This publication contains the installation, operation and
maintenance procedures for standard units of the Gemini
- Ceiling and Cabinet Fans. Carefully read this publication
prior to installation.
Carefully read this publication and any
supplemental documents prior to any
installation or maintenance procedure.
Loren Cook Company’s Gemini catalog provides
additional information describing the equipment, fan
performance, available accessories and specication
data.
For additional safety information, refer to AMCA
publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans.
All of the publications listed above can be obtained
from Loren Cook Company by phoning (417) 869-6474,
extension 166; by FAX at (417) 832-9431; or by e-mail at
info@lorencook.com.
For information and instructions on special equipment,
contact Loren Cook Company at (417) 869-6474.
Rotating Parts & Electrical Shock Hazard:
Disconnect electric power before working on unit.
Follow proper lockout / tagout procedures to ensure
the unit cannot be energized while being installed or
serviced.
A disconnect switch should be placed near the fan
in order that the power can be swiftly cut off, in case
of an emergency and in order that maintenance
personnel are provided complete control of the
power source.
Handling
Lift fan by the outside housing (box) or by the blower
mounting brace. Never lift by the shaft or motor.
Storage
If the fan is stored for any length of time prior to
installation, store it in its original shipping crate and
protect it from dust, debris and the weather.
Installation
Motor Installation
All Gemini units are shipped with motors mounted at
the factory.
Gemini 100 Inline to Ceiling Conversion
The Gemini 100 series can be converted from inline
to ceiling by ordering the Inline to Ceiling Conversion Kit
from Loren Cook Company (Part Number 797180). The
kit includes all parts required, plus detail instructions on
how to convert the Gemini 100.
Gemini 100 Ceiling to Inline Conversion
The Gemini 100 series can be eld converted from
ceiling to inline by following these steps:
1. Remove and discard the inlet box end plate.
2. Install the inline cover panel with sheet metal
screws as shown on the following page.
Ceiling to Inline Conversion Kit can be ordered from
Loren Cook Company (Part Number 797181), or
fabricate the required part using the following sketch.
Grounding is required. All eld-installed wiring
must be completed by qualied personnel. All eld
installed wiring must comply with National Electric
Code (NFPA 70) and all applicable local codes.
Failure to follow these instructions could result in
death or serious injury.
Receiving and Inspection
Carefully inspect the fan and accessories for any
damage and shortage immediately upon receipt of fan.
• Turn the wheel by hand to ensure it turns freely and
does not bind.
• Inspect dampers (if included) for free operation of
all moving parts.
• Record on the Delivery Receipt any visible sign of
damage.
Gemini 100
1
Page 2
Exhaust
Duct Collar
Side
Panel
Intake
Outlet
Box
Mounting
Brackets
SEE NOTE
Mounting
Bracket
Grille
Screw
Figure 1
s
atte
Inline
Cover
Panel
18 Ga. Galvanized Steel
14-1/16
11-15/16
1-7/16
Formed View
16-3/4
13-15/16
Break up at 90
Flat P
rn View
1-3/8
11-15/16
13-5/16
Direction of Discharge (200-900 Series)
The duct collar (damper frame), for fastening a
standard duct, is located so discharge will be from the
top, as shown in gure 1. When discharge from the side
is desired, follow these steps:
1. Remove the side panel and install with the duct
collar in the side position, as shown in gure 2.
2. Move the mounting bracket from the top discharge
to the side discharge position for securing the
housing to the joists.
See in gure 2.
Fan Installation
1. Adjust housing, using the adjust mounting bracket
provided, to allow for the thickness nished ceiling
and grille. Refer to gure 3. If a unit is furnished
with lters allow 3/8” for lters. Refer to gure 4.
2. Fasten duct work to the outside of the duct collar
(damper frame) using sheet metal screws. Make
sure sheet metal screws are placed where they do
not interfere with damper operation.
3. Fasten the housing to the bottom of the joists
through the holes provided in the mounting bracket.
Refer to gures 1 and 2.
For Ceiling Radiation Damper Installation see
separate document “Gemini/CRD Installation
Supplement.”
Figure 2
Side
Panel
Mounting
Brackets
Intake
Duct Collar
Exhaust
Side Discharge
Figure 3. Note: Allow for ceiling thickness.
Suggested Installation: Unit without lter.
Figure 4 Note: Allow for ceiling thickness.
Suggested Installation: Unit with lter.
Mounting
SEE NOTE
Allow 3/8"
for filter
Screw
Bracket
Optional
Filter
Grille
2
Page 3
White
(Common)
Wire
Red
(Low Speed)
Wire
White
(Common)
Wire
Black
(High Speed)
Wire
Plug
options
Notice! Do not install above or inside
shaded area
Gemini 200 - 300 and 600 - 700 Series:
White Line
45
Cooking
Equipment
45
Floor
Wiring Installation
All wiring should be in accordance with local
ordinances and the National Electrical Code, NFPA 70.
