foreign material. In low temperature applications, the water supply line and return line should be insulated to prevent con­densate and antifreeze solution should be used to protect water-to-refrigerant heat exchanger from freezing damage. See submittal drawings for water piping connection loca­tion. The concentration of water/glycol solution depends on the eld application. On open loop systems, a water strainer (16–20 mesh minimum, 20–40 mesh best) is rec­ommended to be installed in the water inlet line to the unit to eliminate contaminants and it must be used for units having water-to-refrigerant brazed plate heat exchanger. A water ow switch is recommended to be installed in line to prevent possible freeze-up due to loss of water ow. An air vent must be installed on the high side of the water line to discharge the non-condensable air in order to avoid
Condensate Drain Trap
Cooling coil drain pan is provided with a 1¼” MPT drain connection. A drain trap and condensate line of equal size must be eld provided on the drain connection to prevent air or sewer gases from being pulled into the unit caused by the negative (suction) pressure and forcing water out of the pan into the unit.
A label with recommended trap height is provided on the unit as per Figure 3.
Condensate drain must be trapped as shown.
Refer to IOM for further instructions and maintenance.
Le drain de condensation doit être fabriqué et intallé tel que
le croquis ci-bas. Voir le manuel d’installation,
opération et maintenance pour instructions.
Curb
6.578”
[167.08 mm]
support
3.375”
[85.73 mm]
6.0” [191 mm] minimum
unexpected high head pressure and poor cooling/heating performance. Manual shut-off valves are recommended to be installed for the convenience of future service.
A circuit balancing valve with pressure and temperature gauge connections is recommended to be installed in the water line for balancing and service.
See Appendix K for water line eld mounted options and
accessories.
CAUTION
In areas where scaling can become serious, a periodic cleaning for the water-to-refrigerant heat exchanger is recommended. Standard water coil cleaning procedure should be followed which must be done by a qualied ser­vice mechanic.
The trap height allows for the maximum suction pressure after the cooling coil with intake damper, dirty pre and nal high efciency lters, high efciency heat wheel plus 1” w.c. per ASHRAE guidelines for outdoor units with intake hood or indoor unit with up to 0.5” w.c. external static intake duct.
Slope the drain lines downward in direction of ow 1/8 inch per foot referring to local codes for proper drainage require­ments. Installing a plug for cleaning of the trap is recom­mended. Prime the trap by lling with water before start-up. Winterize the drain line before freezing on outdoor units.
Check and clear drains annually at start of cooling sea­son. Drainage problems can occur should drains be in­active and dry out, or due to reduced water ow caused by buildup of algae. Regular maintenance will prevent these from occurring.
Unit baserail
Curb
Figure 3: Condensate drain trap label
MAMM-VHC-IOM-1A (JANUARY 2013)
3.0” minimum
PN 500005436
10
Start-up
Pre Start-up Procedure
Before requesting start-up, check that the installation is complete and unit is ready. Complete the pre start-up check list below and in the Appendix H for each unit as items are checked.
1. Set the electrical disconnect to the ‘Off’ position.
2. Check the unit for obstructive packaging, objects near or in blowers, dampers, heat wheel, etc. Remove all red tie down bolts on fan assemblies and heat wheel if so equipped.
3. Check that the fans and heat wheel are rotating freely.
4. Check blower wheels and drive set screws. Tighten if required.
5. Check belt alignment and tension.
6. Check that the air lters are installed and clean. Re­place if necessary.
7. Check coils (if equipped) if ns have been damaged in transit or construction and are clean. Straighten ns with n comb and clean coil if required.
8. Check the refrigerant components and piping that they are in good condition and have no damage or leaks from shipping or installation.
9. Check that the water strainer has been installed for a WSHP with a brazed heat exchanger.
10. Check that ductwork is connected and complete.
11. Check that condensate drain connections have been trapped, installed correctly and lled.
12. Check that all shipped loose or eld supplied compo­nents have been correctly installed and wired and that start interlocks have been completed for the ventilation control desired.
13. Check that the standard eld wiring (FW) terminal diagram has been marked up accordingly and left with the unit.
14. Check that all power supplies and control wiring have been inspected and approved by the Local Authorities having jurisdiction.
15. Check all factory and eld wiring connections for tight­ness. Tighten if necessary.
16. Check that all fuses are properly installed in holders.
17. Check the voltage at the disconnect switch against the nameplate and against phase-to-phase readings on three-phase. If the voltage is not within 10% of rated or 2% of phase-to-phase, have the condition corrected before continuing start-up.
