Lg Ls-c1210hd Installation Guide

Page 1
IMPORTANT! Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
CAUTION
: Improper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-22 causes frostbite burns.
• R-22 is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner
or prominently displayed near the indoor Furnace/Air Handler Unit.
P/NO:3828A30087B
DELUXE HIGH WALL MINI SPLIT
INSTALLATION INSTRUCTIONS
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause
dripping and water damage to wall and floors.
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid,
level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
... in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
Special warnings
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Page 2
2
OUT-LINE OF INSTALLATION
Installation works
Installation Parts
Required Tools
2. Installation of indoor, Outdoor Unit
1. Installation Parts Providided
1)
Selection of the best location
.....3
2) Indoor unit Installation.............4
• Installation Plate
• Four Type "A" screws
• Connecting cable
• Level
• Screw driver
• Electric drill
• Hole core drill; ø70mm(2.76")
3. Piping and drainage of indoor unit
1) Preparation of Pipings.............5
2) Connection of Pipings .........6~7
3) For the left Pipings ............8~10
• Pipes: Gas side.......
1/2"(9K, 12K)
........
5/8"(18K, 24K)
Liquid side....
1/4"(9K, 12K)
.....
3/8"(18K, 24K)
• Insulated drain hose
• Insulation materials
• Flaring Tools set
• Specified Torque Wrenches Liquid side - 1.8kg.m(13ft.lbs):9K, 12K
4.0kg.m(28.9ft.lbs):18K, 24K
Gas side - 5.5kg.m(39.8ft.lbs):9K, 12K
6.6kg.m(47.7ft.lbs):
18K, 24K
Spanner.......................Half union
4. Connecting Pipings and the cable to Outdoor unit
1) Connection of Pipings............11
2) Connection of the cable...11~12
• Additional Drain hose
(Inner Dia ................ø16mm(5/8")
• Specified Torque Wrenches Liquid side - 1.8kg.m(13ft.lbs):9K, 12K
4.0kg.m(28.9ft.lbs):18K, 24K
Gas side - 5.5kg.m(39.8ft.lbs):9K, 12K
6.6kg.m(47.7ft.lbs):
18K, 24K
5. Checking the Drainage and Connecting the cable to Indoor unit
1) Checking the Drainage .........13
2) Connecting of the cable.........14
3) Forming the pipings ...............15
• A glass of water
• Screw driver
6. Air Purging
1) Air Purging ......................16~17 • Hexagonal Wrench (4mm; 5/32")
• Gas-leak Detector
7. Test running
................
18
8. Installation Instruction Templates
...........................................................................................
19
• Two type "B" screws • Owner's Manual
• Thermometer
Page 3
3
2. Installation of Indoor, Outdoor unit
1. Installation Parts Provided
1) Selection of the best location
1. Indoor unit.
2. Outdoor unit.
3.Piping length and the elevation
There should not be any heat source or
steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
• If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted.
• There should not be any animals or plants which could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.
More than
5 cm(2")
More than 5 cm(2")
More than
5 cm(2")
More than eye level
More than 10 cm(4")
More than 10 cm(4")
More than 70 cm(28")
Indoor unit
Outdoor unit
Pipe Size
MODEL
(Cooling Capa.)
GAS LIQUID
Max.
length
A
Max.
Elevation
B
9K, 12K 1/2" 1/4" 15m(50ft) 8m(26ft)
18K, 24K 5/8" 3/8" 15m(50ft) 8m(26ft)
1. Type "A" screw
3. Type "B" screw
4. Holder Remote-Controller
2. Installation Plate
Roof Top Installations
If it is necessary to install units on a roof structure, be sure to elevate and level the units. Ensure the roof structure and anchoring method are adequate for unit location. Consult local codes regarding rooftop mounting.
NOTE: When condensing unit is to be installed on
a bonded guaranted roof, a release must be obtained from the building owner to free the installer from all liabilities.
B
A
Page 4
Avoid areas where electrical wiring, conduits or gas lines are located. Accidentally cutting a live wire or gas line can cause death or injury.
4
2) Indoor Unit Installation
The mounting wall should be strong and solid enough to protect it from the vibration.
