Loren Cook Lo-Pro Installation Manual

Personal Safety

Disconnect switches are recommended. Place the disconnect switch near the fan in order that the power can be swiftly cut off in case of an emergency, and in order that maintenance per­sonnel are provided complete control of the power source.
Lo-Pro
WARNING
This unit has rotating parts. Safety precautions should be exercised at all times during installation, operation, and maintenance. ALWAYS disconnect power prior to working on fan.
Low Profile Centrifugal Exhaust Fans
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
This publication contains the installation, operation
and maintenance procedures for standard units of the
Lo-Pro - Low Profile Centrifugal Exhaust Fans.
• LPD/LPB
Carefully read this publication prior to installation.
Loren Cook catalog, Lo-Pro, provides additional informa­tion describing the equipment, fan performance, available accessories and specification data.
For additional safety information, refer to AMCA publica­tion 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans.
All of the publications listed above can be obtained from Loren Cook Company by phoning 417/869-6474 , exte nsion 166; by FAX at 417/832-9431; or by e-mail at info@loren­cook.com.
For information and instructions on special equipment, contact Loren Cook Company at 417/869-6474.

Receiving and Inspection

Carefully inspect the fan and accessories for any dam­age and shortage immediately upon receipt of the fan.
• Turn the wheel by hand to ensure it turns freely and does not bind.
• Check dampers (if included) for free operation of all moving parts.
• Record on the Delivery Receipt any visible sign of damage.
existing mounting slots.
Damper Installation
If your fan is supplied with dampers, follow the directions below. If your fan does not include dampers, proceed to Belt and Pulley Installation.
a. Place the damper inside the curb. Ensure the damper
motor wiring. d. Operate the dampers manually to ensure the baldes
move freely. e. Install ventilator over curb.
Wall Installation
a. Position unit so that hinge on topcap is facing down.

Handling

Lift the fan by the base or by the shipping carton. Never
lift by the shaft, motor or housing.

Storage

If the fan is stored for any length of time prior to installa­tion, store it in its original shipping crate and protect it from dust, debris and the weather.

Installation

To prevent damage to the fan during shipping, motors 5 HP and larger, and extremely heavy motors (cast iron or severe duty) are shipped loose and must be field mounted by bolting the motor on the motor mounting plate in the
Lo-Pro
Personal Safety
Disconnect switches are recommended. Place the disconnect switch near the fan in order that the power can be swiftly cut off in case of an emer­gency, and in order that maintenance personnel are provided complete control of the power source.
Conduit Nipple