18. Check that all eld piping and venting installation and connections for the heating and cooling options have been completed and test.
19. Set the heating and cooling enable switches to the ‘Off’ position.
Start-up Procedure
To ensure proper operation of each unit, qualied person­nel should perform the start-up and complete the checklist below and the start-up report in Appendix H for permanent record. A completed checklist will provide valuable informa­tion for personnel performing future maintenance.
IMPORTANT
A completed copy must be sent back to the factory for warranty validation and for factory assistance.
All units are factory run tested. Blowers, heat wheel and compressors (if equipped) are set up to run correct when power is connected. If any one blower is running back­wards or compressor is making loud noises disconnect power and switch two leads (on three-phase power) to en­sure proper rotation and avoid damage.
If units are equipped with compressors power must be turned on for 24 hours prior to a call for cooling, for the compressor crank case heaters to be energizing to prevent possible damage.
The BacStat II interface module (if equipped with DDC con­trol package and mounted remotely) may be temporarily connected at the unit for checkout. Ensure it is connected to the Net 2 contacts otherwise it will not give readings.
1. Before proceeding complete the pre start-up check­list.
2. Check that all access panels or doors are closed.
3. Turn the main disconnect to the ‘On’ position.
4. Set the timer, selector switch or BMS contact to the ventilation control scheduling mode selected and check operation according to sequence. Only one of the following modes selected can have their contacts closed or jumped. a. Occupied ventilation (Ov): With the occupancy
contact closed or a jumper placed across termi­nals, heat wheel starts (not in free cooling), de­frost recirculation damper closes (if equipped), outside and exhaust air dampers open fully, the supply blower starts and after exhaust air damper opens fully, the exhaust blower starts.
b. Unoccupied recirculation (Ur): With the unoc-
cupied recirculation contact closed or a jumper
MAMM-VHC-IOM-1A (JANUARY 2013)
11
placed across terminals, heat wheel stops, defrost recirculation damper opens, outside and exhaust air dampers (if equipped) begin to close and supply blower starts.
c. Occupied recirculation (Or) (DDC control pack-
age only): With the occupied recirculation contact closed or a jumper placed across termi­nals, heat wheel starts (not in free cooling), de­frost recirculation damper closes (if equipped), outside air damper (if equipped) opens. After outside air damper opens supply blower starts, exhaust air damper (if equipped) opens; after exhaust air damper opens, exhaust blower starts, occupied recirculation damper opens, outside and exhaust air dampers modulate to the damper minimum setpoints.
5. Check that dampers are operating properly.
6. Check that blowers and heat wheel are rotating in the correct direction.
7. For occupied recirculation scheduling mode the out­side air and exhaust air dampers must be adjusted during start-up to achieve the required outside and ex­haust air volumes. See Airow Balancing for further information.
8. Re-check the voltage at the disconnect switch against the nameplate and against phase-to-phase read­ings on three-phase with all blowers operating. If the voltage is not within 10% of rated or 2% of phase-to­phase have the condition corrected before continuing start-up.
9. Check amperage draw to each motor on each phase against motor nameplate FLA. If signicantly different, check ductwork static and/or take correc­tive action.
10. Before activating the compressor on WSHP units, are water shut-off valves open and is water circulating through the water-to-refrigerant heat exchanger.
11. Enable cooling and check if the sound of the compres­sor is normal or if there is excessive vibration.
12. Check all eld and factory refrigerant and water piping connections for leaks and correct.
13. Enable heating options, see start-up and check out in­structions in Appendix J for electric coil and complete.
14. Check the operation of the control options provided on the unit. A functional description is provided below and in the VHC-36, 42 and 50 DDC Control Package Manual.
15. Check the setpoints on the DDC Points Reference, adjust and record changes as required.
16. When unit has achieved steady state take measure­ments and complete the readings section of the start-
up report in Appendix H and send copy of the start-up
report to Mammoth to validate warranty. Maintain a copy of the report at the unit for future reference.
Optional Controls and Accessory Sequence and Interlocks
Free Cooling
Power connected, unit ventilating, free cooling call. Wheel stops rotating.
Variable Speed Setpoint Free Cooling
Power connected, unit ventilating. Wheel modulates to keep discharge temperature air at setpoint.