1.Mount the installation plate on the wall with four Type "A" screws.
(if mounting the unit on the concrete wall, consider using anchor bolts.)
• Always mount the Installation Plate horizontally by aligning the marking-off line by means of the thread and a level.
2. Drill the piping hole with 70mm(2.75") dia. holecore drill.
• See templates in the back of this manual(page 19, 20) for hole location relative to the installation plate.
• Drill the Piping hole at either the right or the left and the hole should be slightly slanted to the outdoor side.
Type "A" screw
Installation Plate
marking-off line
Thread
Weight
The lower left and right side of Installation Plate
WARNING
Left rear piping
1.8" (46mm)
Right rear piping
1"
(25mm)2"(51mm)
1.9"
(48mm)
Hole center
9K, 12K, 18K, 24K
ø2.75"(70mm)
INDOOR
Installation plate
WALL
OUTDOOR
5-7mm
9K,12K
(0.2~0.3")
18K, 24K
Page 5
5
3. Piping and Drainage of Indoor Unit
1) Preparation of pipings
1. Cut the pipes and the cable.
• Use the pipes purchased locally.
• Measure the distance between the indoor and the outdoor unit.
• Cut the pipes a little longer than measured distance.
• Cut the cable 1.5m(5.0 ft) longer than the length of the pipe.
2. Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end toward down to avoid the metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas leakage.
3. Flaring the pipes.
• Insert the flare nuts, mounted on the connection ports of both indoor and outdoor unit, onto the copper pipes. Some gas may leak, when the flare nuts are removed from the indoor unit, as some gas is charged to prevent the inside of the pipe from rusting.
• Fit the copper pipe end into the Bar of flare tool about 0.5~1.0mm higher. (See illustration)
• Make a flare at the end of copper pipe with a flare tool*.
* Use "RIDGID" or equivalent.
4. Tape the flaring portion to protect it from the dust or damages.
Bar
Yoke
Cone
Handle
Ä
Bar
Copper pipe
When properly flared, the internal surface of the flare will evenly shine and be of even thickness. After the flare part comes into contact with the connectors, carefully check the flare finish.
Pipe cutter
Slanted
Rough
Pipe
Point down
Reamer
"
A"; ø6.35mm (1/4") ¡ 0.5mm
ø9.52mm (3/8") ¡ 0.5 mm ø12.7mm (1/2") ¡ 0.5 mm ø15.88mm (5/8") ¡ 1.0mm
= Improper flaring =
Inclined
Surface
damaged
Cracked
Uneven
thickness
Page 6
If the drain hose will run in the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
* Foamed polyethylene or equivalent is
recommended.
6
2) Connection of Pipings
1. Remove the indoor tubing with Drain hose from the hole
• Remove tubing holder and pull the tubing out of the chassis.
2. Replace the tubing holder into original position.
• Recommended SPEC. of the additional Drain Hose.
*
Foamed Polyethylene or equivalent is recommended.
CAUTION: The unit's drain hose and additional
drain hose must be sealed up by adhesive or tape.
For right rear piping
3. Route the tubing and the drain hose straight backwards.
4. Insert the connecting cable into the indoor unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection later.
5. Tape the tubing, drain hose and the connecting cable. Be sure that drain hose locates at the lowest side of the bundle. Locating at the upper side can be a reason that drain water overflows drain pan inside the unit.
¤ŁPull
¤ Press
To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.
Tubing holder
Connecting cable
Gas side piping
Liquid side piping Drain hose
Taping Indoor/Outdoor
Connecting cable
NOTE
Joint Part
The material of Drain hose
Inner size Material
MAX.
ø16mm(5/8")
soft PVC
Soft PVC hose
(It must be surrounded with an Insulation Material
*
)
Page 7
7
6. Indoor unit installation
• Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it left and right.
7. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks. When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
8. Wrap the insulation material around the connecting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the picture on page 6 for inserting it into the indoor unit and refixing the tubing holder easily.
9. Insulation of connecting tubing
• Because capillary tubing is installed in the outdoor unit, both the liquid and gas side tubes of this air conditioner become cold or hot(Heat pump model). Therefore, to prevent heat loss and wet floors due to dripping of condensation water, both tubes must be well insulated with proper insulation material. The thickness of the insulation material should be a Min. 8mm(5/16").
