2.
3.
2.
1.
1.
1.
2.
3.
9.
8.
6.
7.
4.
5.
ERV Evaporator Coil Supplement
ENERGY RECOVERY VENTILATOR
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
This publication contains supplemental installation, operation and maintenance instructions for an ERV-with optional
evaporator coil.
Carefully read this publication and the installation, operation, and maintenance instruction for standard units of the
ERV- Energy Recovery Ventilators publication prior to any
installation or maintenance procedure.
Loren Cook catalog, ERV , provides additional information
describing the equipment, fan performance, available accessories,
and specification data.
For additional safety information, refer to AMCA Publication
410-96, Safety Practices for Users and Installers of Industrial and
Commercial Fans .
All of the publications listed above can be obtained from Loren
Cook Company by phoning (417)869-6474, extension 166; by FAX
at (417)832-9431; or by e-mail at info@lorencook.com.
For information on special equipment, contact Loren Cook Company Customer Service Department at (417)869-6474.
Mounting
Position the coil such that the suction header is at the entering air-side of the coil and the distributor tubes are at the leaving
air-side of the coil. This orientation provides counterflow heat
exchange which is required for proper coil performance.
The suction connection is located at the bottom of the coil
when properly installed.
See Figure 1 - Evaporator Coils.
Coil Types
Model EN
coils are used for
applications where
capacity control is
not required. Single or multiple distributors are available depending on the number of circuits
required. Model EN evaporators utilize dual suction connections
when multiple distributors are used.
EJ coils come with interlaced circuiting. This form of capacity control utilizes two distributors with each feeding every other
tube in the first row of the coil. Each distributor has a separate
suction connection.
EN
Figure 1 - Evaporator Coils
EJ
Installation
Inspect the
refrigerant distributor and verify that
the nozzle is in
place. The nozzle
is generally held in
place by a retaining ring or it is an
integral part of the
distributor itself
(see Figure 2 Distributor). If a
hot gas bypass kit
was ordered with
the coil, the nozzle
Retainer
Ring
Figure 2 - Distributor
Figure 3 - Hot
Gas Bypass Kit
Nozzle
Distributor
will be located in it rather than the distributor (see Figure 3 - Hot
Gas Bypass Kit).
All field brazing and welding should be performed using high
quality materials and an inert gas purge (such as nitrogen) to
reduce oxidation of the internal surface of the coil.
If a hot gas bypass kit was ordered with the coil install it now.
Complete installation instructions are in the box that contains the
hot gas bypass kit. Align the side port with the hot gas line prior to
brazing into place.
Connect the suction line and suction connection.
Install the expansion valve. Follow the expansion valve manufacturer’s recommendations for installation to avoid damaging the
valve. If the valve is externally equalized, use a tubing cutter to cut
off the plugged end of the factory installed equalizer line. Next, use
a de-burring tool to remove any loose metal from the equalizer line
and attach it to the expansion valve. If the valve is internally equalized, the factory installed equalizer line can be left as is or it can be
cut back and sealed.
The expansion valve’s remote sensing bulb should be
securely strapped to the horizontal run of the suction line at the 3 or
9 o’clock position and insulated.
Connect the liquid line to the expansion valve. Pressurize the
coil, expansion valve assembly and suction connection to 100 psig
with dry nitrogen or other suitable gas. The coil should be left pressurized for a minimum of 10 minutes.
If the coil holds pressure, the hook-up can be considered leak
free. If the pressure drops by 5 psi or less, repressurize the coil and
wait another 10 minutes. If the pressure drops again, there are
more than likely one or more small leaks, which should be located
and repaired. Pressure losses greater than 5 psi would indicate a
larger leak, which should be isolated and repaired. Be sure to check
valves and fittings as potential sites for leakage or bleed. If the coil
is found to be leaking, contact your local representative. Unauthorized repair of the coil may void the coil’s warranty (see warranty
policy on back cover).
Use a vacuum pump to evacuate the coil and any interconnecting piping that has been open to atmosphere. Measure the vacuum in the piping using a micron gauge located as far from the
pump as possible (the vacuum at the pump will be greater than the
rest of the system). Evacuate the coil to 500 microns or less then
close the valve between the pump and the system. If the vacuum
holds to 500 microns or less for one minute, the system is ready to
be charged or refrigerant pumped down in another portion of the
system can be opened to the coil. A steady rise in microns would
indicate that moisture is still present and that the coil should be further vacuumed until the moisture has been removed.
10. Failure to obtain a high vacuum is indicative of a great deal
of moisture or a small leak. Break the vacuum with a charge of dry
nitrogen or other suitable gas and recheck for leaks (soapy water
works well). If no leaks are found, continue vacuuming the coil until
the desired vacuum is reached.
11. All field piping must be self-supporting.
4.
3.
2.
1.
2.
3.
1.
12. Refer to Figure 4 - Hot Gas Bypass Kit Installed and Fig-
ure 5 - General Diagram, for general piping.
Liquid Line
Expansion Valve
Hot Gas B
Hot Gas Side Port
-Pass
Remote Sensing Bulb
Equalizer Line
Suction Line
Nozzle
Distributor
Suction Header
Straps
Coil
Suction Connection
Figure 4 - Hot Gass Bypass Kit Installed
Liquid Line
Expansion Val v e
Distributor
Equal izer Line
Nozzle
Suction Head er
Coil
Operation
Proper air distribution is vital to coil performance. Air flow
anywhere on the coil face should not vary by more than 20%.
Air velocities should be maintained between 200 and 550
feet per minute.
The drain pan should be designed and installed such that
there is no standing water.
Maintenance
Filters should be inspected on a regular basis and changed
as needed. Maintaining clean filters is a cost-effective way to help
maintain maximum coil performance and service life.
Periodic inspection of the coil for signs of corrosion and for
leaks is recommended. Small leaks can be detected using a
Halide torch. Repair and replacement of the coil and the connecting piping, valves, etc., should be performed as needed by a qualified individual(s).
Should the coil surface need cleaning, caution should be
exercised in selecting the cleaning solution as well as the cleaning
equipment. Improper selection can result in damage to the coil
and/or health hazards. Clean the coil from the leaving air-side so
that foreign material will be washed out of the coil rather than
pushed further in. Be sure to carefully read and follow the manufacturer’s recommendations before using any cleaning fluid.
The use of filter-dryers in the system piping is recommended
along with a sight glass that has a moisture indicator. Replace the
filter dryer(s) as needed.
Note: Refrigerant conversions are beyond the scope of this
manual and should only be performed by qualified parties.
Suction Line
Remote Sensin
Bulb
Straps
Figure 5 - General Diagram
Suc tion Connection
Corporate Offices: 2015 E. Dale Street Springfield, MO 65803 417.869.6474
lorencook.com
2
ERV Evaporator Coil IOM Supplement- December 2002