Unit Fault
An external unit fault can be initiated by removing the dry contact jumper to the eld wire terminal in the control panel. This contact is normally closed and requires an open contact to initiate a fault and shut down the unit.
Dirty Filter Sensor
The VHCs can be equipped with dirty lter sensors which monitor the pressure across the lters and close the con­tacts when the lters become restricted with dirt. Field wired connections can be made to the terminal interface
MAMM-VHC-IOM-1A (JANUARY 2013)
for both the supply and exhaust lter sensors (electro-me­chanical controls [EMC] units only).
Remote Fan Control
Remote fan control can be achieved by connecting dry contacts to the terminal interface (during occupied or un­occupied recirculation). These controls could also be the following: SPDT switch, dehumidistat, CO2 sensor, light sen­sor, heat sensor, timer, Building Management System, etc.
CO2 Ventilation Control
VHCs can be directly controlled by a CO2 controller (acces­sory or eld supplied) that can be connected to the supply and exhaust high speed contact terminals (VFD units only).
As the CO2 levels exceed acceptable limits, dry contacts
close raising high speed fan ventilation. See Appendix F,
CO2 Ventilation Control. Alternatively a eld supplied CO2
controller output can be connected to the BMS which can then be connected to the supply and exhaust fan modu­lating signal input terminals (VFD units only). As the CO2
12
levels rise and fall the BMS must modulate the signal to the supply and exhaust fans to change the ventilation rate proportionally. See Appendix G. The minimum VFD speed is factory default set to 40 Hertz.
Smoke Detector
VHCs can be equipped with a duct mount smoke detector which will monitor the air when passing through the duct system into the unit. When sufcient smoke is detected, an alarm condition is activated. By connecting the occupied terminals to the NC alarm auxiliary contacts on the duct sensor, an alarm condition will open the auxiliary contact and stop operation of the VHC. Locate in a normally oc­cupied area of premises. Recommended for compliance to NFPA-90A and IMC code 606.
Cooling Override (DDC Controls Units Only)
These terminals are available for a room or return air sum­mer thermostat. All thermostats are eld installed and wired.
Dehumidication (DDC Controls Units Only)
IMPORTANT
Removal of dry contacts that close on high speed termi­nals is required for VFDs to modulate.
These terminals are available for a room or return air dehu­midistat. All dehumidistats are eld installed and wired.
Heating Override (DDC Controls Units Only)
These terminals are available for a room or return air winter thermostat. All thermostats are eld installed and wired.
For standard eld wiring terminals diagram, refer to Appen-
dix G.
Frost Control
During cold temperatures, defrost and frost prevention are controlled by the unit’s integrated controls as follows.
Preheat will prevent frost formation on the enthalpy wheel to maintain proper operation and provide continuous venti­lation and make-up air. This prevention occurs when a pre­heater is energized to maintain an outdoor air temperature higher or when the wheel speed is reduced to maintain an exhaust air temperature higher than minimum required for the enthalpy wheel to operate frost free.
The requirement for frost control is based upon the outdoor air temperature and humidity content of the return air. In areas where the winter outdoor air condition falls below 5°F [−15°C] or the return air relative humidity is above 30%, frost control is probably required.
Preheat Frost Prevention
Preheat frost prevention is an outdoor air temperature controlled function that allows for continuous ventilation by ensuring a minimum enthalpy wheel entering air tempera­ture of 5° F [−15°C]. The temperature sensor is located be­tween the open wire electric heating coil and the enthalpy
wheel. The electric heating coil is selectable in 1 kW incre­ments and available in two-stage, four-stage or SCR con­trol. With staged control, one stage cycles to maintain 5° F [−15°C] temperature to the enthalpy wheel as the other stages are continuously on as the outdoor air temperature drops. If the selected kW is insufcient, based upon the entered design conditions, selection software automatically
adjusts the minimum kW required to maintain the minimum
wheel entering air temperature.
Non-defrost
No frost control is required in areas where the winter out­door air condition stays above 5°F [−15°C] and the return air humidity level is below 30%.
MAMM-VHC-IOM-1A (JANUARY 2013)
13
!
Airow Balancing
IMPORTANT
On initial power up, the unit will perform a system check and operate at high speed for ve seconds.
