Single Circuit Horizontal and Vertical
Water Source Heat Pumps With R-410A
Installation, Operation and Maintenance Manual
Sizes: 009 to 072 — Horizontal
012 to 072 — Vertical
Model: U Vintage
MAMM-WSHP-IOM-1UB (September 2011)
P/N 71144909
Table of Contents
Model Nomenclature ·················································································································· 3
Transportation and Storage ········································································································ 3
Installation ·································································································································· 4
Discharge Conversion—Horizontal Units ··················································································· 4
Unit Location and Clearances ···································································································· 5
Unit Mounting ····························································································································· 6
Ductwork and Attenuation ·········································································································· 7
Ventilation Air ····························································································································· 7
Piping ········································································································································· 8
Cleaning and Flushing ················································································································ 9
Start-up····································································································································· 10
Operating Limits ······················································································································· 11
Controls ···································································································································· 12
I/O 560 ····································································································································· 12
I/O 583 ····································································································································· 14
I/O 6126···································································································································· 16
General Maintenance ··············································································································· 19
Troubleshooting ························································································································ 20
Performance Troubleshooting ································································································· 21
Unit check-out sheet ················································································································ 22
U Vintage Vertical
Size 012 to 072
MAMM-WSHP-IOM-1UB (September 2011)
U Vintage Horizontal
Size 009 to 072
2
Model Nomenclature
F -024- H- H- U
Voltage
BTU/hr Cooling
Unit Type Temperature Range Vintage
D = 208-230/1/60
E = 265/1/60
F = 208-230/3/60
G = 460/3/60
J = 380/3/50
K = 575/3/60
L = 220-240/1/50
S = 380/3/60
043 = 43,000
052 = 52,000
062 = 62,000
072 = 72,000
Illustrations cover the general appearance of Mammoth products at the time of publication and Mammoth, Inc. reserves the right to make changes
in design and construction at anytime without notice.
009 = 9,000V = Vertical H = Standard Range
012 = 12,000H= Horizontal L = Low Temp Operation
013 = 13,000
016 = 16,000
019 = 19,000
024 = 24,000
030 = 30,000
036 = 36,000
“Mammoth” is a registered trademark of Mammoth, Inc.
Upon receipt of the equipment, check for visible damage. Make a notation on the shipper’s delivery ticket
before signing. If there is any evidence of rough handling, immediately check for concealed damage. If any
damage is found, notify the carrier within 48 hours to
establish your claim and request their inspection and a
report. Then contact the Mammoth Service department
at (952) 358-6618 or info@mammoth-inc.com
for a warranty claim number.
MAMM-WSHP-IOM-1UB (September 2011)
Do not stand or transport the unit on end. In the event
that elevator transfer makes up-ended positioning unavoidable, absolutely ensure that the unit is in the normal upright position for at least 24 hours before operating.
Temporary storage at the job site must be indoors,
completely sheltered from rain, snow, etc. High or low
temperatures naturally associated with weather patterns will not harm units. Excessively high temperatures, 140°F (60°C) and higher, may deteriorate certain
plastic materials and cause permanent damage.
3
Installation
General
IMPORTANT:
Mammoth water source heat pumps should be installed only by qualified personnel, experienced in the
installation of this equipment and related systems.
Read these instructions carefully before unpacking,
installing and operating this unit
1. To prevent damage, this equipment should not be
operated for supplementary heating and cooling
during the construction period.
2. Inspect the unit for any specific tagging numbers
indicated by the factory per a request from the installing contractor.
3. Check the unit nameplate for the size and voltage
rating and confirm against the plans that the unit is
being installed in the correct location.
4. Verify the installation location with the piping, sheet
metal and electrical contractors prior to installation
Discharge Conversion—Horizontal Units
5. Verify all clearances are available for the unit prior
to installation.
6. Note the location and routing of water piping, condensate drain piping, and electrical wiring. The locations of these items are clearly marked on submittal drawings.
7. Mammoth recommends the unit be covered during
construction to protect components from dust and
other harmful material. This is critical while spraying fireproofing material on bar joists, sandblasting,
spray painting and plastering.
NOTE:
Check the unit name plate for correct voltage with the
plans before installing the equipment. Make sure all
electrical ground connections are made in accordance
with local code.
All horizontal units from size 009 to 062 can be field
converted from straight discharge to side discharge.
1. Set the unit on a level surface.
2. Remove the blower access panel.
3. Remove the top panel.
4. Remove the screws that secure the panel where
blower is mounted.
5. Re-install the blower panel assembly for side discharge configuration (assembly will be flipped 180
degrees). See unit specification sheet for dimensional information.
6. Re-install the top of the unit.
7. Re-install the blower access panel where the
blower panel assembly was for straight-through
discharge.
8. After first operation, check all fasteners for tightness.
MAMM-WSHP-IOM-1UB (September 2011)
4
Unit Location and Clearances
The diagrams below show minimum suggested clearances. Any additional clearances would be beneficial,
but not always necessary. The requirements on any
specific unit may increase or be reduced depending on
several factors such as maintenance requirements and
mechanical or electrical installation codes. If return air
is not ducted, enough clearance will be required to provide for adequate airflow.
Horizontal unit clearances
Horizontal units have three access panels; one panel
for the blower, one for the electrical panel and one for
the compressor compartment. Horizontal unit filters are
removed from the right or left side with an option for
bottom removal.
Vertical units need to be accessed on three sides; two
panels for the compressor and blower, one for the electrical panel and compressor compartment. Vertical unit
filters are removed from the right or left side.
MAMM-WSHP-IOM-1UB (September 2011)
Vertical unit clearances
5
Mounting
Vertical units can be mounted on the floor or a concrete
pad, typically in a mechanical closet or other area enclosed from the space to promote a quieter occupied
environment..