Diverter

Terminator Lid
Sealing Nut
Terminator
Terminator
Terminator
Roof Top Installation Shown
Figure 4
Belt and Pulley Installation
1 foot
1/4 inch
Figure 1
Figure 2
Tolerance
Center Distance
Maximum
Gap
Up thru 12” 1/16”
12” up through 48 1/8”
Over 48” 1/4”
Belt tension is determined by the sound of the belts when the fan is first started. The belts will produce a loud squeal, which dissipates after the fan is oper ating at full capacity. If belt tension is too tight or too loose, lost efficiency and damage can occur.
Do not change the pulley pitch diameter to change ten­sion. The change will result in a different fan speed. )
a. Loosen the motor plate adjustment nuts on motor
base and move motor plate in order that the belts can easily slip into the grooves on the pulleys. Never pry, roll, or force the belts over the rim of the pulley.
b. Adjust the motor plate until proper tension is reached.
For proper tension, a deflection of approximately 1/4” per foot of center distance should be obtained by
firmly pressing the belt. Refer to Figure 1. c. Lock the motor plate adjustment nuts in place. d. Ensure pulleys are properly aligned. Refer to Figure 2.
OFFSET ANGULAR OFFSET/ANGULAR
A
W
X Y
CENTER
DISTANCE
(CD)
Wiring Installation
All wiring should be in accordance with local ordinances and the National Electrical Code, NFPA 70. Ensure the power supply (voltage, frequency, and current carrying capacity of wires) is in accordance with the motor name­plate.
Refer to the Wiring Diagrams, next page.
Lock off all power sources before unit is wired to power source.
Leave enough slack in the wiring to allow for moto r m ove­ment when adjusting belt tension. Some fractional motors have to be removed in order to make the connection with the terminal box at the end of the motor.
Follow the wiring diagram in the disconnect switch and the wiring diagram provided with the motor. Cor­rectly label the circuit on the main power box and always identify a closed switch to promote safety (i.e., red tape over a closed switch).
Optional Diverter
a. Position diverter so that air flow is directed up. b. Seal between diverter flange and unit side panel with
RTV 400 silicone. (RTV Silicone is NOT supplied.)
c. Use screws provided to secure diverter to unit.
Optional Grease Terminator Installation
a. Attach hardware to drain hole in the diverter. See Figure 4. b. Screw new canister into lid.
Roof Top Installation Shown
Conduit Nipple
Z
B
GAP
Pulley Alignment
Pulley alignment is adjusted by loosening the motor pulley
setscrew and by moving the motor pulley on the motor shaft.
Figure 2 indicates where to measure the allowable gap for the drive alignment tolerance. All con­tact points (indicated by WXYZ) are to have a cap less than the tolerance sh own in the table. When the pulleys are not the same width, the allowable gap must be adjusted by half of the difference in width. Figure 3 illustrates using a carpenter’s square to adjust the position of the motor pulley until the belt is parallel to the longer leg of the square.
Figure 3
GAP
Diverter
Terminator Lid
Sealing Nut
Terminator
Terminator
Figure 4
Final Installation Steps
a. Inspect fasteners and setscrews, particularly fan
mounting and bearing fasteners, and tighten according to the recommended torque shown in the table on page 4,
2
Terminator
Fan
Motor
Damper
Motor*
Second Damper
Motor
T
ransformer**
T
ransformer**
L3 L2 L1
4
5
6
1 728
3 9
L
1
L2L
3
456
789
12
3
L
1
L2L
3
Low Voltage
208/230 Volts
High Voltage
460 Volts
3 Phase, 9 Lead Motor Y-Connection
Wiring Diagrams
T-1
T-4
Ground B
L
2
L
1
Ground A
Line
Ground A
Ground B
T-1
T-4
Low Speed
High Speed
L
1
L
2
Line
Ground B
J-10
T-5
Ground A
Link A Link B
Low Voltage
Line
L
2
L
1
Ground A
Link A & B
L
1
L
2
Line
Ground B
T-5
J-10
Motor
1 2 3
4 5
6
Together
High Speed
Line
L
1
L
2
L
3
1 2 3
4 5
6
Open
Low Speed
Line
L
1
L
2
L
3
Motor
Low Speed Low Speed Low Speed
High Speed High Speed High Speed
T
3
T
2
T
1
T
11
T
12
T
13
Motor
L
1
L
2
L
3
Line
7
1
6
789 456
12
3
Low Voltage
208/230 Volts
High Voltage
460 Volts
8 2
4
9 3
5
L1L
3
L
2
L
1
L
3L2
3 Phase, 9 Lead Motor Delta-Connection
Single Speed, Single Phase Motor
Wiring Diagrams
When ground is required, attach to ground A or B with no. 6 thread forming
To reverse, interchange any 2 line leads.
screw. To reverse, interchange T-1 and T-4.
2 Speed, 2 Winding, Single Phase Motor 2 Speed, 1 Winding, 3 Phase Motor
When ground required, attach to ground A or B with No. 6 thread forming screw. To reverse, interchange T-1 and T-4 leads.
To reverse, interchange any 2 line leads. Motors require magnetic control.
Single Speed, Single Phase, Dual Voltage 2 Speed, 2 Winding, 3 Phase
When ground required, attach to ground A or B with No. 6 thread forming screw. To reverse, interchange T-5 and J-10 leads.
To reverse: High Speed-interchange leads T11 and T12. Low Speed-interchange leads T line leads.
and T2. Both Speeds-interchange any 2
1
Typical Damper Motor Schematic
For 3 phase, damper motor voltage should be the same between L1 and
. For single phase application, disregard L3. *Damper motors may be
L
2
available in 115, 230 and 460 volt models. The damper motor nameplate voltage should be verified prior to connection. **A transfomer may be pro­vided in some installations to correct the damper motor voltage to the specified voltage.
3
Loading...
+ 5 hidden pages