Mammoth 3/4-5 Tons User Manual

Page 1
Single Circuit Horizontal and Vertical Water Source Heat Pumps With R-410A
Installation, Operation and Maintenance Manual
Sizes: 009 to 072 — Horizontal 012 to 072 — Vertical Model: U Vintage
MAMM-WSHP-IOM-1UB (September 2011)
P/N 71144909
Page 2
Table of Contents
Model Nomenclature ·················································································································· 3 Transportation and Storage ········································································································ 3 Installation ·································································································································· 4 Discharge Conversion—Horizontal Units ··················································································· 4 Unit Location and Clearances ···································································································· 5 Unit Mounting ····························································································································· 6 Ductwork and Attenuation ·········································································································· 7 Ventilation Air ····························································································································· 7 Piping ········································································································································· 8 Cleaning and Flushing ················································································································ 9 Start-up····································································································································· 10 Operating Limits ······················································································································· 11 Controls ···································································································································· 12 I/O 560 ····································································································································· 12 I/O 583 ····································································································································· 14 I/O 6126···································································································································· 16 General Maintenance ··············································································································· 19 Troubleshooting ························································································································ 20 Performance Troubleshooting ································································································· 21 Unit check-out sheet ················································································································ 22
U Vintage Vertical Size 012 to 072
MAMM-WSHP-IOM-1UB (September 2011)
U Vintage Horizontal Size 009 to 072
2
Page 3
Model Nomenclature
F -024- H- H- U
Voltage
BTU/hr Cooling
Unit Type Temperature Range Vintage
D = 208-230/1/60 E = 265/1/60 F = 208-230/3/60 G = 460/3/60 J = 380/3/50 K = 575/3/60 L = 220-240/1/50 S = 380/3/60 043 = 43,000 052 = 52,000 062 = 62,000 072 = 72,000
Illustrations cover the general appearance of Mammoth products at the time of publication and Mammoth, Inc. reserves the right to make changes in design and construction at anytime without notice.
009 = 9,000 V = Vertical H = Standard Range
012 = 12,000 H= Horizontal L = Low Temp Operation
013 = 13,000
016 = 16,000
019 = 19,000
024 = 24,000
030 = 30,000
036 = 36,000
“Mammoth” is a registered trademark of Mammoth, Inc.
©Mammoth, Inc. 2011. All rights reserved throughout the world.
Transportation and Storage
Upon receipt of the equipment, check for visible dam­age. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough han­dling, immediately check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. Then contact the Mammoth Service department
at (952) 358-6618 or [email protected] for a warranty claim number.
MAMM-WSHP-IOM-1UB (September 2011)
Do not stand or transport the unit on end. In the event that elevator transfer makes up-ended positioning un­avoidable, absolutely ensure that the unit is in the nor­mal upright position for at least 24 hours before operat­ing.
Temporary storage at the job site must be indoors, completely sheltered from rain, snow, etc. High or low temperatures naturally associated with weather pat­terns will not harm units. Excessively high tempera­tures, 140°F (60°C) and higher, may deteriorate certain plastic materials and cause permanent damage.
3
Page 4
Installation
General
IMPORTANT:
Mammoth water source heat pumps should be in­stalled only by qualified personnel, experienced in the installation of this equipment and related systems. Read these instructions carefully before unpacking, installing and operating this unit
1. To prevent damage, this equipment should not be operated for supplementary heating and cooling during the construction period.
2. Inspect the unit for any specific tagging numbers indicated by the factory per a request from the in­stalling contractor.
3. Check the unit nameplate for the size and voltage rating and confirm against the plans that the unit is being installed in the correct location.
4. Verify the installation location with the piping, sheet metal and electrical contractors prior to installation
Discharge Conversion—Horizontal Units
5. Verify all clearances are available for the unit prior to installation.
6. Note the location and routing of water piping, con­densate drain piping, and electrical wiring. The lo­cations of these items are clearly marked on sub­mittal drawings.
7. Mammoth recommends the unit be covered during construction to protect components from dust and other harmful material. This is critical while spray­ing fireproofing material on bar joists, sandblasting, spray painting and plastering.
NOTE:
Check the unit name plate for correct voltage with the plans before installing the equipment. Make sure all electrical ground connections are made in accordance with local code.
All horizontal units from size 009 to 062 can be field converted from straight discharge to side discharge.