Horizontal units must be hung from the ceiling. Mounting brackets, rubber grommets, bolts and washers are
shipped in place on the unit. The mounting brackets
are designed to accept up to a 3/8-inch threaded rod
(by others). A flat washer and two nuts (both by others)
should be used to mount the unit on the ceiling attached threaded rods. When installed, the unit should
be slightly pitched toward the condensate drain connection.
Horizontal mounting detail (See unit submittal drawing for specific component locations on your unit)
Hanger
Brackets (4)
Water Outlet FPT
Connection
Access to Compressor
Water Coil, Reversing Valve
Water Inlet FPT
3/4” OD Copper Condensate Drain
Electrical
Flange on Filter Guide
Filter, Left or Tight Side
Removal. Lift and Pull on
Flange on Filter Guide
7/8” or 1-3/32” Hole for line
voltage conduit connection
Grommet detail
Hanger Bracket
Note: Rotate Brackets
90° And Tighten
Retaining nut
(by others)
Threaded Rod
(By Others)
Washer (by others) must cover
entire bottom of grommet
MAMM-WSHP-IOM-1UB (September 2011)
6
Ductwork and Attenuation
Discharge ductwork is normally used with U-vintage
horizontal and vertical single circuit units. Return air
ductwork may also be required.
All ductwork should conform to industry standards
of good practice as described in the ASHRAE Systems
Guide.
The discharge duct system will normally consist of
a flexible connector at the unit connection, a transition
piece to the full duct size, a short run of duct,
and elbow with vanes, and a trunk duct teeing into
a branch duct with discharge diffuses. The transition
piece must not have angles totaling more than
30° or severe reduction in airflow performance can
result.
Do not connect the full duct size to the unit. Use a
transition piece sized according to the discharge collar
on the unit to get to the full duct size. With metal duct
material, the sides of only the elbow and entire branch
duct should be internally lined with acoustic fibrous
insulation for sound attenuation. Glass fiber duct board
material is more absorbing and may permit omission of
the canvas connector.
The ductwork should be laid out so that there is no
line of sight between the unit discharge and
the distribution diffusers.
Do not use sheet metal screws directly into the unit
cabinet for connection of supply or return air ductwork,
especially return ductwork which can hit the drain pan
or the air coil.
Minimum/maximum duct connections
MODEL
009 23.21 9 11.25 6 9.0
013 23.21 9 11.25 6 9.0
016 26.0 9 11.25 6 9.0
019 26.0 11.3 12.4 9.2 10.0
024 26.82 11.3 12.4 9.2 10.0
030 26.82 11.3 12.4 9.2 10.0
036 29.76 12.5 13.25 10.5 11.25
043 29.76 12.5 13.25 10.5 11.25
052 29.76 13 13.5 11 11.5
062 29.76 13 13.5 11 11.5
072 33.51 14.5 13.5 12.5 11.5
MIN. STRAIGHT
DISCH. LENGTH
MAX. DUCT MIN. DUCT
WIDTH HEIGHT WIDTH HEIGHT
Legend
Outside air may be required for ventilation. The
temperature of the ventilation air must be controlled so
that the mixture of outside air and return air entering
the unit is within application limits. It is typical to close
off the ventilation air system during unoccupied periods
(i.e. night setback).
MAMM-WSHP-IOM-1UB (September 2011)
V entilation Air
The ventilation air system is typically a separate
building subsystem with distribution ductwork. Simple
introduction of the outside air into each return air
plenum chamber reasonably close to the unit air inlet is
recommended. Do not duct outside air directly to the
unit inlet. Provide sufficient distance for the thorough
mixing of outside and return air.
.
7
Supply Piping
1. All heat pumps should be connected to supply and
return piping in a two-pipe reverse return
configuration. A reverse return system is inherently
self-balancing and requires only trim balancing
where multiple quantities of heat pumps with
different flow and pressure drop characteristics
exist in the same loop. Check for proper water
balance by measuring differential temperature
reading across the water connections. To insure
proper water flow, the differential temperature
should be between 10°F to 14°F for heat pumps in
the cooling mode.
2. The piping may be steel, copper, or PVC. Avoid
dissimilar metal fittings as they may corrode. If the
use of dissimilar metals is unavoidable, use
dielectric isolation at that connection point.
3. Supply and return run-outs usually join the heat
pump via short lengths of high pressure flexible
hose which are sound attenuators for both heat
pump operating noise and hydraulic pumping
noise. One end of the hose should have a swivel
fitting to facilitate removal for service. Hard piping
can also be brought directly to the heat pump. This
option is not recommended since no vibration or
noise attenuation can be accomplished. The hard
piping must have a union to facilitate heat pump
removal.
4. Make sure that threaded fittings are sealed. Teflon
tape can be used to provide a tight seal.
5. Supply and return shutoff valves are required at
each heat pump. The return valve is used for
balancing and should have a “memory stop” so that
it can always be closed off but can only be
reopened to the proper position for the flow
required.
6. No heat pump should be connected to the supply
and return piping until the water system has been
cleaned and flushed completely. After the cleaning
and flushing has taken place, the initial connection
should have all valves wide open in preparation for
the water system flushing.
Condensate Piping
1. Condensate piping can be steel, copper, or PVC.
Each unit includes a condensate connection.
2. The condensate disposal piping must be trapped.
Vertical units are internally trapped and horizontal
units must be externally trapped. The piping must
be pitched away from the heat pump not less than
¼” per foot. The unit is supplied with a 1-1/4” male
pipe fitting to accommodate the condensate drain
connection.
3. Do not locate any point in the drain system above
the drain connection of any unit.
4. The condensate piping system must be vented at
its highest point.
MAMM-WSHP-IOM-1UB (September 2011)
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.