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots (sound click).
Model
Pipe Size Torque
9K,
Liquid Side (1/4") 1.8kg¡⁄m(13.0ft.lbs)
12K
Gas Side (1/2") 5.5kg¡⁄m(39.8ft.lbs)
18K,
Liquid Side (3/8") 4.0kg¡⁄m(28.9ft.lbs)
24K
Gas Side (5/8") 6.6kg¡⁄m(47.7ft.lbs)
Flare nut
Pipings
Torque wrench
Spanner
Indoor unit tubing
Plastic Bands
Insulation material
Wrap the insulation material around the connecting portion.
Min. 8mm
(5/16")
Min. 8mm
(5/16")
Insulation
Thickness.
For Heat pump model, Heat-resistant insulation material enduring at 230°F should be used.
Page 8
8
For the left pipings
3. Route the indoor tubing with the drain hose to the piping hole as desired position.
4. Insert the pipings, power supply cord and connecting cable into the piping hole.
Indoor
Outdoor
Connecting cable
Piping
¤ŁPull
To remove the holder, press the bottom of chassis near the holder upward and pull the tab out of its hole.
Tubing holder
¤ Press
Page 9
9
5. Insert the connecting cable into the indoor unit.
• Don't connect the cable to the indoor unit.
• Make a small loop with the cable for easy connection later.
6. Tape the tubing, drain hose and the connecting cable.
7. Indoor unit installation
• Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
8. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until the wrench clicks. When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Indoor/outdoor
connecting cable
Connecting cable
Taping
Gas side piping
Liquid side piping
Drain hose
Flare nut
Pipings
Torque wrench
Spanner
Indoor unit tubing
Plastic Bands
Insulation material
Wrap the insulation material around the connecting portion.
9. Wrap the insulation material around the connecting portion.
CAUTION: Take care to arrange the pipings,
drain hose and cables as the right upper picture for inserting it into the indoor unit and refixing the tubing holder easily.
Model
Pipe Size Torque
9K,
Liquid Side (1/4") 1.8kg¡⁄m(13.0ft.lbs)
12K
Gas Side (1/2") 5.5kg¡⁄m(39.8ft.lbs)
18K,
Liquid Side (3/8") 4.0kg¡⁄m(28.9ft.lbs)
24K
Gas Side (5/8") 6.6kg¡⁄m(47.7ft.lbs)
Page 10
10
10. Set the pipings and the connecting cable
to the back of the chassis with the tubing holder
• Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged in the bottom of chassis.
11. Indoor unit installation
• Hook the indoor unit onto the upper portion of installation plate. (Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Piping
Taping
Drain hose
Tubing holder
¤ Hook
¤ŁPush
Connecting cable
Drain hose
Press the lower left and right side of the unit against the Installation Plate until the lower hooks engage with their slots (sound click).
Page 11
2)
Connection of the cable
1. Remove the cover control from the unit by
loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the
conduit panel.
4. Properly connect both the power supply and low
voltage lines to the corresponding terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches
longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
11
4. Connecting Pipings and the cable to Outdoor unit
1) Connecting the pipings to the Outdoor unit
1. Align the center of the pipings and
sufficiently tighten the flare nut with fingers.
2. Finally, tighten the flare nut with torque
wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Outdoor unit
Outdoor unit
Gas side piping (Bigger Dia.)
Liquid side piping (Smaller Dia.)
Torque wrench
High Voltage
Terminal block
Connecting cable
Conduit panel
Power supply cord
Cover control
Over 5mm(2")
Connector trade size for this unit is 1/2". Refer to "How to connect wiring to the terminals" for instructions on connecting depending on the wire type you are using.
NOTE
1. shows field wiring.
2. Separately wire the high and low voltage line.
3. Use heat-proof electrical wiring capable of withstanding temperatures up to 167°F.
4. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)
NOTE
• Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
• Every wire must be connected firmly.
• No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.