1. Set the unit on a level surface.
2. Remove the blower access panel.
3. Remove the top panel.
4. Remove the screws that secure the panel where blower is mounted.
5. Re-install the blower panel assembly for side dis­charge configuration (assembly will be flipped 180 degrees). See unit specification sheet for dimen­sional information.
6. Re-install the top of the unit.
7. Re-install the blower access panel where the blower panel assembly was for straight-through discharge.
8. After first operation, check all fasteners for tight­ness.
MAMM-WSHP-IOM-1UB (September 2011)
4
Page 5
Unit Location and Clearances
The diagrams below show minimum suggested clear­ances. Any additional clearances would be beneficial, but not always necessary. The requirements on any specific unit may increase or be reduced depending on several factors such as maintenance requirements and mechanical or electrical installation codes. If return air is not ducted, enough clearance will be required to pro­vide for adequate airflow.
Horizontal unit clearances
Horizontal units have three access panels; one panel for the blower, one for the electrical panel and one for the compressor compartment. Horizontal unit filters are removed from the right or left side with an option for bottom removal.
Vertical units need to be accessed on three sides; two panels for the compressor and blower, one for the elec­trical panel and compressor compartment. Vertical unit filters are removed from the right or left side.
MAMM-WSHP-IOM-1UB (September 2011)
Vertical unit clearances
5
Page 6
Mounting
Vertical units can be mounted on the floor or a concrete pad, typically in a mechanical closet or other area en­closed from the space to promote a quieter occupied environment..
Horizontal units must be hung from the ceiling. Mount­ing brackets, rubber grommets, bolts and washers are
shipped in place on the unit. The mounting brackets are designed to accept up to a 3/8-inch threaded rod (by others). A flat washer and two nuts (both by others) should be used to mount the unit on the ceiling at­tached threaded rods. When installed, the unit should be slightly pitched toward the condensate drain con­nection.
Horizontal mounting detail (See unit submittal drawing for specific component locations on your unit)
Hanger
Brackets (4)
Water Outlet FPT
Connection
Access to Compressor
Water Coil, Reversing Valve
Water Inlet FPT
3/4” OD Copper Condensate Drain
Electrical
Flange on Filter Guide
Filter, Left or Tight Side Removal. Lift and Pull on
Flange on Filter Guide
7/8” or 1-3/32” Hole for line voltage conduit connection
Grommet detail
Hanger Bracket
Note: Rotate Brackets
90° And Tighten
Retaining nut
(by others)
Threaded Rod
(By Others)
Washer (by others) must cover
entire bottom of grommet
MAMM-WSHP-IOM-1UB (September 2011)
6
Page 7
Ductwork and Attenuation
Discharge ductwork is normally used with U-vintage horizontal and vertical single circuit units. Return air ductwork may also be required.
All ductwork should conform to industry standards of good practice as described in the ASHRAE Systems Guide.
The discharge duct system will normally consist of a flexible connector at the unit connection, a transition piece to the full duct size, a short run of duct, and elbow with vanes, and a trunk duct teeing into a branch duct with discharge diffuses. The transition piece must not have angles totaling more than 30° or severe reduction in airflow performance can result.
Do not connect the full duct size to the unit. Use a transition piece sized according to the discharge collar on the unit to get to the full duct size. With metal duct material, the sides of only the elbow and entire branch duct should be internally lined with acoustic fibrous insulation for sound attenuation. Glass fiber duct board material is more absorbing and may permit omission of the canvas connector.
The ductwork should be laid out so that there is no line of sight between the unit discharge and the distribution diffusers.
Do not use sheet metal screws directly into the unit cabinet for connection of supply or return air ductwork, especially return ductwork which can hit the drain pan or the air coil.
Minimum/maximum duct connections
MODEL
009 23.21 9 11.25 6 9.0
013 23.21 9 11.25 6 9.0
016 26.0 9 11.25 6 9.0
019 26.0 11.3 12.4 9.2 10.0
024 26.82 11.3 12.4 9.2 10.0
030 26.82 11.3 12.4 9.2 10.0
036 29.76 12.5 13.25 10.5 11.25
043 29.76 12.5 13.25 10.5 11.25
052 29.76 13 13.5 11 11.5
062 29.76 13 13.5 11 11.5
072 33.51 14.5 13.5 12.5 11.5
MIN. STRAIGHT DISCH. LENGTH
MAX. DUCT MIN. DUCT
WIDTH HEIGHT WIDTH HEIGHT
Legend
Outside air may be required for ventilation. The temperature of the ventilation air must be controlled so that the mixture of outside air and return air entering the unit is within application limits. It is typical to close off the ventilation air system during unoccupied periods (i.e. night setback).
