Mammoth 3/4-5 Tons User Manual

Single Circuit Horizontal and Vertical Water Source Heat Pumps With R-410A
Installation, Operation and Maintenance Manual
Sizes: 009 to 072 — Horizontal 012 to 072 — Vertical Model: U Vintage
MAMM-WSHP-IOM-1UB (September 2011)
P/N 71144909
Table of Contents
Model Nomenclature ·················································································································· 3 Transportation and Storage ········································································································ 3 Installation ·································································································································· 4 Discharge Conversion—Horizontal Units ··················································································· 4 Unit Location and Clearances ···································································································· 5 Unit Mounting ····························································································································· 6 Ductwork and Attenuation ·········································································································· 7 Ventilation Air ····························································································································· 7 Piping ········································································································································· 8 Cleaning and Flushing ················································································································ 9 Start-up····································································································································· 10 Operating Limits ······················································································································· 11 Controls ···································································································································· 12 I/O 560 ····································································································································· 12 I/O 583 ····································································································································· 14 I/O 6126···································································································································· 16 General Maintenance ··············································································································· 19 Troubleshooting ························································································································ 20 Performance Troubleshooting ································································································· 21 Unit check-out sheet ················································································································ 22
U Vintage Vertical Size 012 to 072
MAMM-WSHP-IOM-1UB (September 2011)
U Vintage Horizontal Size 009 to 072
2
Model Nomenclature
F -024- H- H- U
Voltage
BTU/hr Cooling
Unit Type Temperature Range Vintage
D = 208-230/1/60 E = 265/1/60 F = 208-230/3/60 G = 460/3/60 J = 380/3/50 K = 575/3/60 L = 220-240/1/50 S = 380/3/60 043 = 43,000 052 = 52,000 062 = 62,000 072 = 72,000
Illustrations cover the general appearance of Mammoth products at the time of publication and Mammoth, Inc. reserves the right to make changes in design and construction at anytime without notice.
009 = 9,000 V = Vertical H = Standard Range
012 = 12,000 H= Horizontal L = Low Temp Operation
013 = 13,000
016 = 16,000
019 = 19,000
024 = 24,000
030 = 30,000
036 = 36,000
“Mammoth” is a registered trademark of Mammoth, Inc.
©Mammoth, Inc. 2011. All rights reserved throughout the world.
Transportation and Storage
Upon receipt of the equipment, check for visible dam­age. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough han­dling, immediately check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. Then contact the Mammoth Service department
at (952) 358-6618 or info@mammoth-inc.com for a warranty claim number.
MAMM-WSHP-IOM-1UB (September 2011)
Do not stand or transport the unit on end. In the event that elevator transfer makes up-ended positioning un­avoidable, absolutely ensure that the unit is in the nor­mal upright position for at least 24 hours before operat­ing.
Temporary storage at the job site must be indoors, completely sheltered from rain, snow, etc. High or low temperatures naturally associated with weather pat­terns will not harm units. Excessively high tempera­tures, 140°F (60°C) and higher, may deteriorate certain plastic materials and cause permanent damage.
3
Installation
General
IMPORTANT:
Mammoth water source heat pumps should be in­stalled only by qualified personnel, experienced in the installation of this equipment and related systems. Read these instructions carefully before unpacking, installing and operating this unit
1. To prevent damage, this equipment should not be operated for supplementary heating and cooling during the construction period.
2. Inspect the unit for any specific tagging numbers indicated by the factory per a request from the in­stalling contractor.
3. Check the unit nameplate for the size and voltage rating and confirm against the plans that the unit is being installed in the correct location.
4. Verify the installation location with the piping, sheet metal and electrical contractors prior to installation
Discharge Conversion—Horizontal Units
5. Verify all clearances are available for the unit prior to installation.
6. Note the location and routing of water piping, con­densate drain piping, and electrical wiring. The lo­cations of these items are clearly marked on sub­mittal drawings.
7. Mammoth recommends the unit be covered during construction to protect components from dust and other harmful material. This is critical while spray­ing fireproofing material on bar joists, sandblasting, spray painting and plastering.
NOTE:
Check the unit name plate for correct voltage with the plans before installing the equipment. Make sure all electrical ground connections are made in accordance with local code.
All horizontal units from size 009 to 062 can be field converted from straight discharge to side discharge.
1. Set the unit on a level surface.
2. Remove the blower access panel.
3. Remove the top panel.
4. Remove the screws that secure the panel where blower is mounted.
5. Re-install the blower panel assembly for side dis­charge configuration (assembly will be flipped 180 degrees). See unit specification sheet for dimen­sional information.
6. Re-install the top of the unit.
7. Re-install the blower access panel where the blower panel assembly was for straight-through discharge.
8. After first operation, check all fasteners for tight­ness.
MAMM-WSHP-IOM-1UB (September 2011)
4
Unit Location and Clearances
The diagrams below show minimum suggested clear­ances. Any additional clearances would be beneficial, but not always necessary. The requirements on any specific unit may increase or be reduced depending on several factors such as maintenance requirements and mechanical or electrical installation codes. If return air is not ducted, enough clearance will be required to pro­vide for adequate airflow.
Horizontal unit clearances
Horizontal units have three access panels; one panel for the blower, one for the electrical panel and one for the compressor compartment. Horizontal unit filters are removed from the right or left side with an option for bottom removal.
Vertical units need to be accessed on three sides; two panels for the compressor and blower, one for the elec­trical panel and compressor compartment. Vertical unit filters are removed from the right or left side.
MAMM-WSHP-IOM-1UB (September 2011)
Vertical unit clearances
5
Mounting
Vertical units can be mounted on the floor or a concrete pad, typically in a mechanical closet or other area en­closed from the space to promote a quieter occupied environment..