WARNING
Power Supply
Model Power source
9K,12K 1ø, 115V 14 18 20A
18K 1ø, 230/208V 14 18 15A 24K 1ø, 230/208V 14 18 20A
AWG(MIN.)
¤˝ ¤˛
Fuse or breaker
Capacity
1
Indoor Unit Outdoor Unit
2 3
4
1 2 3
4
5 6
G
To branch circuit
Ground
Power supply
a
L1 L2
Connecting cable(Low voltage)
b
Terminal
(4P)
Terminal
(6P)
Wiring Diagram
Model
Pipe Size Torque
9K,
Liquid Side (1/4") 1.8kg¡⁄m(13.0ft.lbs)
12K
Gas Side (1/2") 5.5kg¡⁄m(39.8ft.lbs)
18K,
Liquid Side (3/8") 4.0kg¡⁄m(28.9ft.lbs)
24K
Gas Side (5/8") 6.6kg¡⁄m(47.7ft.lbs)
Page 12
12
Connection method of the connecting cable(Example)
(1) Dismount two-caps on the conduit panel. (2) Make a hole appropriate for the passage of
connection cable through on cap by tool.
(for low voltage line) (3) Pass the connecting cable through the hole. (4) Properly connect the cable on the terminal block. (5) Fix the connection cable with clamp cord
provided on the unit not to have strain at the
terminal when the connection cable is pulled
outside up to a 35 pound weight. (6) Wind the vinyl tape round the connecting
cable for sealing between the surface of the
connection cable and cap. (7) Mount the taped part of cable on the cap. (8) Finally, mount the holed cap with the wound
cable on the conduit panel.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
§ For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter of
wire-cutting pliers, then strip the insulation to
expose the solid wire about 25mm(15/16") (2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate. (3) Using pliers, bend the solid wire to from a
loop suitable for the terminal screw. (4) Shape the loop wire properly, place it on the
terminal plater and tighten securely with the
terminal screw using a screwdriver.
§ For strand wiring
(1) Cut the wire end with a wire cutter or
wire-cutting pliers, then strip the insulation to
expose the strand wiring about 10mm(3/8"). (2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate. (3) Using a round terminal fastener or pliers,
securely clamp each stripped wire end with a
round terminal. (4) Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
WARNING
G
Terminal block
Cap (Remove)
Clamp cord
Lock nut
Conduit panel
Loop
Round terminal
Screw with special washer
Screw with special washer
Round terminal
Terminal plate
Wire
Wire
Round terminal
Insulation
Strip 25mm(15/16")
Strip 10mm(3/8")
Solid wire
Cap(Reuse)
Taping
(for sealing)
Low voltage line
(connecting cable)
Power supply line (1ø, 230/208V)
Hole
(for low voltage line)
Strand wire
Page 13
13
1) Checking the Drainage
1. Remove the Grille from the cabinet.
• Set the up-and-down air direction louver to open position (horizontally) by finger pressure.
• Remove 3 screws.
• To remove the Grille, pull lower the left and right side of the grille toward you (slightly tilted) and lift it straight upward (Four tabs on the top inside edge of chassis are clear of their slots).
2. Check the drainage.
• Pour a glass of water on the evaporator.
• Ensure if water flows drain hose of indoor unit without any leakage.
5.
Checking the Drainage and Connecting the cable to Indoor unit
Grille
Chassis
Screw(3 places)
• Outside drain hose should be lower than inside.
• The end of drain hose should not come in touch with surface of land.
• The end of drain hose should not dip into sewer or water.
NOTE
Page 14
14
2) Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of
outdoor unit and the terminal No. are the same as those of indoor unit respectively. (Refer to Wiring diagram on page11.)
Connecting cable
2. Attach the Grille onto the cabinet.
• Grasp lower the left and right side of the
Grille and engage four tabs on the top inside edge of the chassis.
• Press the Grille toward the chassis until it
will be back into place.
• Be sure to refer to the wiring diagram label inside the cover control and carry out the correct field wiring. Wrong wiring can cause the unit to misoperate to result in a fire hazard.
• Check local electrical codes and any specified wiring instructions or limitations.