MAMM-WSHP-IOM-1UB (September 2011)
V entilation Air
The ventilation air system is typically a separate building subsystem with distribution ductwork. Simple introduction of the outside air into each return air plenum chamber reasonably close to the unit air inlet is recommended. Do not duct outside air directly to the unit inlet. Provide sufficient distance for the thorough mixing of outside and return air. .
7
Page 8
Supply Piping
1. All heat pumps should be connected to supply and return piping in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing and requires only trim balancing where multiple quantities of heat pumps with different flow and pressure drop characteristics exist in the same loop. Check for proper water balance by measuring differential temperature reading across the water connections. To insure proper water flow, the differential temperature should be between 10°F to 14°F for heat pumps in the cooling mode.
2. The piping may be steel, copper, or PVC. Avoid dissimilar metal fittings as they may corrode. If the use of dissimilar metals is unavoidable, use dielectric isolation at that connection point.
3. Supply and return run-outs usually join the heat pump via short lengths of high pressure flexible hose which are sound attenuators for both heat pump operating noise and hydraulic pumping noise. One end of the hose should have a swivel fitting to facilitate removal for service. Hard piping can also be brought directly to the heat pump. This option is not recommended since no vibration or
noise attenuation can be accomplished. The hard piping must have a union to facilitate heat pump removal.
4. Make sure that threaded fittings are sealed. Teflon tape can be used to provide a tight seal.
5. Supply and return shutoff valves are required at each heat pump. The return valve is used for balancing and should have a “memory stop” so that it can always be closed off but can only be reopened to the proper position for the flow required.
6. No heat pump should be connected to the supply and return piping until the water system has been cleaned and flushed completely. After the cleaning and flushing has taken place, the initial connection should have all valves wide open in preparation for the water system flushing.
Condensate Piping
1. Condensate piping can be steel, copper, or PVC. Each unit includes a condensate connection.
2. The condensate disposal piping must be trapped. Vertical units are internally trapped and horizontal units must be externally trapped. The piping must be pitched away from the heat pump not less than ¼” per foot. The unit is supplied with a 1-1/4” male pipe fitting to accommodate the condensate drain connection.
3. Do not locate any point in the drain system above the drain connection of any unit.
4. The condensate piping system must be vented at its highest point.
MAMM-WSHP-IOM-1UB (September 2011)
8
Page 9
Cleaning and Flushing
1. Prior to first operation of U-Vintage horizontal and vertical units, the water circulation system must be cleaned and flushed of all construction dirt and de­bris
2. If the U-Vintage horizontal and vertical units are equipped with water shutoff valves, either electric or pressure operated, the supply and return run­outs must be connected at each heat pump loca­tion. This will prevent the introduction of dirt into the heat pump.
3. Fill the system at the city water makeup connection with all air vents open. After filling, close all air vents.
4. The contractor should start the main circulator with the pressure reducing valve open. Check vents in sequence to bleed off any trapped air, providing circulation through all components of the system.
5. While circulating water, the contractor should check and repair any leaks in the piping. Drains at the lowest point(s) in the system should be opened for the initial flush and blow down, making sure city water fill valves are set to make up water at the same rate. Check the pressure gauge at the pump suction and manually adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves. Flush should con­tinue for at least two hours, or longer if required, until the drain water is clear and clean.
6. Shut off supplemental heater (if applicable) and circulator pump and open all drains and vents to completely drain down the system. Short circuited supply and return runouts should now be con­nected to the heat pump supply and return connec­tions. Do not use sealers at the swivel flare con­nections of the hoses.
7. Refill the system with clean water. Test the water using litmus paper for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade anti­freeze designed for HVAC systems only. Do not use automotive grade antifreeze.
8. Once the system has been filled with clean water and antifreeze (if used), precaution should be taken to protect the system from dirty water conditions. Dirty water will result in system wide performance degradation and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchang­ers may become clogged which reduces compres­sor service life or causes premature failure.
9. Set the loop water controller heat add setpoint to 70°F and the heat rejection setpoint to 85°F. Sup­ply power to all motors and start the circulation pumps. After full flow has been established through all components including the heat rejecter (regardless of season) and air has been vented and loop temperatures have been stabilized, each of the heat pumps will be ready for check, test and start-up, and water balancing.