Horizontal units must be hung from the ceiling. Mount­ing brackets, rubber grommets, bolts and washers are
shipped in place on the unit. The mounting brackets are designed to accept up to a 3/8-inch threaded rod (by others). A flat washer and two nuts (both by others) should be used to mount the unit on the ceiling at­tached threaded rods. When installed, the unit should be slightly pitched toward the condensate drain con­nection.
Horizontal mounting detail (See unit submittal drawing for specific component locations on your unit)
Hanger
Brackets (4)
Water Outlet FPT
Connection
Access to Compressor
Water Coil, Reversing Valve
Water Inlet FPT
3/4” OD Copper Condensate Drain
Electrical
Flange on Filter Guide
Filter, Left or Tight Side Removal. Lift and Pull on
Flange on Filter Guide
7/8” or 1-3/32” Hole for line voltage conduit connection
Grommet detail
Hanger Bracket
Note: Rotate Brackets
90° And Tighten
Retaining nut
(by others)
Threaded Rod
(By Others)
Washer (by others) must cover
entire bottom of grommet
MAMM-WSHP-IOM-1UB (September 2011)
6
Ductwork and Attenuation
Discharge ductwork is normally used with U-vintage horizontal and vertical single circuit units. Return air ductwork may also be required.
All ductwork should conform to industry standards of good practice as described in the ASHRAE Systems Guide.
The discharge duct system will normally consist of a flexible connector at the unit connection, a transition piece to the full duct size, a short run of duct, and elbow with vanes, and a trunk duct teeing into a branch duct with discharge diffuses. The transition piece must not have angles totaling more than 30° or severe reduction in airflow performance can result.
Do not connect the full duct size to the unit. Use a transition piece sized according to the discharge collar on the unit to get to the full duct size. With metal duct material, the sides of only the elbow and entire branch duct should be internally lined with acoustic fibrous insulation for sound attenuation. Glass fiber duct board material is more absorbing and may permit omission of the canvas connector.
The ductwork should be laid out so that there is no line of sight between the unit discharge and the distribution diffusers.
Do not use sheet metal screws directly into the unit cabinet for connection of supply or return air ductwork, especially return ductwork which can hit the drain pan or the air coil.
Minimum/maximum duct connections
MODEL
009 23.21 9 11.25 6 9.0
013 23.21 9 11.25 6 9.0
016 26.0 9 11.25 6 9.0
019 26.0 11.3 12.4 9.2 10.0
024 26.82 11.3 12.4 9.2 10.0
030 26.82 11.3 12.4 9.2 10.0
036 29.76 12.5 13.25 10.5 11.25
043 29.76 12.5 13.25 10.5 11.25
052 29.76 13 13.5 11 11.5
062 29.76 13 13.5 11 11.5
072 33.51 14.5 13.5 12.5 11.5
MIN. STRAIGHT DISCH. LENGTH
MAX. DUCT MIN. DUCT
WIDTH HEIGHT WIDTH HEIGHT
Legend
Outside air may be required for ventilation. The temperature of the ventilation air must be controlled so that the mixture of outside air and return air entering the unit is within application limits. It is typical to close off the ventilation air system during unoccupied periods (i.e. night setback).
MAMM-WSHP-IOM-1UB (September 2011)
V entilation Air
The ventilation air system is typically a separate building subsystem with distribution ductwork. Simple introduction of the outside air into each return air plenum chamber reasonably close to the unit air inlet is recommended. Do not duct outside air directly to the unit inlet. Provide sufficient distance for the thorough mixing of outside and return air. .
7
Supply Piping
1. All heat pumps should be connected to supply and return piping in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing and requires only trim balancing where multiple quantities of heat pumps with different flow and pressure drop characteristics exist in the same loop. Check for proper water balance by measuring differential temperature reading across the water connections. To insure proper water flow, the differential temperature should be between 10°F to 14°F for heat pumps in the cooling mode.
2. The piping may be steel, copper, or PVC. Avoid dissimilar metal fittings as they may corrode. If the use of dissimilar metals is unavoidable, use dielectric isolation at that connection point.
3. Supply and return run-outs usually join the heat pump via short lengths of high pressure flexible hose which are sound attenuators for both heat pump operating noise and hydraulic pumping noise. One end of the hose should have a swivel fitting to facilitate removal for service. Hard piping can also be brought directly to the heat pump. This option is not recommended since no vibration or
noise attenuation can be accomplished. The hard piping must have a union to facilitate heat pump removal.
4. Make sure that threaded fittings are sealed. Teflon tape can be used to provide a tight seal.
5. Supply and return shutoff valves are required at each heat pump. The return valve is used for balancing and should have a “memory stop” so that it can always be closed off but can only be reopened to the proper position for the flow required.
6. No heat pump should be connected to the supply and return piping until the water system has been cleaned and flushed completely. After the cleaning and flushing has taken place, the initial connection should have all valves wide open in preparation for the water system flushing.
Condensate Piping
1. Condensate piping can be steel, copper, or PVC. Each unit includes a condensate connection.
2. The condensate disposal piping must be trapped. Vertical units are internally trapped and horizontal units must be externally trapped. The piping must be pitched away from the heat pump not less than ¼” per foot. The unit is supplied with a 1-1/4” male pipe fitting to accommodate the condensate drain connection.
3. Do not locate any point in the drain system above the drain connection of any unit.
4. The condensate piping system must be vented at its highest point.
MAMM-WSHP-IOM-1UB (September 2011)
8
Loading...
+ 16 hidden pages