LG ARNU15GB3G4, ARNU07GB3G4, ARNU09GB3G4, ARNU12GB3G4, ARNU18GB4G4 Svc Manual

...
Multi V Air Conditioner
SVC MANUAL(Exploded View)
MODEL : ARNU07GB3G4 ARNU09GB3G4 ARNU12GB3G4 ARNU15GB3G4
ARNU18GB4G4 ARNU24GB4G4
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
http://biz.lgservice.com
- 2 -
Copyright ©2014 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1. Specification
Notes:-
1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. EEV: Electronic Expansion Valve
5. To be added for more available Models
Conversion Formula
kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
Type Ceiling Concealed Duct (Built-in)
Accessory PBSGB30/PBSC30 PBSGB30/PBSC30 PBSGB30/PBSC30
Model Unit ARNU07GB3G4 ARNU09GB3G4 ARNU12GB3G4
Cooling Capacity
kW 2.2 2.8 3.6
kcal/h 1,900 2,400 3,100
Btu/h 7,500 9,600 12,300
Heating Capacity
kW 2.5 3.2 4
kcal/h 2,200 2,800 3,400
Btu/h 8,500 10,900 13,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions
(WxHxD)
Body
mm 820 x 190 x 575 820 x 190 x 575 820 x 190 x 575
inch
32-9/32 x 7-15/32 x 22-5/8 32-9/32 x 7-15/32 x 22-5/8 32-9/32 x 7-15/32 x 22-5/8
Coil
Rows x Columns x FPI 2 x 11 x 21 2 x 11 x 21 2 x 11 x 21 Face Area m
3
0.16 0.16 0.16
Fan
Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number
W 19 x 1, 5 x 1 19 x 1, 5 x 1 19 x 1, 5 x 1
Running Current A 0.76 0.76 0.76 Air Flow Rate(H / M / L)
(High Mode-factor set) External Static Pressure
CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5
cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229
mmAq(Pa) 2(20) 2(20) 2(20)
Air Flow Rate(H / M / L) (Standard Mode) External Static Pressure
CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5
cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229
mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC
Temperature Control
Microprocessor, Thermostat
for cooling and heating
Microprocessor, Thermostat
for cooling and heating
Microprocessor, Thermostat
for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter - - ­Safety Device
Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor
Pipe Connections
Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.)
mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 21(46.3) 21(46.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 33 / 32 / 29 34 / 33 / 32 35 / 34 / 33
Power Supply Ø, V, Hz
1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm
2
CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C
Transmission cable mm
2
CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
- 3 -
Copyright ©2014 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Notes:-
1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. EEV: Electronic Expansion Valve
5. To be added for more available Models
Conversion Formula
kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m
3
/min x 35.3
l/s = CMM x 1000/60
Type Ceiling Concealed Duct (Built-in)
Accessory PBSGB30/PBSC30 PBSGB40/PBSC40 PBSGB40/PBSC40
Model Unit ARNU15GB3G4 ARNU18GB4G4 ARNU24GB4G4
Cooling Capacity
kW 4.5 5.6 7.1
kcal/h 3,900 4,800 6,100
Btu/h 15,400 19,100 24,200
Heating Capacity
kW 5 6.3 8
kcal/h 4,300 5,400 6,900
Btu/h 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions
(WxHxD)
Body
mm 820 x 190 x 575 1,100 x 190 x 575 1,100 x 190 x 575
inch
32-9/32 x 7-15/32 x 22-5/8 43-5/16 x 7-15/32 x 22-5/8 43-5/16 x 7-15/32 x 22-5/8
Coil
Rows x Columns x FPI 2 x 11 x 21 3 x 10 x 18 3 x 10 x 18 Face Area m
3
0.16 0.23 0.23
Fan
Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number
W 19 x 1, 5 x 1 19 x 2 19 x 2
Running Current A 0.76 0.97 0.97 Air Flow Rate(H / M / L)
(High Mode-factor set) External Static Pressure
CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0
cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353
mmAq(Pa) 2(20) 2(20) 2(20)
Air Flow Rate(H / M / L) (Standard Mode) External Static Pressure
CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0
cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353
mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC
Temperature Control
Microprocessor, Thermostat
for cooling and heating
Microprocessor, Thermostat
for cooling and heating
Microprocessor, Thermostat
for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter - - ­Safety Device
Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor
Pipe Connections
Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.)
mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 41 / 40 / 37 43 / 40 / 37 46 / 43 / 37
Power Supply Ø, V, Hz
1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm
2
CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C
Transmission cable mm
2
CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
- 4 -
Copyright ©2014 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2. List of Functions
Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right)
Air flow
Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter
Air purifying Plasma air purifier
Prefilter(washable / anti-fungus) Drain pump
Installation
E.S.P. control Electric heater(operation) High ceiling operation Hot start
Reliability Self diagnosis
Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock
Convenience Forced operation
Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller Wide Character wired remote controller
Picto wired remote controller Individual Deluxe wired remote controller control Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Special
Zone control
function kit
CTIE
Electro thermostat
1
-
-
-
-
3/3/3
-
-
-
­X X
O O O X
-
O O O
O(only heat recovery)
X
O(only heat pump or cooling only)
O O
-
O X O O O
Accessory
Accessory
Accessory Accessory Accessory
X Accessory Accessory
-
-
Function
Category
ARNU07GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y)
O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Loading...