Mammoth 24 Tons User Manual

Multiple Circuit Horizontal and Vertical Water Source Heat Pumps With R-410A
Installation, Operation and Maintenance Manual
Sizes: 084 to 144 — Horizontal 084 to 288 — Vertical Model: M Vintage
MAMM-WSHP-IOM-1MA (November 2011)
P/N 71144916
Table of Contents
Model Nomenclature ················································································································ 3 Transportation and Storage ···································································································· 3 Installation ································································································································ 4 Unit Location ···························································································································· 5 Ductwork and Attenuation ······································································································· 6 Ventilation Air ··························································································································· 6 Piping ········································································································································ 7 Cleaning and Flushing ············································································································· 8 Fan Wall Assembly ··················································································································· 9 Start-up···································································································································· 10 Operating Limits ····················································································································· 11 DDC Controls ·························································································································· 12 I/O’s ········································································································································ 13 Keypad ···································································································································· 14 General Maintenance ············································································································· 15 VFD application parameters ·································································································· 16 Troubleshooting ····················································································································· 17 Performance Troubleshooting ····························································································· 18 Unit check-out sheet ············································································································· 19
M Vintage Vertical Size 084 to 288
MAMM-WSHP-IOM-1MA (November 2011)
M Vintage Horizontal Size 084 to 144
2
Model Nomenclature
F -084- V- H- M
Voltage
BTU/hr Cooling
Unit Type Temperature Range Vintage
F = 208-230/60/3
G = 460/60/3
J = 380-415/50/3
K = 575/60/3
Illustrations cover the general appearance of Mammoth products at the time of publication and Mammoth, Inc. reserves the right to make changes in design and construction at anytime without notice.
084 = 84,000
096 = 96,000
120 = 120,000
144 = 144,000
168 = 168,000
192= 192,000
240 = 240,000
288 = 288,000
V = Vertical H = Standard Range
H= Horizontal L = Low Temp Operation
“Mammoth” is a registered trademark of Mammoth, Inc.
©Mammoth, Inc. 2011. All rights reserved throughout the world.
Transportation and Storage
Upon receipt of the equipment, check for visible dam­age. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough han­dling, immediately check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. Then contact the Mammoth Service department
at (952) 358-6618 or info@mammoth-inc.com for a warranty claim number.
MAMM-WSHP-IOM-1MA (November 2011)
Do not stand or transport the unit on end. In the event that elevator transfer makes up-ended position­ing unavoidable, absolutely ensure that the unit is in the normal upright position for at least 24 hours before operating. Temporary storage at the job site must be indoors, completely sheltered from rain, snow, etc. High or low temperatures naturally associated with weather pat­terns will not harm units. Excessively high tempera­tures, 140°F (60°C) and higher, may deteriorate certain plastic materials and cause permanent damage.
3
Installation
General
IMPORTANT:
Mammoth water source heat pumps should be in­stalled only by qualified personnel, experienced in the installation of this equipment and related systems. Read these instructions carefully before unpacking, installing and operating this unit
1. To prevent damage, this equipment should not be operated for supplementary heating and cooling during the construction period.
2. Inspect the unit for any specific tagging numbers indicated by the factory per a request from the in­stalling contractor.
3. Check the unit nameplate for the size and voltage rating and confirm against the plans that the unit is being installed in the correct location.
4. Verify the installation location with the piping, sheet metal and electrical contractors prior to installation
5. Verify all clearances are available for the unit prior to installation.
6. Note the location and routing of water piping, con­densate drain piping, and electrical wiring. The lo­cations of these items are clearly marked on sub­mittal drawings.
7. Mammoth recommends the unit be covered during construction to protect components from dust and other harmful material. This is critical while spray­ing fireproofing material on bar joists, sandblasting,
NOTE:
Check the unit name plate for correct voltage with the plans before installing the equipment. Make sure all electrical ground connections are made in accordance with local code.
MAMM-WSHP-IOM-1MA (November 2011)
4
Unit Location
Locate the unit in an area that allows for easy removal of the filter and access panels. The diagrams to the right show minimum suggested clearances. Any addi­tional clearances would be beneficial, but not always necessary. Units need to be accessed from three sides: two panels for the two panels for the blower, two electrical access doors and one for the compressor compartment.
Horizontal Service Clearances
The requirements on any specific unit may increase or be reduced depending on several factors such as maintenance requirements and mechanical or electrical installation codes. Horizontal unit filters are removed from the bottom with an option for side removal. Verti­cal unit filters slide out of the left or right side (quad­circuit units must be removed from each side). If return air is not ducted, enough clearance will required to pro­vide for adequate airflow.
MAMM-WSHP-IOM-1MA (November 2011)
Vertical Service Clearances
5
Ductwork and Attenuation
Discharge ductwork is normally used with the M­vintage horizontal and vertical multiple circuit units. Return air ductwork may also be required.
All ductwork should conform to industry standards of good practice as described in the ASHRAE Systems Guide.
The discharge duct system will normally consist of a flexible connector at the unit connection, a transition piece to the full duct size, a short run of duct, and elbow with vanes, and a trunk duct teeing into a branch duct with discharge diffuses. The transition piece must not have angles totaling more than 30° or severe reduction in airflow performance can result.
Ventilation Air
Do not connect the full duct size to the unit. Use a transition piece sized according to the discharge collar on the unit to get to the full duct size. With metal duct material, the sides of only the elbow and entire branch duct should be internally lined with acoustic fibrous insulation for sound attenuation. Glass fiber duct board material is more absorbing and may permit omission of the canvas connector.
The ductwork should be laid out so that there is no line of sight between the unit discharge and the distribution diffusers.
Do not use sheet metal screws directly into the unit cabinet for connection of supply or return air ductwork, especially return ductwork which can hit the drain pan or the air coil.
Outside air may be required for ventilation. The temperature of the ventilation air must be controlled so that the mixture of outside air and return air entering the unit is within application limits. It is typical to close off the ventilation air system during unoccupied periods (i.e. night setback).
The ventilation air system is typically a separate building subsystem with distribution ductwork. Simple introduction of the outside air into each return air plenum chamber reasonably close to the unit air inlet is recommended. Do not duct outside air directly to the unit inlet. Provide sufficient distance for the thorough mixing of outside and return air. .
MAMM-WSHP-IOM-1MA (November 2011)
6
Loading...
+ 14 hidden pages