MAMM-WSHP-IOM-1UB (September 2011)
9
Page 10
Start-up
1. Open all valves to full open position and turn on power to the heat pump.
2. Set room temperature sensor for “Fan Only” opera­tion by selecting “Off” at the system switch and “On” at the fan switch. If “Auto” fan operation is se­lected, the fan will cycle with the compressor. Check for proper air delivery.
3. U-Vintage horizontal and vertical units have time delays which help protect the compressor(s) against short cycling. In the cooling mode, after a few minutes of operation, check the discharge grilles for cool air delivery. Measure the tempera­ture difference between entering and leaving water. It should be approximately 1 ½ times greater than the heating mode temperature difference.
4. In the heating mode, measure the temperature dif­ference between entering and leaving air and en­tering and leaving water. With entering water of 60° F to 80°F, leaving water should be 6°F to 12°F cooler, and the air temperature rise through the U­Vintage horizontal and vertical units should not ex­ceed 35°F. If the leaving air temperature falls be­low 35°F, adjust water flow to the unit to >3 gpm/ ton to avoid freeze damage to the unit.
5. Fill the p-trap with water to ensure that negative pressure does not pull drain gases into the unit.
6. Check the elevation and cleanliness of the conden­sate line. If the air is too dry for sufficient dehumidi­fication, slowly pour enough water into the conden­sate pan to ensure proper drainage.
7. If the unit does not operate, check the following points: a) Is supply voltage to the U-Vintage horizontal and vertical units compatible? b) If the U-Vintage horizontal and vertical units op­erates but stops after a brief period:
i) Is there proper airflow? Check for dirty filter, incorrect fan rotation or incorrect ductwork. ii) Is there proper water flow rate within tem­perature limits? Check water balancing; back­flush unit if dirt clogged. iii) See troubleshooting guide on page 21 for more tips.
MAMM-WSHP-IOM-1UB (September 2011)
10
Page 11
Operating Limits
Environment
This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., generally will not provide sufficient protection against
Application Limits
WATER TEMPERATURES / Degrees F *
MINIMUM ENTERING WATER TEMPERATURE
MAXIMUM ENTERING WATER TEMPERATURE
* Application limits apply at or above standard flow rates specified for size of unit.
Application Limits
AIRTEMPERATURES/DegreesF*
MINIMUMAMBIENTAIRTEMPERATURE**
MAXIMUMAMBIENTAIRTEMPERATURE**
MINIMUMENTERINGAIRTEMPERATURE
MAXIMUMENTERINGAIR
TEMPERATURE
*Applicationlimitsapplyatorabovestandardflowratesspecifiedforsizeofunit.
**Minimumandmaximumambientconditionsapplytoductedsupplyandreturnunitsonly.
extremes in temperature and/or humidity, and equipment performance, reliability, and service life may be adversely affected.
Standard range Low Temp Geothermal
COOLING HEATING COOLING HEATING
50˚ 50˚ 40˚ 25˚
110˚ 90˚ 110˚ 90˚
Standardrange LowTempGeothermal
COOLING HEATING COOLING HEATING
50˚ 50˚ 50˚ 50˚
110˚ 110˚ 110˚ 110˚
65˚ 50˚ 65˚ 40˚
100˚ 80˚ 100˚ 80˚
Additional Information For Initial Start-up Only
Standard Range Units
Units are designed to start-up in an ambient temperature of 50°F (10°C), with entering air at 50°F (10°C), with entering water at 70°F (21°C), with air and water flow rates used in the ISO13256-1 rating test, for initial start-up in winter.
Note: This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Geothermal Range Units
Geothermal heat pump units are designed to start-up in an ambient temperature of 50°F (10°C), with entering air at 40°F (5°C), with entering fluid at 25°F (-4°C), with air and water at flow rates used in the ISO 13256-1 rating test, for initial start-up in winter.
MAMM-WSHP-IOM-1UB (September 2011)
Note: This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature.
Operating voltages
208-230/60/1 . . . . . . . . . 197 volts min.; 253 volts max.
265/60/1 . . . . . . . . . . . . .239 volts min.; 291 volts max.
208-230/3/60. . . . . . . . . .197 volts min.; 253 volts max.
460/3/60. . . . . . . . . . . . . 414 volts min.; 506 volts max.
380/3/50. . . . . . . . . . . . . 342 volts min.; 418 volts max.
575/3/60. . . . . . . . . . . . . 515 volts min.; 632 volts max.
220-240/1/50 . . . . . . . . . 216 volts min.; 264 volts max.
380/3/60. . . . . . . . . . . . . 342 volts min.; 418 volts max.