WARNING
Page 15
15
3) Forming the pipings
1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands.(for the right pipings)
• If you want to connect an additional drain hose, the end of the drain-outlet should keep distance from the ground.(Do not dip it into water, and fix it on the wall to avoid swinging in the wind.)
2. Tape the Pipings, drain hose and Connecting Cable from down to up.
3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.
2. Tape the Pipings and Connecting cable
from down to up.
3. Form the pipings gathered by taping along
the exterior wall, make the Trap to be required to prevent water from entering into the room.
4. Fix the pipings onto the wall by saddle or
equivalent.
In case of the Outdoor unit being installed below position of the Indoor unit.
In case of the Outdoor unit being installed above position of the Indoor unit.
Seal a small opening around the pipings with gum type sealer.
Taping
Pipings
Connecting cable
Plastic band
Trap is required to prevent water from
entering into electrical parts.
Seal a small opening around the pipings with gum type sealer.
Trap
Drain hose
Page 16
16
6. Air Purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
• Pressure in the system rises.
• Operating current rises.
• Cooling(or heating) efficiency drops.
• Moisture in the refrigerant circuit may freeze and
block capillary tubing.
• Water may lead to corrossion of parts in the
refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
1)Air Purging with a Vacuum Pump
§ Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed. Remove the valve caps from both the gas and the liquid side service valves on the outdoor unit. Note that both liquid and gas side service valves on the outdoor unit are kept closed at this stage.
§ Leak test
1. Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
CAUTION: Be sure to use a manifold valve for air
purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
2. Pressurize the system to no more than 150 P.S.I.G
with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
CAUTION: To avoid nitrogen entering the refrigerant
system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertial standing position.
3. Do a leak test of all joints of the tubing(both indoor
and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
4. After the system is found to be free of leaks, relieve
the nitrogen pressure by loosening the charge hose connnector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder (in vertical
standing position)
Pressure
gauge
Page 17
17
§ Evacuation
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varied with the tubing length and capacity of the pump. The following table shows the amount of time for evacuation. Allow the pump to operate until the system has been evacuated down to 300 microns. Allow the pump to continue running for an additional 15 minutes. Turn off the pump and leave the connections secured to the two service valves. After 5 minutes, if the system fails to hold 500 microns or less, check all connections for tight fit and repeat the evacuation procedure.
2. When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
§ Finishing the job
1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve
counter-clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent gas leakage from the system.
5. Replace the vlave caps at both gas and liquid side
service valves and fasten them securely tight.
This complete air purging with a vacuum pump. The air conditoner is now ready to test run.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Vacuum pump
Pressure
gauge
Page 18
• Insert two batteries provided.
Remove the battery cover from the remote controller.
• Slide the cover according to the arrow
direction. Insert the two batteries. (Two "R03" or "AAA" dry-cell batteries or equivalent.)
• Be sure that the (+) and (-) directions are
correct.
• Be sure that both batteries are new.
Re-attach the cover.
• Slide it back into position.
(3) Turn on the power and run the unit.
18
7. Test running
Settlement of Outdoor Unit
Prepare to Remote Control
• Anchor the outdoor unit with a bolt and nut (ø10cm) tightly and horizontally on a concrete or rigid mount.
• When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
• In the case when the vibration of the unit is conveyed to the house, settle the unit with an anti-vibration rubber.
Bolt
Tubing connection
(1) Check that all tubing and wiring have been properly connected. (2) Check that the gas and liquid side service valves are fully open.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
(1) Measure the pressure of the gas side service valve. (2) Measure the outside ambient air temperature. (3) For reference; the gas side pressure of optimum condition is as below;
NOTE:
If the actual pressure are higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for actual operation.
Outside ambient TEMP. The Pressure of the gas side service valve
35°C(95°F) 4~5kg/cm2(56.8~71.0 P.S.I.G)
RESET
RESET
RESET
Page 19
19
8. Installation Instruction Templates
Left Side Installation
Piping hole
Ø2
3
/
4
"
Installation Plate
1.8"
Page 20
20
Right Side Installation
Models 9K 18K
12K 24K
1"
2"
Piping hole
Ø2
3
/
4
"
Piping hole
Ø2
3
/
4
"
1.9"
Installation Plate
Loading...