For proper performance the unit must operate and be balanced at the design supply and exhaust airow rates. Permanent or temporarily eld supplied and installed ow measuring stations (FMS) can be used to measure airow or by using other ASHRAE suggested methods. Where space is limited in the outdoor air or exhaust air ducts for measurements, pressure drop readings can be taken across the enthalpy wheel rotor and airow extrapolated from the curves in Appendix L for the wheel effectiveness category or thickness. Heat recovery performance is tested in accordance to AHRI Standard 1060 and is accurate to within +/− 5% if there is no dirt buildup in the heat recovery wheel rotor.
When FMS are used it is important to locate it in the “warm side” ductwork to minimize the effects of differences in air density especially during cold outside conditions. Air den­sity variations can affect the FMS by more than 15%. The FMS should be located downstream from straight sections of duct and not immediately after fans or obstructions that will cause turbulent ow.
coils or reheat to protect building systems must be eld provided.
Setting Flow Rate
Units supplied with belt driven double width double inlet fans have an adjustable motor sheave factory set at the midpoint of travel at rpm for the ow rate and external static specied. With optional VFD driven motors this factory set­ting is at 60 Hz. For 100% outdoor and exhaust, ow rate should be balanced with motors operating at high speed and at 60 Hz by adjusting the motor sheave pitch diameter. The VFD can be used for ne tuning depending on se­quence.
With the optional direct driven plenum supply fan the VFD is used for speed setting and balancing at the required Hertz.
With the optional internal bypass the airow rate may be reduced. Consult the factory for setting the ow rate during internal bypass.
WARNING
Disconnect the main power switch to the unit before per­forming service and maintenance procedures.
Imbalanced airow may cause supply air temperatures to be below freezing. Adequate freeze protection such as glycol or low limit temperature protection for downstream
MAMM-VHC-IOM-1A (JANUARY 2013)
14
Service
Quarterly Maintenance
Quarterly maintenance (every three months) should include:
Air Filters
The standard medium efciency lters and optional high ef­ciency lters are disposable and should be replaced every three months. More frequent replacement may be required under extremely dirty operating conditions.
To replace the lters, open the lter access door, grasp the lters and pull straight out. The lters will slide completely
Annual Maintenance
Annual maintenance should include:
Aluminum Enthalpy Wheel
No cleaning of the enthalpy wheel is required as it is self-cleaning due to the opposing airows. If it is desired to clean the enthalpy wheel, use low pressure air or a vacuum. Wash the cassette panels with a soft cloth and mild cleaning solution. Visually inspect the cassette brush seals (shown in Figure 4), perimeter seal and drive belt for proper operation.
out of the unit. Slide the new lters into the frame and close the lter access door.
Cassette Panels and Interior of Unit
Remove the lters from the unit. Wipe the foil faced insu­lation, or the optional interior galvanized liner, surfaces and cassette panels with a soft cloth and mild cleaning solution.
System Operation Check
Verication of all control modes should be checked to en­sure proper operation. Refer to Start-up section.
Rotor
Brush seal
Fans
Blower wheels and fan housing should be checked for dirt buildup. If they are dirty, it will be necessary to remove the blower assembly to clean the dust out through the fan mouth.
Dirt on the surface of the coil reduces its ability to transfer heat which lowers the efciency of the unit, resulting in poor air quality and expensive operating costs. Because of the condensate on the coil, the dirt often becomes wet and contributes to the growth of microbial organisms. Negligence in maintenance may result in serious health related indoor air quality problems.
The coil should be kept clean for maximum performance. To achieve maximum efciency, clean the coil often during periods of high demand or when dirty conditions prevail. Mammoth recommends cleaning the coil a minimum of once per year to prevent dirt buildup in the coil ns where it may not be visible.
Coil ns can be cleaned by using steam with detergent, hot water spray or a commercial chemical coil cleaner. After cleaning the coil, be sure to rinse thoroughly.
Figure 4: System operation check
Coils
Cleaning Procedure
CAUTION
Do not use acidic chemical coil cleaners. Do not use al­kaline chemical coil cleaners with a pH value greater than
8.5 or lower than 6 (after mixing) without using an alu-
minum corrosion inhibitor in the cleaning solution. Using these types of cleaners may result in unit damage.
1. Shut down the unit by closing the main disconnect at the power inlet.
2. Open panels or doors to gain access to both sides of the coil section.
3. Remove soft debris from both sides of the coil with a soft brush.
MAMM-VHC-IOM-1A (JANUARY 2013)
15
Loading...
+ 33 hidden pages