Note:
Voltages listed are to show voltage range. However, units operating with over- or under-voltage conditions for extended periods of time will experience premature component failure. Three phase system imbalance should not exceed 2%.
11
Page 12
MAMMOTH CONTROLS
I/O 560
Mammoth I/O Zone 560 controller delivers powerful control and communications features all in a compact, economical package. Fully capable of operating in a 100% stand-alone control mode, the I/O Zone 560 can connect to a Building Automation System (BAS) using any of today’s most popular protocols, such as BACnet, Modbus, N2, LonTalk. The I/O Zone 560 also supports communication to the Mammoth line of intelligent space sensors and keypad/display units.
Key Features and Benefits
 I/O point count: 5 digital outputs (relayed), and 6 universal imputs.  Built-in protocol support: BACnet (ARCNET and MS/TP), Modbus RTU, and N2. Optional plug-in communica-
tions boards: LonTalk
 On-board battery-backed real-time clock is standard, thus enablin g full stand-alone scheduling capabilities as
well as historical trend data storage and alarm event time-stamping.•
 Powerful, high-speed 16-bit processor with 1MB Flash memory and 512KB of battery-backed RAM - plenty of
room for even demanding and complex applications.
 For standard CAV heat pumps without modulatin g waterside economizer (WSE) or hot gas Reheat (HGR).
 For variable air volume (VAV), constant volume (CAV), and make-up air (MAU) ap plications.
MAMM-WSHP-IOM-1UB (September 2011)
12
Page 13
I/O 560 (Base CAV) - Examples of I/O’s
Universal
Input
1 Supply Air Temperature (Monitor Only) Thermistor/Dry Contact
2 Condenser Leaving Water Temperature Thermistor/Dry Contact
3 Thermistor/Dry Contact
4 Compr Lckt/Overflow Compr.#1 HP-5 Alarm Compr. #2 Alarm Thermistor/Dry Contact
5 Load Shead* Compr#1Q HP-5 Alarm* Compr#2Q HP-5 Alarm Thermistor/Dry Contact 6 Emergency Shut Down External Clock (Start) Dirty Filter (Switch Opt) Thermistor/Dry Contact
Condenser Entering Water Temperature
Jumper Setting
Rnet Jumper Setting
1
Digital
Output
1 Supply Fan Start Dry Contact for 24 VAC
Room/Return Air Temperature (RS Std) or Room Air Temperature/Stet-Point/Override (RS-Pro, Optional)
N/A
Jumper Setting
2 Compressor Call #1 Dry Contact for 24 VAC
3 Compressor Call #2 or on/off Waterside Economize or on/off Aux. Heat Dry Contact for 24 VAC
4 Reversing Valve or on/off Waterside Economizer or on/off Aux. Heat Dry Contact for 24 VAC
5 Common Alarm Dry Contact for 24 VAC
Options are in italics. Common options are bolded
* Cost add option must be ordered to get multiplexing board ** A minimum of one keypad display must be ordered per project to set required set-points *** A protocol will be a cost add option
MAMM-WSHP-IOM-1UB (September 2011)
13
Page 14
I/O 583
Mammoth I/O Zone 583 controller delivers powerful control and communications features all in a compact, economical package. Fully capable of operating in a 100% stand-alone control mode, the I/O Zone 583 can connect to a Building Automation System (BAS) using any of today’s most popular protocols, such as BACnet, Modbus, N2, and LonTalk,. The I/O Zone 583 also sup­ports communication to Mammoth line of intelligent space sensors and keypad/display units.
Key Features and Benefits
 I/O point count: 5 digital outputs (relayed), 8 inputs and 3 analog outputs.  Built-in protocol support: BACnet (ARCNET and MS/TP), Modbus RTU, and N2. Optional plug-in communica-
tions boards: LonTalk
 On-board battery-backed real-time clock is standard, thus enablin g full stand-alone scheduling capabilities as
well as historical trend data storage and alarm event time-stamping.•
 Powerful, high-speed 16-bit processor with 1MB Flash memory and 512KB of battery-backed RAM - plenty of
room for even demanding and complex applications.
 For standard CAV heat pumps requiring a modulating control points for a waterside economizer (WSE), hot gas
reheat (HGRH) or auxiliary heating.