Ensure the power supply (voltage, frequency, and current
carrying capacity of wires) is in accordance with the
motor nameplate. Refer to Wiring Diagrams.
Lock off all power sources before unit is wired to power
source.
Follow the wiring diagram in the disconnect switch and
the wiring diagram provided with the motor. Correctly
label the circuit on the main power box and always
identify a closed switch to promote safety (i.e., red tape
over a closed switch).
Note: Insulate Unused Leads. Fan plug box is designed
for single speed operation, using an FSC to vary speed if
required. Do not wire to more than two leads.
Black (High)
Red (Low)
Line
Electrical Shock & Fire Hazard:
Insulate Unused Lead
Failure to follow these instructions could result in
death or serious injury.
Gemini 400 - 500 Series:
White Line
Black Line
Gemini 800 - 900 Series:
White Line
Black (High)
Blue (Medium)
Red (Low)
Line
Wiring Diagrams
Gemini 100 Series:
Snap either the red wire, low-speed plug or the black
wire, high-speed plug into the eld wiring compartment
as shown. Low speed: Connect red and white wires to
line. Red wire, low-speed plug is for Model 122, 142, 162
and 182. High speed: Connect black and white wires to
line. Black wire, high-speed plug is for Model 124, 144,
164 and 184.
Electrical Shock & Fire Hazard:
Insulate Unused Leads Separately
Failure to follow these instructions could result in
death or serious injury.
1. Inspect fasteners and setscrews, particularly fan
mounting fasteners, and tighten as required.
2. Inspect for correct amperage and voltage with an
ammeter and voltmeter.
3. Ensure blower is secured to duct work.
4. Ensure all accessories are installed.
5. Inspect wheel-to-inlet clearance. Make sure wheel
does not rub against the inlet.
6. Test the fan to be sure the rotation is the same as
indicated by the arrow marked Rotation.
Grille installation is described after the operation
and inspection sections.
Operation
Pre-Start Checks
1. Lock out all the primary and secondary power
sources.
2. Inspect fasteners and setscrews, particularly those
used for mounting the fan, and tighten if necessary.
3. Inspect motor wiring.
4. Ensure fan and ductwork are clean and free of
debris.
5. Test the fan to ensure the rotation of the wheel is
the same as indicated by the rotation label.
6. Restore power to unit.
Start Up
Before attaching the grille, turn the fan on and inspect
for the following:
• Direction of rotation.
• Excessive vibration.
• Unusual noise.
• Motor noise.
• Improper motor amperage or voltage.
If a problem is discovered, immediately shut off the fan.
Lock out all electrical power and check for the cause of
the trouble — refer to the ‘Troubleshooting’ section.
4
Page 5
Inspection
Inspection of the fan should be conducted at the rst
30 minute interval of satisfactory operation. During the
inspection, stop the fan and inspect as per directions
below.
• Inspect bolts, setscrews, and motor mounting bolts.
• Adjust and tighten as necessary.
Grille Installation
Attach the grille by hand-tightening the knurled screws.
When the unit is furnished with a lter, place the knurled
screws through the hole in the grille. Install the lter
through the holes provided in the lter frame.
Maintenance
Establish a schedule for inspecting all parts of the fan.
The frequency of inspection depends on the operating
conditions and location of the fan.
Fans exhausting contaminated air (airborne abrasives)
should be inspected every three months.
Regular inspections are recommended for fans
exhausting non-contaminated air.
It is recommended the following inspections be
conducted twice per year.
• Inspect bolts and setscrews for tightness. Tighten
as necessary.
• Inspect for cleanliness. Clean exterior surfaces
only. Removing dust and grease on motor housing
assures proper motor cooling.
Access
Gemini 100:
To inspect, clean or repair refer to gure 6 and follow
these steps:
1. Remove grille.
2. Remove blower assembly from housing:
1. Disconnect the motor from electrical supply
2. Remove the mounting bolts on the inlet plate
assembly and remove the motor/wheel assembly
3. Remove the blower wheel with an allen wrench
Gemini 200 - 700 series
To inspect, clean, or repair, refer to gure 7 and follow
these steps:
1. Remove grille.
2. Remove blower assembly from housing:
1. Disconnect the motor from electrical supply.
2. Remove mounting bolts.
3. Slide discharge ange out of spring clip and
remove motor/blower assembly from box.
3. Remove inlet ring from blower housing.
4. Remove blower wheel with an allen wrench.
Blower Mounting Brace
Wheel
Mounting Bolts
Unit
Mounting
Bracket
Adjustment
Wiring
Box
Duct Collar
Bolts
Motor
Damper
Blade
Electrical Supply
Junction Box & Cover
Grill Mount
Holes
Mounting Bolts (4)
Inlet Plate
5
Page 6
Gemini 800 - 2000 series:
(Ensure proper clearance between wheel and inlet ring)
To inspect, clean, or repair, refer to gure 8 and follow
these steps:
1. Remove grille.
2. Remove blower assembly from housing:
1. Disconnect the motor from the electrical supply.
2. Remove motor plate bolts.
3. Slide motor plate and remove motor/blower
assembly from box.