MAMM-WSHP-IOM-1UB (September 2011)
14
Page 15
I/O Zone 583 (RHT, CAV, NMUA) - Examples of I/O’s
Universal
Input
1 Supply Air Temperature (Monitor Only) Thermistor/Dry Contact
2 Condenser Leaving Water Temperature Thermistor/Dry Contact
3 Condenser Entering Water Temperature Thermistor/Dry Contact
4 Cooling Coil Leaving Air Temperature Sensor
5 6 Load Shead* Comp #1Q HP-5 Alarm* Comp r#2Q HP-5Alarm
7 Compr Lckt/Overflow Comp #1 HP-5 Alarm Comp #2 Alarm Thermistor/Dry Contact 8 Emergency Shut Down External Clock (Start) Dirty Filter (Switch Opt)
Space or Return Humidity
Jumper Setting
Thermistor/Dry Contact
Thermistor/Dry Contact Thermistor/Dry Contact
Thermistor/Dry Contact
Rnet Jumper Setting
1
Analog Output
Room/Return Air Temperature (RS Std) or Room Air Temperature/Stet-Point/Override (RS-Pro, Optional)
N/A
Jumper Setting
N/A
1 Reheat** 0-10VDC
2 Water Side Economizer** 0-10VDC
3
Analog Output
1 Supply Fan Start Dry Contact for 24 VAC
2 Compressor Call #1 Dry Contact for 24 VAC
3 Compressor Call #2 Dry Contact for 24 VAC
4 Reversing Valve Dry Contact for 24 VAC
5 Common Alarm Dry Contact for 24 VAC
Options are in italics. Common options are bolded.
Auxiliary Heat**
0-10VDC
Jumper Setting
N/A
* Cost add option must be ordered to get multiplexing board ** Requires DC relay for single stage, UCS for multi-stage, or actuator for modulating control *** A minimum of one keypad display must be ordered per project to set required set-points **** A protocol will be a cost add option
MAMM-WSHP-IOM-1UB (September 2011)
15
Page 16
I/O Flex 6126
The standard factory-integrated DDC controller provides control flexibility that can be easily customized to meet any sequence of operation needs. It is fully capable of operating in a 100% stand-alone mode or can connect to a Building Automation System (BAS) using any of today’s four leading protocols: BACnet, Modbus, N2, and Lontalk. The base controller provides ample input/output capacity, plus support for an expander board if additional I/O capacity is required.
Key Features and Benefits
 6160 I/O points: 6 digital outputs, 12 universal inputs, and 6 analog outputs.  8160 I/O points: 16 universal inputs, 8 digital outputs.  Optional built-in protocol support: BACnet® (ARCNET, MS/TP, and PTP modes), Modbus® (RTU and ASCII
modes supported), N2, or Lontalk®.
 Powerful, high-speed 16-bit microprocessor with 1 MB Flash memory and 1 MB of battery-backed RAM  Built-in support through an Rnet port for control’s custom configurable keypad/display unit, BACview6 (4-line by
40 character per line display) for intelligent sensors.
 For variable air volume (VAV), constant volume (CAV), and make-up air (MAU) ap plications.
MAMM-WSHP-IOM-1UB (September 2011)
16
Page 17
Examples of I/O’s
INPUTS
Point Description UD #1 UD #2 UD #3
UD #4 Contact, 0-10VDC, UD #5 0-20MA
UD #6 UD #7 UD #8 UD #9
UD #10 UD #11 UD #12
Point Description UO #1 UO #2 UO #3 UO #4 UO #5
UO#6
DO #1 DO #2 DO #3 DO #4 DO #5 DO #6
+Pulse Room Air Temperature RTD/Therm/Dry





 Entering Air Temperature or Return Air Temperature (AiSE)

4-20mA, 0-10Vdc Heating Source Control Signal 0-10 Vdc
Supply Fan VFD Control Signal
120 VAC FORM C
 Field-Lin (MWU or Open Min OA)  Common Alarm  Compressor Call #2

BMS Supply Air, Duct Static Reset or Room Air Temperature Setpoint
System Switch Emergency Shut Down Remote Start High Static Low Static VFD in Bypass Economizer Lockout Cooling Lockout Heating Lockout
Supply Fan Status Compressor Fault Condensate Overflow Duct Static Pressure or Airflow Switch Filter Static Pressure or Dirty Filter Switch #1 Outside Air Temperature (AiSE Only) Condenser Water Temperature
Supply Air Temperature
OUTPUTS
Spare
Economizer Valve (WiSE)/Damper Control Signal (AiSE) WiSE Bypass Valve Signal Spare
Start Supply Fan Start Condenser Pump or Switch Reversing Valve
Compressor Call #1
MAMM-WSHP-IOM-1UB (September 2011)
17
Page 18
MAMMOTH DDC CONTROLS
Keypad
Locally access controllers and operational properties with the easy-to-use BACview into an Rnet connection on a 6126 controller and allows you to display and modify properties. The BACview and four programmable function keys. A large 4-line by 40-character backlit LCD display is provided for easy reading even in poor lighting conditions. The device also includes an alarm indicator light.