3. Remove inlet rings from blower housing (both
sides).
4. Mark the wheel and housing to ensure correct
replacement of blower wheels (one is clockwise
and the other is counter-clockwise), then remove
the blower wheels with an allen wrench.
Wheel
Blower Housing
Mo tor Plate
Motor Plate B olts
2. Poor fan inlet conditions. There should be a straight
clear duct at the inlet.
3. Improper wheel alignment.
4. Damper held shut by tape.
5. Screw attaching duct work to collar interfering with
damper operation.
Excessive Vibration and Noise
1. Damaged or unbalanced wheel.
2. Speed too high.
3. Incorrect direction of rotation. Make sure the fan
rotates in same direction as the arrows on the
motor or belt drive assembly.
4. Motor needs lubrication or replacement.
5. Fan surge.
Overheated Motor
1. Motor improperly wired.
2. Incorrect direction of rotation. Make sure the fan
rotates in same direction as the arrows on the
motor or belt drive assembly.
3. Cooling air diverted or blocked.
4. Improper inlet clearance.
5. Incorrect fan RPMs.
6. Incorrect voltage.
Motor
Inlet Ring
Reassembly
Simply reverse the disassembly instructions. Make sure
the wheels do not rub on the inlet rings. When replacing
the motor, make sure the motor and wheels are properly
aligned with the blower housing.
Notice! Ensure that the blower discharge ange is
secured in slot of the cabinet on Gemini 200 - 700
series.
Motor Bearings
Motor bearings are pre-lubricated and sealed.
Under normal conditions they will not require further
maintenance for a period of ten years.
Motor Services
Should the motor prove defective within a one-year
period, contact your local Loren Cook representative
or your nearest authorized electric motor service
representative
Troubleshooting
Problem and Potential Causes:
Low Capacity or Pressure
1. Incorrect direction of rotation. Make sure the fan
rotates in same direction as the arrows on the
motor or belt drive assembly.
6
Page 7
Gemini 100 Parts List
1
2
3
4
5
6
7
8
9
10
Air Flow
11
11
Gemini 200 - 900 Parts List
Parts
Number
1Inlet Box End Plate
(Ceiling only)
2Housing/Scroll
3Field Wiring Compartment
4Motor
5Tinnerman Clip (Grill)
6Mounting Bracket
7Backdraft Damper
8Wheel
9Motor Mount/Inlet
10Inlet Box
11Grille
Parts
Number
1Backdraft
Gemini 200 700
Damper
Gemini 800 900
Backdraft
Dampers (2)
2Damper FrameDamper Frame
(2)
3Mounting Bracket
(2)
Mounting Bracket
(2)
4WheelWheel (2)
5Grille (Ceiling
and Wall)
Grille (Ceiling
and Wall)
6Blower HousingBlower Housing
(2)
7MotorMotor
8InsulationInsulation
9CabinetCabinet
10Cabinet Side
Cover
1
2
Cabinet Side
Cover
4
Air Flow
3
10
67
5
8
9
7
Page 8
Gemini 1000 - 2000 Parts List
Parts
Number
1Grille (ceiling and wall)
2Backdraft Damper (2)
3Wheel (2)
4Blower Housing (2)
5Motor
6Insulation
7Mount Brackets (2)
8Cabinet
9Cabinet Side Cover
2
1
4
Gemini 200 - 700
8
5
6
Limited Warranty
Loren Cook Company warrants that your Loren Cook
fan was manufactured free of defects in materials
and workmanship, to the extent stated herein. For
a period of one (1) year after date of shipment, we
will replace any parts found to be defective without
charge, except for shipping costs which will be paid
by you.
This warranty is granted only to the original
purchaser placing the fan in service.
This warranty is void if the fan or any part thereof
has been altered or modied from its original design
or has been abused, misused, damaged or is in
worn condition or if the fan has been used other
than for the uses described in the company manual.
This warranty does not cover defects resulting from
3
9
normal wear and tear.
To make a warranty claim, notify Loren Cook
Company, General Ofces, 2015 East Dale Street,
Springeld, Missouri 65803-4637, explaining in
writing, in detail, your complaint and referring to the
specic model and serial numbers of your fan. Upon
receipt by Loren Cook Company of your written
complaint, you will be notied, within thirty (30) days
of our receipt of your complaint, in writing, as to the
manner in which your claim will be handled. If you
are entitled to warranty relief, a warranty adjustment
will be completed within sixty (60) business days of
the receipt of your written complaint by Loren Cook
Company.
This warranty gives only the original purchaser
placing the fan in service specically the right. You
7
may have other legal rights which vary from state to
state.
Corporate Ofces 2015 E. Dale Street Springeld, MO 65803
Phone 417-869-6474 Fax 417-862-3820 lorencook.com
8
Gemini IOM - May 2011
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.