6 features a numeric keypad, directional keys,
Key Features and Benefits
 Compatible with all EPiC system controllers.  Flexible design allows panel or wall mounting; can be located up to 500 feet from the controller.  Hand-held version can be plugged into RS room temperature sensors.  Backlit LCD display enhances reading even in poor lighting conditions.  Customized menus for each product.  Password protection provides security.  One keypad can be used on different units/programs since the menus a re pa rt of the control program.
6 keypad/display. It plugs
MAMM-WSHP-IOM-1UB (September 2011)
18
Page 19
General Maintenance
Normal maintenance on U-Vintage horizontal and verti­cal units is generally limited to filter changes.
Air filter changes are required at regular intervals. The time period between changes will depend upon the pro­ject requirements. Some applications such as motels produce a lot of lint from carpeting and linen changes, and will require more frequent filter changes. It is sug­gested that the filter be checked at 60-day intervals for the first year until experience is acquired. If light cannot be seen through the filter when held up to sunlight or a bright light, it should be changed. A more critical stan­dard may be desirable.
The condensate drain pan should be checked annually and cleaned and flushed as required.
Recording of performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. A comparison of logged data with start-up and other annual data is useful as an indicator of general equipment condition.
Periodic lockouts almost always are caused by air or water problems. The lockout (shutdown) of the heat pump is a normal protective result. Check for dirt in the water system, water flow rates, water temperatures, airflow rates (may be dirty filter), and air temperatures. If the lockout occurs in the morning following a return from night setback, entering air below machine limits may be the cause.
MAMM-WSHP-IOM-1UB (September 2011)
19
Page 20
Troubleshooting
R-410A
The In’s and Out’s of R-410A
R-410A is a non-ozone depleting blend of two Refrigerants — HFC-125 and HFC-32 in a fifty percent mixture. Refrigerant 410A exhibits higher operating pressure and refrigeration capacity than R-22.
Although R-410A is non-flammable at ambient tem­perature and atmosphere pressure, it can become combustible under pressure when mixed with air. (NOTE: R-410A should not be mixed with air under pressure for leak testing. Pressure mixtures of dry nitro­gen and R-410A can be used for leak testing.)
Lubrication
R410A should be used only with polyolester (POE) oil. The HFC refrigerant components in R-410A will not be compatible with mineral oil or alkylbenzene lubricants. R-410A systems will be charged with the OEM recom­mended lubricant, ready for use with R-410A.
Troubleshooting Refrigeration Circuit
Symptom
Charge
Undercharge System (Possible Leak)
Overcharge Sys­tem Pressure
Low Air Flow Heating
Low Air Flow Cooling
Low Water Flow Heating
Low Water Flow Cooling
High Air Flow Heating
High Air Flow Cooling
High Water Flow Heating
High Water Flow Cooling
TXV Restricted High Low
Head
Pressure
Low Low Low High Low Low Low Low Pressure
High High High Normal Low
High High High
Low Low Low
Low Low
Normal Normal
High High High High Low Low High High Pressure
Low Low Low Low High Low Low Low Temp
Low High Normal High Low Low Normal High Pressure
Normal Low Low Low Normal Normal Low High Pressure
Low Low Low Low HIgh Normal Low Low Temp
Suction
Pressure
Compressor
Amp Draw
Low Low High Low High Low Temp
Normal
Low
Charging
Due to the zeotropic nature of R-410A, it should be charged as a liquid. In situations where vapor is nor­mally charged into a system, a valve should be in­stalled in the charging line to flash the liquid to vapor while charging.
WARNING!
It is very important to make certain that the recycle or recovery equipment used is designed for R-410A. The pressure of R-410A refrigerant is approximately 60 percent greater than that of R-22. Pressure gauges require a range up to 800 PSIG high side and 250 PSIG low side. Recovery cylinders require a 400 PSIG rating.
All Mammoth U-Vintage units are designed for commercial use. Units are designed for the cooling mode of operation and fail safe to heating.
Super
Heat
High
Normal
Low
Normal
High High Low Low
Subcooling
Low High Low High Pressure
Low Low Low Low Temp
Air
Temp
Differential
Normal
Low
Water
(Loops)
Temp
Differential
Normal High Pressure
Safety
Lock
Out
MAMM-WSHP-IOM-1UB (September 2011)
20
Page 21
Performance Troubleshooting
Performance Troubleshooting
Insufficient Capacity X X Dirty Filter Replace or clean
Not cooling or heating properly
X X Leaky duct work
Unit doesn’t operate in cooling
X X
X Defective reversing valve Perform RV touch test
X X
X X Unit undersized
X X
X X Inlet water to hot or cold Check load, loop sizing, loop backfill, ground moisture
High head pressure X
X
Heating Cooling Possible Cause Solution
X X Reduced or no air flow
X X Low refrigerant charge Check superheat and subcooling
Restricted metering de­vice
Thermostat improperly located
Scaling in waterside heat exchanger
Reduced or no air flow in heating
Reduced or no water flow in cooling
Check for dirty air filter and clean or replace, Check fan motor operation and airflow restriction. External static too high? Check static vs. blower table
Check supply and return air temperatures at the unit and at distant duct registers: If significantly different, duct leaks are present
Check superheat and subcooling– replace
Check location and for air drafts behind stat
Recheck loads & sizing. Check sensible, cooling load and heat pump ca­pacity
Perform scaling check and clean if necessary
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. External static too high? Check static vs. blower table
Check pump operation or valve operation/setting. Check water flow; adjust to proper flow rate
X Inlet water to hot Check load, loop sizing, loop backfill, ground moisture
X
X
X X Unit overcharged Check superheat and subcooling
X X
Low suction pressure X
X
X
X
X X Insufficient charge Check for refrigerant leaks
Low discharge air temperature in heating
X Poor performance See insufficient capacity
X To high of air flow Check fan motor speed selection and airflow
Air temperature out of range in heating
Scaling in waterside heat exchanger
Non-condensable in system
Reduced water flow in heating
Water temperature out of range
Reduced air flow in cool­ing
Air temperature out of range
Bring return air temp within design parameters
Perform scaling check and clean if necessary
Vacuum system, reweigh in charge
Check pump operation or valve operation/setting. Check water flow adjust to proper flow rate
Bring water temp within design parameters
Check for dirty air filter and clean or replace. Check fan motor operation and airflow restrictions. External static too high? Check static vs. blower table
Too much cold vent air? Bring entering air temp within design parameters.
MAMM-WSHP-IOM-1UB (September 2011)
21
Page 22
UNIT CHECK-OUT SHEET
Customer Data
Customer Name ________________________________________ Date _________________________________________
Address ________________________________________________________________________________________________
Phone ________________________________________________ Unit Number___________________________________
Unit Nameplate Data
Make _______________________ Model Number _______________________ _ Serial Number _______________________
Compressor: RLA_______ LRA _______ Refrig, Charge (oz.) _______
Blower Motor(s): FLA (or NPA)________ HP __________
Maximum Fuse Size: (Amps) __________ Minimum Circuit Ampacity (Amps) __________________
Operating Conditions
Unit Conditions Cooling Mode Heating Mode Measured At:
Entering Air Temperature _____________ _____________ ________________________ _________ Leaving Air Temperature _____________ _____________ ______________________ ___________ Entering Fluid Temperature _____________ _____________ n/a
Leaving Fluid Temperature _____________ _____________ n/a Fluid Flow (gpm) _____________ _____________ n/a
Fluid Side Pressure Drop _____________ _____________ n/a
Compressor Mode Cooling Heating
Suction Pressure (psig) _______ _______
Discharge Pressure (psig) _______ _______ Suction Temp (at compressor) _______ _______ Discharge Temp (at compressor) _______ _______
Suction Superheat (at compressor) _______ _______ Liquid Line Leaving Condenser Temp _______ _______ Liquid Subcooling _______ _______
Volts/Amps Phase
L1 L2 L3
Compressor Volts _____ _____ _____ Compressor Amps _____ _____ _____ Blower Volts _____ _____ _____ Blower Amps _____ _____ _____
MAMM-WSHP-IOM-1UB (September 2011)
22
Page 23
Notes
Page 24
[email protected] www.mammoth-inc.com
Mammoth, Inc. has a policy of continuous product improvement and reserves the right to change design and specifications without notice.
© 2011 Mammoth, Inc. MAMM-WSHP-IOM-1UB September 2011
Loading...